H2 COOLER
EXCITER COOLER
SEAL OIL COOLER (AIR SIDE)
SEAL OIL COOLER (H2 SIDE)
PRIMARY WATER COOLER
EXCITATION SYSTEM
GAS SYSTEM
GENERAL
MAKE BHEL
TYPE THDF 115/59
CODE IEC 34-1, VDE 0530
COOLING
STATOR WINDING DIRECTLY WATER COOLED
STATOR CORE, ROTOR DIRECTLY HYDROGEN
COOLED
RATING
APPARENT POWER 588 MVA
ACTIVE POWER 500 MW
POWER FACTOR 0.85 (LAG)
TERMINAL VOLTAGE 21 KV
PERMISSIBLE VARIATION IN VOLTAGE +/- 5%
SPEED /FREQ RPM/ Hz 3000/50
STATOR CURRENT 16200 Amps
HYDROGEN PRESSURE Kg/cm2 4
SHORT CIRCUIT RATIO 0.48
FIELD CURRENT (CALCULATED VALUE) 4040 Amps
CLASS & TYPE OF INSULATION MICALASTIC (SIMILAR TO
CLASS F)
NO. OF TERMINAL BROUGHT OUT 6
RESISTANCE IN OHMS AT 20 OC (UNIT # 6)
STATOR WINDING BETWEEN TERMINALS
U-X 0.0014132
V-Y 0.0014145
W-Z 0.0014132
ROTOR WINDING F1-F2 0.0672
MAIN EXCITER
ACTIVE POWER 3780 KW
CURRENT 6300 A
VOLTAGE 600V
PILOT EXCITER
APPARENT POWER 65 KVA
CURRENT 195 A
VOLTAGE 220 V (1+/- 10%)
FREQUENCY 400 Hz
GENERATOR PROTECTION
Generators are high quality for securing the best possible continuity of power supply.
In addition to a suitable technical design &responsible mode of operation, provision has
therefore been made for automatic protection facility. The following protection have been
provided in the 500 mw TG.
NTPC/SINGRAULI
DC SUPPLY SYSTEM FAILURE
220 V D.C POWER FAILURE IN STAGE -I (5X200MW)
INDICATIONS & CONSEQUENCES:
1. Annunciation of “LOSS of 220 V DC supply” will appear.
1. 220 V DC Voltmeters reading at generator panel & DCDB will show ZERO V.
2. MFR, TLR & UTR will not actuate, however,
a. All coal feeders will TRIP.
b. All Hot air gates will CLOSE.
c. All HONV will CLOSE.
d. HOTV & HORV will not OPERATE from UCB.
e. Generator and Turbine will continue to RUN
f. PSW pumps will TRIP.
g. Speeder Gear motor will become INOPERATIVE from UCB.
h. Field breaker status indication will DISAPPEAR. However breaker will continue to
be in CLOSED CONDITION.
3. 6.6 KV auxiliaries will continue to run, however,
a. Their Interlocks & protection will not work.
b. Their indicating lamps will NOT GLOW but ammeters will show the current.
c. Scoop position of all BFPs will come down to MINIMUM. & recirculation valve will
open.
NTPC/SINGRAULI
2
INSTRUCTIONS FOR SAFE SHUT DOWN OF UNIT
1. On DC failure PSW pump will trip. Immediately rush to Start PSW pump motor by
switching on overhead switch provided inside the PSW/SSW panel at ‘0’ meter.
2. Gradually reduce load locally by manual operation of speeder gear hand wheel up to 5
to
10 MW.
3. As a parallel action, inform SCE /ASCE on station paging.
4. Inform unit # 1 UCE to start DG set
5. In case of abnormalities Such as :
Main steam temperature less than 465 Dec C
Stator slot temp. more than 90 Dec C
Drum level high-high.
Following action to be taken:
_ Hand trip the Turbine from local.
_ Trip Generator breaker.
_ Mechanically trip field breaker
_ Open the vacuum breaker.
_ Mechanically trip UATs A and B incomer breakers.
_ Mechanically Charge EMCC by closing DG set incomer after
mechanically tripping the incomer breaker from USS.
_ Start AC lube oil pump from ATRS panel
_ Start AC seal oil pump by operating over ride switch in local panel,
_ Start PSW pump motor by switching on overhead switch provided inside
the PSW/SSW panel at ‘0’ meter.
_ Voltage and frequency of DG set should be watched closely
_ Ensure lube oil and seal oil system is normal. Put the Turbine on barring
gear.
_ In case of seal oil failure, purge out H2 gas and fill CO2 & Inform all the
concerned.
_ Trip all HT motor breakers manually
NTPC/SINGRAULI
3
6.2.0 220V DC POWER FAILURE IN STAGE –II(2X500MW)
INDICATIONS & CONSEQUENCES:
- Annunciation of “LOSS of 220 V DC supply” will appear.
- 220 V DC Voltmeters reading at generator panel & DCDB will show ZERO V.
- All coal feeders will TRIP.
- 6.6 KV auxiliaries indicating lamps will NOT GLOW. However ammeters will show the
running status.
- 0.4 KV auxiliaries indicating lamps will NOT GLOW. However ammeters will show the
running status.
- Boiler will trip on loss of 220V DC power. HOTV will not get closed, however, HONV
will get close through MFR.
- Turbine will trip (as +/-24V DC supply is available).
- Interlock & protection of C&I system will remain out.
- Generator will not trip and as turbine has tripped “Motoring” will take place.
- Air side SOP will continue to run. H2 side SOP will trip. No alarm /annunciation will be
available at CXW 01 panel only ammeter will indicate whether motor is running or not.
- 50% protections of generator on DC 1 from same unit will be out and remaining 50%
protection on DC 2 from other unit will be in service.
INSTRUCTIONS FOR SAFE SHUT DOWN OF UNIT
1. Run the DG set from control room. Ensure correct selection of DC source at local
control panel of DG set.
2. Charge the EMCC after Mechanically opening incomer breaker from USS-A. In case
of non-availability of DG set, charge the Emergency MCC from the other Unit
after Mechanically tripping the incomers from USS-A and DG set
3. Hand Trip Generator Breaker from control room. Then trip field control breaker
manually in equipment control room CJN 1 panel.
4. Run AOP from ATRS panel and SOP from CXW panel after charging EMCC. Ensure
SOP running, failing which H2 purging should be initiated.
5. Trip the 6.6KV breaker of UAT-A and UAT-B manually from local. Unit bus will be
dead as tie will not come in service due to DC failure.
6. Run the standby air compressors from healthy units.
7. Put the Machine on barring gear.
8. Keep a close watch on Turbine, Boiler and Generator parameters.
NTPC/SINGRAULI
4
Loss of DC to UPS (5x200 MW Stage-I & 2x500 MW stage-II)
Two numbers inverters and three numbers UPS chargers, with batteries banks, are
provided
for individual units. In case of Loss of UPS DC supply, UPS supply will change over to
standby alternate AC source and unregulated AC supply will remain available for C&I
system
since AC supply is available.
Indication/Consequences
Following annunciations will appear on loss of DC to inverters.
- UPS charger A/B/C trouble &/or
- UPS Inverter A/Static switch A trouble &/or
- UPS inverter B/Static switch B trouble.
ACTION:-
- Inform HOD (C&I), HOD (Opn.) and Shift Charge Engineer.
- Check for any abnormalities in UPS charger room as well as battery room.
- After removal of fault take inverter back into service with the help of C&I Engineer.
Loss of ±24 volt D.C. (5x200 MW Stage-I)
SOP, ACLOP, DCLOP, Speeder gear, valves etc on ATRS panel will not operate either on
auto or manual from ATRS panel. However DC LOP can be started from the direct on/of
switch on UCB. In the same way AC LOP can also be started from direct on/of switch in
unit
number 1 & 3 (for other units the switch is being provided in shutdown).
NTPC/SINGRAULI
5
Loss of ±24 volt D.C. (2x500 MW Stage-II)
Two Numbers (+)24V and two Numbers (-)24V battery chargers along with (+)24V
battery
bank of 1500 AH & (-) 24V battery bank of 600 AH are provided to each 500MW Units.
Indication/Status
- Loss of + 24 volt D.C. Power supply fail alarm will appear on “AN D 010” fascia window
- ATRS panel indication will not glow
- Turbine trip will not get actuated.
- Loss of excitation & GCB trip
- All controllers output of ATRS will become ZERO.
- Turbine control through ATRS will remain out.
ACTION:-
- Inform SCE.
- Take necessary action for early & safe shut down of unit.
- Run DC seal oil p/p from local.
- Run DC Lube oil p/p from local.
- Station one responsible person in the MOT room who will start JOP at TG speed < 500
rpm
on instruction of control engineer.
- Hand trip the turbine from local.
- Trip the generator breaker and boiler in case they do not trip on protection.
- Identify the fault and restore the system.
NOTE:-1. Do not take chance to run the unit on loss of 24V DC.
2. Try to take shut down of unit before 24V DC voltage falls to Zero.
NTPC/SINGRAULI
6
Switchyard DC Supply (For Protection & Control system) failure
There are two sets of Batteries for 400/132 KV Switch yard.
Main - 1 Batteries: 300AH/220 volts (110 cells) batteries
Main - 2 Batteries: 300AH/220 volts (110 cells) batteries
Both Main-I/Main-II remain in the service for Indication, Control, Protection and
Emergency light in
control room, charger room, Compressor room and cable galleries.
Indication/status when 220 volts DC Supply Main 1 fails.
- “DC Supply Failed” annunciation will appear
- Trip coil 1 faulty flag on all 400 kV CB & trip coil faulty flag on all 132 kV panels will
come
- 220V DC Voltmeter of DC1 mounted on top of 400 kV control panel and at float charger
panel will show Zero
- Indicating lamps of 400/132KV breakers and isolators will not glow in control room and
in
yard local control panel.
- All breakers/Isolator “ON” or “OFF” status will remain same. However Ammeters will
show
current
- Hand tripping operation of any feeder will not be possible.
- Protection tripping from DC1 will fail but from DC2 will remain in service for 400 kV
feeders
- All protection tripping for 132 kV feeders will fail.
Indication/status when 220 volts DC Supply Main 2 fails.
- “TC-2 Faulty” annunciation will appear on 400 kV breakers
- 220V DC Voltmeter of DC 2 mounted on top of 400 kV control panel and at float
charger
panel will show Zero
- Hand tripping as well as protection trip of feeders through DC 1 will be in service for all
400
kV panel as well as 132 kV panel
- Protection tripping from DC 2 will be out of service for 400 kV feeders.
Instructions when DC Supply Main 1 fails
- Change annunciation /supply to DC-2 at Bus section panel.
- If restoration of Main - 1 DC is not possible within 2 to 3 hours, decision to shut down
by
initiating protection trip to be taken for 400KV feeders.
- No protection/tripping will be possible for 132KV feeders. However 132 kV will be dead
after
tripping all 400 kV feeders.
NTPC/SINGRAULI
7
Instructions when DC Supply Main 2 fails
- Eforts for restoration of DC –II supply to be taken up. If same is not possible within 5 to
6
hours decision to shut down through hand trip is to be taken for 400KV feeders.
- 132KV Feeders will be healthy and available for 132KV panels only DC-1 has been
provided.
(For 132 kV panel DC-2 is also from same DC DB. This will be connected in due
course).
Instructions when both DC Supply Main-1 & Main-2 fail
simultaneously
- Eforts to be made to restore at least one of DC-1 or DC-II after which selective tripping
can
be taken p as may be decided.
- Using a 220V DC + emergency source tripping of all units one by one can be initiated.
- In extreme cases, emergency trip provided on ABCB’s, MOCB’s and unit 4/5 Generator
CB’s
can be actuated to isolate units 1 to 5 Unit 6 & 7 having SF6 CB will not be possible to
be
isolated.
- The lines can be got tripped from other end as required.
Switchyard 50 Volts PLCC DC supply failure
PLCC battery, 500 AH 50 volts (24cells) battery. In case of 50 volts PLCC D.C. Supply
failure:
Indication/Status.
- Annunciation of “Carrier’s protection fail” will appear 50V DC Voltmeter reading : Zero
volt
(on PLCC DCDB)
- PLCC will fail & there will be no speech communication from other stations.
- Protection system will fail though PLCC however on unit basis protection system will
remain
in service there will be no tripping through PLCC i.e. No feeder tripping will take place in
case
of tripping from other end.
Instructions
- Immediate action to be taken for normalization of D.C. supply to PLCC.
- Operator should rush to PLCC D.C.D.B. battery room / battery charger room to check if
any
fire has taken place/fuses blown.
- At least portable battery charger/temporary supply should be taken in service with the
help of
Electrical Maint.
NTPC/SINGRAULI
8
C.W. System D.C. Power Supply System
CW has two sets of 50 volt battery each having 24 cells and 1000 Ah capacity.
- 50 Volts DC supply have been used for all 6.6 kV & 0.4 kV breaker ON/OFF indication,
their
control panel indication and their protection and control system.
- For relay panel/control panel.
- For emergency light in CW pump house and CW switchgear.
- For emergency closure of 2 x 500MW CW pump discharge valve.
Indications in case of DC supply failure.
- 50 Volts DC volt meter will show zero reading at DCDB
- None of the indicating lamps on 6.6KV CW buses, control panel of both CW pumps
houses
as well as Relay panel in switchgear will glow.
- All pumps running status will remain same and pump running status can be known by
their
ammeter reading. However for emergency trip operation breaker can be tripped through
mechanical trip at breaker.
- In stage-I, CW discharge valve status will remain same as it was prior to DC failure.
The
valve operations should be done manually.
- In stage-II, CW discharge valve will close on DC supply failure, thus loss of DC supply
is
detrimental to Stage-II CW pumps as pumps
INSTRUCTIONS:
On 6.6 kV buses DC selection is provided in Bus VT panel. On failure of DC, go to
switch
board & put above selection from DC1 to DC 2 or vice versa
Condition 1: Only DC 1 fails
a) Put selector switch of DC at bus VT panels of 6.6KV to DC 2.
b) Put selector switch at Bus coupler of LTMCC stage-I to DC 2.
c) Transformer protection is out. Trip transformer from 132KV yard manually if
required. (For 6.6KV Bus A & Bus B only DC 1 is provided. Provision of DC2
through selector switch yet to be made available.)
d) Put of DC 1 and switch on DC 2 at dist board located at Auxiliary Pump house.
Try restoration of DC 1.
NTPC/SINGRAULI
9
Condition 2: Only DC 2 fails
a) Put selector switch of DC at bus VT panels of 6.6KV to DC 1.
b) Put selector switch at Bus coupler of LTMCC stage-I to DC 1.
c) Transformer protection is out. Trip transformer from 132KV yard manually if
required. (For 6.6KV Bus A & Bus – B only DC 1 is provided. Provision of DC2
through selector switch yet to be made available.)
d) Put of DC 2 and switch on DC 1 at dist board located at Auxiliary Pump house.
Try restoration of DC 2
Condition 3: Both DC sources fail
a) Immediately trip 500MW CW pumps by tripping transformer C and D from 132 KV
switchyard Control room.
b) Stage-I will remain in operation without protection and control DC try restoration of at
least one DC. If not possible trip entire stage-I from 132KV C.R
(Loss of DC Supply is detrimental to 2X500MW CW Pumps because
pumps will keep on
running on shut off head)
SPECIFICATION OF TRANSFORMERS
GENERATOR TRANSFORMER
MANUFACTURER BHEL
NO. OF UNITS 3
RATING HV & LV (MVA) 200 MVA
NO LOAD VOLTAGE, HV 400 / 3 KV
NO LOAD VOLTAGE, LV 21 / 3 KV
RATED CURRENT, HV 866.0 Amp
RATED CURRENT, L 9523.8 Amp
NO. OF PHASES 1
FREQUENCY 50 Hz
TYPE OF COOLING FORCED OIL & FORCED WATER
CONNECTION SYMBOL WHEN YN 11
FORMED A BANK
IMPEDANCE AT PRINCIPLE TAP 15% MAX
ON LOAD TAP CHANGER TAPPING IN 12 EQUAL ATEPS OF
1.25% EACH PROVIDED ONHV
WINDING TO GIVE (+) 10% TO
(-) 5%
TEMPRATURE RISES VARIATION OF HIGH VOLTAGES
i) OIL BY THERMOMETER 50 OC
ii) WINDING BY RESISTANCE 60 OC
OTI & WTI, AUXILIARY CONTACTS
SETTINGS
i) OTI ALARM 85 OC
TRIP 90 OC
ii) WTI ALARM 105 OC
TRIP 115 OC
STATION TRANSFORMER
MANUFACTURER NGEF
NO. OF UNITS 2
CAPACITY 20/35/50 MVA
VOLTAGE RATIO 132/6.9/6.9 KV
VECTOR GROUP Y/Yno/Yno
COOLING FORCED OIL & FORCED AIR
UNIT AUXILIARY TRANSFORMER
MANUFACTURER NGEF
NO. OF UNITS 4
CAPACITY 25 MVA
VOLTAGE RATIO 21/6.9 KV
VECTOR GROUP DYN
COOLING NATURAL OIL & FORCED AIR
PERCENTAGE IMPEDANCE 7.8%
CW TRNSFORMER
MANUFACTURER NGEF
NO. OF UNITS 1
CAPACITY 25 MVA
VOLTAGE RATIO 132/6.9 KV
VECTOR GROUP Y/Yn
COOLING ONAF
PERCENTAGE IMPEDANCE 0.135 +/- 10%
ESP TRNSFORMER
NO. OF UNITS 4
CAPACITY 2000 KVA
VOLTAGE RATIO 6.6 KV / 0.433 KV
VECTOR GROUP DYn1
ASH SLURRY TRNSFORMER
NO. OF UNITS 3
CAPACITY 1600 KVA
VOLTAGE RATIO 6.6 KV / 433 V
PERCENTAGE IMPEDANCE 0.08 +/- 10%
STATION SERVICE TRNSFORMER
NO. OF UNITS 4
CAPACITY 1600 KVA
VOLTAGE RATIO 6.6 KV / 0.433 KV
VECTOR GROUP DYO1
PERCENTAGE IMPEDANCE 0.08 +/- 10%
WTP SERVICE TRNSFORMER
NO. OF UNITS 2
CAPACITY 1000 KVA
VOLTAGE RATIO 6.6 KV / 0.433 KV
VECTOR GROUP DYO1
PERCENTAGE IMPEDANCE 0.05 +/- 10%
CHP TRNSFORMER
NO. OF UNITS 4
CAPACITY 1600 KVA
VOLTAGE RATIO 6.6 KV / 433 V
UNIT SERVICE TRNSFORMER
NO. OF UNITS 4
CAPACITY 1600 KVA
VOLTAGE RATIO 6.6 KV / 0.433 KV
VECTOR GROUP DY1
PERCENTAGE IMPEDANCE 0.08 +/- 10%
CW PUMP HOUSE SERVICE TRNSFORMER
NO. OF UNITS 2
CAPACITY 630 KVA
VOLTAGE RATIO 6.6 KV / 0.433 KV
VECTOR GROUP DYn1
PERCENTAGE IMPEDANCE 0.05 +/- 10%