Sie sind auf Seite 1von 11

Hkkjrh; ekud IS 16205 (Part 24) : 2018

(Reaffirmed )
Indian Standard

osQoy izcaèku osQ fy, dUM;wV


iz.kfy;k¡
Hkkx 24 fo'ks"k vis{kk,¡ μ tehu osQ uhps fo|eku osQcy
izcaèku

Conduit Systems for Cable


s
Management
ipe

m
Part 24 Particular Requirements Conduit Systems Buried
.co
ip

Under Ground
ail
uls
gm
oT
i@
mp ed t
uls

ICS 29.120.10
ns
plt
e
Lic

© BIS 2018

Hkkjrh; ekud C;wjks


BUREAUOFINDIANSTANDARDS
ekud Hkou] 9 cgknqj'kkg ”kiQj ekxZ] ubZ fnYyh&110002
MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI-110002
www.bis.org.in www.standardsbis.in

February 2018 Price Group 4


Electric Wiring Accessories Sectional Committee, ETD 14

FOREWORD
This Indian Standard (Part 24) was adopted by the Bureau of Indian Standards, after the draft finalized by the
Electric Wiring Accessories Sectional Committee had been approved by the Electrotechnical Division Council.
This standard (Part 24) specifies requirements for conduit systems buried under ground. The other part in the
series are:
Part 1 General requirements
Part 21 Particular requirements — Rigid conduit systems
Part 22 Particular requirements — Pliable conduit systems
Part 23 Particular requirements — Flexible conduit systems
This standard (Part 24) is to be read in conjunction with Part 1 of this standard to which reference has been given
regarding general requirements as well as test methods. Should however, any deviation exists between Part 1 and
s
this standard, the provision of the latter shall apply.
ipe

m
Where a particular clause or subclause of Part 1 is not mentioned in this Part 24, that clause or subclause applies
.co
as far as is reasonable. Where this Part 24 states addition or replacement the relevant text of Part 1 is to be adopted
ip

accordingly. Clauses and table which are additional to those of Part 1 are numbered starting from 101 and additional
ail
uls

subclauses are numbered with the main clause number followed by 101, for example, 7.101.
This standard is based on IEC 61386-24 ‘Conduit systems for cable management — Part 24 Particular requirements
gm
oT

for conduit systems buried under ground’, issued by International Electrotechnical Commission (IEC) with following
modifications:
i@
mp ed t

a) Reference temperature has been changed


uls

b) Referred to standards have been changed


ns

This standard supersedes IS 14930 (Part 2) : 2001 to align National Standard with corresponding International
plt

Standard.
e
Lic

For the purpose of deciding whether a particular requirement of this standard is complied with, the final value,
observed or calculated expressing the result of a test, shall be rounded off in accordance with IS 2 : 1960 ‘Rules
for rounding off numerical values or analysis (revised)’. The number of significant places retained in the rounded
off value should be the same as that of the specified value in this standard.
IS 16205 (Part 24) : 2018

Indian Standard
CONDUIT SYSTEMS FOR CABLE MANAGEMENT
PART 24 PARTICULAR REQUIREMENTS CONDUIT SYSTEMS
BURIED UNDER GROUND

1 SCOPE as follows:
This clause of Part 1 is replaced by the following: Modification:
This standard (Part 24) specifies requirements and tests NOTE — Annex A is not applicable
for conduit systems buried underground including
6.1 According to mechanical properties
conduits and conduit fittings for the protection and
management of insulated conductors and/or cables in Replacement:
electrical installations or in communication systems.
6.1.1 Resistance to Compression
This standard applies to metallic, non-metallic and
composite systems including threaded and non-threaded 6.1.1.1 Type 450 (code 450)
entries which terminate the system.
NOTE — A conduit system according to 6.1.1.1 is intended to
be directly buried underground without additional precautions
2 NORMATIVE REFERENCES
s
6.1.1.2 Type 750 (code 750)
This clause of IS 16205 (Part 1) is applicable except
ipe

as follows: m NOTE — A conduit system according to 6.1.1.2 is intended to


be directly buried underground without additional precautions
.co
ip

IS 14763, Not applicable


6.1.2 Resistance to Impact
Addition:
ail
uls

6.1.2.1 Light (code L)


IS/ No. Title
gm

6.1.2.2 Normal (code N)


oT

ISO 2768-1: General tolerances – Part 1: Tolerances


1989 for linear and angular dimensions 6.1.3 Resistance to Bending
i@

without individual tolerance


mp ed t

6.1.3.1 Rigid
indications
uls

3 DEFINITIONS 6.1.3.2 Pliable


ns

This clause of IS 16205 (Part 1) is applicable except 6.2 According to Temperature


plt

as follow Not applicable


e
Lic

Addition: 7 MARKING AND DOCUMENTATION

3.101 Multiwall Conduit This clause of IS 16205 (Part 1) is applicable except


as follows:
A conduit consisting of several walls which may be a
combination of plain and/or corrugated walls 7.1 Addition:

4 GENERAL REQUIREMENTS c) the code “L” or “N” according to 6.1.2; and


d) the code “450” or “750” according to 6.1.1.
This clause of IS 16205 (Part 1) is applicable. This code shall be marked immediately after
the code according to c).
5 GENERAL CONDITIONS FOR TESTS
7.1.1 Not applicable.
This clause of IS 16205 (Part 1) is applicable except
as follows: Addition:

Replacement 7.1.101 Conduits shall be marked according to 7.1 at


regular intervals along their length of preferably 1 m
5.1 The schedule of type and acceptance tests are given but not longer than 3 m.
in 101.
7.2 Replacement
6 CLASSIFICATION
Conduit fittings shall be marked in accordance with 7.1
This clause of IS 16205 (Part 1) is applicable except on the product. 7.3 and 7.4 Not applicable.
1
IS 16205 (Part 24) : 2018

7.5 Replacement NOTE — Compression test on fittings is under consideration

Compliance with 7.1 to 7.2 is checked by inspection The test for conduits containing non-metallic materials
shall not be started until 10 days after manufacture.
7.6 Addition:
10.2.2 Samples shall be (200 ± 5) mm long.
Add the following note after Note 3:
10.2.3 Before the test, the outside and inside diameters
4 An alternative test is under consideration of the samples shall be measured as specified in 8.
Addition: 10.2.4 The samples shall be compressed between two
7.101 The manufacturer shall provide in his literature flat steel plates having minimum dimensions
all information necessary for the proper and safe (100 × 220 × 15) mm, the length 220 mm being along
installation and use. the length of the sample. The samples shall be
compressed at a rate of (15 ± 0.5) mm/min and the load
In addition, for conduit systems according to 6.1.1.1 recorded at the vertical deflection equivalent to 5
the manufacturer shall give instruction for installation percent of the average value of the original inside
precautions following the relevant national technical diameter of the sample.
rules, if any.
10.2.5 When reaching the deflection of 5 percent, the
7.102 The use of standard mark is governed by the applied force shall be at least:
provision of Bureau of Indian Standards Act, 1986 and
rules and regulations made there under. The details of a) 450 N for conduits according to 6.1.1.1; and
conditions under which the licence for the use of b) 750 N for conduits according to 6.1.1.2.
s
Standard Mark may be granted to manufacturer or
ipe
NOTE — The deflection is calculated with the inner diameter
producers may be obtained from the Bureau of Indian m but the measurement of the outside diameter may be sufficient.
Standards.
.co
In case of doubt, it will be necessary to measure the inner
ip

diameter.
8 DIMENSIONS 10.2.6 After the test, there shall be no crack allowing
ail
uls

This clause of Part 1 is replaced by the following: the ingress of light or water between the inside and the
gm

outside.
oT

Conduit dimensions shall be preferably according to


Table 101. 10.3 Impact Test
i@
mp ed t

Compliance of the minimum inside diameter shall be Replacement:


checked by measurement according to two
uls

perpendicular diameters on the same section and 10.3.1 Twelve samples of conduits each (200 ± 5) mm
ns

calculating the average value. in length or conduit fittings are subjected to an impact
plt

test by means of the apparatus shown in Fig. 101.


e

Compliance of the outside diameter shall be checked


Conduits are tested alone.
Lic

using a ring gauge or any suitable method.


Fittings are tested when assembled with conduits by
9 CONSTRUCTION using a suitably shaped 120° veeblock.
This clause of IS 16205 (Part 1) is applicable except NOTES
as follows: 1 If necessary, for the test purposes conduit fittings may be
trimmed as long as the test result is not affected.
9.3 and 9.4 Not applicable.
2 For determination of mass of hammer, the hammer is to be
considered as the head of hammer plus the guidance carriage.
10 MECHANICAL PROPERTIES
10.3.2 The test apparatus shall be placed on a firm flat
This clause of IS 16205 (Part 1) is applicable except
surface.
as follows:
The samples shall be conditioned in a cold chamber at
10.1.4 Replacement: the temperature of (–5 ± 1)°C for 2 h.
Compliance is checked by the tests of 10.2 to 10.4. The samples shall be removed from the cold chamber
and placed on the vee-block as shown in Fig. 101.
10.2 Compression Test
The hammer shall falls once on each sample. The time
Replacement:
between removal of the sample from the cold chamber
10.2.1 Conduits and bends are subjected to a and completion of impact shall not be exceed 10 s. The
compression test. energy values are specified in Table 102.

2
IS 16205 (Part 24) : 2018

The test shall be made on the weakest part of the conduit 12 THERMAL PROPERTIES
fitting except that it shall not be applied within 5 mm
This clause of IS 16205 (Part 1) is not applicable.
of any sample entry. Samples of conduit are tested on
the centre of their length. 13 FIRE HAZARD
10.3.3 After the test, at least nine of the twelve samples This clause of IS 16205 (Part 1) is applicable except
shall pass the test. There shall be no crack allowing the as follows:
ingress of light or water between the inside and outside.
13.1.2 Under consideration.
10.4 Bending Test
14 EXTERNAL INFLUENCES
Replacement:
This clause of IS 16205 (Part 1) is applicable.
10.4.1 This test shall be carried out on pliable conduits.
14.1 Resistance of Chemical attack
10.4.2 The test is made on six samples having an
appropriate length. Three samples are tested at room Under Consideration.
temperature, the other three are tested at (–5 ± 1)°C.
15 ELECTROMAGNETIC COMPATIBILITY
For the test at –5°C, the samples shall be conditioned
This clause of IS 16205 (Part 1) is applicable.
in a cold chamber for 2 h.
The test apparatus consists of a device as shown in 101 TESTS
Fig. 102 allowing to bend the conduit with a bending 101.1 Type Tests
s
radius equal to the minimum bending radius specified
ipe

by the manufacturer. m The following shall constitute the type tests:


a) Dimensions(see 8);
.co
One of the ends of the samples shall be fixed on the
ip

test apparatus by means of an appropriate device. The b) Construction (see 9);


sample then bent to an angle of approximately 90° and
ail

c) Mechanical properties (see 10);


uls

hold. d) Electrical properties (see 11);


gm
oT

10.4.3 During the test, the samples shall not flatten. e) Fire hazards (see 13);
f) External influences (see 14); and
Compliance shall be checked by passing a ball having
i@

g) Electromagnetic compatibility (see 15).


mp ed t

a diameter equal to 95 percent of the minimum inner


diameter of the sample declared by the manufacturer,
uls

101.2 Acceptance Tests


through the sample whilst it is bent around the test
ns

apparatus. The following shall constitute the acceptance test


plt
e

10.5, 10.6, 10.7 and 10.8 Not applicable. a) Dimensions (see 8);
Lic

b) Mechanical properties (see 10); and


11 ELECTRICAL PROPERTIES
c) Electrical properties (see 11).
This clause of IS 16205 (Part 1) is not applicable.
NOTE — Recommended sampling plan and criteria for
conformity for acceptance test is given in Annex C.

3
IS 16205 (Part 24) : 2018

Table 101 Conduits Diameters


(Clause 8)
Sl Nominal Size Nominal Outside Tolerances Min. Inside Diameter
No. mm Diameter mm mm
mm
(1) (2) (3) (4) (5)
i) 25 25 + 0.5 18
0
ii) 32 32 + 0.6 24
0
iii) 40 40 + 0.8 30
0
iv) 50 50 + 1.0 37
0
v) 63 63 + 1.2 47
0
vi) 75 75 + 1.4 56
0
vii) 90 90 + 1.7 67
0
viii) 110 110 + 2.0 82
0
ix) 120 120 + 2.2 90
0
s
x) 125 125 + 2.3 94
0
ipe

xi) 140 m 140 + 2.6


0
106
.co
ip

xii) 160 160 + 2.9 120


0
ail

xiii) 180 180 + 3.3 135


uls

0
xiv) 200 200 + 3.6 150
gm
oT

0
xv) 225 225 +4.1 170
0
i@
mp ed t

xvi) 250 250 + 4.5 188


0
uls

xvii) 315 315 + 5.7 237


0
ns
plt

NOTES
e

1 Tolerances on outside diameters (OD) are given as follows:


Lic

a) Outside diameter specified are nominal dimensions.


b) Outside diameter maximum is nominal outside diameter +(0.018 X nominal outside diameter values) rounded off to
+0.1 mm.
c) Minimum inside diameter is nominal outside diameter divided by 1.33.
2 Any other sizes than those mentioned in Table 101 shall be as per the agreement between the buyer and the seller.

Table 102 Impact Test Energy Values


(Clause 10.3.2)
Sl Nominal Size of Light (L) Normal (N)
No. Conduit
mm
Mass of Fall Height Energy Mass of Fall Height Energy
Hammer 0 J Hammer 0 J
+1
mm ( –1 ) +1
mm ( –1 )
kg ( 0 ) kg ( 0 )
percent percent
percent percent
(1) (2) (3) (4) (5) (6) (7) (8)
i) Upto and including 60 3 100 3 5 300 15
ii) 61 to 90 3 200 6 5 400 20
iii) 91 to 140 3 400 12 5 570 28
iv) above 140 3 500 15 5 800 40

4
IS 16205 (Part 24) : 2018

s
ipe

m
.co
ip
ail
uls
gm
oT
i@
mp ed t
uls
ns
plt
e
Lic

Key Tolerances as per class m of ISO 2768-1


1 Frame
2 Guide rails
3 Graduated scale
4 Guidance carriage
5 Head of hammer
6 120° vee block
7 Rigid base
NOTE — This drawing is not intended to govern design except as regards the dimensions shown

F IG. 101 IMPACT TEST A PPARATUS

5
IS 16205 (Part 24) : 2018

s
ipe

m
.co
ip
ail
uls

Key IEC 986/04


gm
oT

1 Sample
2 Centre of bending cylinder
i@

3 Support
mp ed t

4 Guide for conduit


uls

NOTE — This drawing is not intended to govern design except as regards the dimensions shown
ns
plt

F IG. 102 BENDING TEST APPARATUS


e
Lic

ANNEX A
(Normative)
CLASSIFICATION CODING FOR CONDUIT SYSTEMS

This annex of IS 16205 (Part 1) is not applicable.

ANNEX B
(Normative)
DETERMINATION OF MATERIAL THICKNESS

This annex of IS 16205 (Part 1) is applicable.


6
IS 16205 (Part 24) : 2018

ANNEX C
(Clause 101.2)
RECOMMENDED SAMPLING PLAN AND CRITERIA FOR CONFORMITY
FOR ACCEPTANCE OF LOT

C-1 LOT C-3 NUMBER OF TESTS AND CRITERIA FOR


ACCEPTANCE
C-1.1 In any consignment , all the length of same
nominal size and class manufactured from the same C-3.1B From each of the lengths selected at random
material under essentially similar conditions of according to col 2 of Table 103, suitable lengths of
production shall be grouped together to constitute a sample shall be taken. Each of this test samples shall
lot. be subjected to the test given in 8.The number of test
samples not fulfilling the requirements of this test shall
C-2 SCALE OF SAMPLING be less than or equal to the corresponding permissible
C-2.1 For judging the conformity of a lot to the number of defectives given in col 3 of Table 103.
requirement of the acceptance tests, sampling shall be C-3.2 The lots conforming to the dimensional
done for each lot separately. For this purpose, the requirements shall be further tested for other acceptance
number of lengths to be selected at random from the tests .The lots shall be considered to have met the
lot shall be in accordance with Table 103. requirements for these tests if none of the samples
C-2.2 These lengths shall be selected from the lot at selected according to col 4 of Table 103 fails.
s
ipe

random .In order to ensure the randomness of selection, m


procedures given in IS 4905 may be followed.
.co
ip

Table 103 Scale of Sampling


ail
uls

(Clause C-2.1 and C-3.1B)


gm
oT

Sl No. Lot Size For Dimensional Requirements Other Acceptance


Tests
i@

Permissible No. of
Sample Size
mp ed t

Defectives
(1) (2) (3) (4) (5)
uls

i) Up to 300 13 0 2
ii) 301 to 500 20 0 3
ns

iii) 501 to 1000 32 1 4


plt

iv) 1001 to 3000 50 2 5


e

v) 3001 and above 80 3 7


Lic

7
Lic
ens
mp ed t
plt oT
uls uls
i@ ip
gm ipe
ail s
.co
m
Bureau of Indian Standards

BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods
and attending to connected matters in the country.

Copyright

BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publications), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of
‘BIS Catalogue’ and ‘Standards : Monthly Additions’. s
This Indian Standard has been developed from Doc No.: ETD 14 (6476).
ipe

m
.co
ip

Amendments Issued Since Publication


ail
uls

Amend No. Date of Issue Text Affected


gm
oT
i@
mp ed t
uls
ns

BUREAU OF INDIAN STANDARDS


plt

Headquarters:
e
Lic

Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002


Telephones : 2323 0131, 2323 3375, 2323 9402 Website: www.bis.org.in

Regional Offices: Telephones


Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg
NEW DELHI 110002 { 2323 7617
2323 3841
Eastern : 1/14 C.I.T. Scheme VII M, V. I. P. Road, Kankurgachi
KOLKATA 700054 { 2337 8499, 2337 8561
2337 8626, 2337 9120
Northern : Plot No. 4-A, Sector 27-B, Madhya Marg, CHANDIGARH 160019
{ 26 50206
265 0290
Southern : C.I.T. Campus, IV Cross Road, CHENNAI 600113
{ 2254 1216, 2254 1442
2254 2519, 2254 2315
Western : Manakalaya, E9 MIDC, Marol, Andheri (East)
MUMBAI 400093 { 2832 9295, 2832 7858
2832 7891, 2832 7892
Branches: A H M E D A B A D . B E N G A L U R U . B H O PA L . B H U B A N E S H WA R . C O I M B ATO R E .
D E H R A D U N . D U R G A P U R . FA R I D A B A D . G H A Z I A B A D . G U WA H AT I .
HYDERABAD. JAIPUR. JAMMU. JAMSHEDPUR. KOCHI. LUCKNOW. NAGPUR.
PA RWA N O O . PAT N A . P U N E . R A I P U R . R A J K O T. V I S A K H A PAT N A M .
Published by BIS, New Delhi

Das könnte Ihnen auch gefallen