Version V1.0
Revision date
BOM
Emerson Network Power provides customers with technical support. Users may contact the
nearest Emerson local sales office or service center and company headquarters.
Chapter 1 Preface
This chapter mainly introduces the special requirements on the equipment room environment and the features and
advantages of Liebert_DM series air conditioners (AC for short).
J14 Monitoring
ON
J12 Display board power supply
J18 SCR output J39 Display board data line
to contactor J21 Switch input, such as high
pressure switch
J31 DI input power supply
Outstanding man-machine interface: The Liebert_DM series ACs provide a large Chinese/English LCD, a
user-friendly man-machine interface and an expert diagnosis system, as well as implement multi-level password
protection (avoid misoperation) and intelligent display of running states.
High reliability: Relying on the excellent quality and considerate services of Emerson, the Liebert_DM series ACs
ensure 24-hour reliable running all year round.
Strong adaptability to power grid: The Liebert_DM series ACs allow a wide range of voltage and provide the
following distinctive functions: unique phase loss protection, phase-sequence detection and protection, automatic
high-voltage & low-voltage detection and protection, self-recovery upon power failure.
All-weather operation: According to the distinct heating load feature of equipment rooms, the Liebert_DM series ACs
implement 24-hour running all year round in temperature ranging from -15°C to +45°C. If a Lee-Temp outdoor unit is
configured, the allowed running temperature ranges from -34°C to +45°C.
Strong network management: Being configured with a standard RS485 monitor interface, the Liebert_DM series
ACs implement flexible automatic switchover between active and standby devices, work shift, remote turn-off and
turn-on, remote alarm, and fault query and troubleshooting over standard telecommunication protocols.
Easy maintenance: The Liebert_DM series ACs provide a full front maintenance structure, facilitating maintenance.
Table 1-1 describes the differences between the Liebert_DM series ACs and commercial ACs.
Table 1-1 Differences between the Liebert_DM series ACs and commercial ACs
Design focus Liebert_DM series AC Commercial AC
Precision ±1°C; ±1%RH Generally ±3°C
Temperature control Humidifying and dehumidifying control None in general
Monitoring Local and romote monitoring None
All-rear-round continually operating All-year-around cooling No cooling needed in winter
Testing before delivery Strict requirement Simple testing
Control design Precise control CPU
Cleanliness High Low
Chapter 2 Overview
This chapter expounds the appearance, model description, product introduction, components and variety of accessory
options.
2.1 Appearance
Taking the indoor unit of the Liebert_DM series air conditioner as an example, the appearance as shown in Figure 2-1.
DM E 07 M C T 1
1: Standard; 2: High efficiency
Version code
C: cooling only; O: with heater; H: with heater and humidifier
Input power supply. M: 380V-3-ph-50Hz
Cooling capacity. 07: 7.5kW ; 12: 12.5kW
E: indoor unit; C: outdoor unit; L: Lee-Temp outdoor unit
Liebert_D series air conditioner
The Liebert_DM AC provides a micro-processing controller that can automatically switch over to the required function
(cooling or heating, dehumidifying or humidifying), based on the programmed setpoints and room ambient conditions.
Each Liebert_DM AC consists of an indoor unit and an outdoor unit. Both units are installed on the floor separately.
Indoor unit
The Liebert_DM AC includes units with a cooling capacity of 7.5kW and 12.5kW, which are applicable to power supply
of 380V, 3-ph. You can select them according to the actual equipment room conditions.
Outdoor unit
The outdoor unit adopts air cooled mode. It is classified into two models: standard model and Lee-Temp model. The
Lee-Temp model can be used at lower temperature (see Table 1-1) than the standard model.
Condenser
Adopt a fin-tube heat exchanger with high heat dissipation and wavy fins. It is free of dust accumulation, and can be
easily cleaned and maintained.
Low-temperature unit
Make the AC unit operate in cooling mode normally at the lowest outdoor temperature of -34°C.
2.5 Options
2.5.1 Humidifier
The humidifier can add pure water vapor (up to 2.5kg/hour) into the room to control the indoor humidity within ranges
required by devices and computer.
The humidifier consists of a steam canister with automatic flushing control function, inlet tube, drain tube, solenoid
valve and steam distributor.
Note
1. The electrode humidifier should be installed and tested in factory.
2. The Liebert_DM AC can control the ambient humidity only after a humidifier is installed.
2.5.2 Heater
A ceramic heater with positive temperature coefficient can be selected. It is safe and reliable. When the surface
temperature is too high, it will reduce the heating power to avoid danger caused by over-temperature. A temperature
switch is provided on the surface of the heater, and it will cut off the power of the heater when the surface temperature
is too high. When the surface temperature decreases to normal, the temperature switch will restore the operation of
the heater automatically.
Note
The power SPD should be installed in factory.
This chapter expounds the technical parameter, mechanical parameter and operating environment of the
indoor/outdoor unit of the Liebert_DM series AC.
Compressor Number 1 1 1 1 1 1
Front face area (m2) 0.37 0.37 0.37 0.37 0.37 0.37
Evaporator coil
Face air velocity (m/s) 2.1 2.1 2.1 21 2.1 2.1
Electric heater Power (kW) - 3.2 3.2 - 3.2 3.2
Electrode Humidifier water rate
- - 2.5 - - 2.5
humidifier (kg/h)
Front filter size (mm, 1 578 × 914 578 × 914 578 × 914 578 × 914 578 × 914 578 × 914
pcs) ×8 ×8 ×8 ×8 ×8 ×8
Filter Side filter size (mm, 1 376 × 427 376 × 427 376 × 427 376 × 427 376 × 427 376 × 427
pcs) ×8 ×8 ×8 ×8 ×8 ×8
Number 3 3 3 3 3 3
Liquid return pipe ID
12.7 12.7 12.7 12.7 12.7 12.7
(mm)
Discharge pipe ID (mm) 16 16 16 16 16 16
Port size Humidifier
- - 19 - - 19
Charging pipe OD (mm)
Condensed water drain
20 20 20 20 20 20
pipe OD (mm)
Net weight (kg) 140 142 145 140 142 145
Electrical Max. current (A) 10.5 10.5 22 10.5 10.5 22
parameter Air breaker 32 32 32 32 32 32
Note: all the cooling capacity is nominal, ±5% error exists in the actual capacity
600 50
510 38 0
5
1850
1750
510 600
510
600
DME07kW DME12kW
Figure 3-1 Dimensions of the indoor unit (unit: mm)
The shadows in Figure 3-1 indicate a reasonable installation and service space. For 7.5kW units, 510mm must be
reserved to facilitate maintenance; For 12.5kW unit, 600mm must be reserved to facilitate maintenance.
The AC unit equipped with a heater should be kept a distance of minimum 150mm from combustible substance. When
testing the AC unit, keep the external static pressure below 150Pa lest the air volume becomes too low and the heater
becomes too hot.
352 787
352 787
1240
829
352 103
7
352 103
7
1240
829
575
575
Figure 3-3 Dimensions of Lee-Temp outdoor unit (unit: mm)
Table 3-5 Mechanical parameters of indoor unit and outdoor unit
Model Cooling capacity (kW) Dimensions (W × D × H, mm) Net weight (kg)
DME07*** 7.5 510 × 385 × 1750 90
Indoor unit
DME12*** 12.5 600 × 500 × 1850 145
DMC07WT1 - 787 × 352 × 829 40
DMC12WT1 - 787 × 352 × 1240 60
Outdoor unit
DML07W1 - 1037 × 352 × 829 53
DML12W1 - 1037 × 352 × 1240 95
This chapter mainly introduces the general arrangement, general principle, piping, model configuration and cooling
cycle.
Note
1. : Factory piping.
2. : Field piping (by technicians).
3. *: Check valve and traps are optional and not supplied by Emerson. But they are recommended for normal system operation
and easy maintenance. They should be installed on site by technicians.
4. +: Solenoid valve is a part of extended piping kit.
Table 4-2 Vertical distance between indoor unit and outdoor unit
Relative position Value
Outdoor unit installed higher than indoor unit Maximum: 20m
Outdoor unit installed lower than indoor unit Maximum: 5m
5. The equivalent length of each part is given in Table 4-3. The resistance loss caused by elbows and valves has been
taken into consideration. The installer should confirm if these values are appropriate for site conditions.
Table 4-3 Equivalent length of each part
Equivalent length (m)
Liquid pipe OD (inch)
90° elbow 45° elbow T-type three way
3/8 0.21 0.10 0.76
1/2 0.24 0.12 0.76
5/8 0.27 0.15 0.76
3/4 0.3 0.18 0.76
7/8 0.44 0.24 1.1
1-1/8 0.56 0.3 1.4
4.3 Piping
All equipment must be installed vertically. The Liebert_DM AC is available in two installation modes: outdoor unit
installed higher than indoor unit and indoor unit installed higher than outdoor unit. See Figure 4-2 and Figure 4-3 for
details.
Outdoor unit
Indoor unit
Max. 20m
Trap
Indoor unit
Protection tube
Min. 5m
Outdoor unit
This chapter gives a detailed description on appearance, LCD screen, control buttons, control screen, control logic,
alarm function of the micro-processing controller of the Liebert_DM AC.
5.1 Appearance
The micro-processing controller panel is shown in Figure 5-1.
More detailed operating status of certain component and alarm information are available from the Main Menu screen.
The selected menu item will be highlighted while browsing. The digit to be changed will be highlighted while you are
changing setting.
ON/OFF button
Up button
Enter button
Down button
Esc button
ON/OFF button Press this button for 3s to turn on or off the unit
Enter button (ENT) Enter the selected menu screen. Validate the parameter setting value
Exit the current menu and return to the Normal screen or previous menu screen. Abort parameter change;
Esc button (ESC)
silence the audible alarm
Move the cursor up or increase the parameter value. For a toggle selection: scroll through the options. For a
Up button
multi-screen menu: scroll up the screen
Move the cursor down or decrease the parameter value. For a toggle selection: scroll through the options.
Down button
For a multi-screen menu: scroll down the screen
Note
After changing the parameter, if you do not press the Enter button to validate the changed parameter, the change will be invalid.
5.4.1 ON Screen
After the AC unit is powered on, the LCD screen will display the ON screen, as shown in Figure 5-4.
Connecting
Please wait...
Password: 1***
Three levels of passwords are provided for accessing the menus. The detailed descriptions are listed in Table 5-2.
Table 5-2 Password level
Password level User Initial password Remark
Browse all menu information. Only set temperature and
Level 1 General operator 0001 humidity setpoints (see Figure 5-12) and cannot change any
values and settings
Level 2 Maintenance personnel - Set all parameters
Level 3 Factory technician - -
For detailed operation on entering the password, refer to 5.3.2 Operation Example. If entering a wrong password, you
can only view the menu, but cannot change the settings. In this case, you can press the Esc button to return to the
Normal screen, and then press the Enter button to enter the Password screen again.
Note
If pressing the Enter button in the Password screen instead of inputting any password, you can only view the menu settings but
cannot change any parameters.
Indoor temperature
0% +100%
Set point
Indoor temperature
-100% 0%
Set point
Exit
Enter dehumidifying
dehumidify-
mode
ing mode
Indoor humidity
+50% +100%
Set point
In the dehumidifying mode, the fan switches to high gear immediately when the cooling requirement is larger than
125%. The fan switches back to low gear when the temperature drops normal.
Figure 5-10 shows the high/low gear switch diagram of the fan in the dehumidifying mode.
Switch to
Switch to low gear
high gear
Indoor
temperature
Set point +125%
Figure 5-10 High/low gear switch diagram of the fan in the dehumidifying mode
In the temperature compensation mode, the compressor is turned on when the cooling requirement is larger than 0%
and it is turned off when the cooling requirement is smaller than -100%; the electronic heater is turned on when the
cooling requirement is smaller than 0% and it is turned off when the cooling requirement is larger than 25%.
Figure 5-11 shows the control logic of the compressor in a) and the control logic of the electronic heater in b).
The
The compressor The electric heater The electric heater
compressor
is turned on is turned on is turned off
is turned off
In the non-temperature compensation mode, the compressor is turned on and the electronic heater is turned off when
the cooling requirement is no smaller than 0%; the compressor is turned off and the electronic heater is turned on
when the cooling requirement is smaller than -100%.
Figure 5-12 shows the control logic of the compressor in a) and the control logic of the electronic heater in b).
The The
humidifier is humidifier is
turned on turned off
0%
-100% Indoor
Set point temperature
Figure 5-13 Humidification logic
Vin F E L2
100%
MaxV B
C D
A
Vx
L1 100% output
During fan startup, the voltage is obtained based on the pressure-voltage curve if the pressure is kept within the set
range and the voltage is the value of MaxV if the pressure exceeds the set range. During fan operating, the power
system stops supplying power to the fan if the condensation pressure is smaller than (Pset - 1), namely Poff. The
control process is A -> B -> C -> D -> E -> F -> C -> B -> A -> G -> H -> I (point A corresponds to the pressure ranging
from B to G). In the case of 100% voltage output, the voltage restores to MaxV after the pressure drops by 2 bars to
the point of Pmaxv. Table 5-3 lists the voltage and pressure parameters.
Table 5-3 Voltage and pressure setting table
Parameter Lower limit Upper limit Default
Min. power supply voltage (%) 30 50 30
Max. power supply voltage (%) 60 100 100
Start pressure (Bar) 11 15 13
Pressure bandwidth (Bar) 4 6 5
Rt At 0: 00 23: 00 12: 00 -
Alarm
reporting
No. Alarm Alarm Prerequisite Alarm Mode Clearance Method Alarm Output
delay (unit:
second)
than the high temperature heater is high temperature
threshold for a duration of closed threshold - 2°C) for a
alarm reporting delay while duration of alarm
the return air temperature reporting delay
sensor operates normally
The fan is enabled for 10
Keep the return air
minutes and the return air
The alarm is temperature higher
temperature is kept lower
Low triggered and than the value (current Enabled/d
than the low temperature
5 temperature the cooling low temperature 30 isabled/
threshold for a duration of
alarm system is threshold + 2°C) for a closed
alarm reporting delay while
closed duration of alarm
the return air temperature
reporting delay
sensor operates normally
The fan is enabled for 10
minutes and the return air Keep the return air
humidity is kept higher than The alarm is humidity lower than
High Enabled/
the high humidity threshold triggered and the value (current high
6 humidity 30 disabled/
for a duration of alarm humidification humidity threshold -
alarm closed
reporting delay while the stops 2%) for a duration of
return air humidity sensor alarm reporting delay
operates normally
The fan is enabled for 10
minutes and the return air Keep the return air
humidity is kept lower than The alarm is humidity higher than
Low Enabled/
the low humidity threshold triggered and the value (current low
7 humidity 30 disabled/
for a duration of alarm dehumidificati humidity threshold +
alarm closed
reporting delay while the on stops 2%) for a duration of
return air humidity sensor alarm reporting delay
operates normally
Keep the humidifier
The humidifier switch is kept Enabled/
Humidifier The alarm is switch turned off for a
8 turned off for a duration of 10 disabled/
fault triggered duration of alarm
alarm reporting delay closed
reporting delay
The alarm is Keep the return air
Fault of the The return air temperature is
triggered and temperature within the Enabled/
return air kept out of the allowed range
9 the cooling allowed range for a 10 disabled/
temperature for a duration of alarm
system is duration of alarm closed
sensor reporting delay
forcibly started reporting delay
The high pressure alarm is The alarm is
High reported for three times triggered and
Manually clear the Enabled/
10 pressure within an hour or the alarm is the /
alarm disabled
locking kept uncleared within 10 compressor is
minutes locked
The low pressure alarm is The alarm is
Low reported for three times triggered and
Manually clear the Enabled/
11 pressure within an hour or the alarm is the /
alarm disabled
locking kept uncleared within 10 compressor is
minutes locked
The discharge temperature The alarm is
Discharge alarm is reported for three triggered and
Manually clear the Enabled/
12 temperature times within an hour or the the /
alarm disabled
locking alarm is kept uncleared for compressor is
20 minutes locked
The alarm is Keep the floor wetting
Floor The floor wetting switch is Enabled/
triggered and switch turned off for a
13 wetting kept turned off for a duration 10 disabled/
humidification duration of alarm
alarm of alarm reporting delay closed
stops reporting delay
Alarm
reporting
No. Alarm Alarm Prerequisite Alarm Mode Clearance Method Alarm Output
delay (unit:
second)
The alarm is Enabled/
Power loss occurs when the The alarm is
14 Power loss automatically cleared / disabled/
AC units are in operation triggered
one second later closed
The alarm is
Enabled/
Over-voltag The input voltage increases triggered and Restore the input
15 3 disabled/
e alarm by 15% the system is voltage
closed
locked
The alarm is
Enabled/
Under-volta The input voltage decreases triggered and Restore the input
16 3 disabled/
ge alarm by 15% the system is voltage
closed
locked
The alarm is
Enabled/
Frequency The input frequency is triggered and
17 Restore the frequency 3 disabled/
deviation deviated by 5Hz the system is
closed
locked
The alarm is
Enabled/
Open phase triggered and
18 Open phase occurs Manual restoration 3 disabled/
alarm the system is
closed
locked
The alarm is
Enabled/
Negative triggered and
19 Negative phase occurs Manual restoration / disabled/
phase alarm the system is
closed
locked
Custom The set polarities are kept Keep the set polarities
Enabled/
alarm 1 inconsistent with those input The alarm is consistent with those
20 30 disabled/
(lightning for a duration of alarm triggered input for a duration of
closed
protection) reporting delay alarm reporting delay
The alarm is
The number of normally triggered and
online energy-saving cards the dormancy Keep the number of
Energy is less than the set number mode cannot the cards consistent Enabled/
21 saving card or more than one be activated if with the set number 30 disabled/
fault energy-saving card exceed all and keep the cards in closed
the allowed temperature energy-saving normal temperature
range cards are
faulty
The value (temperature
measured by using the
sensor NTC0 - return air
temperature) is kept larger
Keep the value
than the set temperature for The alarm is
(temperature
a duration of alarm reporting triggered and
measured by using the
delay when the fan is in shut down all Enabled/
22 Air flow loss sensor NTC0 - return 10
normal operation. The air the devices disabled
air temperature)
flow detection thermal except for the
smaller than the value
resistor output is closed fan
(set temperature - 2°C)
when the fan is shut down.
This alarm is not reported if
the fan is closed and the
temperature sensor is faulty
Fault of Keep the condensing
The condensing pressure is
pressure pressure within the
kept out of the allowed range The alarm is Enabled/
23 sensor 1 allowed range for a 3
for a duration of alarm triggered disabled
(lightning duration of alarm
reporting delay
protection) reporting delay
24 Humidity The return air humidity is The alarm is Keep the return air 10 Enabled/
Alarm
reporting
No. Alarm Alarm Prerequisite Alarm Mode Clearance Method Alarm Output
delay (unit:
second)
sensor fault kept out of the allowed range triggered humidity within the disabled/
for a duration of alarm allowed range for a closed
reporting delay duration of alarm
reporting delay
Keep the temperature
The temperature measured
measured by using the
by using the air flow loss
air flow loss sensor Enabled/
Air flow sensor (NTC0) is kept out of The alarm is
25 (NTC0) within the 10 disabled/
sensor fault the allowed range for a triggered
allowed range for a closed
duration of alarm reporting
duration of alarm
delay
reporting delay
Note:
1. Alarm reporting delay is a fixed configuration.
2. In the case of system locking, the compressor, heater, humidifier, and outdoor fan are locked.
Main Menu
Alarm Menu Set Points System Status Temp Calib System Menu Help Menu LCD Setting
Heat Num
Hum Num
Change Password
Factory Reset
Red Yellow
Transformer T2
Indoor connection
Black Yellow Fuse
terminal TB1
TB1-N
NN Black Yellow
Grounding point of the NN
TB1-N Transformer T1 23 24 Indoor connection
electrical control box NN
TB1-N TB1-N 2122 terminals TB2
NN
TB1-1 TB1-11
TB2-21
TB2-22
1 11
TB1-2
TB1-3
2 12 TB1-13
3 13
J3-1
J3-2
Yellow-green
TB1-4
4 14
TB1-5 TB1-15
KM2-A1
5 15
J28-4
PE Yellow-green
6 16
Black
Black
Black
Black
Black
Black
Black
Black
TB1-7
J28-7 7 17
Black
Black
Black
Black
TB1-8 Standby unit is available
8 18
Black
Black
J28-8
TB1-9
J28-9 9 19
QF-1
QF-3
QF-5
Public alarm
SPD-N
SPD-1 TB1-10
SPD-2
SPD-3
J28-10 1020
PE
N
Black J18-1
J01-1
J01-3
J01-5
J01-7
1 3 5 Power 1 1 2 1 2
N L1 L2 L3 Black J18-2
Black 2 J13 J31
PE1L1N1 PE N MCB ALARM
Power SPD KM1-A1 J18-3
3 J18 1 2 3 4 5 6 7 8
2 4 6 SPD/D
COM NC
4
5
J01 J14 2
1
J14-2
J14-1
DB9
Monitoring
Black
Black
card
Black
Black
Black
Black
Power
J2-2
J2-1
Black J02
J1-N
2 1 2 2
J1 Black J02
J19-2
J19-1
1 J1-L
1
board
TB2-21
To outdoor 380V/50Hz 3N~ J2 GND GND
J18-3
KM1-21
Filter J12 2 12V 12V
4
Display
KM1-1
KM1-3
KM1-5
KM2-1
KM2-3
unit 1 Gray 3
A A
2 J4
J03 J39 2
A1 1 3 5 21 A1 1 3 5 13 board Yellow-green J03
2 J29 1
B B
1 board
1 1 2 3 4 5 6 7 8
KM1 KM2
J3
A2 2 4 6 22 A2 2 4 6 14 5 4 3 2 1
J34
Gray Temp/Hum
KM1-22
KM1-2
KM1-4
KM1-6
J3-4
J3-1
J3-2
detection board
J3-4
J28-3
1 2 3 4 5 6 7 8 1
Brown
Black
J30
Gray
Grounding point 2
KM1-A2 N1 L1 of the electrical J28-3 Black
3 KM2-A2
Brown
Brown Black
White
Black
control box J28-4
Blue
Blue
4 TB2-22
T2
T3
6 Black
J28-7
7 TB1-7
J28-8 Black
8 TB1-8
Compr- Electric Indoor J19-1 91
J28-9 Black TB1-9
Yellow-green
SPD-NC 1 J28-10 Black
heater J19-2 TB1-10
SPD-COM 2
essor fan 3
0
1
Black
4 Black High pressure switch
J19
Brown
Brown
J19-5 2
5 Blue
Remote turn on/off J19-6 3
6 Blue Low pressure switch
Electric heater belt J19-7 4 Black
Grounding point of the Grounding point 7 J21 J21-5
Standby unit request 5
of the electrical Start capacitor
J19-8
of the compressor 8 J21-6 Brown Air discharging switch
electrical control box 6
control box J23 J36 7
3 2 1 Floor overflow
8
GND
+5V
VIN
Cable description:
Green
Connection cables between indoor
Black
Red
and outdoor connection terminal
Factory supplied line
Energy- +12V
Red Yellow
Transformer T2
Indoor connection Black Yellow Fuse
terminal TB1
N N Black Yellow
TB1-N
Grounding point of the
TB1-N
N N
TB1-N Transformer T1 272829303132 Indoor connection
electrical control box N N
TB1-N TB1-N 21 2223242526 terminal TB2
N N
TB1-1 TB1-11
1 11
TB2-28
TB2-21
TB2-22
TB2-23
TB2-24
TB2-25
TB2-26
TB2-31
TB1-2
2 12
J3-1
J3-2
TB1-3 TB1-13
3 13
TB1-4
4 14
PE Yellow-green
TB1-5 TB1-15
5 15
TB1-6
PE Yellow-green
6 16
KM2-A1
KM3-A1
J28-6
KA1-3
TLR
J28-4
G0
G
QF-1 Black
QF-3 Black
QF-5 Black
Black
Black
Black
Black
Black
Black
Black
Black
J28-7 TB1-7 7 17
Black
Black
Blue
TB1-8
8 18 Standby unit is available
J28-8
TB1-9
J28-9 9 19
SPD-N
Public alarm
SPD-1
SPD-2
SPD-3
TB1-10
J28-10 10 20
N
Black J18-1
1 3 5 1
J01-1
J01-3
J01-5
J01-7
1 2 1 2
PE1 L1N1
Power N L1 L2 L3
Power SPD
Black J18-2
2 J13 J31
PE N Black J18-3
MCB ALARM KM1-A1 3 J18 1 2 3 4 5 6 7 8
2 4 6 COM NC SPD/D Black J18-4 J14-2
4
J01 J14 2 J14-1
5 1 DB9 Monitoring card
Power
Black
Black
Black
Black
J02
J2-1
J2-2
KM1-1 Black
Black
Black
KM1-21 Black
Black
2 J1-N J02-2 2
J19-2
J19-1
To outdoor unit 380V/50Hz 3N~ J1 J1-L Black
TB2-28
2 1
board
TB2-21
TB2-22
1 1 GND GND
J18-3
J2 J12 2 4
Display
KM2-1
KM2-3
12V 12V
KA1-4
Gray
KM1-3
KM1-5
1
KM3-1
KM3-3
3
J4
Filter J03 J39 2
1
A
B
A
B
2
1 board
A1 1 3 5 21 A1 1 3 5 13 A1 1 3 5 13 3 6 4 board Yellow-green J03 2
1
J29
1 2 3 4 5 6 7 8
KM1 KM2 KM3 KA1 J3
A2 2 4 6 22 A2 2 4 6 14 A2 2 4 6 14 1 5 2 5 4 3 2 1 J34
Gray Temp/Hum
J3-1
J3-2
detection board
J3-4
KM1-22
KM1-2
KM1-4
KM1-6
KM3-3
KM3-6
J3-4
TLR
J28-3
J28-5
1 2 3 4 5 6 7 8 J28-1 Black
1 +VR
Grounding point J30 J28-2 Brown
Black
Black
Black
2 SET
KM1-A2 N1 L1 of the electrical J28-3 Black
Brown
Brown
White
KM2-A2
Black
3
Blue
J28-4 Black
Blue
Blue
control box
HUM-N
4 TB2-24
HUM-L
Control J28-5 Black KA1-1
J28 5 J28-6
T1
T2
T3
Black TB2-31
6
J28-7 Black
7 TB1-7
8 J28-8 Black TB1-8
Comp- Humidify Indoor J19-1
board J28-9 Black
Yellow-green
SPD-NC 1 9 TB1-9
J19-2 J28-10 Black
SPD-COM 10 TB1-10
ressor -ing tub fan J19-3
2
Black
Black
AL 3
J19-4 1 Black
AL 4 J19 High pressure switch
J19-5 2 Black
Brown
Brown
5 Blue
Remote turn on/off J19-6 3
6 Blue Low pressure switch
J19-7 4
Grounding point Electric heater belt of Electric heater Grounding point 7 Black
of the electrical of the electrical Start capacitance Standby unit request J19-8
8
J21 5
the compressor J23 J36 Brown Air discharging switch
control box control box 6
3 2 1 7
8 Floor overflow
Black GND
Red +5V
Green VIN
KM3-A2 TLR G TB2-23
TB2-25 TLR G0 TB2-26
control board
J19-4 AL CANH
card
Humidifying
CANL
EV2 Outlet solenoid Pressure
G valve sensor
EV1
J28-1 +VR Inlet solenoid
J28-2 SET valve
GND
AB LS Water level
AB LS probe
Cable description: CS Conductivity
Connection cable between the CS probe
Factory supplied line indoor and outdoor terminal
Field supplied line L L1 Indoor
Parts supplied line N N1
PE1
terminal
block
Inserted terminal Outdoor
connection
Connection description: terminal
Appendix 3 Glossary
AC Air conditioner
ID Inside diameter
LCD Liquid crystal display
Lee-Temp Low temperature
OD Outside diameter
SPD Surge protective device
SCR Silicon controlled rectifier
Australia Pakistan
T: 1800-065345 T: 92-42-36622526 to 28
F: 61-2-97810252 F: 92-42-36622530
Indonesia Philippines
T: 62-21-2513003 T: 63-2-7207400
F: 62-21-2510622 F: 63-2-6203693
Japan Singapore
T: 81-3-54038564 T: 65-64672211
F: 81-3-54032919 F: 65-64670130
Korea Thailand
T: 82-2-34831500 T: 66-2-6178260
F: 82-2-5927886 F: 66-2-6178277 to 78
Malaysia Vietnam
T: 603-78845000 T: 84-4-37628908
F: 603-78845188 F: 84-4-37628909
New Zealand
T: 64-3-3392060
F: 64-3-3392063
AP13DPG-LiebertDM_Aircooled-TM