Attention
Dangerous
1. Attention! Dangerous to sense!
2. Do not touch the power terminal after supply AC power, in order to avoid electric shocks.
3. When connect with Instrument power, please make sure to power off!
Admonition
1. Please make sure of terminal position is correct before AC power supply in order to avoid of serious damage.
2. Please pre-determined power supply voltage and instrument specifications (AC85~265V or DC24V) correspond in order to avoid of serious damage.
3. Please confirm receipt of proper use of wiring (Input, Output, Alarm) terminals.
4. Please select of proper pressure terminal with the type of M3 screw an d it s bi g g e s t torque must be within the range such as 8kG. .
5. Please do not be installed under the conditions of easy to interfere, corrosive gases, high temperature and humidity.
6. To avoid other interference, please keep the power wires supplied distance from power wire and load wire.
7. When the input sensors is T/C, if necessary to extend the lead wire, Please use compensation wire according to the T/C.
8. When input the sensor is RTD, if we need to extend the lead wire, please use smaller impedance value, and the same wire.
Connecting
A.power supply
A.power supply
B. Control Output
B. Control Output C. Input signal
C. Input signal
Single phase zero 3-Phase zero
corssing control corssing control
D.Alarm output 3-Linear propotional motor control Single phase angle control E.Transmission
D.Alarm output output
E.Communication
F.add-ons power output G.Communication
A.Power supply
A.Power supply
B.Contol Output
C.Input signal B.Control output
C.Input signal
D.Alarm output
E.Communication D.Alarm output E.Transmission output F.Communication
Volt + 17 11 7
mA
- 20 14 10
Operation instruction
1.Start up After power supply,operate as following: 4.Set up Alarm
For instance:when set AL1=5(when PV>5,alarm1 acts)
Led and indicator Indicat e units(C) Indi cate upp er and Start to use
will blink and input typs (K2) lower limit ation
scope(0.0-400.0) Press Key Press key to Press key Press key confirm
To Al1 the 2th number increase AL1 the set value
2.Set up SV For instance : when SV=200, operate as following ;
*There are 17 kinds of alarm mode,please refer to alarm mode index
*Alter alarm mode:Press key 5 seconds,meantime press key
enter into level3 to set ALT1
Press SET key to Press shi ft key , digit Press UP key to Press SET, activate Auto
AT start blinki ng in SV set YES Tuning (At light on).
The setting range is
Manipulation
range :-1999~9999
Proportion band range :0.0~200.0%
of group 1(%) p=0 is ON/OFF
range :0~9999
range: 0~150(S)
Working cycle SSR output=1, 4~20mA output=0 The same as ALT1
of group 1(S)
Relay output generally is set above 10
As P1=0.0, range :0~1000
it indicates 1st output hystersis Range:0-1000(use for ON/OFF)
adjustment PV>(SV+HYS1),OFF
PV<=(SV+HYS1),ON
range :0~9999
Proportion band
of group 2(%) The same as P1
range :0~9999
range :-1000~1000
Please repair it
Return to INP
Technical Parameters
Technical Specification
Model
Size
Power optional
Frequency
Power consumption Approx 4VA Approx 4VA Approx 4VA Approx 4VA Approx 4VA Approx 4VA
Memory Power disconnection preserve memory
Sensing signal input. Sampling time:250mS,display accuracy:0.2%of FS
Input
Linear current
Linear voltage
Location for decimal point (Just used for input of linear current and voltage)
Control Output (Heat model or cool model)
Electric life:100,000 times or more(under rated load)
Model
programming elevates
temperature,hold warm
Total have 2 groups(per 8 segments)can set,or connect to 16 segments for use
Can use for heat up/cooling dual output control
The Electric life:100,000 times or more(under rated load)
2nd
out-
Pulse voltage Use for SSR ON=24V,OFF=0V,largest loading current:20mA
put
Linear current 4-20mA,0-20mA largest loading impedence:560Ω
Linear voltage largest loading current:20mA
The 2nd alarm Electric life:100,000 times or more(under rated load)
The 3rd alarm Electric life:100,000 times or more(under rated load)
Can transit :PV/SV
Transit
output Linear current 4~20mA,0~20mA largest loading impedance: 560Ω
Linear voltage largest loading current:20mA
Example Illustration
There is the following processing requirement temperature curve.It is required to full power when the temperature rises,
and half-power when keeping warm.Then ,when starting the process,it will begin from the oven temperature at that time.
Specofic setup as[internal parameter PTN=1(all you do is indicate the startup of section8 in grou1 in the controller) ]:
Heating power restriction in section 1
Set value temperature in Set val ue in the first section OUT1=100%(indicating no restricton T1 temperature rise
section1 SV1=50 degrees of time TM1=0.15(indi cat ing so that 100% output is available) process completed
15 minute s)
Set value in the section 2 ofHeating power restriction in section 2 T2 temperature preserve
Set value temperature in time TM2 =0.20(indicating
OUT2=50%(indicating most restricton process completed
section2 SV2=50 degrees 20 minutes) so that 50% output is available)
Set val ue temper ature in Set value in the section 3 of Heating power restriction in section3 T3 temperature rise
time TM3=0.16(indicating OUT3=100%(indicating no restricton
section3 SV3 =100 degr ees process completed
16 minutes) so that 100% output is available)
Set value in the section 4 of Heating power restriction in section 4
(minutes) Set val ue temperat ure in T4 temperature preserve
time TM4=1.10(indicating OUT4=50%(indicating most restricton
sect ion4 SV4=100 degrees 1hour 20 minutes) so that 50% output is available) process completed
Set value temperature in Set value in the section 5 of Heating power restriction in section 4 T5 temper ature reduse
section5 SV5=85 degrees time TM5=0.14(indicating OUT5=50%(indicating most restricton proc ess com pleted
14 minutes) so that 50% output is available)
Set value temperature in Set value in the section 5 of Heating power restriction in section 4 T6temperature preserve
time TM6=0.16(indicating OUT6=50%(indicating most restricton
section6 SV6=85 degrees 16 minutes) process complete d
so that 50% output is available)
Set value temperature in Set value in the section 7,8 Heating power restriction in section 7,8 It indicates that you fail to
start up section7and 8,and
sectio n7,8 SV7,8=0 degrees of time TM7,8=0 OUT7,8=0 the program is over here
Application instance
1、101 instrument is used for heating and cooling control 2、201 instrument is used for heating control
P907-101 If the power of the heating fuse is not big,just trigger SSR with the
instrument directly. We can provide the SSR with AC380V and 450A max.
Setting:CYT1=10
P908-201 Setting:CYT1=1
AL1 AC85~265V
.. C R
OUT1
T/C
。 .
-
.+ RTD
。.
J- 1
+
AC220V J- 2 HEATER OVEN - B B
R
A
OVEN
-
SSR ~ HEATER
+ ~
。。
~~
COLLING FAN POWER SOURCE
3、701 valve control instrument 4、801 instrument is used for electric heating control
P909-801
..A.Power
● ●
● ●
P909-701
Setting:
CYT1=1-100Sec
(1)、indicat e the heati ng volt ange so as to provide the synchrono us singn input and LIN E with the sam e volt age
(2)、AL1 indicat e the upp er limit alarm(11)
AC85~265V RUCY=5-200Sec
● LINE
●
AC220 LINE
CLS
OPN
COM
T/C
+
ACTUATOR -
OPEN
COM
CLOSE ○
M ← FEED
BACK
-
.+ R . K2
G1
FUSE
K1
-
.+
T/C
OVEN
.
FUSE
AC380V G2 HEATER
BURNER OVEN
FUEL S
→
5、601 is used for electric heating control 6、901 is used for electric heating control
/ R / S / T CONTROLLER
/R / S / T CONTROLLER
RG1
/
FAST
/ FUSE
G1
/ FUSEK3 /
●
TG1 SCR Module RG2 FAST
●
RG1 K1 K1
● ●
● ●
TG2 TG1 K2 DIODE/SCR
RG2 ●
G1 G3 Module G2
← TG2 G2
● ● K2
/ U / V /W ●
WECAN SUPPLY
HEATER SINK
G3
/ U / V / W ←///// K3
TIME CHART:
OFF 3φLOAD
CYCLE TIME=200m Sec.
→
Appendix Forms
Series name Code Basic model code Main Output code Output 2 Code Alarm code Retra nsmitte r Code Input type Code Remote setpoint Code communication code Water proof code Auxiiary
and dust proof power output Code
Set value type NONE NONE NONE NONE T/C NONE NONE
NONE NONE
Program type Relay contan t output Relay contant output One set PV retransmiter RTD
YES
SSR pulse output SSR pulse output Two set SV retransmiter Linear signal
4-20mA continuous current output 4-20mA continuous current output Three set
0-20mA continuous current output
0-10V voltage output
Solid relay Relay
fine planel 1φSCR Zero-crosover
fine planel 3φSCR Zero-crosover
fine planel 3φSCR Zero-crosover
(Only use in triggering 3groups
of KS bidirectional thyristor)
No feedback motor
Feedback motor
1φSCR phase angle
3φSCR phase angle
Input type
Symbol Code Range Symbol Code Range Symbol Code Range
Sym bol Code Range