Sie sind auf Seite 1von 28

Contents

Section 6
Power/Vac® Switchgear Equipment

Page
INTRODUCTION ................................................................................................ 6-2

BASIC EQUIPMENT APPLICATIONS ................................................................ 6-2

GENERAL PURPOSE FEEDERS (GPF) .......................................................... 6-4

BREAKER BYPASS FEEDERS (BBF).............................................................. 6-6

TRANSFORMER PRIMARY FEEDERS (TPF) ................................................... 6-7

SINGLE-SOURCE INCOMING LINES (SSIL) ..................................................... 6-8

DUAL-SOURCE INCOMING LINES (DSIL) ...................................................... 6-11

BUS TIES (BT) ................................................................................................. 6-13

BUS ENTRANCES (BE) .................................................................................. 6-15

INDUCTION MOTOR FEEDERS (IMF) ............................................................. 6-16

SYNCHRONOUS MOTOR FEEDERS (SMF) .................................................. 6-22

GENERATORS (GEN) ..................................................................................... 6-24

UTILITY METERING SECTIONS ...................................................................... 6-26

STANDARD BREAKER AND AUXILIARY CONFIGURATIONS ........................ 6-27


Power/Vac® Switchgear Equipment

INTRODUCTION included in this section. Contact your GE Sales


Representative for additional information.
This section contains information covering typi-
cal circuit application packages for Power/Vac® BASIC EQUIPMENT APPLICATIONS
metalclad switchgear equipment.
The first part of this section contains basic DEFINITION
equipment description for the protection, instru-
mentation, and control portions of the equipment. A brief definition of each of the 11 basic equip-
Eleven standard applications are shown, complete ment circuits is given in the following paragraphs.
with the type of the basic equipment and devices
for these commonly used configurations. Charts GENERAL PURPOSE FEEDERS
showing the allowable Power/Vac breaker and aux-
iliary compartment stacking combinations follow General purpose feeder (GPF) equipment is a
this data. The last part of this section shows a metalclad circuit breaker and compartment con-
sample lineup developed from the preceding infor- trolling and protecting a set of conductors supply-
mation. ing one or more secondary distribution centers,
one or more branch-circuit distribution centers, or
Devices illustrated in Section 6 are assumed any combination of these two types of equipment.
to utilize 125V dc control voltage. A general purpose feeder includes circuit
To use Section 6, proceed in the following overcurrent protection, circuit current indication,
manner: and circuit control.

• Determine the type of each circuit in the BREAKER BYPASS FEEDERS


one-line diagram (developed in accor-
dance with procedures outlined in Sec- Breaker bypass feeder (BBF) is metalclad
tion 2). equipment similar to a general purpose feeder,
except two breaker units are connected in parallel
• Select from the 11 basic circuit descrip- to feed a common load. Phase current transform-
tions, the circuits which meet the require- ers for both circuit breakers are connected in par-
ments of the installation. allel to a common set of phase relays and instru-
ments. This arrangement is used when a means
• Select from the option tables those to remove a feeder circuit breaker for maintenance
options desired for the protection, instru- is desired, yet still maintain service to the con-
mentation, and control portion of each nected load. Every breaker bypass vertical sec-
circuit. tion has positions for two circuit breaker remov-
able elements. It is not necessary to include a
• Determine the requirements for auxiliary circuit breaker removable element in each breaker
compartments to house voltage transform- bypass position. One spare circuit breaker re-
ers or control power transformers. movable element per lineup or bus section is usu-
ally considered sufficient for each equipment
• Determine the incoming and outgoing cir- lineup.
cuit conductor configurations required for
each circuit. TRANSFORMER PRIMARY FEEDERS

• Select the equipment configurations nec- Transformer primary feeder (TPF) is similar to
essary for each circuit and auxiliary com- a general purpose feeder except, the entire load
partment from the part of this section cov- is one transformer and often includes differential
ering Breaker and Auxiliary Compart- protection for the entire circuit. Liquid filled trans-
ments (pages 6-27 to 6-28). formers of a MVA rating to justify differential pro-
tection for the circuit are usually equipped with
The basic equipment and options in this sec- fault-pressure relays for additional internal protec-
tion constitute a structured lineup of metalclad tion. Both the differential and fault-pressure re-
equipment. Some lineups, however, may require lays trip a hand reset lockout relay, which trips
devices and circuit arrangements other than those the primary and secondary transformer circuit
breakers.
6-2
Section 6

SINGLE-SOURCE INCOMING LINES INDUCTION MOTOR FEEDERS,


FULL-VOLTAGE-START
Single source incoming line (SSIL) equipment
is metalclad equipment for a circuit to a main
power distribution bus from the only source of Induction motor feeder (IMF) is similar to a
power supplying the bus. A system with this type general purpose feeder except it is used for con-
of incoming line is called a radial system. A sys- trolling and protecting full-voltage-start motors and
tem with two or more incoming lines supplying is designated as motor “branch circuit” protective
distribution buses sectionalized by normally open equipment. For motors greater than 1500 hp,
bus-tie circuit breakers requires the same type of motor differential protection is typically required.
protection, instrumentation, and control as single
source incoming lines, with the possible excep- Reduced-voltage-start applications, utilizing reac-
tion of the connection of the overcurrent relays. tors or autotransformers, are available. Contact
your GE Sales Representative for additional infor-
DUAL SOURCE INCOMING LINES mation.

Dual source incoming line (DSIL) equipment


is metalclad equipment for a circuit to a main SYNCHRONOUS MOTOR FEEDERS,
power distribution bus from one or two sources of FULL-VOLTAGE-START
power supplying the main bus. The other source
of power may be either another incoming line or a Synchronous motor feeder (SMF) is similar
local generator. Both sources supply a common to an induction motor feeder, except it is used for
distribution bus with or without a normally closed controlling and protecting full-voltage-start synchro-
bus-tie circuit breaker. nous motors and is designated as motor “branch
circuit” protective equipment. For motors greater
BUS TIES than 1500 hp, motor differential protection is typi-
cally required.
Bus-tie (BT) is metalclad equipment connect-
ing two power distribution buses through a tie
breaker. Such equipments often are not equipped GENERATORS
with overcurrent relays because of the difficulty of
obtaining selective system operation with bus-tie These metalclad equipments (GEN) connect,
overcurrent relays. A bus tie requires two com- control and protect synchronous generators driven
partments of adjacent sections; see available ar- by gas turbines or diesel engines.
rangements later in this section. (Figure 6-15)

BUS ENTRANCES FUTURE UNIT

A bus entrance (BE) is a metalclad vertical These metalclad future unit (FU) compart-
section in which one of the compartments con- ments are a basic mechanically prepared circuit
tains incoming conductors (cable or bus duct) breaker unit, except the breaker is to be provided
which are connected directly to the main bus (also at a future date. Provisions are made to receive a
referred to as a cable tap). No incoming breaker breaker of specified rating.
is used. This arrangement applies to lineups of It is recommended to equip these base units with
switchgear, without main circuit breakers, which the breaker stationary auxiliary switch and breaker
connect the incoming line directly to the main bus. position switch if the active feeders are so
It also applies to sub feeds, from a lineup of equipped, and install current transformers (possi-
switchgear, without circuit breakers, connecting bly multiratio). This minimizes field installation,
the outgoing conductors to the main bus. down time and adjustment procedures when the
application of this base unit is determined.
The selected relays may be added to the door
when the circuit application is determined, or a
new door may be purchased with relays and de-
vices completely wired.

6-3
Power/Vac® Switchgear Equipment
GENERAL PURPOSE FEEDERS Current Transformers for Differential Circuits

DEFINITION For a feeder included in a bus-differential-pro-


tected zone, add a separate set of three current
A general purpose feeder equipment (GPF) is transformers located on the outgoing side of the
a metalclad equipment controlling and protecting feeder. For a transformer-differential-protected
a set of conductors supplying one or more branch- zone, add a separate set of three current trans-
circuit distribution centers, one or more branch- formers located so that the feeder circuit breaker
circuit distribution centers, or any combination of is included in the zone.
these centers.
Indication
PROTECTIVE SCHEME SELECTION
INSTRUMENTATION AND METERING—— Most
GPF-1 solid-state protective relays today offer basic load
Use this type of feeder for systems which current indication (such as GE’s SR735/737& MIF
are impedance or solidly grounded and for II). Some relays include extensive metering func-
which selectivity is not required with down- tions such as Amps, Volts, Watts, Vars, PF and
stream residually connected ground re- demand functions (such as GE’s SR750/760,
lays. F650, F35 &, F60)
This type of feeder equipment includes
three phase-overcurrent protection (50/51) TEST BLOCKS— On circuits that require the pro-
and one instantaneous overcurrent ele- visions for insertion of portable recording meters
ment (50GS) connected to a ground-sen- or other similar devices, add current and voltage
sor CT (GSCT). test blocks. The basic current test block is wired
to maintain the circuit when the test plug is re-
GPF-2 moved.
Use this type of feeder for systems which
are impedance or solidly grounded and for INDICATING LAMP— Additional indicating lamps
which selectivity is required with down- can be provided, such as for circuits requiring a
stream residually connected ground re- circuit breaker disagreement or spring-charged in-
lays. This type of feeder equipment in- dication function.
cludes three phase-overcurrent protection
(50/51) and residually connected time- Control
overcurrent ground element (51N).
CONTROL VOLTAGE— Available control voltages
GPF-3 are 48VDC, 125VDC, 250VDC, 120VAC and
Use this type of feeder for ungrounded or 240VAC. For AC control, if a reliable 120/240VAC
solidly grounded systems for which no source is not available at the site, then include a
ground relays are desired. This type of control power transformer connected to each in-
feeder equipment includes three phase- coming line in each lineup, plus an auto-charged,
overcurrent protection (50/51) and no capacitor-trip device for each circuit breaker in the
ground fault element. lineup.

OPTIONAL EQUIPMENT SELECTION REMOTE CONTROL— For circuit breakers con-


trolled from a remote location, choose the remote
Protection control scheme from those listed in Table 5-1 (page
5-7 of this guide). From this table, Scheme C is
AUTOMATIC RECLOSING— For open-wire over- recommended, since it provides maximum oper-
head distribution circuits on which this feature is ating flexibility. It requires the use of a breaker
desired, use the GE MIF II, F650 or SR760 relay position switch in conjunction with the breaker
which includes automatic-reclosing (79) and cut- control switch to provide the permissive function.
off switch (79CO) functionality. With Scheme C, remote close and trip is pos-
sible only with the breaker in the “test” position;
and local trip with the breaker in the “connected”
or “test” position.

6-4
Section 6
Figure 6-1 General Purpose Feeder

Switchgear Main Bus

To Load

52

R G

CS 52
SR735/737 or MIF II
50/51
3 50/51N
50/51GS

52
3
Optional CTs for
Bus Differential To Load

Ground
Connection for
GPF1 36"
To Load

6-5
Power/Vac® Switchgear Equipment
BREAKER BYPASS FEEDERS

DEFINITION A lineup utilizing this arrangement of feeders


is often specified with only one bypass position
A breaker bypass feeder (BBF) is metalclad breaker element for the lineup, since typically only
equipment similar to a general purpose feeder, one feeder circuit breaker is bypassed at a time.
except two breaker units are connected in parallel
to feed a common load. A complete vertical sec- PROTECTIVE SCHEME SELECTION
tion (Unit A and Unit B) is required for each breaker Basic devices included in a breaker bypass
bypass feeder circuit. The purpose of this arrange- feeder are the same as those included in a gen-
ment is to allow removal of the normal service eral purpose feeder. Select BBF-1, BBF-2, or BBF-
breaker for maintenance without interrupting ser- 3 on the same basis as GPF-1, GPF-2, or GPF-3.
vice on the feeder. Previously, this type of service
required either a main and transfer bus arrange- OPTIONAL EQUIPMENT SELECTION
ment or feeder tie switches. Options for a breaker bypass feeder are the
same as for a general purpose feeder. Select op-
tions for BBF-1, BBF-2, or BBF-3 on the same
basis as for GPF-1, GPF-2, and GPF-3.

Figure 6-2 Breaker Bypass Feeder

Optional Bus
Differential
3
CTs

Spare
Breaker
R G

CS 52
52
SR735/737
Switchgear or MIF II
Main Bus 50/51
50/51N
50/51GS

R G

CS
52
52

Optional Bus
Differential 3
Ground
CTs Connection
for BBF1 To Load

1
36"

To Load

6-6
Section 6

TRANSFORMER PRIMARY FEEDERS and a HEA lockout relay (86T). Differential pro-
tection can be in the form of separate relays, such
DEFINITIONS as GE Type STD single-phase transformer differ-
ential relays (87T), or as part of a complete multi-
A transformer primary feeder (TPF) equipment, function transformer protection package, like GE’s
is similar to a general purpose feeder except the SR745, T35 or T60 relays.
entire load is one transformer, and the circuit is
typically protected with transformer differential re- OPTIONAL EQUIPMENT SELECTION
lays. If transformer differential protection is not
required, use a General Purpose Feeder. Options for a transformer primary feeder
are the same as for a general purpose feeder ex-
PROTECTIVE SCHEME SELECTION cept that automatic reclosing is not used. Select
options for TPF-1, TPF-2, or TPF-3 on the same
Basic devices included in a transformer pri- basis as for GPF-1, GPF-2, or GPF-3.
mary feeder are the same as those included in a
general purpose feeder plus three additional cur-
rent transformers for the differential protection, a
transformer fault-pressure auxiliary relay (63PX)

Figure 6-3 Transformer Primary Feeder

Switchgear Main Bus


Optional
VTs
To Load

SR745 52
W
R G
50/51
86T 50/51N
CS 52 50/51GS
1 87T, 87TG

Option for 52
Bus 3 To CTs at
Differential Transformer
To Load

Ground 36"
To Connection for
Transformer TPF1

6-7
Power/Vac® Switchgear Equipment
SINGLE SOURCE INCOMING LINES OPTIONAL EQUIPMENT SELECTION
(or dual source with normally open tie
breakers) Protection

DEFINITION OVERCURRENT RELAY CHARACTERISTICS —


Time current characteristics for overcurrent relays
A single source incoming line (SSIL) is a are determined by system studies. After the time
metalclad section containing a power circuit current characteristic has been established, make
breaker, acting as is the main disconnect between sure the relays selected offer the required time
a main power distribution bus and the only source current characteristics that satisfy the application.
of power supplying the bus.
CURRENT SUMMATION CONNECTION — For
A system with two or more incoming lines, line-ups containing bus-tie breakers, specify the
which supply distribution buses sectionalized by incoming line overcurrent relays to be wired for
normally open bus-tie breakers, requires essen- current summation (also known as partial differ-
tially the same type of protection, instrumenta- ential). Add a lockout relay (86) and a set of three
tion, and control for each incoming line as a single CT’s mounted on the tie breaker, for each set of
source incoming line. relays to be wired this way.

PROTECTIVE SCHEME SELECTION OPEN-PHASE PROTECTION — For incoming


lines fed from transformers with fused primaries or
SSIL-1 Use this type of incoming line for an im- sources subject to single-phase operation, add
pedance or solidly grounded system fed negative-sequence voltage protection (60/47) and
from a local wye-connected transformer time delay (62). The function is available in multi-
with a current transformer in the transformer function relay protection packages, such as GE
neutral connection. This type of incoming Type SR750/760 and F650, or as a single function
line would include three-phase time- relay Type NBV or MIV II.
overcurrent protection (51), and a ground-
over-current element (51G) to be connected TRANSFORMER DIFFERENTIAL PROTECTION
to the neutral current transformer of a local — Add differential protection for incoming lines fed
power transformer feeding the incoming from transformers with a means to trip a primary
line. breaker. Differential protection can be in the form
of separate relays, such as GE Type STD single-
SSIL-2 Use this type of incoming line for and im- phase transformer differential relays (87T), or as
pedance or solidly grounded system fed part of a complete multi-function transformer pro-
from a remote wye-connected transformer, tection package, like GE’s SR745, T35 or T60 re-
or a local wye-connected transformer with lays. In addition, add one Type HEA lockout relay
no current transformer in the transformer (86T), one Type HAA fault pressure auxiliary tar-
neutral connection. get relay (63FPX), and a set of three current trans-
This type of incoming line would include formers. For impedance grounded systems with
three-phase time-overcurrent protection larger transformers and for which three-phase trans-
(51), and residually connected ground- former differential relaying is not sensitive enough
overcurrent relay (51N). to detect secondary ground faults, include ground
differential relay protection (87TG) with a single
SSIL-3 Use this type of incoming line for un- function relay GE Type IFD, or as part of a com-
grounded or solidly grounded systems for plete multi-function transformer protection pack-
which no ground relays are desired. age.
This type of incoming line would include
three-phase time-overcurrent protection BUS DIFFERENTIAL PROTECTION — For sys-
(51), and no ground relays. tems requiring bus differential protection, add a
GE Type MIB three-phase solid state differential
protection relay (87B) and one Type HEA hand
reset lockout relay (86B). Bus differential requires
a dedicated set of three CTs on the incoming line.

6-8
Section 6
CURRENT TRANSFORMERS FOR REMOTELY TEST BLOCKS — For circuits that require the pro-
LOCATED DIFFERENTIAL RELAYS — For incom- visions for insertion of portable recording meters
ing lines included in bus or transformer differential or other similar devices, add current and voltage
zones for which relays are not mounted on the test block. Basic test block is wired to maintain
incoming line equipment, add a separate set of the circuit when the test plug is removed.
three current transformers for each differential func-
tion. INDICATING LAMP —Additional indicating lamps
can be provided, such as for circuits requiring a
DIRECTIONAL POWER, UNDERFREQUENCY, circuit breaker disagreement or spring-charged in-
AND UNDERVOLTAGE PROTECTION — To de- dication function.
tect utility tie circuit fault conditions prior to auto-
matic reclosing and to initiate programmed load Control
shedding, add, either singly or in combination, a
power directional relay (32), underfrequency relay CONTROL VOLTAGE —Available control voltages
(81), undervoltge relay (27) and timer (62). This are 48VDC, 125VDC, 250VDC, 120VAC and
applies for systems with local generation or large 240VAC. For AC control, if a reliable 120/240VAC
motors. These features are included in the GE source is not available at the site, then include a
Type SR750 and F650 relays. control power transformer connected to each in-
A study of each system is required to assure coming line in each lineup, plus an auto-charged,
proper selection and circuit location of these re- capacitor-trip device for each circuit breaker and
lays. each lockout relay (86) in the lineup. For dual
sources with normally open-tie circuit breaker and
AUTOMATIC THROWOVER — For lineups with a ac control, add CPT throwover contactor.
normally open tie breaker or a normally open al-
ternate incoming line breaker, add automatic pri- REMOTE CONTROL — For circuit breakers con-
mary throwover equipment if desired. This con- trolled from a remote location, choose the remote
sists of two undervoltage relays (27), two multi- control scheme for those listed in Table 5-1 (page
contact auxiliary relays (27X), two timers (2 and 5-7 of this guide). From this table, Scheme C is
62), two auxiliary relays (2X and 62X), and one recommended, since it provides maximum oper-
manual-automatic selector switch (43). Automatic ating flexibility. It requires the use of a breaker
throwover equipment requires an empty auxiliary position switch in conjunction with the breaker
compartment for mounting, custom designed for control switch to provide the permissive function.
each application. If using GE Type SR750 multi- With Scheme C, remote close and trip is possible
function relays on the incoming line and tie break- only with the breaker in the “connected” position;
ers, only two timers (2 and 62), two auxiliary re- local close with the breaker in the “test” position;
lays (2X and 62X), and one manual-automatic and local trip with the breaker in the “connected”
switch (43) are required. or “test” position.

Indication Location of Optional Devices

INSTRUMENTATION AND METERING — For in- If several optional devices are added to an in-
coming lines for which voltage indication and a coming line section, there may not be sufficient
relay voltage source are not required, omit the volt- space to mount them all. In this case, specify
meter, voltmeter switch, and two voltage transform- excess relays to be mounted on the tie-breaker
ers. For circuits requiring the indication or meter- vertical section or on an adjacent auxiliary com-
ing of additional electrical quantities, add indicat- partment.
ing analog meters as appropriate, or a multifunc-
tion meter such as GE Type PQM II. Some relays
include extensive metering functions such as
Amps, Volts, Watts, Vars, PF and demand func-
tions (such as GE’s SR750/760 &, F650).

6-9
Power/Vac® Switchgear Equipment

Figure 6-4 Single Source Incoming Line

Optional Bus VTs


Switchgear Main Bus

Optional CTs
for 3 Incoming Line
Transformer
2
Differential

SR750
52
R G
51, 51N, 51G
CS 52 27, 59, 47
81, 32, 25C
I,V,W,Var, PF

3 To Ground
2
or Neutral
CT
Optional 3
CTs for Bus 2
Differential
2

Incoming 36"
Source

6-10
Section 6

DUAL SOURCE INCOMING LINES

DEFINITION

Dual source incoming line equipment (DSIL) DSIL-3 Use this type of incoming line for un-
is a metalclad section containing a power circuit grounded systems only.
breaker acting as is a main disconnect between a
main power distribution bus, and one of two sources This type of incoming line equipment in-
of power supplying the main bus. The other source cludes three phase-overcurrent (51) and
of power may be either another incoming line or a directional phase-overcurrent relays (67),
local generator. Both sources supply a common no ground fault detection. These protec-
distribution bus, with or without a normally closed tive functions are available in a single re-
bus-tie breaker. lay package, such as the GE SR750,
F650 or F60 relays. There are additional
BASIC EQUIPMENT SELECTION functions available as required.

DSIL-1 Use this type of incoming line for an im- OPTIONAL EQUIPMENT SELECTION
pedance or solidly grounded system fed
from a local wye-connected power trans- Protection
former, with a current transformer in the
transformer neutral connection. OVERCURRENT RELAY CHARACTERISTICS —
Time current characteristics for overcurrent relays
This type of incoming line equipment in- are determined by system studies. After the time
cludes three phase-overcurrent relays (51) current characteristic has been established, make
and three directional phase-overcurrent re- sure the relays selected offer the required time
lays (67). It includes one ground- current characteristics that satisfy the application.
overcurrent relay, (51G) connected to the
neutral CT of a local power transformer OPEN-PHASE PROTECTION — For incoming
feeding the incoming line and one residu- lines fed from transformers with fused primaries or
ally connected directional ground- sources subject to single-phase operation, add
overcurrent relay (67N), polarized from the negative-sequence voltage protection (60) and
power transformer neutral CT. These pro- timer (62), as well as current-balance detection
tective functions are available in a single (60C), to distinguish which incoming line has
relay package, such as the GE SR750, single-phase operation.
F650 or F60 relays.
TRANSFORMER AND BUS DIFFERENTIAL PRO-
DSIL-2 Use this type of incoming line for an im- TECTION — Add relays and current transformers
pedance or solidly grounded system fed to obtain this protection, using the same consid-
from a remote wye-connected power trans- erations as for single source incoming lines.
former.
DIRECTIONAL POWER, UNDERFREQUENCY,
This type of incoming line equipment in- AND UNDERVOLTAGE PROTECTION — Add
cludes three phase-overcurrent (51) and separate relays or enable these functions in mul-
directional phase-overcurrent (67). It also tifunction relays to obtain this protection using the
includes residual connected ground- same considerations as for single source incom-
overcurrent (51G) and residually con- ing lines.
nected directional ground-overcurrent
(67N) polarized from a wye-broken delta Indication
auxiliary VT connected to a set of wye-
wye VT’s. These protective functions are INSTRUMENTATION AND METERING — For cir-
available in a single relay package, such cuits requiring the indication or metering of addi-
as the GE SR750, F650 or F60 relays. tional electrical quantities, add indicating analog
meters as appropriate, or a multifunction meter
such as GE Type PQM II. Some relays also in-
6-11
Power/Vac® Switchgear Equipment
clude extensive metering functions such as Amps, Control
Volts, Watts, Vars, PF and demand functions (such
as GE’s SR750/760 &, F650). Optional feature involving control voltage and
permissive control switch are the same as for
TEST BLOCKS — For circuits that require the pro- single-source incoming line equipments.
visions for insertion of portable recording meters
or other similar devices, add current and voltage Location of Optional Devices
test block. Basic test block is wired to maintain
the circuit when the test plug is removed. If several optional devices are added to an in-
coming line equipment, there may not be suffi-
INDICATING LAMP— Additional indicating lamps cient space to mount them all. In this case,
can be provided, such as for circuits requiring a specify excess relays to be mounted on the tie-
circuit breaker disagreement or spring-charged in- breaker vertical section, or on an adjacent auxil-
dication function. iary compartment.

Figure 6-5 Dual Source Incoming Line

Optional Bus
VTs
Switchgear Main Bus

Optional CTs
for 3 Incoming Line
Transformer
Differential 2

SR750
52
R G
51, 51N, 51G,
CS 52 67, 67N, 27, 59,
47, 81, 32, 25C
I, V, W, Var, PF

3
To
Ground or 2
Neutral
Optional
3 CT
CTs for
Bus 2
Differential
2

Line VTs

Incoming 36"
Source

6-12
Section 6

BUS TIES

DEFINITION

A bus-tie is metalclad equipment connecting compartments. The control panel for automatic
two power distributions buses through a tie breaker. throwover of CPTs can be placed on a swinging
Such equipment is sometimes specified without auxiliary panel, above a bus-tie, behind the front
overcurrent relays because of the difficulty of ob- door of an auxiliary compartment.
taining selective system operation when using bus-
tie over-current relays. Indication

BASIC EQUIPMENT SELECTION INSTRUMENTATION —For indication of current,


add three current transformers (if no CTs are
Basic bus-tie circuit breaker and auxiliary bus present for overcurrent relaying), an ammeter, and
is located in the bottom compartment of each of an ammeter switch, or a digital three phase am-
two vertical sections. The top compartment of ei- meter.
ther or both vertical sections can be used as ei-
ther an auxiliary compartment or a feeder com- TEST BLOCKS — For circuits that require the
partment. See Figure 6-15 for arrangement re- provisions for insertion of portable recording meters
strictions when selecting Bus Tie equipment. or other similar devices, add current and voltage
test blocks. Basic current test block is wired to
The basic equipment included in a bus-tie is a maintain the circuit when the test plug is removed.
circuit breaker control switch and indicating lights.
INDICATING LAMP —Additional indicating lamps
OPTIONAL EQUIPMENT SELECTION can be provided, such as for circuits requiring a
circuit breaker disagreement or spring-charged in-
Protection dication function.

OVERCURRENT PROTECTION — For systems Control


requiring overcurrent protection relays for bus-tie
equipment, specify incoming line overcurrent Optional features involving control voltage and
relay(s) (50/51) to be wired for a summation cur- a permissive control switch are the same as for
rent connection. If residually connected ground- single source incoming line equipment. For cir-
overcurrent relays (51N) are required with an in- cuit breakers where ac control is specified, in-
coming line, the equipment may be wired also for clude a secondary automatic-throwover contactor
a summation current connection. Include a sec- for control power.
ond set of three current transformers if your sys-
tem has a second incoming line.

BUS-DIFFERENTIAL PROTECTION — For sys-


tems requiring bus-differential protection, relays can
be mounted in bus-tie vertical sections. Each set
of bus-differential protection includes three phase
high-speed bus-differential relays (87B) such as
GE Multilin MIB, one Type HEA hand-reset lock-
out relay (86B), and three current transformers. If
the bus-differential relays have been included in
the incoming line (SSIL or DSIL) package, then
additional relays are not required.

AUTOMATIC THROWOVER — For systems with


a normally open bus tie circuit breaker that re-
quire automatic throwover, add equipment listed
under “Single Source Incoming Line Options” in a
auxiliary compartment above one of the bus-tie
6-13
Power/Vac® Switchgear Equipment

Figure 6-6 Bus Tie

Switchgear Ma in Bus A Switchgear Ma in Bus B


Optional CTs for
3 Bus Differential

R G
50/51 MIF II or
CS 52 50/51N SR750 *

3 Optional CTs for


Bus Differential

* Use SR750 if Tie breaker part of 3-breaker autotransfer

Auxiliary Auxiliary
Space Space

52

36" 36"

6-14
Section 6

BUS ENTRANCES OPTIONAL EQUIPMENT SELECTION

DEFINITION Indication

Bus-entrance equipment, also referred to as INSTRUMENTATION AND METERING - For cir-


a cable tap, is a metalclad vertical section in which cuits requiring the indication or metering of elec-
one of the compartments contains incoming or trical quantities, add three current transformers or
outgoing conductors which connect directly to the two voltage transformers. Cannot locate both a
main bus without the use of a circuit breaker. Con- set of CTs and VTs in a Bus Entrance. Select
ductors can be either cables or non-seg bus duct. instrumentation and metering required as neces-
sary.
BASIC EQUIPMENT SELECTION
TEST BLOCKS - For circuits that require the pro-
Select this type of equipment as a means to visions for insertion of portable recording meters
connect either incoming or outgoing conductors or other similar devices, add current and voltage
directly to the bus for circuits that require no cir- test blocks. Basic current block is wired to main-
cuit breakers. See Section 1 and Figure 6-15 for tain the circuit when the test plug is removed.
configuration restrictions when selecting Bus En-
trances.

Figure 6-7 Bus Entrance

Incoming/Outgoing

Switchgear Main Bus

Optional
Optional
3 CTs CTs OR
VTs
2

OR

Optional VTs

Auxiliary
Space or
Breaker

Cable or Bus
Duct

36"

6-15
Power/Vac® Switchgear Equipment
INDUCTION MOTOR FEEDERS,
lockout relay (86M); zero-sequence
FULL-VOLTAGE-START,
ground fault (50GS); and full function
metering. Additional protective
DEFINITION
functions are available in the SR469.
The Multilin SR469 relay operates from
These metalclad feeder equipments (IMF)
three current transformers, one in
are used for controlling and protecting full-voltage-
each phase, a ground sensor CT and
start motors and are designated as “branch cir-
three current transformers located at
cuit” protective equipment. Economics usually
the motor.
preclude protecting a motor smaller than 1500 hp
(IMF1) with a device package as complete as that
IMFE
used for larger motors (IMF2). The equipment is
These metalclad feeder equipments
specified for use on impedance grounded or sol-
(IMFE) are used for controlling and
idly grounded systems. See “Optional Equipment
protecting full-voltage-start, essential-
Selection” for modifications of this equipment for
service motors and are designated as
use on systems with other types of grounding.
motor “branch circuit” protective
Also see IEEE C37.96-2000 IEEE Guide for AC
equipment. Such motor feeders
Motor Protection for relaying recommendations.
sound an alarm only for motor
overload, but trip the circuit breaker
PROTECTIVE SCHEME SELECTION
for locked rotor and short-circuit
conditions. Basic equipment for an
IMF1
IMFE include a GE Multilin 239 digital
motor protection relay which provides
Basic equipment for and IMF1
three-phase overload indication,
includes three-phase running overload,
locked-rotor tripping, short-circuit
locked rotor, and short-circuit
tripping (49/50/83), zero-sequence
protection (49/50); undervoltage
ground-fault protection and load
protection with time delay (27, 62)
current indication. No undervoltage
(only one required per lineup); zero-
protection is included. The Multilin
sequence ground-fault protection
239 relay operates from three current
(50GS); and load current indication.
transformers, one in each phase, and
The overcurrent relays operate from a
a ground sensor CT
three CT’s, one in each phase, and a
ground-sensor CT. Complete
economical motor protection
packages are available in the GE
OPTIONAL EQUIPMENT SELECTION
Multilin 269 and 239 digital motor
(For IMFE, IMF1, IMF2)
protection relays. For undervoltage
protection when using the Multilin 239,
Protection
add a separate GE Multilin MIV
undervoltage relay. When using the
For ungrounded systems, omit the ground-sensor
Multilin 269, specify the optional MPM
overcurrent relay and the current transformer.
module, or add a separate MIV relay
as noted above.
When equipment is used to feed more than one
motor from the same bus, only one GE Multilin
IMF2
MIV undervoltage relay is required. However, for
multiple motors, add auxiliary relay(s) (27X), with
Basic equipment for an IMF2 is a GE
sufficient contacts to trip each additional motor
Multilin SR469 digital motor protection
feeder breaker.
relay which includes (26/50/83) for
locked rotor and short-circuit
On smaller motors, where economically justified
protection; over temperature (49);
to include motor differential protection, add one
undervoltage with time delay (27, 62);
GE Type 12HFC23, 3-element, instantaneous
3-phase self-balancing machine
overcurrent relay operating from the three current
differential (87M); one Type HEA
transformers (mounted at the motor terminals) and
6-16
Section 6
connected for balanced-current motor differential 5-7 of this guide). From this table, Scheme C is
protection (87M). recommended, since it provides maximum oper-
For larger motors (greater than 1500HP), complete ating flexibility. It requires the use of a breaker
protection including motor differential can be ob- control switch to provide the permissive function.
tained by using the GE Multilin SR469 relay (with With Scheme C, remote close and trip is possible
motor mounted CTs). only with the breaker in the “connected” position;
local close with the breaker in the “test” position;
The CT’s located at the motor and used for the and local trip with the breaker in the “connected”
motor differential (87M) circuit, are typically fur- or “test position.
nished by the motor manufacturer. They are not
supplied with the switchgear. In addition, remote control for motors requires
a lockout relay (86), which prevents breaker clos-
For lineups with bus differential protection, add ing (after a relay-initiated trip) until the lockout
three current transformers. device is manually reset. (The 86 device speci-
fied on IMF2 may be used for both 87M and re-
For motors with RTDs, the GE Multilin 469, 369, mote control.)
269+ and 239 digital motor protection relays offer
RTD sensing inputs. Location of Optional Devices

Indication If several optional devices are added to a mo-


tor feeder equipment, there may not be sufficient
INSTRUMENTATION AND METERING - For cir- space to mount them all. In this case, specify
cuits requiring the indication or metering of addi- that the excess relays are to be mounted on an
tional electrical quantities, and using the Multilin adjacent auxiliary compartment. This makes the
269+, add the MPM module. For circuits without vertical section a custom section.
metering built into the multifunction protective re-
lay, add a GE PQM II power quality meter which Reduced Voltage Starting
includes indication of all three phases of current,
in addition to Volts, Watts, Vars, PF and demand Power distribution system voltage regulation
functions. requirements sometimes mandate reduced cur-
rent starting to minimize the current inrush and
TEST BLOCKS - For circuits that require the pro- voltage sag when starting large motors. Inserting
visions for insertion of portable recording meters a reactor and then bypassing it as the motor comes
or other similar devices, add current and voltage up to speed is one method of accomplishing this
test blocks. Basic current test block is wired to objective.
maintain the circuit when the test plug is removed.
An auto transformer connection is an alter-
INDICATING LAMP - For circuits requiring a cir- nate method of reduced voltage starting. This
cuit breaker disagreement or spring-charged indi- method applies a reduced voltage via the auto-
cation function, add a white indicating lamp. transformer, which is shorted out as the motor
comes up to speed.
Control
Figures 6-9 through 6-10 illustrate the typical
REMOTE CONTROL — For circuit breakers con- POWER/VAC circuits and arrangements for these
trolled from a remote location, choose the remote special motor starting requirements.
control scheme from those listed in Table 5-1 (page

6-17
Power/Vac® Switchgear Equipment

Figure 6-8 Induction Motor Feeder

Switchgear Main Bus

Bus VTs

To Motor
3

2
269+ MTM
W
R G
27,47
49/51,50, 26 52
86M I, V
CS 52 50/51GS, 83
W, Var
37,38,46,48
1 PF, Hz

3
Option for
Bus 2
Differential
87M
Optional Bus
1 VTs

To 3 Self-
To Motor Balance Motor
Differential CTs 36"
at Motor

6-18
Section 6

Figure 6-9 IMF, Reduced Voltage Reactor Start

Switchgear Main Bus

3 3

To Bus VTs

269+ MTM
R G R G
27,47 To
49/51,50, 26
CS I, V CS
50/51GS, 83 Reactor
W, Var
37,38,46,48
Start 6 PF, Hz 42 Run Start 52

Option for 3 3 Option for


Bus 86M Bus
Differential Differential
1 1

87M

52 Run

Remote
To 3 Self-
Starting
Balance Motor
Reactor
Differential CTs
at Motor To Motor

36"

6-19
Power/Vac® Switchgear Equipment

Figure 6-10 IMF Reduced Voltage Autotransformer Start

Switchgear Main Bus

3 3

To Bus VTs

269+ MTM
R G R G
27,47
49/51,50, 26
CS I, V CS
50/51GS, 83
W, Var
37,38,46,48
Start 6 PF, Hz 42 Run

Option for 3 3 Option for


Bus 86M Bus
Differential Differential
1 1

87M

To 3 Self-Balance Motor
Remote Atuo-
Transformer

Differential CTs at Motor

1. Starting sequence
a. Close #52/N
b. Close #6
c. Accelerate motor
52
Neutral d. Open #52/N
Shunt e. Close #42
f. Open #6
2. Autotransformer and neutral breaker
will usually be located at motor.

6-20
Section 6

Figure 6-11 Remote Mounted Autotransformer (Standard)


Remote Power/Vac®
Remote PowerVAC
Autotransformer and Switchgear
Part
Part of Power/Vac®
of PowerVAC Switchgear
Enclosure Section, Located at
Siwtchgear Lineup Section, Located at
Switchgear Lineup (by others) Autotransformer
Autotransformer
To Autotransformer Cable
Connection to
Start Bkr

Auxiliary
Space
Start 52
Cable
Connection to
Run Bkr

Cable
Connection to
Motor Neutral
52 Run 52
Shunt
Internal Bus or
Cable
Connection

To Autotransformer

36" 36"

Autotransformer Mounted in Custom


Switchgear Section

Auxiliary
Start 52 Space

Internal Bus or
Cable
Connection

52 52
Neutral
Run
Shunt
Internal Bus or
Cable
Cable Connection
Connection to
Motor

36" 72" max 36"

This option only available for small auto transformers. No extension of main bus available for future add-on.
6-21
Power/Vac® Switchgear Equipment

SYNCHRONOUS MOTOR FEEDERS, ancing machine differential (87M); one


FULL-VOLTAGE START, Type HEA lockout relay (86M); zero-
DIRECT-CONNECTED EXCITERS sequence ground fault (50GS); and full
function metering. Additional protec-
tive functions are available in the
DEFINITION SR469. The Multilin SR469 relay op-
erates from three current transform-
These metalclad feeder equipments (SMF) are ers, one in each phase, a ground sen-
used for controlling and protecting full-voltage-start sor CT and three current transform-
synchronous motors and are designated as mo- ers located at the motor.
tor “branch circuit” protective equipment. Econom-
ics usually preclude protecting a motor smaller .
than 1500 hp (SMF1) with a device package as OPTIONAL EQUIPMENT SELECTION
complete as that used for larger motors (SMF2). (For SMF1 and SMF2)
Also see IEEE C37.96-2000 IEEE Guide for AC
Motor Protection for relaying recommendations. Protection

PROTECTIVE SCHEME SELECTION If six-CT machine differential relaying


(87M) is desired, omit the three-phase Type
SMF1 12HFC23 instantaneous relay (if used) and three
CT’s (supplied by motor manufacturer) at the ma-
Basic equipment for and SMF-1 (1500 chine terminals. Use the SR469 relay and six
HP and less) includes three-phase CT’s (three in machine neutral leads and three in
running overload, locked rotor, and metalclad switchgear.) Specify the SR469 relay
short-circuit protection (49/50); be wired for current summation differential in lieu
undervoltage protection with time de- of self-balance.
lay (27, 62) (only one required per
lineup); zero-sequence ground-fault For starting control, synchronization and
protection (50GS); load current indi- enhanced protection in collector-ring and brushless
cation. The overcurrent relays oper- type motors, add the GE Multilin SPM relay.
ate from a three CT’s, one in each
phase, and a ground-sensor CT. For ungrounded systems, omit the ground-
Complete economical motor protec- sensor overcurrent relay (50GS) and the current
tion package is available in the GE transformer.
Multilin 469 digital motor protection
relay. When equipment is used to feed more than
The equipment is specified for use on one motor from the same bus, only one GE Multilin
impedance grounded or solidly MIV undervoltage relay is required. However, for
grounded systems. See “Optional multiple motors, add auxiliary relay(s) (27X), with
Equipment Selection” for modifica- sufficient contacts to trip each additional motor
tions of this equipment for use on sys- feeder breaker.
tems with other types of grounding or
having motors with other types of ex- On smaller motors, where economically
citation. justified to include motor differential protection, add
one GE Type 12HFC23, 3-element, instantaneous
SMF2 overcurrent relay operating from the three current
Basic equipment for an SMF2 (greater transformers (mounted at the motor terminals) and
than 1500 HP) is a GE Multilin SR469 connected for balanced-current motor differential
digital motor protection relay which in- protection (87M).
cludes three-phase running overload, For larger motors (greater than 1500HP), complete
locked rotor, and short-circuit protec- protection including motor differential can be ob-
tion (49/50); undervoltage protection tained by using the GE Multilin SR469 relay (with
with time delay (27, 62) (only one re- motor mounted CTs).
quired per lineup); 3-phase self-bal-
6-22
Section 6
Excitation Control

Field application equipment or exciter pack- REMOTE CONTROL - For circuit breakers con-
ages for a synchronous motor are typically fur- trolled from a remote location, choose the remote
nished with the motor package. Excitation pack- control scheme from those listed in Section 5,
ages and panels can be sourced and mounted in Table 5-1. From this table, Scheme C is recom-
a switchgear compartment or section. These ap- mended, since it provides maximum operating flex-
plication panels are considered custom design. ibility. If requires the use of a breaker position
switch in conjunction with the breaker control
Indication switch to provide the permissive function. With
Scheme C. remote close and trip is possible only
INSTRUMENTATION AND METERING – The GE with the breaker in the “connected” position; local
Multilin 469 provides extensive metering capabili- close with the breaker in the “test” position; and
ties. For circuits requiring additional or separate local trip with the breaker in the “connected” or
metering, add a GE PQM II power quality meter “test” position.
which includes indication of all three phases of
load current, in addition to Volts, Watts, Vars, PF In addition, remote control for motors requires
and demand functions. a lockout relay (86), which prevents breaker clos-
ing (after a relay-initiated trip) until the lockout
TEST BLOCKS - For circuits that require the pro- device is manually reset. (The 86 device speci-
visions for insertion of portable recording meters fied on SMF2 may be used for both 87M and re-
or other similar devices, add current and voltage mote control.)
test blocks. Basic current test block is wired to
maintain the circuit when the test plug is removed. Location of Optional Devices

INDICATING LAMP - For circuits requiring a cir- If several optional devices are added to a motor
cuit breaker disagreement or spring-charged indi- feeder equipment, there may not be sufficient
cation function, add a white indicating lamp. space to mount them all. In this case, specify
that the excess relays are to be mounted on an
adjacent auxiliary compartment. This makes the
vertical section a custom section.

Figure 6-12 Synchronous Motor Feeder

Switchgear Main Bus

Bus VTs

To Motor
3
2

SR469
W
R G
49/51,50, 26, 27
50/51GS, 83, 47, 59 52
CS 52 86M
37,38,46,48, 87, 81
1 I, V, W, Var, PF , Hz

Option for 3
Bus
Differential
2

Optional Bus
1 VTs, or
Auxiliary Space
for Excitation
Equipment

To 3 Motor
To Motor Differential
36"
CTs at Motor

6-23
Power/Vac® Switchgear Equipment

GENERATORS

DEFINITION Protection

Generator metalclad equipment (GEN) con- FOR GENERATORS ON GROUNDED SYSTEMS


trols and protects a synchronous generator driven - Use ground overcurrent relay connection (51G).
by a steam turbine, gas turbine, a diesel engine,
a gasoline engine, a water-wheel turbine, or a FOR GENERATORS OPERATING IN PARALLEL
motor. The generator may be operated as an iso- WITH OTHER POWER SOURCES ON
lated system source or in parallel with other power GROUNDED SYSTEMS - Add one Type DIFC
sources. The basic equipment specified here is ground relay (51GN). See GER-3011.
adaptable to any of these circumstances with the
addition of the proper optional equipment. Most FOR LARGE GENERATORS (larger than 5000 kW)
generator equipments are custom. - Add loss-of-field relay (40), negative sequence
current relay (46), and voltage-balance relay (60).
BASIC PROTECTIVE SCHEME These features are all available in the GE Multilin
489 digital generator protection relay.
The basic equipment includes no field control
or voltage regulator equipment, since this equip- Synchronizing
ment is normally supplied with the generator and
located in a separate cubicle either adjacent to For manual synchronization of machine to bus,
the generator or near the switchgear. specify a synchronizing panel with two voltmeters,
Basic GEN protection utilizes the GE a frequency meter, a synchroscope, and two indi-
Multilin 489 digital generator protection relay, which cating lamps.
includes three-phase voltage-restrained overcurrent
(51V), ground overcurrent (51G or 50G), reverse For automatic synchronizing, custom pack-
power/anti-motoring protection (32) and generator ages are available. Contact your GE Representa-
differential (87G). Include one Type HEA lockout tive.
relay (86G). The relay operates from three
switchgear mounted CT’s, one in each phase, three Isolated Systems
CTs located at the generator (furnished by the
generator manufacturer) and a set of VTs con- Omit the synchronizing switch and add one
nected to the generator side of the circuit breaker. frequency meter and a voltmeter.

Current Transformers
Field Control and Voltage Regulation
Add three current transformers for lineups that
To obtain field control for remote-mounted field include bus differential protection.
application equipment, add one motor-operated
rheostat control switch and one field ammeter. Indication and Metering

For generators with brushless exciters and For generators requiring supplementary indi-
without remote SC-VT regulators, add one cation and metering, add one GE Type PQM meter
metalclad equipment vertical section containing and current or voltage test blocks as required.
provisions for mounting a voltage regulator,
brushless exciter field control, mounting for an
exciter field rheostat, and an exciter field amme-
ter. Add one or two VT’s and one CT to the gen-
erator circuit breaker vertical section for use with
the voltage regulator, if required.

6-24
Section 6

Figure 6-13 Generator

Switchgear Main Bus

Generator

SR489 52
W
R G
51V, 50/51G
CS 52 86M 27, 47, 59
81, 32, 87G
1 I,V,W,Var, PF

Optional To
3 2
CTs for Ground or Optional Bus
VTs
Bus Neutral
Differential CT
2
2

To
Generator 36"
To Differential
Generator CTs

6-25
Power/Vac® Switchgear Equipment
POWER COMPANY METERING

DEFINITION

Metalclad equipment that contains Util- Consult the serving Utility on your project, for
ity owned metering transformers and meters. their specific requirements regarding metering sec-
These sections are custom, and designed to meet tion design and construction. All metering section
the specific requirements of the specified Utility. designs must be approved by the Utility, prior to
Sections are dedicated for Utility use, therefore manufacture.
cannot contain any Owner/Customer equipment.
Standard designs utilize either 36" wide or 48"
wide sections. Some Utilities require a separate
cable entry or pull section for the incoming cables,
in addition to the metering section. Section
designs can be for “Hot Sequence” (metering
before main disconnect/breaker) or “Cold
Sequence” (metering after main disconnect/
breaker) as shown in Figure 6-14.

Figure 6-14. Utility Metering Arrangements

Utility
CTs
MAIN
52 52 MAIN

Utility
CTs

VTs

Utility
VTs

CPT Utility
VTs
VTs

Utility Section Main Breaker Main Breaker Utility Section


Typical Hot Sequence Metering Typical Cold Sequence Metering

6-26
Figure 6-15.
Standard Power/Vac® Breaker Stacking Configurations
1200A-3000A 1200A-3000A
(3) (7) (2) (5) (2) (6) (3) Bus Entrance Bus Entrance

Aux Blank Blank (9) 1200- Aux (9)


1200A 1200A
Unit Unit Unit Aux Unit 2000A Unit

(4)

1200- 4000A 1200- Aux Aux


1200A 2000A 3500A
3000A (1) Aux Unit 3000A Unit Unit (9)
(3) (3) 1200A-3000A
Bus Entrance

®
Standard
StandardPower/Vac
Power/VAC Tie Breaker
BusBus Stacking
Tie Breaker Configurations
Stacking Configurations

(3) (9) (3) (9) (7) (3) (7) (3) (9) (3) (9)
Aux, Aux, Aux, Aux, Aux,
1200A Breaker 12-2000A Bkr 1200 - Bus Rollout Bus Rollout or 12-2000A Bkr Blank 12-2000A Bkr
or or 2000A (8) Aux (8) Bus Entrance or or
Bus Entrance Bus Entrance Bus Entrance Bus Entrance

Aux, Aux, Aux,


1200 - Bus Rollout Breaker or Breaker or 1200 - Breaker or Bus Rollout 3500- Bus Rollout
3000A
2000A (8) Bus Entrance Bus Entrance 3000A Bus Entrance (8) 4000A (8)

(5) (6)

(1) 4000A breakers require fans on top of structure for forced air cooling.
(2) Blank Unit above 3500A & 4000A breakers have room for device mounting .
(3) Auxiliary Units can contain rollout tray for VTs & CPTs, or additional device mounting.
(4) Full height Auxiliary Units can contain additional device mounting or be used for material storage .
(5) 3500A must be derated to 3250A in outdoor construction.
(6) 4000A is not available in outdoor construction.
(7) Rollouts located above a 3000A breaker, are only available on indoor construction.
(8) Auxilary Bus Ties can contain 1 bus connected rollout tray.
(9) Bus Entrance can also contain a VT rollout tray, or CTs (not both)

6-27
Section 6

Each section in standard indoor construction is 36" W x 95" H x 94" D.


Figure 6-16.

6-28
PT-CPT

A PT-CPT PT-CPT PT-CPT PT-CPT PT-CPT

1200A 1200A 1200- 1200A Blank


2000A 2000A 2000A 2000A
PT PT PT PT PT

PT PT 1200- PT 1200- PT PT PT 1200-


3500A or
3000A 3000A 4000A 3000A
PT-CPT PT-CPT PT-CPT PT-CPT Fuse R/O PT-CPT
B

1 2 3 4 5 6 7 8 9 10

Standard Power/Vac ® Auxiliary Compartment Configurations


1. 4 high auxiliaries capability
2. 1200A/2000A breaker in A, two bus connected rollouts in B
3. 1200A, 2000A or 3000A breaker in B, two line connected rollouts in A (rollouts above 3000A Bkr on indoor construction only)
4. 1200A/2000A breaker in A, two rollouts in B, one line & one bus connected
5. 1200A, 2000A or 3000A breaker in B, two bus connected rollouts in A (rollouts above 3000A Bkr on indoor construction only)
6. 1200A/2000A breaker in A, with line connected rollout in superstructure. Two rollouts in B, line connected
from adjacent section (1200A, 2000A or 3000A breaker)
7. 1200A/2000A breaker in A, two rollouts in B, one line connected fused R/O, with large CPT mounted in rear
8. 3500A/4000A breaker in B compartment with line connection to adjacent section 9. A compartment must beblank
9. Two rollouts in A or B compartments, line connected to 3500A/4000A breaker in adjacent section 8,
Rollouts can be combination of line or bus connected.
10. 1200A, 2000A or 3000A breaker in B, one line and one bus connected rollouts in A (rollouts above 3000A Bkr on indoor construction only)

NOTE: ALL ROLLOUT TRAYS ARE HARD BUS CONNECTED. NO CABLE CONNECTED TRAYS.
Power/Vac® Switchgear Equipment

A Compartment B Compartment
Rollout Unit Devices Ratings
Lower Upper Lower Upper
VT 2 - VTs (1) 5KV through 15KV Yes Yes Yes Yes
VT 3 - VTs (1) 5KV through 15KV Yes Yes Yes Yes
CPT 1 - CPT (1) 5, 10, 15KVA No Yes Yes No
Fused Unit 1 - CPT (2) 25, 37.5KVA (4) Yes N/A Yes N/A
Fused Unit CPT Fuses (3) Remote 225kVA Max Yes N/A Yes N/A

(1) Fuses are an integral part of VT or CPT. CPTs are single phase
(2) CPT is installed in the rear cable compartment. CPT fuses are installed in a key interlocked fuse rollout in the Lower A or Lower B compartment
(3) Fused rollout tray must be key interlocked with remote CPT secondary breaker
(4) Contact GE Sales Office for availablity of larger CPTs or 3-phase bank.

Das könnte Ihnen auch gefallen