Sie sind auf Seite 1von 3

-

C X10
+
C
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 U X20
S
LD32 LD30 LD28 LD26 LD24 LD22 LD20 LD18 LD16 LD14 LD12 LD10 LD08 LD06 LD04 LD02 T 6 -
O
M 5 +
LD31 LD29 LD27 LD25 LD23 LD21 LD19 LD17 LD15 LD13 LD11 LD09 LD07 LD05 LD03 LD01
E 4 -
F101 F117 F150 F151 R 3 +
126

D100

D101

Alarm
PEPPERL+FUCHS 2
L
A 1
B
2 50 (T1A) (T1A) (T2A) (T2A) E

D103

D104
2 50 L Alarm
X1B 1 1 49 49 Ch.1-16 Ch.17-32 PW1 PW2
LD101 LD117 LD150 LD151 DIN-Rail
X1A K1
2 50
2 50
1 1 49 49
TB-C3-DI32-AKB-Y188683

216 max. 67

Technical Description
Field termination: X10 Pressure clamp terminal 24 V DC / 6 mA , max. 100 mA per channel
System connector: X1A, X1B 50 pin YO50 (AKB331) DI
Power feed: X20.3 ... 6 Redundant Power feed 24 V DC SELV/PELV / 2 A, max. 3,15 A
Alarm: X20.1, X20.2 Power Alarm Relay contact max. 30 V DC, 1 A
F101; 117 Fuse channels 1...16 and 17...32 1 A, max. 1,5 A
F150; 151 Power feed fuse 2 A, max. 3,15 A
X20 6 pin screw terminal (removable) Power feed terminal

Function: Termination-Board to connect to the Yokogawa CS 3000 R3 I/O card. The TB System connector X1A/X1B links to the Yokogawa I/O card via a standard cable
supplied by Yokogawa. Two system connectors in parallel allow for redundant applications. The connections X10 to/from the field are clamp terminals. The unit has a 24 V DC
redundant power supply feed, monitored by a potential free relay contact. (X20. 1, 2) LED PW1, PW2 and Alarm indicate the actual power status. Loops are powered directly from
the board: 3-wire sensor, potential free contact, active voltage surce (see circuit diagram). Two groups (Ch. 1 ... 16 and Ch. 17 ... 32) are separatly fused (F101, F117). Fuses are
supervised and monitored by the Alarm relay. The board is designed to be mounted on DIN-Rail (DIN EN5022).

Circuit diagram X20


1

Alarm 2
X1A/X1B
0V 12, 14, 16, 18
3
+
+24 V DC COM1 ... 16
PW1/24 = - 4
Power supply
11, 13, 15, 17
monitoring
F101

F117

+ 5
COM17 ... 32
PW2/24 = - 6 1
& CBSE
2
CBSE
X10
01C 50
IN-1
01+ Yokogawa
01-
R LD01 AKB-System cable ADV151
C
. .
ADV161
+ . .
. ch. 1...16 .
. .
- 16C LD101 R1-16
20
IN-16
C 16+

+ 16-
R LD16
Yokogawa
49 AKB-System cable ADV151
unauthorized distribution and reproduction prohibited

17C
C IN-17
17+ ADV161
17-
- R LD17
. .
. .
. ch. 17...32 .
. .
32C 19
LD117 R17-32
IN-32
32+
32-
R LD32
copyright according to DIN34

Options: TB-C3-DI32-SCSI50: PN XXXXX (36-9318_2) with SCSI connector 22.11.05 Bro DG/-- --/--
Date S Off. contr. contr.
TZ
in ch. techn. Norm
FI-Module Dept.: PA-PG-TB No.36-9318i1
PEPPERL+FUCHS Non IS termination board DG Replaces:
Up date: Sheet 1
DI 32 channels - redundant 05.06.14 xxxxx / 36-xxxx
Mannheim-Schönau
TB-C3-DI32-AKB-Y188683 Scale: 1:2 of 3
Channels 1 ... 16 Channels 17 ... 32
X1B X1A X1B X1A
Field X10 YO YO Ch. Field X10 YO YO Ch.

C C
50 50 49 49
1 +
R IN-1 17 +
R IN-17
LD01 LD17
- -
C C
48 48 47 47
2 +
R IN-2 18 +
R IN-18
LD02 LD18
- -
C C
46 46 45 45
3 +
R IN-3 19 +
R IN-19
LD03 LD19
- -
C C
44 44 43 43
4 +
R IN-4 20 +
R IN-20
LD04 LD20
- -
C C
42 42 41 41
5 +
R IN-5 21 +
R IN-21
LD05 LD21
- -
C C
40 40 39 39
6 +
R IN-6 22 +
R IN-22
LD06 LD22
- -
C C
38 38 37 37
7 +
R IN-7 23 +
IN-23
LD07 LD23
- -
C C
36 36 35 35
8 +
R IN-8 24 +
R IN-24
LD08 LD24
- -
C C
34 34 33 33
9 +
R IN-9 25 +
R IN-24
LD09 LD25
- -
C C
32 32 31 31
10 +
R IN-10 26 +
R IN-26
LD10 LD26
- -
C C
30 30 29 29
11 +
R IN-11 27 +
R IN-27
LD11 LD27
- -
C C
28 28 27 27
12 +
R IN-12 28 +
R IN-28
LD12 LD28
- -
C C
26 26 25 25
13 +
R IN-13 29 +
R IN-29
LD13 LD29
- -
C C
24 24 23 23
14 +
R IN-14 30 +
R IN-30
LD14 LD30
- -
C C
22 22 21 21
15 +
R IN-15 31 +
R IN-31
LD15 LD31
- -
unauthorized distribution and reproduction prohibited

C C
20 20 19 19
16 +
R IN-16 32 +
R IN-32
LD16 LD32
- -
X20 0V
1 1 CBSE
5(+) + 24 V DC
2 2 CBSE
F101

6(-)
F117

3..10 3..10
Power feed

R1-16 R17-32
3(+) n.c. n.c.
12 12 11 11
LD101

LD117

4(-)
COM17-32
COM1-16

1
Power 14 14 13 13
copyright according to DIN34

A B
2
supply
16 16 15 15
monitoring
18 18 (A, B) see circuit diagram page 3 17 17

22.11.05 Bro DG/-- --/--


Off. contr. contr.
Date S TD
in ch. techn. Norm
FI-Module Dept.: PA-PG-TB No. 36-9318i1
PEPPERL+FUCHS Non IS termination board DG Replaces:
DI 32 channels - redundant Up date: 05.06.14 xxxxx / 36-xxxx Sheet 2
Mannheim-Schönau
TB-C3-DI32-AKB-Y188683 Scale: -:- of 3
Connection power supply and error message (Alarm)
single redundant
power supply power supply
Alarm or Alarm (minus 4, 6 interconnected on board)
1 2 3 4 5 6 1 2 3 4 5 6
PCB X20 X20

External
Powersupply 1
wiring
Powersupply 2

Alarm output
(Dry contact NO)
(Steady current)

Alarm LD indication and contact status


LD red
Power supply 1 Power supply 2 LD green X20.1, X20.2 Alarm contact (Flashing)
LD150 ON
PS ON and Fuse 150 OK PS ON and Fuse 151 OK contact closed LD135 OFF
LD151 ON

LD150 ON
PS ON and Fuse 150 OK PS OFF contact open LD135 ON
LD151 OFF

LD150 OFF
PS OFF PS ON and Fuse 151 OK contact open LD135 ON
LD151 ON

LD150 ON
PS ON and Fuse 150 OK PS ON and Fuse 151 broken contact open LD135 ON
LD151 OFF

LD150 OFF
PS ON and Fuse 150 broken PS ON and Fuse 151 OK contact open LD135 ON
LD151 ON

LD150 OFF
PS ON and Fuse 150 broken PS ON and Fuse 151 broken contact open LD135 OFF
LD151 OFF

LD150 OFF
PS OFF PS OFF contact open LD135 OFF
LD151 OFF

LD101 OFF
F101 or 117 broken contact open LD135 ON
LD117 OFF
unauthorized distribution and reproduction prohibited
copyright according to DIN34

22.11.05 Bro DG/-- --/--


Off. contr. contr.
Date S TD
in ch. techn. Norm
FI-Module Dept.: PA-PG-TB No. 36-9318i1
PEPPERL+FUCHS Non IS termination board DG Replaces:
DI 32 channels - redundant Up date: 05.06.14 xxxxx / 36-xxxx Sheet 3
Mannheim-Schönau
TB-C3-DI32-AKB-Y188683 Scale: -:- of 3

Das könnte Ihnen auch gefallen