RE26 CONTROLLER

NE • Universal temperature input (thermocouples and


W
resistance thermometers) or standard signals
FEATURES:
(current and voltage).
Password
protection PID • Control output: relay, OC.
algorithm
A

• Addi onal output in op on: relay or OC.


Oon/off Auto- • Control: PID with self-tuning and Fuzzy Logic,
algorithm tuning on/off.
• „So start” func on.
Soft
Start
Auto
• Manual control mode.

Fuzzy
Logic EXAMPLE OF APPLICATION

Supply 12 V
Auxiliary output
OC
INPUTS: RE26 L
Main output

0..10 V
0..20 mA N
Fan

Thermocouple
OUTPUTS: Heater

OBJECT

Temperature measurement with automatic control of the heater and fan.

INPUT
Input type Marking Range Error Addi onal error
Pt100 Pt100 -199 .. 850°C 0.2%
GALVANIC Pt1000 Pt1000 -199 .. 850°C 0.2%
ISOLATION: Fe-CuNi J -100 .. 1200°C 0.3% Compensa on of thermocouple cold
Cu-CuNi T -100 .. 400°C 0.3% junc on: temperature changes:
NiCr-NiAl K -100 .. 1372°C 0.3% ≤ 2°C
PtRh10-Pt S 0 .. 1767°C 0.5%
PtRh13-Pt R 0 .. 1767°C 0.5%
PtRh30-PtRh6 B 300 .. 1820°C 0.5% Ambient temperature change:
NiCr-CuNi E -100 .. 999°C 0.3% ≤ 100% of the intrinsic error/ 10 K
NiCrSi-NiSi N -100 .. 1300°C 0.3%
Sup. Chromel-kopel (GOST) L -100 .. 800°C 0.3%
Current I 0 .. 20 mA
Export department: Current I 4 .. 20 mA
English: +48 68 32 95 0.2% +1 digit
302 / 321 / 276 / 386 / 233 Voltage U 0 .. 5 V
German: +48 68 32 95 305 Voltage U 0 .. 10 V
French: +48 68 32 95 304
Russian: +48 68 32 95 321
Fax: +48 68 32 54 091 OUTPUTS
e-mail: export@lumel.com.pl
Output type Proper es Remarks
LUMEL S.A.
- 1 main output
ul. Sulechowska 1 Relay NO contacts, 2 A/ 230 V
65-022 Zielona Góra - 1 addi onal output (op on)
POLAND - 1 main output OC type (in serial with the resistance
OC transistor
WWW.LUMEL.COM.PL - 1 addi onal output (op on) 200 :), Umax= 24 V, Imax= 20 mA
RE26 CONTROLLER
EXTERNAL FEATURES
Readout field 2 x LED 10 mm, 4 digits
Weight < 0.2 kg
SEE ALSO:
Overall dimensions 48 x 48 x 93 mm
Protec on grade (acc. to EN 60529) from frontal side: IP40 from terminal side: IP20

RATED OPERATING CONDITIONS


- 85 .. 253 V d.c./a.c.
Supply voltage frequency: 40 .. 440 Hz
- 20 .. 40 V d.c./a.c.
Temperature ambient: 0...23...50˚C storage: -20...70˚C
Humidity < 85% inadmissible condensa on
Opera ng posi on any Temperature sensors.
External magne c field < 400 A/m
Power input < 6 VA
SAFETY AND COMPATIBILITY REQUIREMENTS
noise immunity acc. to EN 61000-6-2
Electromagne c compa bility
noise emissions acc. to EN 61000-6-4
Pollu on level 2
Installa on category III
Maximal opera ng phase-to-earth for supply circuit, outputs: 300 V for input circuits: 50 V
voltage
Al ude a.s.l. < 2000 m SSR relays of LU
series.
CONNECTION DIAGRAMS

supply

resistance resistance resistance


thermometer thermometer thermometer
Pt100 Pt100 Pt1000
output 1 - relay output 2 - relay

Power controller RP.


Load Load
Supply Supply

thermocouple current input input


output 1 - OC output 2 - OC

Fig.1. Connection of input signals Fig.2. Connection of the supply and load circuit
OUR OFFER

ORDERING
RE26 - X X X X X
Input:
universal for thermocouple and resistance
1
thermometer sensors
linear universal
www.lumel.com.pl
current 0/4 .. 20 mA, 2
voltage 0 .. 5/10 V For more informa on
as per order X about LUMEL's
Main output: products please visit
relay 1 our website:
OC transistor 2 www.lumel.com.pl
Ordering example:
Auxiliary output: The code RE26 - 1 1 2 2 8 means:
without output 0 RE26 - controller of RE26 type Export department:
1 - universal input for thermocouple English: +48 68 32 95
relay 1 302 / 321 / 276 / 386 / 233
OC transistor 2 and resistance thermometer sensors
1 - main output: relay German: +48 68 32 95 305
Supply: 2 - auxiliary output: OC transistor French: +48 68 32 95 304
85 .. 253 V d.c./a.c. 1 2 - supply: 20 .. 40 V d.c./a.c. Russian: +48 68 32 95 321
8 - without extra requirements. Fax: +48 68 32 54 091
20 .. 40 V d.c./a.c. 2 e-mail: export@lumel.com.pl
Acceptance tests:
LUMEL S.A.
without extra quality requirements 8 ul. Sulechowska 1
with an extra quality inspec on cer ficate 7 65-022 Zielona Góra
acc. to customer’s request* X * the code will be established by the manufacturer POLAND
WWW.LUMEL.COM.PL

RE26-19A