Beruflich Dokumente
Kultur Dokumente
Table: Architecture
Function Enterprise Server Automation Server Comment
Number of concurrent 5 5 –
mobile connections
Table: LonWorks
Function Enterprise Server Automation Server Comment
a) Xenta 280/300/401 needs to be of version 3.6 or higher. In version 3.8, a new feature improves the performance up to 500%
when reading values in StruxureWare Building Operation.
b) When using both LonWorks and BACnet MS/TP networks on the Automation Server, the network with more than 10 devices
connected is considered to be the main network. The other network then supports up to 10 devices. The main network will
support the number of devices specified in the table for the used protocol. For example, if the Automation Server has 64
LonWorks devices connected to it, the BACnet MS/TP network can support 10 devices.
Table: Modbus
Function Enterprise Server Automation Server Comment
Maximum number of 2 2 –
concurrent TCP client
connections when acting as
TCP server
Table: BACnet
Function Enterprise Server Automation Server Comment
Maximum number of 64 64 –
foreign devices per sever
© 2013 Schneider Electric. All rights reserved.
a) When using both LonWorks and BACnet MS/TP networks on the Automation Server, the network with more than 10 devices
connected is considered to be the main network. The other network then supports up to 10 devices. The main network will
support the number of devices specified in the table for the used protocol. For example, if the Automation Server has 64
LonWorks devices connected to it, the BACnet MS/TP network can support 10 devices.
Number of records per N/A 500 Built-in logs for all I/O
implicit log module points; not
changeable
Table: Alarms
Function Enterprise Server Automation Server Comment
Table: Events
Function Enterprise Server Automation Server Comment
Backup operations
Back up the system when users are not interacting
with the servers or the system. In larger systems,
Figure: Enterprise Server sending values
the scheduled backups of the Automation Servers
Enterprise Server communication load are recommended to be split over time.
In addition to the above strict limitations, the total
communication load on the Enterprise Server must Automation Server database
be considered. This includes events, extended The Automation Server database has a limit of
trend logs, and alarms. In systems with significant 104,000 objects. This limitation is normally more
communication load, the following than adequate but might be restrictive if a
recommendations exist: significant number of LonWorks devices are used.
• The performance of the PC is important. Use A trend log with thousands of records is counted as
solid-state drive, in combination with significant only one object.
RAM memory size and CPU performance.
You can see the number of objects the database
• Install the Enterprise Server on a solid state contains in the Tree size property of the
drive and the Enterprise Server database to a System/Modules/RuntimeDBManager/RtDb Object
second disk (RAID). Tree object.
• The size of the database impacts backup and
upgrade time. Limit the total size of the Concurrent users
historical database by limiting the size and User type definitions:
quantity of the extended trend logs.
• Don't schedule all the reports to be generated • An operator views and monitors the system
at the same time. and can make changes to the system, such as
create trend logs, alarms, schedules, users,
Design considerations and perform some object property changes.
Load measurements • An engineer also makes other changes to the
There are two server properties that are relevant for system that are typically not supported by
understanding the load on the Automation Server: WebStation, such as create and change
Graphics, Function Block, and Script objects;
• Memory usage (%) create devices; import and export; and backup
and restore.
• CPU usage (%)
The server accepts one change at a time and
© 2013 Schneider Electric. All rights reserved.
The Memory usage (%) property measures the queues up concurrent changes. Changes made by
current RAM memory usage. The memory usage an operator are quickly handled by the server and
should never exceed 80 %. No peaks should be no noticeable delay occurs when the changes
seen above this limit. queue up. Some of the engineering changes might
take a longer time. Changes made during that time
The CPU usage (%) property measures the current are handled by the server when the engineering
CPU load in the Automation Server. The CPU change is finished.
usage should stay below 80 %. It is normal that the
CPU usage peaks at 100 % on occasion when
lower priority activities are performed. This peak
does not affect the overall performance.
The transfer interval when a Function Block or To limit unnecessary communication, create
Script program input gets a value from another BACnet objects in the server, and if possible, use
Automation Server equals the program cycle time. COV to avoid polling. Use alarms and trend logs in
The transfer intervals for these values are in many the server to monitor the BACnet objects.
cases unnecessarily short. Create a server value so
you can change the transfer interval manually for a Modbus
program input:
Multi-read is supported, but not multi-write.
• Create a server value on the Automation Server
To be able to use the maximum number of Modbus
where the program resides.
RTU devices when the Automation Server is the
• Bind the server value to read the value from the master, both COM ports must be used for Modbus.
other Automation Server. If one of these ports is used for BACnet MS/TP, the
supported number is limited to half.
• Configure the transfer interval.
• Bind the server value to the program input. Modbus only allows you to poll values, so alarms
monitoring Modbus values consume bandwidth
If short update intervals are required, monitor the
and will at some point affect the network
CPU and memory usage of the Automation Server
performance. To avoid this, create a server value so
where the value resides.
you can manually change the transfer interval for an
alarm:
Field busses
All field busses • Create a server value on the Automation Server
where the alarm resides.
Do not use the change of value trend log type to
© 2013 Schneider Electric. All rights reserved.
monitor a value outside of the Automation Server • Bind the server value to read the value from the
where the trend log resides. Modbus device.
• Configure the transfer interval.
If possible, avoid having the Automation Server poll
values for alarms or trend logs from devices on a • Bind the server value to the alarm.
field bus. Instead, use the capabilities of the field
bus protocol to transfer the value to the Automation
Server where the alarm or trend log resides.
I/O modules supply, the second slot for the Automation Server,
The I/O module bus supports 32 devices. This limit and the remaining slots are used for the I/O
is determined by the terminal base hardware and modules and if needed, additional PS-24V power
cannot be extended. Out of the 32 addressable supplies.
slots, the first slot is used for the PS-24V power