THE CIRCUIT DIAGRAM FOR A SINGLE LINE TO GROUND FAULT ON AN UNLOADED Y-CONNECTED
GENERATOR WITH ITS NEUTRAL GROUND THROUGH A REACTANCE IS SHOWN IN FIG. 12.1, WHERE
PHASE A IS THE ONE ON WHICH THE FAULT OCCURS. THE RELATIONS TO BE DEVELOPED FOR THIS TYPE
OF FAULT WILL APPLY ONLY WHEN THE FAULT’S IS ON PHASE A, BUT THIS SHOULD CAUSE NO
DIFFICULTY SINCE THE PHASES ARE LABELED ARBITRARILY AND ANY PHASE CAN BE DESIGNATED AS
PHASE A. THE CONDITIONS AT THE FAULT ARE EXPRESSED BY THE FOLLOWING EQUATIONS:
Ib = 0 Ic = 0 Va = 0
𝐼𝑎0 1 1 1 1 𝐼𝑎1
(𝐼𝑎1) = (1 𝑎 2) (
𝑎 0 )
3
𝐼𝑎2 1 𝑎2 𝑎 0
𝑉𝑎0 0 𝑍0 0 0 𝐼𝑎1
(𝑉𝑎1) = (𝐸𝑎 ) − ( 0 𝑍1 0 ) ( 𝐼𝑎1)
𝑉𝑎2 0 0 0 𝑍2 𝐼𝑎1
𝐸0
𝐼𝑎1 =
𝑍1 + 𝑍2 + 𝑍0
EXAMPLE 12.1 A SALIENT-POLE GENERATOR WITHOUT DAMPERS IS RATED 20MVA, 13.8 KV AND HAS A
DIRECT AXIS SUBTRANSIENT REACTANCE OF 0.25 PER UNIT. THE NEGATIVE AND ZERO SEQUENCE
REACTANCE ARE RESPECTIVELY, 0.35 AND 0.10 PER UNIT. THE NEUTRAL OF THE GENERATOR IS SOLIDLY
GROUNDED. DETERMINE THE SUBTRANSIENT CURRENT IN THE GENERATOR AND THE LINE TO GROUND
FAULT OCCURS AT THE TERMINALS WITH GENERATOR OPERATING UNLOADED AT RATED VOLTAGE.
NEGLECT RESISTANCE.
SOLUTION:
ON A BASE OF 20 MVA ,13.8KV Ea = 1 PER UNIT SINCE THE INTERNAL VOLTAGE IS EQUAL TO THE
TERMINAL VOLTAGE AT NO LOAD. THEN IN PER UNIT,
𝐸0 1.0 + 𝑗0
𝐼𝑎1 = = = −𝑗1.43 𝑃. 𝑈.
𝑍1 + 𝑍2 + 𝑍0 𝑗0.25 + 𝑗0.35 + 𝑗0.10
BASE CURRENT =
20000
= 837 𝐴
√3 𝑋 13.8
SINCE THE GENERATED VOLTAGE – TO – NEUTRAL Ea WAS TAKEN AS 1.0 PER UNIT, THE ABOVE LINE –
TO – LINE VOLTAGES ARE EXPRESSED IN PER UNIT OF THE BASE VOLTAGE TO NEUTRAL. EXPRESSED IN
VOLTS, THE POSTFAULT LINE VOLTAGES ARE
13.8
𝑉𝑎 = 1.01 𝑥 𝐿77.7 = 8.05 𝐿 77.7 𝑘𝑉
√3
13.8
𝑉𝑏 = 1.980 𝑥 𝐿270 = 15.78 𝐿 270 𝑘𝑉
√3
13.8
𝑉𝑐 = 1.01 𝑥 𝐿102.3 = 8.05 𝐿 102.3 𝑘𝑉
√3
BEFORE THE FAULT THE LINE VOLTAGES WERE BALANCED AND EQUAL TO 13.8 kV. FOR COMPARISON
WITH THE LINE VOLTAGES AFTER THE FAULT OCCURS, THE PREFAULT VOLTAGES, WITH Van = Ea AS
REFERENCE, ARE GIVEN AS
THE PHASOR DIAGRAMS OF PREFAULT AND POSTFAULT VOLTAGES ARE SHOWN IN FIG. 12.3.