This unit is normally used for switching on ¾ synchronization without frequency adjustmen
parallegenerating sets with either the mains supply under the following suppositions:
or witother generating sets
difference in revolutions between idle and full
Suppositions for switching in parallel are load no more than 3 %.
closing time of the alternator circuit breaker
coincidence of the phase (tim from giving the command till closing the
equal voltage mai contacts) no more than 90 ms
equal frequencies Compound alternators with voltage regulation i
transient conditions no longer than 0.3 s
Synchronizing unit SY1 is monitoring these values no heavy fly whee.
angives an output impulse, when they are within
theipre-set limits After switching in parallel, start loading the
generatin set:
Manual synchronization by possibly unskilled
personnel is dangerous and can result in damage of ¾ by manual adjustment of the speed governor
thequipment. It is therefore recommendable to use motor
aautomatic synchronizing device
¾ automatic load equalization with the load
The frequency equalization can be made as follows balancing unit WLA. This unit gives output
impulses for thspeed governor motor to balance
by manual adjustment of the speed governor the effectivpower to two or more generating sets
motor in parallel(refer to technical description WLA)It
automatic frequency adjustment by the is possible to preset the control value of
frequenccontrol unit FN2. Output impulses are individuagen-sets with the LWR2
given frothis unit for the speed governor motor.
(refer to technical description FN2)
The synchronizer unit SY1 is supplied from one 1. max. permissible difference in frequency
phase of each system. The unit compares the two
frequencies, the difference in voltage and measures The max. permissible frequency difference is
the phase coincidence and gives led impulse to close dependent on the kind and size of the driving engine
the alternator circuit breaker. and thfly wheel of the generating set
3. Front plate
Attention!
4. Connection diagram
Type : SY1
Adjust
Weight : 0.4 kg
Maintenance : none
URS-Approbation : 92.004.272
Dimensions and drill-holes
7. Order form
Synchronizing Unit SY 1
Number
Voltage 100
127
230
400
Nominal Frequency 50 / 60 Hz 50
400 Hz 400