Feeder

33kV FEEDER No. 1

33kV FEEDER No. 2


Fixing
Identification
Pos. Mat. Nom. Current Description Total Location
Nr.

6 3 3

C1
String set twin goat

6 Quantity to Order: 3 3

12 Line T-Off to 6 6

Goat to Centipede
C2 AL
900 A R = 26mm K-2
T = 26.5mm

12 Quantity to Order: 6 6

12 Feeder Isolator 6 6
12 Busbar 1 Isolator 6 6
Twin Centipede to Palm
C3 AL 1 12 Busbar 2 Isolator 6 6
1600 A Palm with 4 x 14mm dia. Holes YP-1
50mm x 50mm spacing

36 Quantity to Order: 18 18

12 Feeder Circuit Breaker 6 6

Twin Centipede to Palm


C4 AL 2
1600 A Palm with 4 x 15mm dia. Holes YP-1
44.5mm x 44.5mm spacing

12 Quantity to Order: 6 6

18 T-Off from high busbar 9 9

80mm Tube T-Off to Twin


C5 AL Centipede
1600 A TBBT-80/C2-26
R = 80mm
T = 26.5
18 Quantity to Order: 9 9

6 T-Off from Low busbar 1 3 3


6 T-Off from Low busbar 2 3 3
120mm Tube T-Off to Twin
Twisted

C6 AL Centipede (TWISTED)
1600 A TBBT-120/C2-26
R = 120mm
T = 26.5
12 Quantity to Order: 6 6

Approved By: Date: Project Name: Revision:


- - GROOTEGELUK A
Checked By: Date: Title: Dept:
- - 33kV RETICULATION UPGRADE PROJ PSS
Prepared By: Date: CENTRAL SWITCHING STATION
D. Botha 19/04/19 LIST OF CLAMPS
Contract Nr.: Sheet Nr.:
1
Drawing Nr.: Total Sheets:

List of Clamps GG Main;List 1


Feeder

33kV FEEDER No. 1

33kV FEEDER No. 2


Fixing
Identification
POS. Symbol Mat. Nom. Current Description Total Location
nr

42 21 21

C7 AL Twin centipede 26.5mm


1600 A S-10
150mm Spacing

42 Quantity to Order: 21 21

6 T-Off to surge arrester 3 3

Twin centipede to Single


C8 AL Centipede
1600 A Y-5/6
T = 26.5mm
S = 26.5mm
6 Quantity to Order: 3 3

12 Current Transformer 6 6

Twin centipede to 38mm Stud


C9 AL
1600 A T = 26.5mm Y-1/3
S = 38mm

12 Quantity to Order: 6 6

C10

Quantity to Order:

C11

Quantity to Order:

C12

Quantity to Order:

Approved By: Date: Project Name: Revision:


- - GROOTEGELUK A
Checked By: Date: Title: Dept:
- - 33kV RETICULATION UPGRADE PROJ PSS
Prepared By: Date: CENTRAL SWITCHING STATION
D. Botha 19/04/19 LIST OF CLAMPS
Contract Nr.: Sheet Nr.:
0 2
Drawing Nr.: Total Sheets:
0

List of Clamps GG Main;List 2


FIG.01 FIG.02 FIG.03 FIG.04 FIG.05

x= a= 50mm c= e= 14mm x= a= 44.5mmc= e= 15mm


y= b= d= 50mm T= y= b= d= 44.5mmT=

FIG.06 FIG.07 FIG.08 FIG.09 FIG.10

FIG.11 FIG.12 FIG.13 FIG.14 FIG.15

FIG.16 FIG.17
Approved By: Date: Project Name:
Revision:

- -
GROOTEGELUK A
Checked By: Date: Title:
Dept:

- -
33kV RETICULATION UPGRADE PROJECT PSS
Prepared By: Date:
CENTRAL SWITCHING STATION
D. Botha 19/04/2019
LIST OF CLAMPS
Contract Nr.:
Sheet Nr.:

 0
Drawing Nr: Total Sheet:
3

0
List of Clamps GG Main;Fixing Detail
RED = Statements
ORANGE = Assumptions

Clamp
Position Detail Notes
no.
1 String set Goat conductor (25.96mm) dia.
2 Line T-Off From OHL to twin Centipede Assuming OHL is twin goat conductor
8 Surge arrester T-Off Twin Centipede to single centipede Need SA terminal detail to ensure it can accommodate centipede (26.46mm) dia conductor
7 Conducter spacer Twin centipede 150mm spacing
3 Isolator (Both sides) 4 x 14mm dia. Holes 50 x 50 Detail from Drawing, Assuming all isolators are the same
9 Current transformer both sides 38mm Stud Change to clamp no. 9
4 Circuit Breaker Both sides 4 x 15mm dia. Holes 44.5 x 44.5 Detail from Circuit Breaker brochure
7 Conducter spacer
5 High Bussbar T-Off (3 off them) Busbar tube 80mm diameter?
Busbas to PI ( assuming it is included) These will not be changed
7 Conducter spacer
3 Isolator (Both sides) Detail from Drawing, Assuming all isolators are the same
7 Add conductor spacer between Isol and furthest busbar phase
6 Low busbar t-off Busbar tube 120mm diameter?
7 Conducter spacer
3 Isolator (Both sides) Detail from Drawing, Assuming all isolators are the same
7 Add conductor spacer between Isol and furthest busbar phase
6 Low busbar t-off Busbar tube 120mm diameter?