Beruflich Dokumente
Kultur Dokumente
Section 6
Power/Vac® Switchgear Equipment
Page
INTRODUCTION ................................................................................................ 6-2
• Select the equipment configurations nec- Transformer primary feeder (TPF) is similar to
essary for each circuit and auxiliary com- a general purpose feeder except, the entire load
partment from the part of this section cov- is one transformer and often includes differential
ering Breaker and Auxiliary Compart- protection for the entire circuit. Liquid filled trans-
ments (pages 6-27 to 6-28). formers of a MVA rating to justify differential pro-
tection for the circuit are usually equipped with
The basic equipment and options in this sec- fault-pressure relays for additional internal protec-
tion constitute a structured lineup of metalclad tion. Both the differential and fault-pressure re-
equipment. Some lineups, however, may require lays trip a hand reset lockout relay, which trips
devices and circuit arrangements other than those the primary and secondary transformer circuit
breakers.
6-2
Section 6
A bus entrance (BE) is a metalclad vertical These metalclad future unit (FU) compart-
section in which one of the compartments con- ments are a basic mechanically prepared circuit
tains incoming conductors (cable or bus duct) breaker unit, except the breaker is to be provided
which are connected directly to the main bus (also at a future date. Provisions are made to receive a
referred to as a cable tap). No incoming breaker breaker of specified rating.
is used. This arrangement applies to lineups of It is recommended to equip these base units with
switchgear, without main circuit breakers, which the breaker stationary auxiliary switch and breaker
connect the incoming line directly to the main bus. position switch if the active feeders are so
It also applies to sub feeds, from a lineup of equipped, and install current transformers (possi-
switchgear, without circuit breakers, connecting bly multiratio). This minimizes field installation,
the outgoing conductors to the main bus. down time and adjustment procedures when the
application of this base unit is determined.
The selected relays may be added to the door
when the circuit application is determined, or a
new door may be purchased with relays and de-
vices completely wired.
6-3
Power/Vac® Switchgear Equipment
GENERAL PURPOSE FEEDERS Current Transformers for Differential Circuits
6-4
Section 6
Figure 6-1 General Purpose Feeder
To Load
52
R G
CS 52
SR735/737 or MIF II
50/51
3 50/51N
50/51GS
52
3
Optional CTs for
Bus Differential To Load
Ground
Connection for
GPF1 36"
To Load
6-5
Power/Vac® Switchgear Equipment
BREAKER BYPASS FEEDERS
Optional Bus
Differential
3
CTs
Spare
Breaker
R G
CS 52
52
SR735/737
Switchgear or MIF II
Main Bus 50/51
50/51N
50/51GS
R G
CS
52
52
Optional Bus
Differential 3
Ground
CTs Connection
for BBF1 To Load
1
36"
To Load
6-6
Section 6
TRANSFORMER PRIMARY FEEDERS and a HEA lockout relay (86T). Differential pro-
tection can be in the form of separate relays, such
DEFINITIONS as GE Type STD single-phase transformer differ-
ential relays (87T), or as part of a complete multi-
A transformer primary feeder (TPF) equipment, function transformer protection package, like GE’s
is similar to a general purpose feeder except the SR745, T35 or T60 relays.
entire load is one transformer, and the circuit is
typically protected with transformer differential re- OPTIONAL EQUIPMENT SELECTION
lays. If transformer differential protection is not
required, use a General Purpose Feeder. Options for a transformer primary feeder
are the same as for a general purpose feeder ex-
PROTECTIVE SCHEME SELECTION cept that automatic reclosing is not used. Select
options for TPF-1, TPF-2, or TPF-3 on the same
Basic devices included in a transformer pri- basis as for GPF-1, GPF-2, or GPF-3.
mary feeder are the same as those included in a
general purpose feeder plus three additional cur-
rent transformers for the differential protection, a
transformer fault-pressure auxiliary relay (63PX)
SR745 52
W
R G
50/51
86T 50/51N
CS 52 50/51GS
1 87T, 87TG
Option for 52
Bus 3 To CTs at
Differential Transformer
To Load
Ground 36"
To Connection for
Transformer TPF1
6-7
Power/Vac® Switchgear Equipment
SINGLE SOURCE INCOMING LINES OPTIONAL EQUIPMENT SELECTION
(or dual source with normally open tie
breakers) Protection
6-8
Section 6
CURRENT TRANSFORMERS FOR REMOTELY TEST BLOCKS — For circuits that require the pro-
LOCATED DIFFERENTIAL RELAYS — For incom- visions for insertion of portable recording meters
ing lines included in bus or transformer differential or other similar devices, add current and voltage
zones for which relays are not mounted on the test block. Basic test block is wired to maintain
incoming line equipment, add a separate set of the circuit when the test plug is removed.
three current transformers for each differential func-
tion. INDICATING LAMP —Additional indicating lamps
can be provided, such as for circuits requiring a
DIRECTIONAL POWER, UNDERFREQUENCY, circuit breaker disagreement or spring-charged in-
AND UNDERVOLTAGE PROTECTION — To de- dication function.
tect utility tie circuit fault conditions prior to auto-
matic reclosing and to initiate programmed load Control
shedding, add, either singly or in combination, a
power directional relay (32), underfrequency relay CONTROL VOLTAGE —Available control voltages
(81), undervoltge relay (27) and timer (62). This are 48VDC, 125VDC, 250VDC, 120VAC and
applies for systems with local generation or large 240VAC. For AC control, if a reliable 120/240VAC
motors. These features are included in the GE source is not available at the site, then include a
Type SR750 and F650 relays. control power transformer connected to each in-
A study of each system is required to assure coming line in each lineup, plus an auto-charged,
proper selection and circuit location of these re- capacitor-trip device for each circuit breaker and
lays. each lockout relay (86) in the lineup. For dual
sources with normally open-tie circuit breaker and
AUTOMATIC THROWOVER — For lineups with a ac control, add CPT throwover contactor.
normally open tie breaker or a normally open al-
ternate incoming line breaker, add automatic pri- REMOTE CONTROL — For circuit breakers con-
mary throwover equipment if desired. This con- trolled from a remote location, choose the remote
sists of two undervoltage relays (27), two multi- control scheme for those listed in Table 5-1 (page
contact auxiliary relays (27X), two timers (2 and 5-7 of this guide). From this table, Scheme C is
62), two auxiliary relays (2X and 62X), and one recommended, since it provides maximum oper-
manual-automatic selector switch (43). Automatic ating flexibility. It requires the use of a breaker
throwover equipment requires an empty auxiliary position switch in conjunction with the breaker
compartment for mounting, custom designed for control switch to provide the permissive function.
each application. If using GE Type SR750 multi- With Scheme C, remote close and trip is possible
function relays on the incoming line and tie break- only with the breaker in the “connected” position;
ers, only two timers (2 and 62), two auxiliary re- local close with the breaker in the “test” position;
lays (2X and 62X), and one manual-automatic and local trip with the breaker in the “connected”
switch (43) are required. or “test” position.
INSTRUMENTATION AND METERING — For in- If several optional devices are added to an in-
coming lines for which voltage indication and a coming line section, there may not be sufficient
relay voltage source are not required, omit the volt- space to mount them all. In this case, specify
meter, voltmeter switch, and two voltage transform- excess relays to be mounted on the tie-breaker
ers. For circuits requiring the indication or meter- vertical section or on an adjacent auxiliary com-
ing of additional electrical quantities, add indicat- partment.
ing analog meters as appropriate, or a multifunc-
tion meter such as GE Type PQM II. Some relays
include extensive metering functions such as
Amps, Volts, Watts, Vars, PF and demand func-
tions (such as GE’s SR750/760 &, F650).
6-9
Power/Vac® Switchgear Equipment
Optional CTs
for 3 Incoming Line
Transformer
2
Differential
SR750
52
R G
51, 51N, 51G
CS 52 27, 59, 47
81, 32, 25C
I,V,W,Var, PF
3 To Ground
2
or Neutral
CT
Optional 3
CTs for Bus 2
Differential
2
Incoming 36"
Source
6-10
Section 6
DEFINITION
Dual source incoming line equipment (DSIL) DSIL-3 Use this type of incoming line for un-
is a metalclad section containing a power circuit grounded systems only.
breaker acting as is a main disconnect between a
main power distribution bus, and one of two sources This type of incoming line equipment in-
of power supplying the main bus. The other source cludes three phase-overcurrent (51) and
of power may be either another incoming line or a directional phase-overcurrent relays (67),
local generator. Both sources supply a common no ground fault detection. These protec-
distribution bus, with or without a normally closed tive functions are available in a single re-
bus-tie breaker. lay package, such as the GE SR750,
F650 or F60 relays. There are additional
BASIC EQUIPMENT SELECTION functions available as required.
DSIL-1 Use this type of incoming line for an im- OPTIONAL EQUIPMENT SELECTION
pedance or solidly grounded system fed
from a local wye-connected power trans- Protection
former, with a current transformer in the
transformer neutral connection. OVERCURRENT RELAY CHARACTERISTICS —
Time current characteristics for overcurrent relays
This type of incoming line equipment in- are determined by system studies. After the time
cludes three phase-overcurrent relays (51) current characteristic has been established, make
and three directional phase-overcurrent re- sure the relays selected offer the required time
lays (67). It includes one ground- current characteristics that satisfy the application.
overcurrent relay, (51G) connected to the
neutral CT of a local power transformer OPEN-PHASE PROTECTION — For incoming
feeding the incoming line and one residu- lines fed from transformers with fused primaries or
ally connected directional ground- sources subject to single-phase operation, add
overcurrent relay (67N), polarized from the negative-sequence voltage protection (60) and
power transformer neutral CT. These pro- timer (62), as well as current-balance detection
tective functions are available in a single (60C), to distinguish which incoming line has
relay package, such as the GE SR750, single-phase operation.
F650 or F60 relays.
TRANSFORMER AND BUS DIFFERENTIAL PRO-
DSIL-2 Use this type of incoming line for an im- TECTION — Add relays and current transformers
pedance or solidly grounded system fed to obtain this protection, using the same consid-
from a remote wye-connected power trans- erations as for single source incoming lines.
former.
DIRECTIONAL POWER, UNDERFREQUENCY,
This type of incoming line equipment in- AND UNDERVOLTAGE PROTECTION — Add
cludes three phase-overcurrent (51) and separate relays or enable these functions in mul-
directional phase-overcurrent (67). It also tifunction relays to obtain this protection using the
includes residual connected ground- same considerations as for single source incom-
overcurrent (51G) and residually con- ing lines.
nected directional ground-overcurrent
(67N) polarized from a wye-broken delta Indication
auxiliary VT connected to a set of wye-
wye VT’s. These protective functions are INSTRUMENTATION AND METERING — For cir-
available in a single relay package, such cuits requiring the indication or metering of addi-
as the GE SR750, F650 or F60 relays. tional electrical quantities, add indicating analog
meters as appropriate, or a multifunction meter
such as GE Type PQM II. Some relays also in-
6-11
Power/Vac® Switchgear Equipment
clude extensive metering functions such as Amps, Control
Volts, Watts, Vars, PF and demand functions (such
as GE’s SR750/760 &, F650). Optional feature involving control voltage and
permissive control switch are the same as for
TEST BLOCKS — For circuits that require the pro- single-source incoming line equipments.
visions for insertion of portable recording meters
or other similar devices, add current and voltage Location of Optional Devices
test block. Basic test block is wired to maintain
the circuit when the test plug is removed. If several optional devices are added to an in-
coming line equipment, there may not be suffi-
INDICATING LAMP— Additional indicating lamps cient space to mount them all. In this case,
can be provided, such as for circuits requiring a specify excess relays to be mounted on the tie-
circuit breaker disagreement or spring-charged in- breaker vertical section, or on an adjacent auxil-
dication function. iary compartment.
Optional Bus
VTs
Switchgear Main Bus
Optional CTs
for 3 Incoming Line
Transformer
Differential 2
SR750
52
R G
51, 51N, 51G,
CS 52 67, 67N, 27, 59,
47, 81, 32, 25C
I, V, W, Var, PF
3
To
Ground or 2
Neutral
Optional
3 CT
CTs for
Bus 2
Differential
2
Line VTs
Incoming 36"
Source
6-12
Section 6
BUS TIES
DEFINITION
A bus-tie is metalclad equipment connecting compartments. The control panel for automatic
two power distributions buses through a tie breaker. throwover of CPTs can be placed on a swinging
Such equipment is sometimes specified without auxiliary panel, above a bus-tie, behind the front
overcurrent relays because of the difficulty of ob- door of an auxiliary compartment.
taining selective system operation when using bus-
tie over-current relays. Indication
R G
50/51 MIF II or
CS 52 50/51N SR750 *
Auxiliary Auxiliary
Space Space
52
36" 36"
6-14
Section 6
DEFINITION Indication
Incoming/Outgoing
Optional
Optional
3 CTs CTs OR
VTs
2
OR
Optional VTs
Auxiliary
Space or
Breaker
Cable or Bus
Duct
36"
6-15
Power/Vac® Switchgear Equipment
INDUCTION MOTOR FEEDERS,
lockout relay (86M); zero-sequence
FULL-VOLTAGE-START,
ground fault (50GS); and full function
metering. Additional protective
DEFINITION
functions are available in the SR469.
The Multilin SR469 relay operates from
These metalclad feeder equipments (IMF)
three current transformers, one in
are used for controlling and protecting full-voltage-
each phase, a ground sensor CT and
start motors and are designated as “branch cir-
three current transformers located at
cuit” protective equipment. Economics usually
the motor.
preclude protecting a motor smaller than 1500 hp
(IMF1) with a device package as complete as that
IMFE
used for larger motors (IMF2). The equipment is
These metalclad feeder equipments
specified for use on impedance grounded or sol-
(IMFE) are used for controlling and
idly grounded systems. See “Optional Equipment
protecting full-voltage-start, essential-
Selection” for modifications of this equipment for
service motors and are designated as
use on systems with other types of grounding.
motor “branch circuit” protective
Also see IEEE C37.96-2000 IEEE Guide for AC
equipment. Such motor feeders
Motor Protection for relaying recommendations.
sound an alarm only for motor
overload, but trip the circuit breaker
PROTECTIVE SCHEME SELECTION
for locked rotor and short-circuit
conditions. Basic equipment for an
IMF1
IMFE include a GE Multilin 239 digital
motor protection relay which provides
Basic equipment for and IMF1
three-phase overload indication,
includes three-phase running overload,
locked-rotor tripping, short-circuit
locked rotor, and short-circuit
tripping (49/50/83), zero-sequence
protection (49/50); undervoltage
ground-fault protection and load
protection with time delay (27, 62)
current indication. No undervoltage
(only one required per lineup); zero-
protection is included. The Multilin
sequence ground-fault protection
239 relay operates from three current
(50GS); and load current indication.
transformers, one in each phase, and
The overcurrent relays operate from a
a ground sensor CT
three CT’s, one in each phase, and a
ground-sensor CT. Complete
economical motor protection
packages are available in the GE
OPTIONAL EQUIPMENT SELECTION
Multilin 269 and 239 digital motor
(For IMFE, IMF1, IMF2)
protection relays. For undervoltage
protection when using the Multilin 239,
Protection
add a separate GE Multilin MIV
undervoltage relay. When using the
For ungrounded systems, omit the ground-sensor
Multilin 269, specify the optional MPM
overcurrent relay and the current transformer.
module, or add a separate MIV relay
as noted above.
When equipment is used to feed more than one
motor from the same bus, only one GE Multilin
IMF2
MIV undervoltage relay is required. However, for
multiple motors, add auxiliary relay(s) (27X), with
Basic equipment for an IMF2 is a GE
sufficient contacts to trip each additional motor
Multilin SR469 digital motor protection
feeder breaker.
relay which includes (26/50/83) for
locked rotor and short-circuit
On smaller motors, where economically justified
protection; over temperature (49);
to include motor differential protection, add one
undervoltage with time delay (27, 62);
GE Type 12HFC23, 3-element, instantaneous
3-phase self-balancing machine
overcurrent relay operating from the three current
differential (87M); one Type HEA
transformers (mounted at the motor terminals) and
6-16
Section 6
connected for balanced-current motor differential 5-7 of this guide). From this table, Scheme C is
protection (87M). recommended, since it provides maximum oper-
For larger motors (greater than 1500HP), complete ating flexibility. It requires the use of a breaker
protection including motor differential can be ob- control switch to provide the permissive function.
tained by using the GE Multilin SR469 relay (with With Scheme C, remote close and trip is possible
motor mounted CTs). only with the breaker in the “connected” position;
local close with the breaker in the “test” position;
The CT’s located at the motor and used for the and local trip with the breaker in the “connected”
motor differential (87M) circuit, are typically fur- or “test position.
nished by the motor manufacturer. They are not
supplied with the switchgear. In addition, remote control for motors requires
a lockout relay (86), which prevents breaker clos-
For lineups with bus differential protection, add ing (after a relay-initiated trip) until the lockout
three current transformers. device is manually reset. (The 86 device speci-
fied on IMF2 may be used for both 87M and re-
For motors with RTDs, the GE Multilin 469, 369, mote control.)
269+ and 239 digital motor protection relays offer
RTD sensing inputs. Location of Optional Devices
6-17
Power/Vac® Switchgear Equipment
Bus VTs
To Motor
3
2
269+ MTM
W
R G
27,47
49/51,50, 26 52
86M I, V
CS 52 50/51GS, 83
W, Var
37,38,46,48
1 PF, Hz
3
Option for
Bus 2
Differential
87M
Optional Bus
1 VTs
To 3 Self-
To Motor Balance Motor
Differential CTs 36"
at Motor
6-18
Section 6
3 3
To Bus VTs
269+ MTM
R G R G
27,47 To
49/51,50, 26
CS I, V CS
50/51GS, 83 Reactor
W, Var
37,38,46,48
Start 6 PF, Hz 42 Run Start 52
87M
52 Run
Remote
To 3 Self-
Starting
Balance Motor
Reactor
Differential CTs
at Motor To Motor
36"
6-19
Power/Vac® Switchgear Equipment
3 3
To Bus VTs
269+ MTM
R G R G
27,47
49/51,50, 26
CS I, V CS
50/51GS, 83
W, Var
37,38,46,48
Start 6 PF, Hz 42 Run
87M
To 3 Self-Balance Motor
Remote Atuo-
Transformer
1. Starting sequence
a. Close #52/N
b. Close #6
c. Accelerate motor
52
Neutral d. Open #52/N
Shunt e. Close #42
f. Open #6
2. Autotransformer and neutral breaker
will usually be located at motor.
6-20
Section 6
Auxiliary
Space
Start 52
Cable
Connection to
Run Bkr
Cable
Connection to
Motor Neutral
52 Run 52
Shunt
Internal Bus or
Cable
Connection
To Autotransformer
36" 36"
Auxiliary
Start 52 Space
Internal Bus or
Cable
Connection
52 52
Neutral
Run
Shunt
Internal Bus or
Cable
Cable Connection
Connection to
Motor
This option only available for small auto transformers. No extension of main bus available for future add-on.
6-21
Power/Vac® Switchgear Equipment
Field application equipment or exciter pack- REMOTE CONTROL - For circuit breakers con-
ages for a synchronous motor are typically fur- trolled from a remote location, choose the remote
nished with the motor package. Excitation pack- control scheme from those listed in Section 5,
ages and panels can be sourced and mounted in Table 5-1. From this table, Scheme C is recom-
a switchgear compartment or section. These ap- mended, since it provides maximum operating flex-
plication panels are considered custom design. ibility. If requires the use of a breaker position
switch in conjunction with the breaker control
Indication switch to provide the permissive function. With
Scheme C. remote close and trip is possible only
INSTRUMENTATION AND METERING – The GE with the breaker in the “connected” position; local
Multilin 469 provides extensive metering capabili- close with the breaker in the “test” position; and
ties. For circuits requiring additional or separate local trip with the breaker in the “connected” or
metering, add a GE PQM II power quality meter “test” position.
which includes indication of all three phases of
load current, in addition to Volts, Watts, Vars, PF In addition, remote control for motors requires
and demand functions. a lockout relay (86), which prevents breaker clos-
ing (after a relay-initiated trip) until the lockout
TEST BLOCKS - For circuits that require the pro- device is manually reset. (The 86 device speci-
visions for insertion of portable recording meters fied on SMF2 may be used for both 87M and re-
or other similar devices, add current and voltage mote control.)
test blocks. Basic current test block is wired to
maintain the circuit when the test plug is removed. Location of Optional Devices
INDICATING LAMP - For circuits requiring a cir- If several optional devices are added to a motor
cuit breaker disagreement or spring-charged indi- feeder equipment, there may not be sufficient
cation function, add a white indicating lamp. space to mount them all. In this case, specify
that the excess relays are to be mounted on an
adjacent auxiliary compartment. This makes the
vertical section a custom section.
Bus VTs
To Motor
3
2
SR469
W
R G
49/51,50, 26, 27
50/51GS, 83, 47, 59 52
CS 52 86M
37,38,46,48, 87, 81
1 I, V, W, Var, PF , Hz
Option for 3
Bus
Differential
2
Optional Bus
1 VTs, or
Auxiliary Space
for Excitation
Equipment
To 3 Motor
To Motor Differential
36"
CTs at Motor
6-23
Power/Vac® Switchgear Equipment
GENERATORS
DEFINITION Protection
Current Transformers
Field Control and Voltage Regulation
Add three current transformers for lineups that
To obtain field control for remote-mounted field include bus differential protection.
application equipment, add one motor-operated
rheostat control switch and one field ammeter. Indication and Metering
For generators with brushless exciters and For generators requiring supplementary indi-
without remote SC-VT regulators, add one cation and metering, add one GE Type PQM meter
metalclad equipment vertical section containing and current or voltage test blocks as required.
provisions for mounting a voltage regulator,
brushless exciter field control, mounting for an
exciter field rheostat, and an exciter field amme-
ter. Add one or two VT’s and one CT to the gen-
erator circuit breaker vertical section for use with
the voltage regulator, if required.
6-24
Section 6
Generator
SR489 52
W
R G
51V, 50/51G
CS 52 86M 27, 47, 59
81, 32, 87G
1 I,V,W,Var, PF
Optional To
3 2
CTs for Ground or Optional Bus
VTs
Bus Neutral
Differential CT
2
2
To
Generator 36"
To Differential
Generator CTs
6-25
Power/Vac® Switchgear Equipment
POWER COMPANY METERING
DEFINITION
Metalclad equipment that contains Util- Consult the serving Utility on your project, for
ity owned metering transformers and meters. their specific requirements regarding metering sec-
These sections are custom, and designed to meet tion design and construction. All metering section
the specific requirements of the specified Utility. designs must be approved by the Utility, prior to
Sections are dedicated for Utility use, therefore manufacture.
cannot contain any Owner/Customer equipment.
Standard designs utilize either 36" wide or 48"
wide sections. Some Utilities require a separate
cable entry or pull section for the incoming cables,
in addition to the metering section. Section
designs can be for “Hot Sequence” (metering
before main disconnect/breaker) or “Cold
Sequence” (metering after main disconnect/
breaker) as shown in Figure 6-14.
Utility
CTs
MAIN
52 52 MAIN
Utility
CTs
VTs
Utility
VTs
CPT Utility
VTs
VTs
6-26
Figure 6-15.
Standard Power/Vac® Breaker Stacking Configurations
1200A-3000A 1200A-3000A
(3) (7) (2) (5) (2) (6) (3) Bus Entrance Bus Entrance
(4)
®
Standard
StandardPower/Vac
Power/VAC Tie Breaker
BusBus Stacking
Tie Breaker Configurations
Stacking Configurations
(3) (9) (3) (9) (7) (3) (7) (3) (9) (3) (9)
Aux, Aux, Aux, Aux, Aux,
1200A Breaker 12-2000A Bkr 1200 - Bus Rollout Bus Rollout or 12-2000A Bkr Blank 12-2000A Bkr
or or 2000A (8) Aux (8) Bus Entrance or or
Bus Entrance Bus Entrance Bus Entrance Bus Entrance
(5) (6)
(1) 4000A breakers require fans on top of structure for forced air cooling.
(2) Blank Unit above 3500A & 4000A breakers have room for device mounting .
(3) Auxiliary Units can contain rollout tray for VTs & CPTs, or additional device mounting.
(4) Full height Auxiliary Units can contain additional device mounting or be used for material storage .
(5) 3500A must be derated to 3250A in outdoor construction.
(6) 4000A is not available in outdoor construction.
(7) Rollouts located above a 3000A breaker, are only available on indoor construction.
(8) Auxilary Bus Ties can contain 1 bus connected rollout tray.
(9) Bus Entrance can also contain a VT rollout tray, or CTs (not both)
6-27
Section 6
6-28
PT-CPT
1 2 3 4 5 6 7 8 9 10
NOTE: ALL ROLLOUT TRAYS ARE HARD BUS CONNECTED. NO CABLE CONNECTED TRAYS.
Power/Vac® Switchgear Equipment
A Compartment B Compartment
Rollout Unit Devices Ratings
Lower Upper Lower Upper
VT 2 - VTs (1) 5KV through 15KV Yes Yes Yes Yes
VT 3 - VTs (1) 5KV through 15KV Yes Yes Yes Yes
CPT 1 - CPT (1) 5, 10, 15KVA No Yes Yes No
Fused Unit 1 - CPT (2) 25, 37.5KVA (4) Yes N/A Yes N/A
Fused Unit CPT Fuses (3) Remote 225kVA Max Yes N/A Yes N/A
(1) Fuses are an integral part of VT or CPT. CPTs are single phase
(2) CPT is installed in the rear cable compartment. CPT fuses are installed in a key interlocked fuse rollout in the Lower A or Lower B compartment
(3) Fused rollout tray must be key interlocked with remote CPT secondary breaker
(4) Contact GE Sales Office for availablity of larger CPTs or 3-phase bank.