Programming Manual

Logix 5000 Controllers Import/Export Project Components


1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix, 1789
SoftLogix, 5069 CompactLogix, 5069 Compact GuardLogix, Studio 5000 Logix Emulate
Important user information
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this
equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and
wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried
out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or
application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements
associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the
examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described
in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to
personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic
loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence

Important: Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be
present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous
temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc
Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work
practices and for Personal Protective Equipment (PPE).

Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes

This manual includes new and updated information. Use these reference
tables to locate changed information.

Grammatical and editorial style changes are not included in this summary.

Global changes

This table identifies changes that apply to all information about a subject in
the manual and the reason for the change. For example, the addition of new
supported hardware, a software design change, or additional reference
material would result in changes to all of the topics that deal with that
subject.

Subject Reason
None

New or enhanced features

This table contains a list of topics changed in this version, the reason for the
change, and a link to the topic that contains the changed information.

Topic Name Reason


Introduction on page 13 Added information about data exchange files that represent Rockwell
Automation devices in the automation system.
Additional Considerations for Data Exchange Added information about data exchange with other software
on page 69 applications, data exchange file type capabilities and limitations, and
data exchange device support tables.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 3


Table of contents

Summary of Changes Studio 5000 environment ................................................................................ 9


Additional resources ....................................................................................... 9
Legal notices ................................................................................................. 10
Preface
Chapter 1

Import and export logic Introduction................................................................................................... 13


Export considerations ................................................................................... 17
components Security considerations for exporting components ................................ 19
Export logic components .............................................................................. 19
Import considerations ................................................................................... 20
Online import ......................................................................................... 20
Motion .................................................................................................... 22
Safety...................................................................................................... 23
Security .................................................................................................. 23
Multiple components .............................................................................. 23
Import logic components .............................................................................. 24
Configuration properties for import .............................................................. 25
Properties for imported components ...................................................... 25
Configure multiple component properties.............................................. 29
Program connections .............................................................................. 32
Create a new connection .................................................................. 36
Configure component references ........................................................... 38
References configuration example ......................................................... 40
Undefined references.............................................................................. 41
Attention flags ........................................................................................ 41
Errors and warnings on import ............................................................... 42
Project documentation .................................................................................. 42
Find and replace ............................................................................................ 44
Compatibility.......................................................................................... 45

Chapter 2

Additional considerations Introduction................................................................................................... 47


Export considerations ................................................................................... 47
for rungs Import considerations ................................................................................... 47

Chapter 3

Additional considerations Introduction................................................................................................... 49


Export considerations ................................................................................... 49
for routines Import considerations ................................................................................... 49

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 5


Table of contents

Chapter 4

Additional considerations for Introduction................................................................................................... 51


Export considerations ................................................................................... 51
programs and equipment Import considerations ................................................................................... 51
phases
Chapter 5

Additional considerations for Introduction................................................................................................... 53


Export considerations ................................................................................... 53
user-defined types Import considerations ................................................................................... 53

Chapter 6

Import and export Add-On Introduction................................................................................................... 55


Create export files ......................................................................................... 55
Instructions Export to separate files ........................................................................... 56
Export to one file .................................................................................... 57
Import an Add-On Instruction ...................................................................... 58
Import considerations ............................................................................. 58
Import configuration .............................................................................. 59
Update an Add-On Instruction to a later revision using import.................... 60

Chapter 7

Import and export tag-based Introduction................................................................................................... 63


Create export files ......................................................................................... 63
alarms and alarm definitions Import alarms and alarm definitions ............................................................. 63
Import considerations ................................................................................... 64

Chapter 8

Additional considerations Introduction................................................................................................... 67


Export considerations ................................................................................... 67
for tags Import considerations ................................................................................... 67

Chapter 9

Additional considerations for Data exchange with other software applications .......................................... 69
Data exchange file type capabilities and limitations..................................... 70
data exchange Data exchange device support tables ............................................................ 72
1715 ........................................................................................................ 72
1719 ........................................................................................................ 72
1732 ........................................................................................................ 72
1734 POINT I/O ..................................................................................... 72
1738 ........................................................................................................ 74
1746 ........................................................................................................ 74

6 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Table of contents

1747 ........................................................................................................ 74
1753 ........................................................................................................ 74
1756 ControlLogix ................................................................................. 74
1757 ........................................................................................................ 79
1768 CompactLogix ............................................................................... 79
1769 ........................................................................................................ 80
1771 ........................................................................................................ 81
1783 Stratix ............................................................................................ 81
1784 ........................................................................................................ 82
1785 ........................................................................................................ 82
1788 ........................................................................................................ 82
1789 ........................................................................................................ 82
1791DS ................................................................................................... 82
1791ES ................................................................................................... 83
1794 FLEX I/O ...................................................................................... 83
1797 ........................................................................................................ 83
1799 ........................................................................................................ 84
193/592................................................................................................... 84
20-750 .................................................................................................... 84
5069 CompactLogix ............................................................................... 84
5094 ........................................................................................................ 85
ArmorPoint ............................................................................................. 85
ArmorStart.............................................................................................. 85
Communication ...................................................................................... 85
DPI to EtherNet/IP ................................................................................. 87
Drive ....................................................................................................... 87
Embedded ............................................................................................... 88
Energy Management Products ............................................................... 89
HMI ........................................................................................................ 89
Kinetix .................................................................................................... 89
Motion .................................................................................................... 89
MPI to EtherNet/IP................................................................................. 90
PowerFlex .............................................................................................. 90
Specialty ................................................................................................. 92
Other....................................................................................................... 93
Index

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 7


Preface

Studio 5000 environment The Studio 5000 Automation Engineering & Design Environment®
combines engineering and design elements into a common environment. The
first element is the Studio 5000 Logix Designer® application. The Logix
Designer application is the rebranding of RSLogix 5000® software and will
continue to be the product to program Logix 5000™ controllers for discrete,
process, batch, motion, safety, and drive-based solutions.

The Studio 5000® environment is the foundation for the future of


Rockwell Automation® engineering design tools and capabilities. The Studio
5000 environment is the one place for design engineers to develop all
elements of their control system.

These documents contain additional information concerning importing and


Additional resources exporting projects and project components.

Resource Description
Logix 5000 Controllers Import/Export Reference Manual, Provides detailed reference information and examples for
publication 1756-RM084 importing and exporting projects and components.
Logix 5000 Controllers Security Programming Manual, Describes how to configure security for controller projects
publication 1756-PM016 using the Logix Designer application.
Product Certifications webpage, available Provides declarations of conformity, certificates, and other
at http://ab.rockwellautomation.com certification details.

View or download publications


at http://www.rockwellautomation.com/literature. To order paper copies of
technical documentation, contact the local Rockwell Automation distributor
or sales representative.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 9


Preface

Legal notices Copyright Notice

Copyright © 2018 Rockwell Automation Technologies, Inc. All Rights


Reserved. Printed in USA.

This document and any accompanying Rockwell Software products are


copyrighted by Rockwell Automation Technologies, Inc. Any reproduction
and/or distribution without prior written consent from Rockwell Automation
Technologies, Inc. is strictly prohibited. Please refer to the license agreement
for details.

End User License Agreement (EULA)

You can view the Rockwell Automation End-User License Agreement


("EULA") by opening the License.rtf file located in your product's install
folder on your hard drive.

Other Licenses

The software included in this product contains copyrighted software that is


licensed under one or more open source licenses. Copies of those licenses are
included with the software. Corresponding Source code for open source
packages included in this product are located at their respective web site(s).

Alternately, obtain complete Corresponding Source code by contacting


Rockwell Automation via the Contact form on the Rockwell Automation
website: http://www.rockwellautomation.com/global/about-us/contact/contac
t.page
Please include "Open Source" as part of the request text.

A full list of all open source software used in this product and their
corresponding licenses can be found in the OPENSOURCE folder included
with the Release Notes. The default installed location of these licenses is
C:\Program Files (x86)\Common
Files\Rockwell\Help\<Product>\ReleaseNotes\OPENSOURCE\index.htm.

Trademark Notices

Allen-Bradley, ControlBus, ControlFLASH, Compact GuardLogix, Compact


I/O, ControlLogix, CompactLogix, DCM, DH+, Data Highway Plus,
DriveLogix, DPI, DriveTools, Explorer, FactoryTalk, FactoryTalk
Administration Console, FactoryTalk Alarms and Events, FactoryTalk Batch,
FactoryTalk Directory, FactoryTalk Security, FactoryTalk Services Platform,
FactoryTalk View, FactoryTalk View SE, FLEX Ex, FlexLogix, FLEX I/O,
Guard I/O, High Performance Drive, Integrated Architecture, Kinetix,
Logix5000, Logix 5000, Logix5550, MicroLogix, DeviceNet, EtherNet/IP,
PLC-2, PLC-3, PLC-5, PanelBuilder, PowerFlex, PhaseManager, POINT
I/O, PowerFlex, Rockwell Automation, RSBizWare, Rockwell Software,
RSEmulate, Historian, RSFieldbus, RSLinx, RSLogix, RSNetWorx for

10 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Preface

DeviceNet, RSNetWorx for EtherNet/IP, RSMACC, RSView, RSView32,


Rockwell Software Studio 5000 Automation Engineering & Design
Environment, Studio 5000 View Designer, SCANport, SLC, SoftLogix,
SMC Flex, Studio 5000, Ultra 100, Ultra 200, VersaView, WINtelligent,
XM, SequenceManager are trademarks of Rockwell Automation, Inc.

Any Rockwell Automation logo, software or hardware product not


mentioned herein is also a trademark, registered or otherwise, of Rockwell
Automation, Inc.

Other Trademarks

CmFAS Assistant, CmDongle, CodeMeter, CodeMeter Control Center, and


WIBU are trademarks of WIBU-SYSTEMS AG in the United States and/or
other countries. Microsoft is a registered trademark of Microsoft Corporation
in the United States and/or other countries. ControlNet is a trademark of
ControlNet International. DeviceNet is a trademark of the Open DeviceNet
Vendors Association (ODVA). Ethernet/IP is a trademark of ControlNet
International under license by ODVA.

All other trademarks are the property of their respective holders and are
hereby acknowledged.

Warranty

This product is warranted in accordance with the product license. The


product’s performance may be affected by system configuration, the
application being performed, operator control, maintenance, and other related
factors. Rockwell Automation is not responsible for these intervening factors.
The instructions in this document do not cover all the details or variations in
the equipment, procedure, or process described, nor do they provide
directions for meeting every possible contingency during installation,
operation, or maintenance. This product’s implementation may vary among
users.

This document is current as of the time of release of the product; however,


the accompanying software may have changed since the release. Rockwell
Automation, Inc. reserves the right to change any information contained in
this document or the software at any time without prior notice. It is your
responsibility to obtain the most current information available from Rockwell
when installing or using this product.

Environmental Compliance

Rockwell Automation maintains current product environmental information


on its website
at http://www.rockwellautomation.com/rockwellautomation/about-us/sustain
ability-ethics/product-environmental-compliance.page

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 11


Preface

Contact Rockwell

Customer Support Telephone — 1.440.646.3434

Online Support — http://www.rockwellautomation.com/support/

12 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Chapter 1

Import and export logic components

This chapter explains import and export of logic components and the
Introduction exchange of data files that represent Rockwell Automation devices in the
automation system.

Use the Logix Designer application to perform online edits for the Logix
family of controllers.

The import/export functionality provides a greater degree of flexibility


during development and deployment of projects. Import/Export supports the
ability to export a component of a Logix Designer project and then import
that component into either the same, or a different project, offline or online
(even in Remote Run mode). Import/Export provides the ability to import
components to create something new in a project, or to update something that
exists.

Export and import these logic components offline and online:

• Rungs
• Routines
• Programs and equipment phases
• User-defined data types (UDT) and user-defined string types
• Add-On Instructions
• Trends
• Modules

Changes or additions to a project that may be impractical to do with online


editing can be completed offline and then imported in one operation into a
running controller by using the extended import/export feature. Engineering
collaboration is also facilitated because many engineers can work on one or
more of the project components independently offline and then use import to
merge the changes into one project.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 13


Chapter 1 Import and export logic components

With online editing, modify or create a component and then modify other
components referenced by that component in the project sequentially.
Importing online differs from online edits in that it provides the ability to
create and delete components, as well as update referenced components, in
one step.

ATTENTION: All Rockwell Automation XML files are encoded in UTF-8 file format. Users editing
XML files must use a text editor like Notepad that supports UTF-8 encoding. When saving the
edited file by using a non-UTF-8 compatible editor after making changes, the encoding breaks,
resulting in a non-valid XML file.

Data Exchange

Exchange data files that represent Rockwell Automation devices in the


automation system produced in a tool such as EPLAN Electric P8 or
AutoCAD Electrical. Create a Logix Designer project file that represents a
controller-centric subset of the system without having to manually add,
name, or recreate high-level configuration of the associated devices.

• Import or export hardware diagrams to or from a standard file type to


share data between different software applications and the Logix
Designer Professional Edition using these formats:
• Web Ontology Language (OWL)
• AutomationML (AML)

The .rdf and .aml file types are used only for PLC data exchange as described
below. When saving the Logix Designer project file to the data exchange file
types, none of the tasks, programs, routines Add-On Instructions,
user-defined type data from the project is stored. Only export the project file
types when exchanging data with eCAD tools.

Tip: Import of eCAD data via data exchange file types is only possible when creating a
new Logix Designer project. This data cannot be merged into an existing project.
Tip: Data exchange features differ between Studio 5000 Logix Designer and Studio
5000 Architect. Use the data exchange interface in Studio 5000 Architect to
exchange I/O point tag/alias data and to conduct merge workflows into Studio
5000.

EPLAN Electric P8

For EPLAN Electric P8, use AML data files (.aml) and associated PLC data
import/export workflows to exchange data between the Logix Designer
application version 32.00.00 and EPLAN Electric P8 version 2.7 and later.

14 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

This workflow shows the process for data exchange from supported Studio
5000® applications to the EPLAN Electric P8 application when starting the
data exchange within Studio 5000.

Number Description
Architect v 3.0 and later
• Multiple controller environment
• Hardware device configuration exchange
• IO point tag (alias) exchange
• Round trip/merge exchange
Logix Designer v 32
• Single controller environment
• Hardware devices configuration exchange
• Round trip/merge data exchange not supported, must always bring data into new .ACD file
Version 2.7 and later
• Import AML file to transfer PLC data to EPLAN Electric P8 interface
• Automation data attachment to part data/macros properly configured for AML
• Data can be connected manually if part data/macros aren't AML compatible
• Recreate Ethernet/ControlNet connections on single line drawing
• IO point symbolic address/function text placement from Architect ONLY
• Make IO point symbolic address/function text edits bring back into Architect ONLY

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 15


Chapter 1 Import and export logic components

This workflow shows the process for data exchange from the EPLAN
Electric P8 application to supported Studio 5000 applications when starting
the data exchange within EPLAN.

Number Description
Version 2.7 and later
• Utilize specific workflows are defined by EPLAN TechTip:PLC data Exchange to configure RA devices as
PLC Boxes with rack/slot, IO point symbolic address, function definition and network topology
properties in EPLAN Electric P8
• IO point symbolic address and function text placement to Architect ONLY
• Make IO point symbolic address/description edits in Architect ONLY, bring back into EPLAN
Architect 3.0 and later
• Multiple controller environment
• Hardware device configuration exchange
• IO point tag (alias) exchange
• Round trip/merge exchange
Logix Designer v 32
• Single controller environment
• Hardware devices configuration exchange
• Round trip/merge data exchange not supported, must always bring data into new .ACD file

AutoCAD Electrical

For AutoCAD Electrical, use the Rockwell Automation Data Adapter to


exchange data between the Logix Designer application version 32.00.00 and
AutoCAD Electrical versions 2014 through 2018. Data Adapter is a tool used
to translate Rockwell Automation hardware data in OWL (.rdf) format for
auto generation of two-dimensional footprint and PLC I/O schematic
drawings in AutoCAD Electrical. Download the Data Adapter tool from

16 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

Rockwell Automation's Product Download and Compatibility Center


(PCDC).

This workflow shows the supported process for bidirectional data exchange
from Studio 5000 applications to AutoCAD Electrical applications.

Number Description
Architect v 3.0 and later
• Multiple controller environment
• Hardware device configuration exchange
• IO point tag (alias) exchange
• Round trip/merge exchange
Logix Designer v 32
• Single controller environment
• Hardware devices configuration exchange
• Round trip/merge data exchange not supported, must bring changes into new .ACD file
Data Adapter v 10
• Stand alone tool
• MUST be installed in same environment as AutoCAD Electrical
• Can also be co-located with Studio 5000
Version 2014 - 2018
• Rockwell Automation PLC and IO footprint symbol placement
• PLC and IO schematic symbol placement
• IO point name placement from Architect ONLY
• Make IO point name edits, use tool to bring back into Architect ONLY

Export considerations Keep these considerations in mind when exporting components.

• More than is expected may appear in an .l5x file. Some components


referenced by the exported component are also exported.
• Starting with version 24.00.00 of Logix Designer application, use
program parameters to share data directly between programs in
addition to Controller-scoped tags. For more information on program

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 17


Chapter 1 Import and export logic components

parameters, refer to 1756-PM021, Logix 5000 Controllers Program


Parameters Programming Manual.
When exporting a The exported component includes The exported file also includes referenced
the
Set of rungs Rungs Controller-scoped tags, program-scoped tags,
user-defined data types, user-defined string
types, Add-On Instructions

Routine Routine Controller-scoped tags, program-scoped tags,


user-defined data types, user-defined string
types, Add-On Instructions
Program Program, routines, and program-scoped Controller-scoped tags, user-defined data types,
(For considerations when tags user-defined string types, Add-On Instructions
exporting multiple programs When exporting a program from the Logical
using multi-select, see Multiple Organizer, the program logical hierarchy is
Components.) exported in addition to the program specified.
Refer to the online help for information about
the Logical Organizer.
Equipment Phase Equipment phase, routines, Controller-scoped tags, user-defined data types,
phase-scoped tags, and user-defined string types, Add-On Instructions
controller-scoped PHASE tag
User-defined data type User-defined data type User-defined data types, user-defined string
types, Add-On Instructions
User-defined string type User-defined string type
Add-On Instruction Add-On Instruction, Logic routine and User-defined data types, user-defined string
any scan mode routines, and parameter types, Add-On Instructions
and local tags
Trend Trend

For example, if exporting a rung with an instruction that uses


(references) a bit in a tag that is a user-defined type tag, the export
content includes the referenced tag and the referenced user-defined
type, along with the rungs. When importing the rung, choose whether
to also import the referenced tag and user-defined type.
• Only the offline data values of tags are exported to the .l5x file, even
when the project is online with the controller. When exporting
components that include tags while online, the software prompts to
upload tag values before exporting the component.
Important: Whether exporting while offline or online with the controller, only offline data values of tags are
exported to the .l5x file.

• Export a component that has Test Edits, but the resulting file cannot be
imported. If an .l5x file with Test Edits is selected for import, then the
import aborts.

See also

1756-PM021, Logix 5000 Controllers Program Parameters


Programming Manual

18 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

Multiple Components on page 23

Security considerations for The table describes considerations to keep in mind when exporting secured
components.
exporting components
For this security setting Keep this in mind
Permission set A permission set that restricts viewing an Add-On Instruction or routine in the
Logix Designer application does not prevent a user from exporting and viewing
the Add-On Instruction or routine in clear text. To prevent exporting the
component, configure the permission set to deny the Routine: Export or AOI:
Export permissions.
To prevent exporting a component in clear text, configure the permission set to
deny the Add-On Instruction: Export Unencoded permission for Add-On
Instructions and the Routine: Export Unencoded permission for routines.
Source Key Protection When a component is protected with a Source Key, users without the source
key cannot alter the logic of the component, and the protected component is
written to the export file in an encoded format.
License-Based Source Protection The protected component is written to the export file in an encoded format
unless the user's license contains Export permission. To export in
non-encrypted text, the license must contain the Export permission, and when
saving the export file, the user must clear the Encode Protected Content
check box.

For more information on security considerations, see the Logix 5000


Controllers Security Programming Manual, publication 1756-PM016.

See also

Logix 5000 Controllers Security Programming Manual, publication


1756-PM016

Export logic components Export logic components to import the component into another project, or to
create a backup copy of a component while modifying the original.

To export logic components:

1. In the Logix Designer application Controller Organizer, select the


logic component to export.

Tips: • Select multiple programs, Add-On Instructions, and user-defined data types for export. See the Import
and Export Add-On Instructions chapter for detailed information.
• Also export logical components from the Logical Organizer. Select multiple programs and include
child folders and programs in their hierarchical levels. Refer to the Logix Designer application online
help for instructions.

2. Right-click and select Export <logic component>.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 19


Chapter 1 Import and export logic components

3. In File Name, enter a file name for the export file.

Tip: Export multiple Add-On Instructions to a single file or to multiple files. See Configure multiple component
properties for detailed information.

4. (Optional) Edit the default description or add a description, if desired.

A default description is supplied for some component exports.


Tip: The file description can be viewed in a tooltip during import when selecting which file to import.

5. Select Export.

See also

Configure multiple component properties on page 29

Import considerations This section covers general considerations for all component-type imports.
See the chapters for specific components (program, routine, rungs, Add-On
Instructions, User-Defined data types, tags, and data exchange) for additional
export and import considerations for that component, whether it is imported
directly or as a reference during another component import.

Important: When editing online, if the program scan time is large, or the number of modified rungs is large, HMI
and Logix Designer application communication timeouts may occur when edits are finalized.
The timeout is caused by the (scan time) x (number of changed rungs). A large program with a very
fast scan, or a lot of rungs (but only a few modified), may not timeout.

Tip: Starting with version 24.00.00 of the Logix Designer application, use program parameters to share data
between programs in much the same way as using controller-scoped tags. Program parameters are imported
and exported in the same way as tags in most instances. For more information on program parameters, refer
to the Logix 5000 Controllers Program Parameters Manual, publication 1756-PM021.

See also

1756-PM021, Logix 5000 Controllers Program Parameters


Programming Manual

Online import The table describes considerations for importing components while online.

Topic Consideration
Tag data values When overwriting tags while online, data values are not written to the online project. Data
values for overwritten tags while online are written only to the offline project.
Data values for tags created while online are written to the offline and online project.
Select the Preserve existing tag values in offline project check box to prevent tag values
from being overwritten in the offline project.

20 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

Topic Consideration
Locking controller edits When performing an online import, the controller is locked, preventing other workstations
connected to the controller from making edits until the import completes. If another
workstation has the controller locked, an online import cannot be initiated.

Tag attributes Tag attributes (for example, External Access, Constant, and Style) are written to the online
project and the offline project.
If existing tags are to be overwritten with new attributes that are incompatible with existing
user logic, the import is not allowed.
Online options When importing programs, equipment phases, routines, or rungs online, the logic can be
imported as:
• Pending Edits that exist only in the offline project and are not downloaded to the
controller.
• Accepted Edits that are downloaded to the controller where they can be tested, accepted,
or canceled.
• Finalized Edits that are downloaded to the controller, assembled, and cannot be canceled.
As with normal online editing, with any online option chosen, any tags, data types, or Add-On
Instructions that are created or modified are downloaded immediately. In addition, any task,
program, or routine properties that are modified are downloaded immediately. These changes
remain in the controller, even if logic edits are later canceled. Pending Edits and Accepted
Edits options do not apply to Add-On Instructions and user-defined types, so Online Options
are not presented during an Add-On Instruction or user-defined type import.
Under these conditions, only the Finalize All Edits in Program option is available.
• When online with the controller and importing a program that contains connections to
InOut parameters and:
• Changing the final connection of an InOut parameter online.
• When the connections are different than what is currently downloaded to the
controller. Finalize All Edits In Program is the only option because the program is
overwritten on Import. Configure the InOut connections such that the InOut parameter
connection is taken not from the destination controller but from the Import file, or from a
new final name for the connection entered by the user.
• When importing a program or programs with connections online and in Remote Run
mode, and:
• A connection is changed from connect to disconnect.
• A connection is changed from disconnect to connect.
• The final name of a connection is changed.
• A connection is added and its operation is set to connect.
• When importing program hierarchies or multiple programs online and in Remote Run
mode.
External access If the External Access is changed, it may change the behavior of the running HMI.
Changed External Access attributes for overwritten tags can cause changes to HMI behavior,
regardless of whether logic changes are tested, accepted, or finalized.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 21


Chapter 1 Import and export logic components

Topic Consideration
Asynchronous import Import operations are not synchronized with the Program Scan (just as online editing
operations are not synchronized). For most objects, this does not matter because:
• Existing online tag data values are never overwritten.
• New tags and their initial data values are written to the controller before the new logic
runs.
• The switch-over to the new logic is synchronized with the program scan (just like online
editing).
In general, although online tag data values are not overwritten, some object attributes can
change asynchronously to the Program Scan. Some examples:
• Changed attributes of existing programs or equipment phases (such as changing the Initial
Step Index of an equipment phase) are written to the controller before switch-over, so old
logic can run with the new configuration.
• An existing program without a main routine could become configured with a main routine
as part of import, and that main routine runs immediately even though the new logic for
that routine has not yet been accepted.
• Changing Logix-based alarm tag configuration (such as alarm messages or associated tag
definitions) can go into effect while the old alarm trigger logic is still active, resulting in
alarm messages that do not match the condition.
Communication timeouts Communication timeouts may occur when rungs are deleted online in Run mode if the
program scan time is long or the number of rungs being deleted is large.
If using Partial Import Online and choosing Pending or Accept edits, when finalizing those
edits, a timeout can occur. This timeout can occur as HMI or Logix Designer application
communication timeouts. Keep these timing considerations in mind.
• Finalizing online edits while in Run mode causes brief interruptions to communication,
which are usually unnoticeable.
• The length of the communication interruption is related to the product of the (task scan
time) x (the number of changed rungs).
• When very long program scans or large quantities of changed rungs occur, the
communication interruption can be long enough to cause timeouts.
• The timeout of a Rockwell Automation HMI is typically 8 seconds, while a Logix Designer
online session typically has a 30-second timeout.
• It does not matter whether the edits came from individual online edits or from a Partial
Import Online (choosing Pending or Accepted edits).
• Partial Import Online (choosing Finalize Edits) does not cause the communication timeout,
due to the use of asynchronous transaction commit processing.

Motion The table describes considerations for importing motion components while
online.

Topic Consideration
Motion components Motion tags (Axis, Coordinate System, and Motion Group) cannot be created, modified or
limitations while online deleted during an online import, however, existing motion tags can be referenced. When
doing an offline import, motion tags can be created and modified.

22 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

Safety The table describes considerations for importing safety components.

Topic Consideration
Safety components Safety components cannot be created, modified or deleted during an online import.
limitations while online
Safety components Safety components cannot be created, modified or deleted during an offline import. If a
limitations while offline Safety Signature exists, the project is Safety locked. A non-recoverable safety fault is
present if the Safety Partnership status between the primary controller and the safety
partner is any value other than OK, or if Safety modify permissions are denied.

Scheduled location In a Safety project, Safety programs cannot be imported into a Standard task and vice
versa.
Safety programs imported Safety programs imported into a Standard project are converted to Standard programs
into a standard project during the import processing and a warning appears in the Errors Pane during initial
parsing of the .l5x file. In this case, imported logic does not verify after import if it contains
instructions that are only valid in a Safety routine.
Controller Fault Handler and A Safety program cannot be scheduled in the Controller Fault Handler or Power-Up
Power-Up Handler Handler folders.

Security The table describes considerations for importing a secured project or


component.

Topic Consideration
Project or components If the project or components in it are secured by a permission set, the import process may not
are secured by a be able to create, delete, or modify some components, depending on the security actions that
permission set have been granted or denied for those components.
Project or components A CmStick containing a license with Use permission must be present locally on any USB port
are secured by on the computer. Use permission cannot be obtained from a network license server. All other
License-Based Source license privileges can be contained on the local CmStick, or provided by a license server on the
Protection network.

For more information on security considerations, see the Logix 5000


Controllers Security Programming Manual, publication 1756-PM016.

See also

Logix 5000 Controllers Security Programming Manual ,


publication 1756-PM016 .

Multiple components The table describes considerations for importing multiple User-defined types
and Add-On Instructions and multiple target programs.

Topic Consideration
Importing multiple When User-defined types (UDTs) and Add-On Instructions (AOIs) are imported using the
User-defined types (UDTs) Multiple Components option, all UDTs and AOIs are treated as references. Unlike child
and Add-On Instructions components, referenced components can be configured independently from the import
(AOIs) target.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 23


Chapter 1 Import and export logic components

Topic Consideration
Controller Fault Handler and When importing multiple target programs, the Controller Fault Handler and Power-Up
Power-Up Handler disabled Handler are unavailable in the Schedule In list.

Use these steps to import logic components. Import components from the
Import logic components Controller Organizer and from the Logical Organizer.

Importing components into a controller while online can affect controller operation. Use caution when
modifying logic while online in Remote Run or Run mode.

To import logic components:

1. Select the item and choose the import component menu item as
described in the table.

To import a Right-click And choose


Set of rungs A rung or set of rungs within a Ladder routine Import Rungs
editor
Routine A program Import Routine
Program A task, the Controller Fault Handler folder, the Import Program
Power-Up Handler folder, or the Unscheduled
Programs folder
Equipment Phase A task or the Unscheduled Programs folder Import Equipment Phase
Important: This feature is disabled in
this version of the Logix
Designer application.
User-defined data type User-Defined folder Import Data Type
User-defined string type Strings folder Import String Type
Add-On Instruction Add-On Instructions folder Import Add-On Instruction
Trend Trends folder Import Trend

2. Select the file to import.

Select multiple components for import. See Configure multiple


component properties for information.

3. Select Import.

4. Continue by selecting the configuration options described in the


section below, Configuration properties for import.

See also

Configure multiple component properties on page 29

24 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

Configuration properties This section describes configuration options for importing components.

for import Tip: Trends do not require any import configuration, so the Import Configuration dialog box
does not appear and the trend is imported immediately.

Properties for imported When importing components, the previously exported information is brought
components into the project based on the selected import configuration. Determine how
the imported component (a program, for example) connects to the existing
project either by overwriting an existing component of the same type, or by
creating a new one.

The screen capture shows a typical Import Configuration dialog box. (The
dialog box might contain options different than those shown here, depending
on the imported component.)

An import component collides with an existing component if a component of


the same type, scope, and with the same name exists in the project. By
configuring the Final Name of the imported component, you determine
whether the imported component collides with an existing component, or it
does not (if a component of the same type, scope and with the same name
does not exist in the project). For a collision, you can use the existing project
component or you can overwrite it. For a non-collision, you can create a
project component or you can discard, and not import, the component from
the import file. In any case, any imported logic references are updated to be
the same as the Final Name.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 25


Chapter 1 Import and export logic components

By configuring the Operation for the component, you determine whether it is


imported from the file or an existing component is used. Incompatibility of a
collision or other situations, for example, project security privileges, may
affect what Operations are permitted for a component.

The table describes the configuration options.

Configuration Description
Import Name The Import Name is read-only and shows the name of the component as read from the
import file.
Operation The Operation determines whether the component from the import file is imported. Not all
operations are applicable to a given component in all situations. Sometimes there is only
one possible operation permitted in a particular situation.
Choose from these options:
• Use Existing (collisions) to use the existing component in the project. The component
definition in the import file is not imported. If the component collides and there is no
definition for the component in the import file, then this is the only Operation
available.
• Overwrite (collisions) to import the component definition from the import file and
overwrite the existing component definition in the project.
Important: If selecting Overwrite for a reference tag, the tag data that is different is
written to the offline project only, even if online with the controller.
• Create (non-collisions) to import the component from the import file creating a new
component in the project.
• Discard (non-collisions) to discard the component and abort import. If the main
component from the import file (the program during a program import, for example) is
discarded, the references can still be imported. If a referenced component is discarded,
any imported logic references are not defined in the project and might not verify after
import.
• Undefined (non-collision) is the only Operation available if the component does not
collide and there is no definition for the component in the import file. The imported
logic is not verified after import.
• Delete (non-collision) indicates that this component will be deleted from the project on
import.
Final Name The Final Name determines the name of the component that shows in the project after the
import (except in the case of a Delete Operation).
Create or avoid collisions by changing the Final Name. If change the Final Name to differ
from the Import Name, all logic references in the import content are updated.
If change the Final Name of a component during configuration so that it collides with a
different existing component after it was colliding with another, any changes made to the
Operation are preserved.
Description The Description that is shown depends on the Operation. If the Operation is:
• Overwrite or Create, the description is initially the description from the import file. Edit
it during import configuration.
• Discard, the description is initially the description from the import file. It is read-only
and may not be edited.
• Use Existing or Delete, the description is the existing component description. It is
read-only and may not be edited.
• Undefined, no description is shown.
The description for members of an expanded tag follow the same rule the tag follows. Only
members of the tag that have descriptions are shown when the tag is expanded.

26 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

Configuration Description
Schedule In The Schedule In setting determines the task in which the imported component is
scheduled.
The default setting for Schedule In depends on the Operation setting and whether you
import the component into the Controller Organizer or the Logical Organizer.
If you import the component into the Controller Organizer:
• When selecting a task or handler and Operation is set to Overwrite, Schedule In is
set to the selected task or handler.
• When selecting a task or handler and Operation is set to Use Existing, Schedule In is
set to the task or handler where the program is scheduled in the destination project.
• When the selection in Controller Organizer is not a task or handler, Schedule In is
set to Unscheduled Programs/Phases.
If importing the component into the Logical Organizer:
• When set Operation to Create or Discard, Schedule In is set to Unscheduled
Programs/Phases.
• When set Operation to Use Existing or Overwrite, Schedule In is set to
the Task or Handler for which the program is scheduled in the destination project.
Adjust the Schedule In setting when:
• Operation is set to Create (the target component is being created).
• Operation is set to Overwrite and not online in Remote Run mode.
Change the Schedule In setting when:
• Import a program folder.
• Operation is set to any setting other than Create or Overwrite.
Preserve scheduling for child When selecting this setting, any child programs that exist in the destination project remain
programs that already exist scheduled as configured in the project. When clearing this setting, all imported programs
are scheduled in the task specified by the Schedule In setting.
This setting is available when Operation is set to Create or Overwrite; otherwise it is
read-only. When enabled, this setting is selected by default. The setting is not preserved
between import sessions.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 27


Chapter 1 Import and export logic components

Configuration Description
Parent Determines where the imported component is organized.
The default setting for Parent depends on whether exported the component from
the Controller Organizer or the Logical Organizer, whether importing it to
the Controller Organizer or the Logical Organizer, and on the Operation setting.
• If exported the program from the Controller Organizer and importing it to either
the Controller Organizer or the Logical Organizer:
• Parent is set to the selected program in the Logical Organizer if the
operation is Create or Discard.
• Parent is set to the parent configured in the destination project
if Operation is set to Use Existing or Overwrite.
• If exported the program from the Logical Organizer and importing it to the Logical
Organizer:
• Parent is set to the selected program in the Logical Organizer
if Operation is set to Create or Discard.
• Parent is set to the parent configured in the destination project
if Operation is set to Use Existing.
• Parent is set to the selected item in the Logical Organizer if Operation is
set to Overwrite.
• If exported the program from the Logical Organizer and importing it to
the Controller Organizer:
• Parent is set to <none> if Operation is set to Create, Discard,
or Overwrite.
• Parent is set to the parent configured in the destination project
if Operation is set to Use Existing.

When there is a collision, the components colliding may be identical, or they


may be different. If they are the same, the Operation defaults to Use
Existing. If they are different, imported components default to Overwrite
while referenced components default to Use Existing. Choose Overwrite to
use the component definition from the import file, or Use Existing to use the
component in the project. Icons on the Import Configuration dialog box
(next to the Operation control) show whether colliding components are
identical or different.

Situation Icon
Component shows only in the import file (non-collision)

Component shows only in the project (non-collision)


Component collides with a component in the project and differences exist
Component collides with a component in the project and they are identical No icon

To see the differences between the import component and the colliding
project component, select Collision Details and a dialog box opens. Use the
information in the dialog box to determine whether to overwrite or to use the
existing component.

28 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

For components that do not collide, select Properties for more information
on the component.

Important: A component selected for import that collides with an existing component defaults to overwriting the
project component unless the components are identical, in which case, the project component is used. If
the project component is used, references may still be imported.

Configure multiple component This section describes the settings to use to import and configure multiple
components.
properties
To configure multiple component properties:

1. Select components for export from a project.

2. Export those components.

3. Select those components and import them into another project.

Use one of these methods to import multiple components.


• Select File>Import Component and choose the component type
to import.
• Copy the programs, Add-On Instructions, or user-defined data
type, right-click a task in the organizer, and select Paste With
Configuration.
Tip: The Paste With Configuration menu option works when copying from the
Controller Organizer to the Logical Organizer, and vice versa.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 29


Chapter 1 Import and export logic components

The screen capture shows a typical Import Configuration dialog box


for multiple components. (The dialog box might contain options
different than those shown here, depending on the imported
components.)

Imported items are listed in the Import Content pane. These items are
listed in the Import Content pane based on the items that are part of
the import content.

30 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

• Programs -- If importing multiple programs, the grid shows the


programs that are being imported into the project. If importing
multiple hierarchies, the grid shows the programs and the children
of the programs that are being imported into the project.
• Tags, Add-On Instructions, data types and other components --
References include any tags directly referenced by any imported
logic or tags (using Alias For).
• Connections -- Lists the connections, from programs that are
external to the programs in the import content, that are also
connected to programs in the existing project.

The table describes the multiple-import configuration parameters.

Configuration Description
Multiple Programs The Import Content pane shows the number of programs that are being imported into
the project.
The value shown in the parenthesis excludes children of the programs.
If differences occur among the programs, the difference icon appears in
the Differences column of the Programs grid.
Imported Programs Shows the number of parent and child programs (if applicable) that are being imported
into the project.

Operation Identifies what is done with the programs upon import.


• If Import is selected, all programs are imported into the project.
• If Discard is selected, the programs are not imported into the project.
The field is set to Import by default. Select Discard, if necessary.
Tip: To see the Operation value for a specific program, check the Programs grid of the
program's child program.
Schedule In Shows the task in which the imported programs are scheduled.
The default value for Schedule In is either the selected task or Unscheduled
Programs/Phases based on which method was use to import the content, and from which
organizer the import was initiated.
• If using Paste Special>With Configuration in the Controller Organizer, the
default value is the selected task.
• If using the Paste Special>With Configuration option or the File>Import
Component option in the Logical Organizer, the default value is Unscheduled
Programs/Phases.
Set Operation to Import to modify Scheduled In.
Do not change scheduling of When selected, programs that exist in the project remain scheduled as they are configured
existing programs in the project. The check box is selected by default.
When cleared, upon import, programs are scheduled in the task specified in Schedule In.
To modify this option:
• Operation must be set to Import.
• The controller cannot be in Remote Run mode.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 31


Chapter 1 Import and export logic components

Configuration Description
Parent Specifies how the programs are organized upon import.
• When importing a program into the Logical Organizer, the default is the Parent in
the selected program in the Logical Organizer.
• The default is <none> when a Parent is not specified in the selected program in
the Logical Organizer, or when importing programs into the Controller Organizer.
If a Parent is not specified, the programs remain organized as they are configured in the
project.
Set Operation to Import to modify the Parent option.
Do not change parent of Select this check box and programs that exist in the project remain organized as they are
existing programs configured in the project. The check box is selected by default.
Clear this check box and upon import, programs are organized in the program that is
specified in Parent.
All child programs are imported as organized in the import content regardless if the check
box is selected or cleared.
Set Operation to Import to modify this option.

See also

Program connections on page 32

Program connections When importing a program, it might require configuration of connections to


program parameters or controller scope tags that exist in the project.
Configure connections when selecting the target program on the Import
Configuration dialog box and Operation is set to Overwrite or Create. If
Operation is set to Use Existing or Discard, the Connections grid does not
appear.

When importing multiple programs, any connections between the programs


being importing cannot be configured, and do not appear in the Connections
grid. However, any connections with endpoints outside these programs do
appear and may be configured.

The Logix Designer application imports the connection endpoints, and they
remain what they were in the original project. If the endpoints exist in the
destination project, they bind automatically. If the endpoints do not exist,
they are flagged as errors and the Final Connection name must change to
bind them to the correct connections, or remove the connections.

These diagrams describe how imported connections are established.

32 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

In My Original Project, the parameters in Program1 are connected to


parameters in Program2.

When importing the original Program1 into My New Project, the parameters
in Program1 connect automatically to matching parameters in Program2.
Parameters that do not match are flagged as errors. Change the Final
Connector for those parameters.

If the endpoint names are different in My New Project (for example,


Program3), either open the Connections grid and change the Final
Connection name on the endpoints from Program2 to Program3, or go to the
References grid and change the final name on Program2 to Program3 in one
place, and all the connections change automatically.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 33


Chapter 1 Import and export logic components

To open the Connections grid, select Connections on the Import


Configuration dialog box.

This screen capture shows the Connections grid as it would appear when
importing Program1 into My New Project, as described earlier in this section.
To fix the connection errors, select Disconnect in the Operation field, or
select a different connection in the Final Connection field.

The indicator column at the far left of the Connections grid shows the
condition of the connection. The table describes the connection conditions.

Indicator Connection Condition

* Indicates a row in which content has changed and the change has not been saved.

Indicates a row in which the connection endpoints are invalid due to a syntax error. If selecting OK to
begin the import, an error message opens. Fix or remove the connection before proceeding.

34 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

Indicator Connection Condition

* Indicates a row in which content has changed and the change has not been saved.

Indicates that the connection being imported will contain an error at the completion of the import.
Proceed with the import, and the connection is created, but fix the error before downloading the project
to the controller.
Indicates a row in which to create a connection.

The table describes the Connections grid columns and settings.

Column Description
Parameter The parameter identified in this field is the parameter in the import content that is to be connected to
another parameter on a program that exists in the project.
A New Connection option is available on the last row of the grid if the import content contains only
one program. Create connections that are not part of the import content by connecting a program
parameter in the import content to an endpoint connection on a program that is in the project to have
a new connection that did not exist in the import content nor in the program that exist in the project.
See Create a new connection for more information.
Data Type Shows the data type of the parameter. A parameter can only be connected to a member or bit of a tag
or parameter with the same data type or an error occurs when verifying the program.

Usage Shows the usage type of the parameter as Input, Output, InOut, or Public.
Import Connection Shows the name of the connection endpoint for the parameter as read from the import file. Import
Connection is blank if the connection is only defined in the program that exists in the project.

Differences Indicates if there are differences between the connections in the import content and the connections
in the target project.
Also identifies if a connection exists in the import content, or if it exists in the program that is in the
project. Select the Browse button in the Details column to see more extensive component properties.
Two icons show how the imported content matches the content of the program that exists in the
project:
Indicates a connection that is present in the import content and not in the project.

Indicates a connection that is present in the project and not in the import content.

Operation Identifies whether the connection is made upon import of the program into the project.
Select Connect or Disconnect to change the connection status for the connection.
Connect - Upon import of the program, this connection that is defined in the import content will be
created in the project. This is the default value when a connection between the parameter and the
final connection is valid.
Disconnect - Upon import of the project, the connection that is defined in the import content will not
be created in the project. This is the default value when the connection between the parameter and
the final connection is not valid.
See the example later in this section for more information on the Operation field.
Details Select the Browse button to open the Connection Properties dialog box. On the Connection
Properties dialog box, select Connect or Disconnect to change the connection status for the
connection.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 35


Chapter 1 Import and export logic components

Column Description
Final Connection The parameter or tag in the existing project that the import parameter will be connected to.
Change the value in Final Connection based on the value in Operation. Type the final connection
name or select the down arrow to make a selection from the tag browser. If the parameter is a
MODULE InOut parameter, the module browser appears instead of the tag browser. For more
information about the tag browser and module browser, see the online help topics Using the Tag
Browser and Using the Module Browser.
If entering an invalid final connection, the error indicator displays in the leftmost column. Hover the
cursor over the error indicator to see a description for the cause of the error.
See the example later in this section for more information on the Final Connection field.

Using the Operation and Final Connection fields to establish connections

This is an example on using the Operation and Final Connection fields to


establish connections.

Parameter in Connection in Operation Value Final Connection field What happened in this case
Imported File Imported File
\Prog1.InA \Prog2.OutA Connect \Prog2.OutA This connection exists in both the import content and in the program in the
project, so the connection is the same.
\Prog1.InB \Prog2.OutB Connect \Prog2.OutB The endpoint parameter does not exist in the target project file.
If importing the program offline, the error flag appears. Continue the
import, but resolve the error before downloading the project to the controller.
If importing the program online, the red-x error appears, resolve the
error before continuing the import.
To resolve the error, either:
• Set the Operation Value to Disconnect (see Example Row 3 in this table).
• Select an existing parameter in the Final Connection field to reassign the
connection (see Example Row 4 in this table).
\Prog1.InB \Prog2.OutB Disconnect \Prog2.OutB Example Row 3: Parameter \Prog2.OutB does not exist in the target project, so
set Operation Value to Disconnect.
\Prog1.InA \Prog2.OutA Connect \Prog3.OutB Example Row 4: Parameter \Prog2.OutA does not exist in the target project, so
in Final Connection, select an existing parameter to reassign the connection.

\Prog1.InC none Connect \Prog3.OutD This connection did not exist, so in Final Connection, select an existing
parameter to create the connection. See Create a new connection for more
information on creating connections.

See also

Create a new connection on page 36

Create a new connection When importing one program, create a new connection on the last row of the
Connections grid. The new connection connects a program parameter in the
import content to an endpoint connection in a program that is in the project.
The new connection did not previously exist in the import content nor in the
project. The New Connection row is not available when importing multiple
programs with existing connections between the programs that are importing.

36 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

Type the parameter name for the new connection or select the down arrow to
make a selection from the tag browser. Because only parameters that are in
the import content are valid for the Parameters field, only the parameters that
reside in the import content are listed in the tag browser. For more
information about the tag browser, see Using the Tag Browser in the online
help.

When both the parameter and final connection have been specified, the
connection is made (added) to the connection grid after moving off the New
Connection row or after pressing Enter. If entering an invalid parameter or
final connection, the connection is not created and the error indicator
displays in the leftmost column. Hover the cursor over the error indicator to
see a description for the cause of the error.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 37


Chapter 1 Import and export logic components

Configure component In addition to determining how the component is imported, configure how
references are imported. The references are all other components used by the
references exported component at the time it was exported. For example, a program .l5x
file contains the definition of all controller-scoped tags, user-defined data
types, user-defined string types, and Add-On Instructions referenced by the
program at the time the program was exported. During import configuration,
determine what the references from the imported component connect to after
import. Connect a reference to an existing component in the project and not
import the referenced component from the import file. Or, use the referenced
component in the import file either by creating a new component in the
project from the definition in the import file or by overwriting an existing
component of the same type in the project.

As with imported components, if the Final Name of a referenced component


(such as a tag) matches a component of the same type and scope in the
project, these components collide. If there is no collision, the component is
identified as needing to be created (Operation is Create).

Icons in the Differences column ( ) on the Import Configuration dialog


box show whether components collide with differences, or the component
only exists in the import file or the project.

38 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

Select the icon in the Details column ( ) and a Collision dialog box opens
showing the differences between the import component and the colliding
project component. Use the information in the Collision dialog box to
determine whether to overwrite or use the existing component.

For components that do not collide, click the same icon for more information
on the component.

Tip: A referenced component that collides with an existing component defaults to using the project component (Operation is
Use Existing), even if the definitions of the components are different. To import the referenced component definition from
the import file, Overwrite must be selected.

Connecting a referenced component to a component of the same type, but


with another name in the project, causes any reference to the component in
the imported logic to be updated to the new name. For example, if connecting
a Boolean reference tag A to B[3].ACCUM.4 (where B is an existing tag in
the project that is an array of structures), then all references in the imported
logic that used to say A now say B[3].ACCUM.4. Another way to connect
reference tags to existing tags in the project is to modify their Alias For
field. This is permitted when the reference tag is being created or the
reference tag is overwriting an existing tag (offline only), regardless of
whether it was originally an alias tag. Use the Import Configuration dialog
box to configure the references that must connect during the import process.

Important: It is important to note that even if a component has an Operation of Discard, Use Existing, or Undefined, if the
Final Name differs from the Import Name, then the imported logic references to that component are updated to
reflect the Final Name. For example, if entering an invalid name as the Final Name for a tag reference,
the Operation is set to Discard but the imported logic references to that tag are still updated to the invalid Final
Name.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 39


Chapter 1 Import and export logic components

References configuration The example shows how an imported routine plugs into the components in a
project after configuring it.
example

For example, if importing a routine, the routine itself is the main import
component. References that should be connected during the import could
include program-scope tags, controller-scope tags, user-defined data types,
any routines called by JSR instructions, and any Add-On Instructions in the
routine logic.

In this example, a routine export file contains the definitions of Tag_A,


Tag_B, AOI_1, and UDT_1. The routine also contains a reference to
Routine_A, but excludes the logic in Routine_A.

During import configuration, connect each:

• Reference tag in the import routine to a program or controller-scoped


tag in the project.
• Reference routine in the import routine to a routine in the project.
• User-defined data type defining a reference tag in the import routine to
a user-defined data type in the project.
• Add-On Instruction in the import routine to an Add-On Instruction in
the project.

40 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

These tags, user-defined data types, and Add-On Instructions might exist in
the project, or they can be created when importing the routine.

• Tag_A is set to Create, so the imported logic referencing Tag_A


references the newly created Tag_A in the project.

Tag_B has its Final Name changed to Tag_D and is set to Use Existing, so it
is not created, and imported logic referencing Tag_B instead references
existing Tag_D.

• Routine_A has its Final Name changed to Routine_B, so imported


JSRs to Routine_A uses the existing Routine_B.
• AOI_1 is set to Overwrite an existing Add-On Instruction called
AOI_1, so not only do imported logic and tags use AOI_1, but also any
existing references to AOI_1 in the project now uses the new definition
of AOI_1 from the imported routine.
• UDT_1 is set to Overwrite an existing user-defined data type called
UDT_2, so imported logic and tags use UDT_2 and the existing
UDT_2 is overwritten (except for the name) with the definition from
UDT_1. Logic and tags from the project now use the new definition of
UDT_2.

Undefined references In the Logix Designer editor, it is possible to create logic that references tag,
user-defined data type, or Add-On Instruction components that do not yet
exist. These are considered undefined references. If exporting that logic,
there is no component definition to export for that undefined reference. On
import, these tags, user-defined data types, or Add-On Instructions appear
with an Operation of Undefined during import configuration unless the
component exists in the project (in which case the Operation is Use
Existing). Similarly, when logic references any type of component other than
a tag, user-defined data type, user-defined string type, or Add-On Instruction
(for example, a routine that is referenced by a JSR instruction), the definition
for these referenced components are excluded from the import file and they
also appear with an Operation of Undefined if the component does not exist
in the project.

During import configuration, these undefined references can be configured as


well. Since there is no definition for these components in the .l5x file, a
project component cannot be overwritten or a component created during the
import process. Use an existing component for that reference. Configure
which component in the project to connect the reference to, or leave the
reference undefined. An undefined reference that collides with an existing
component defaults to using the project component.

Attention flags Attention (red) flags provide alert to import situations that may be
unintended or may lead to a project that does not verify successfully after
import. What they describe may or may not prevent the import from
proceeding. If online, and the project does not verify successfully when
accepting or finalizing edits, the import fails. Not all attention flags cause a
project to fail verification. The red flag indicates the potential problem to
Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 41
Chapter 1 Import and export logic components

make a decision about what to do. Ignore the attention message or try to
change the Final Name or Operation of the component to resolve the issue.

Tip: Hover the cursor over the attention flag to open a tooltip that explains the issue.

Errors and warnings on import When an import fails or is canceled, all changes caused by the import are
discarded, leaving the project in the same state it was in before the import,
even if the project is online with the controller. If the import fails, the
Import Configuration dialog box opens with Errors selected. To attempt to
import again, inspect the errors and warnings, reconfigure the import, and
click OK.

The Logix Designer application provides the option to set the display
Project documentation language for project documentation, such as tag descriptions and rung
comments, using any of the supported localized languages. Store project
documentation for multiple languages in one project file rather than in
language-specific project files. Define the localized languages that the
project supports and set the current, default, and optional custom localized
language. The software uses the default language if the current language's
content is blank for a particular component of the project. Use a custom
language to tailor documentation to a specific type of project file user. When
configuring project documentation in the Logix Designer application for a
project, dynamically switch between languages in that project within the
software.

These project documentation items support multiple languages:

• Component descriptions in tags, routines, programs, equipment phases,


User-Defined data types, and Add-On Instructions
• Engineering units and state identifiers added to tags, User-Defined data
types, or Add-On Instructions
• Trends
• Controllers
• Alarm Messages (in configuration of ALARM_ANALOG and
ALARM_DIGITAL tags)
• Tasks
• Property descriptions for modules in the Controller Organizer
• Rung comments, Sequential Function Chart fields, and Function Block
Diagram fields

The export and import features of the Logix Designer application support
project documentation. Transfer project components between projects that
have different project documentation settings.

42 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

If a component was exported to an .l5x file from a project with project


documentation turned off and is then imported into a project with project
documentation turned on, all project documentation brought in by the import
is associated with the project’s current language.

If a component was exported to an .l5x file from a project with project


documentation turned on, all language switched comments are exported with
the component. When importing an .l5x file that includes language switched
comments, the Import Configuration dialog box includes a Current
Import Documentation Language selection.

If the project has project documentation turned on, all language-switched


comments from the .l5x file are imported into the project. This may result in
additional languages being available in the project after import. Selecting a
language in Current Import Documentation Language allows editing of
that language’s comments from the import file during the import
configuration process.

If the project does not have project documentation turned on, import only one
set of localized comments from the import file. In this case, selecting a
language in Documentation to Import determines which language’s
comments are imported with components from the import file. Edit the
language’s comments during the import configuration process, but only the
final language selected when import proceeds is imported with components.

Important: Only comments associated with imported components are brought in from the import file.
If an existing component is used, import file comments for that component are not
imported.

Important: Multiple localized alarm messages can be stored (in configuration of ALARM_ANALOG or
ALARM_DIGITAL tags) even if the project does not have project documentation turned on.
Therefore, all alarm messages are imported, regardless of the Documentation Language to
Import selection on the Import Configuration dialog box.

Important: The Documentation Language to Import selection does not affect the setting of the
language defined in the project after import.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 43


Chapter 1 Import and export logic components

Find and replace Use the Find controls in the Import Configuration dialog box control bar to
search for text within the dialog box. Use the Find/Replace dialog box to
configure whether Find searches through the Import Name, Final Name,
Description, Alias For, and the Data Type fields. As the search progresses,
the Import Configuration dialog box automatically switches to different
panes within the dialog as needed.

Replace text fields during the search. Replacing text fields facilitates
development of a component template to import repeatedly, replacing
template text during each import. When designing a program template, keep
in mind that during a program import, the program tag names and
descriptions cannot be edited or replaced. However, during import, edit the
names and descriptions of controller-scoped tags referenced from the
program. Similarly, when importing an equipment phase, edit the names and
descriptions of tags in the equipment phase, and when importing an Add-On
Instruction, editing the names and descriptions of the parameters and local
tags is not allowed.

To find and replace:

1. On the Import Configuration dialog box, select Find/Replace.

2. In the Find What box, enter text that to search. Enter a search string or
select text from a previous search.

3. To replace text that is found, in the Replace With box, enter the
replacement text.

To use wildcards in the search string and in the replacement text,


select Use Wildcards. Use asterisks (*) as wildcard characters. The
table provides examples of Find-Replace operations using wildcards.
Find What Replace With Text Found Replacement Result
tk1_*_001 PRE_*_010 tk1_me_001 PRE_me_010
tk3_* tk4_* tk3_unit tk4_unit
*001 *002 mi_2001 mi_2002
*tank* *TNK* M1_tank_003 M1_TNK_003
* PRE_* some_name PRE_some_name

4. To limit search and replace to the currently selected pane,


select Search current view only. Change the selected pane without
closing the Find/Replace dialog box.

44 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export logic components Chapter 1

5. Use the Find Within check boxes to configure which fields to search.

6. Select Find to search for the next matching item.

7. Select Replace to replace the text in a text field. Select Replace All to
replace all instances of the search text specified in Find What with the
text in Replace With field.

See also

Properties for imported components on page 25

Compatibility The import/export feature supports backward compatibility for import


operations and forward compatibility for export operations.

Backward compatibility means that the Logix Designer application can


import .l5k or .l5x files that were generated by a previous version of the
application. In some cases, an older .l5k file might not correctly import into a
later version of the application.

The import/export feature supports forward compatibility for export


operations. It does not support backward compatibility for export operations.
This means that earlier versions of the Logix Designer application cannot
read .l5k or .l5x files that were created with later versions of the application.
In some cases, an .l5k or .l5x file created with a later version of the Logix
Designer application may import with warnings into an earlier version of the
application. In these cases, attributes on components may be set to default
values during import.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 45


Chapter 1 Import and export logic components

Each version of the Logix Designer application exports .l5k files with a
specific import/export Logix Designer application version number. The
Logix Designer application imports any .l5k file with the same major
revision number and the same or lower minor revision number. The major
Logix Designer application version number increments when file properties
prevent the application from supporting backward compatibility for import
operations. The minor version number increments whenever there is a change
in the file (a new module, an attribute is added, the set of options for an
attribute is changed) that does not affect backward compatibility for Logix
Designer application import operations.

Important: Use caution when copying and pasting components between different versions of Logix Designer
application. Logix Designer application supports pasting to only the same or later version. Pasting
to an earlier version of Logix Designer application is not supported. When pasting to an earlier
version, the paste action might succeed but the results might not be as intended.

46 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Chapter 2

Additional considerations for rungs

This chapter explains import and export of rungs.


Introduction
Export considerations One rung or a contiguous set of selected rungs may be exported to an .l5x
file.

The export file may also include any program-scoped tags, controller-scoped
tags, Add-On Instructions, user-defined data types, and user-defined string
types that are referenced by the rungs. If they exist in the project, the
definitions for the referenced tags, Add-On Instructions, and user-defined
data types are exported to the .l5x file. In the case of rungs exported from an
Add-On Instruction routine, if they exist at the time of export, any
parameters and local tags referenced are exported.

Import considerations When importing rungs, configure how the referenced components are
imported during import configuration. By default, referenced components
that collide with project components are not imported.

Considerations when importing rungs.

Topic Consideration
Pending Edits exist If rungs are imported into a program or equipment phase that contains pending edits, all
pending edits in the program are accepted if Accept Program Edits is selected during
import of the rungs. Similarly, all pending edits in the program are finalized if Finalize All
Edits In Program is selected during import of the rungs.

Accepted Edits exist Rungs cannot be imported into a program or equipment phase that contains routines with
Accepted Edits or Test Edits. Existing edits must first either be assembled or canceled.
First scan When importing rungs into an existing program, the S:FS bit is not set during the
program’s next scan. This applies when importing rungs into an existing equipment phase
as well.
Collision handling If selecting Overwrite Selected Rungs in the Import Rungs dialog box, the imported
rungs overwrite the rungs selected in the project.
If Overwrite Selected Rungs is cleared, the imported rungs are inserted before the
selected rungs in the project if the ladder editor is in Insert mode, they are inserted after
the selected rungs if the ladder editor is in Append mode.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 47


Chapter 2 Additional considerations for rungs

Topic Consideration
Tag scope When exporting rungs from a program or equipment phase and import them into an
Add-On Instruction routine, any referenced controller-scoped or program-scoped tags are
converted on import. The tag is converted to a local tag unless local scoped is not allowed
(for example, a Motion Group tag cannot be a local tag), in which case the tag is converted
to an InOut parameter.
When exporting rungs from an Add-On Instruction routine and import them into a routine
in a program or equipment phase, the referenced parameters and local tags are converted
on import. The parameter or local tag are converted to a program-scoped or phase-scoped
tag unless it is not allowed (for example, a Motion Group tag cannot be a program-scoped
tag), in which case it is converted to a controller-scoped tag.

For considerations for referenced user-defined types, Add-On Instructions,


and tags that may be imported with the rungs, see import and export of
user-defined types, Add-On Instructions and tags.

See also

Import and export user-defined types on page 53

Import and export Add-On Instructions on page 55

Import and export tags on page 67

48 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Chapter 3

Additional considerations for routines

This chapter explains the import and export of routines.


Introduction
Export considerations A routine can be exported to an .l5x file. Routines of all language types,
Function Block Diagram, Sequential Function Chart, Ladder Diagram and
Structured Text, may be exported. However, routines may not be exported
from an Add-On Instruction container and SoftLogix external routines may
not be exported.

The export file may also include any program-scoped tags, controller-scoped
tags, Add-On Instructions, user-defined data types, and user-defined string
types that are referenced by the routine. If they exist in the project, the
definitions for the referenced tags, Add-On Instructions, and user-defined
data types are exported to the .l5x file.

Import considerations When importing a routine, configure how the referenced components are
imported during import configuration. By default, referenced components
that collide with project components are not imported.

Considerations when importing a routine.

Topic Consideration
Pending Edits exist If a routine is imported into a program or equipment phase that contains other routines
with pending edits, all pending edits in the program are accepted if Accept Program
Edits is selected during import of the routine. Similarly, all pending edits in the
program are finalized if Finalize All Edits In Program is selected during import of the
routine.
Accepted Edits exist A routine may not be imported into a program or equipment phase that contains
routines with accepted edits or test edits. Existing edits must first either be assembled
or canceled.
Routine type An existing routine may not be overwritten by a routine that is another routine type.
First scan When importing a routine into an existing program, the S:FS bit is not set during the
program’s next scan. This applies when importing a routine into an existing equipment
phase as well.
SFC routine execution SFC execution settings are configured on a controller project, not per SFC routine. If
configuration exporting an SFC routine and importing it into another project with different SFC
execution settings, the functionality of the routine could change. For example, a
change in the Last Scan of Active Steps setting could leave physical outputs in an
undesired state.
Equipment Phase state routines When state routines are created while online with the controller and logic edits are
accepted but not tested, the routine will behave as if it was not implemented.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 49


Chapter 3 Additional considerations for routines

For considerations for referenced user-defined types, Add-On Instructions,


and tags that may be imported with the rungs see import and export of
user-defined types, Add-On Instructions, and tags.

See also

Import and Export user-defined types on page 53

Import and export Add-On Instructions on page 55

Import and export Tags on page 67

50 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Chapter 4

Additional considerations for programs and


equipment phases

Introduction This chapter explains import and export of programs. All topics apply to
equipment phases as well; any exceptions are noted.

A program can be exported to an .l5x file. The exported program includes all
Export considerations of its program tags and routines, which are imported with the program
automatically.

The export file may also include any controller-scoped tags, Add-On
Instructions, user-defined data types, and user-defined string types referenced
by the program. The definitions for the referenced tags, Add-On Instructions,
and user-defined data types are exported to the .l5x file if they exist in the
project.

As with other export types, I/O module data type definitions are not
exported.
I/O module data types are created within a project when the associated I/O
module is created in the project. On import, program-scoped tags may not be
modified. As a result, if a program-scoped tag aliases an I/O module type tag,
the I/O module must first exist in the project in order to import the program.
To export the program so that it can be imported into a project with another
module type, first alias the program-scoped tag to a controller-scoped tag of a
non-I/O module type, and then alias the controller-scoped tag to the I/O
module. These program-scoped tags can then be created during the import of
the program if necessary.

Import considerations When importing a program, the program-scoped tags and routines are
imported as part of the program. The Operation, Final Name, Description,
and any other settings of the program-scoped tags and routines cannot be
modified; instead, the Operations are based on the Operation selected for the
program.

Programs cannot overwrite equipment phases, and vice-versa. Programs and


equipment phases must have unique names.

Configure how the referenced components are imported during import


configuration. By default, referenced components that collide with project
components are not imported.

Considerations when importing a program.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 51


Chapter 4 Additional considerations for programs and equipment phases

Topic Consideration
Accepted or Test Edits exist A program with Accepted Edits or Test Edits may not be overwritten.
Deletes of program-scoped tags and routines When importing a program to replace an existing program, any tags or routines in the existing program that are not in the new
during program overwrite program are deleted during import. However, if online and Import Logic Edits as Pending or Accept Program Edits is selected in
the Online Options dialog box, then these tags and routines cannot be deleted because they are referenced by existing logic
until edits are finalized. In this situation, although they were identified during import configuration with an Operation of Delete,
these tags and routines are not deleted as part of the import. Delete them in the Logix Designer editor after finalizing edits.

Safety program scheduled location A Safety program cannot be scheduled in the Controller Fault Handler or Power-Up Handler folders.
Configuration of Equipment Phase state routines In the configuration for an equipment phase state routine, when the Complete State Immediately if not Implemented
option is selected in version 17.00.00 and later of the application, an implemented, but empty (no logic), phase state routine
behaves the same as an unimplemented phase state routine. The state immediately completes and execution of the phase
continues. The phase then enters the next state in the state machine.
00In version 16.00.00 or later of the application, if an equipment phase enters a state for which a state routine exists, but
contains no logic, execution of the phase stops regardless of whether the Complete State Immediately if not Implemented
option is selected. The routine does complete, but there is no logic to run.
If importing a new state routine and, in the Online Options dialog box, select:
• Import Logic Edits as Pending, an empty routine is created in the controller and the pending edits only exist in the offline
project.
• Accepts Program Edits, an empty routine is created in the controller and the logic is placed in a test edits container in the
routine. If not actively testing edits, the routine is empty when running.
• Finalize All Edits in Program, the routine is created with the new logic and is not empty.
In the first two cases, if the Complete State Immediately if not Implemented option is selected, the empty routine
completes immediately and allows phase execution to continue.
First scan If a new program or equipment phase is created in a controller in Remote Run mode, logic in that program or equipment phase
receives a value of 1 for the S:FS system flag (First Scan flag) until the main routine has run once.
Any other logic imports (that is overwriting an existing program or equipment phase, or any routine or rung imports) does not
result in a value of 1 for S:FS system flag.
Pre-scan Logic imported while online with the controller in Remote Run mode is not pre-scanned before it begins to run.

Program scheduled location while online An imported program that is configured to overwrite an existing program cannot be scheduled into a location that differs from
the existing program while online with the controller in Remote Run mode; the existing scheduled location is used.
Renamed tags When overwriting an existing program and the imported program is modified such that a program-scoped tag has been
renamed, during import, the existing tag is deleted and a tag with the new name is created. All logic references are updated to
reference the new tag. Therefore, the online tag values are not preserved and the tag values from the imported tag are
downloaded to the controller. To preserve the data values of the renamed tag and minimize the logic changes, rename the
program tag in the online project to the new name before importing the modified program.
Importing multiple programs Controller Fault Handler and Power-Up Handler Disabled: When importing multiple target programs, the Controller Fault
Handler and Power-Up Handler are unavailable in the Schedule In list.

For considerations for referenced user-defined types, Add-On Instructions,


program tags, and referenced tags that may be imported with a program see,
Importing and exporting user-defined types, Add-On Instructions, and tags.

See also

Import and export user-defined types on page 53

Import and export Add-On Instructions on page 55

Import and export tags on page 67

52 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Chapter 5

Additional considerations for user-defined types

This chapter explains import and export of user-defined data types and
Introduction user-defined string types.

A user-defined type (either user-defined data type or user-defined string


Export considerations type) can be exported to an .l5x file.

The export file may also include any Add-On Instructions, user-defined data
types, and user-defined string types referenced by the exported user-defined
type. The definitions for the referenced Add-On Instructions and data types
are exported to the .l5x file if they exist in the project and if Include all
referenced Add-On Instructions and User-Defined Types is selected
during export.

Also export user-defined data type references when a program, routine, set of
rungs, or Add-On Instruction is exported.

Import considerations When importing a user-defined type, configure how the referenced
components are imported during import configuration. By default,
referenced components that collide with project components are not
imported.

User-defined types cannot overwrite Add-On Instructions. User-defined


types and Add-On Instructions must have unique names.

Considerations when importing a user-defined type.

Topic Consideration
Tag data Imported tags that reference a user-defined data type in the import file may be
affected if the user-defined data type is not imported as well. In this case, the imported
tag’s data may be converted if the existing data structure is different and tag data may
be lost.
If an existing user-defined data type is overwritten, project tag data may be converted
if the data structure is different and tag data may be lost.
Data type modification while A user-defined data type that is referenced in the project may not be overwritten. If the
online existing user-defined data type is not referenced, it may be overwritten while online.
Final Name change If the Final Name of a user-defined type reference is modified during import
configuration, all logic, tags, Add-On Instructions, and other user-defined types in the
import that reference the user-defined type are updated to reference the new name. As
a result, the edit date of any Add-On Instructions that references the user-defined type
is updated.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 53


Chapter 5 Additional considerations for user-defined types

See Import and export Add-On Instructions for considerations for referenced
Add-On Instructions that may be imported with the user-defined type.

See also

Import and Export Add-On Instructions on page 55

54 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Chapter 6

Import and export Add-On Instructions

This chapter explains import and export of Add-On Instructions.


Introduction
Create export files When exporting an Add-On Instruction, the exported Add-On Instruction
includes all of its parameters, local tags, and routines. These are imported
with the Add-On Instruction automatically.

Optionally, include any nested Add-On Instructions or user-defined data


types that are referenced by the exported Add-On Instruction. Referenced
Add-On Instructions and data types are exported to the .l5x file, if
the Include all referenced Add-On Instructions and User-Defined
Types check box is selected during the export.

Add-On Instruction definition references may also be exported when a


program, routine, set of rungs, or user-defined data type is exported.

Tip: If an Add-On Instruction uses Message (MSG) instruction and InOut parameters of
type MESSAGE, consider exporting a rung containing the Add-On Instruction to
include the MESSAGE tags. This captures the message configuration data, such as
type and path.

In deciding how to manage Add-On Instruction definitions in export files,


consider the goals in storing the definitions.

If Then
Want to store many Add-On Instructions that share a set of common Add-On See Export to separate files.
Instructions or user-defined data types in a common location
Want to distribute an Add-On Instruction as one file See Export to one file.
Want to manage each Add-On Instruction as a standalone instruction
Want to preserve the instruction signature on Add-On Instruction

Tip: Add-On Instructions with instruction signatures are encrypted upon export to prevent
modifications to the export file.

See also

Export to separate files on page 56

Export to one file on page 57

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 55


Chapter 6 Import and export Add-On Instructions

Export to separate files To store many Add-On Instructions that share a set of common Add-On
Instructions or user-defined data types in a common location, export each
Add-On Instruction and user-defined data types to separate files without
including references.

To export to separate files:

1. Select the Add-On Instruction in the Controller Organizer, and


choose Export Add-On Instruction.

2. Select the common location to store the .l5x file.

3. Type a name for the file.

4. Clear the Include all referenced Add-On Instructions and


User-Defined Types check box.

5. Select Export.

6. Repeat the previous steps to individually export the other shared


Add-On Instructions and user-defined data types.

By using export in this way, manage the shared Add-On Instruction and
user-defined data types independently of the Add-On Instructions that
reference them. Using this approach, can update the shared component
without regenerating all the export files for the instructions that reference it.
That is, it is stored in only one file instead of in every file whose instruction
references it. This approach makes it easier to maintain the instructions to
update only one export file.

56 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export Add-On Instructions Chapter 6

To use Add-On Instructions that were exported in a separate file without


references, first import any user-defined data types of Add-On Instructions
that the exported instruction references before the import of the referencing
instruction can be successful. (This assumes that the referenced user-defined
data types of Add-On Instructions do not exist in the project.) To do this,
work from the bottom up. Import the lowest-level user-defined data types
and any user-defined data types that reference them. Then, import the
lowest-level Add-On Instructions, followed by any Add-On Instructions that
reference those low-level Add-On Instructions. Once all items referenced by
the Add-On Instruction are in place, the import of the Add-On Instruction
succeeds.

See also

Export to one file on page 57

Export to one file To manage each Add-On Instruction as a standalone, export the instruction
and any referenced Add-On Instructions or user-defined data types into one
export file. By including any referenced Add-On Instructions or user-defined
data types, also makes it easier to preserve the instruction signature of an
Add-On Instruction.

To export to one file:

1. Select the Add-On Instruction in the Controller Organizer and


choose Export Add-On Instruction.

2. Choose the location to store the .l5x file.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 57


Chapter 6 Import and export Add-On Instructions

3. Type a name for the file.

4. Select the Include all referenced Add-On Instructions and


User-Defined Types check box.

5. Click Export.

This procedure exports the selected Add-On Instruction and all referenced
instructions into the same export file. This file can be used to distribute an
Add-On Instruction. When the exported Add-On Instruction is imported into
the project, the referenced instructions are also imported in one step.

See also

Export to separate files on page 56

Import an Add-On Import an Add-On Instruction that was exported from another Logix
Designer project. When importing an Add-On Instruction, the parameters,
Instruction local tags, and routines are imported as part of the Add-On Instruction. Once
the project has the Add-On Instruction, use it in programs.

Import considerations This section covers import guidelines for Add-On Instructions or Add-On
Instruction references.

Editing an .l5k or .l5x File


The EditedDate attribute of an Add-On Instruction must be updated if the Add-On Instruction is modified by
editing an .l5k or .l5x file. If the Logix Designer application detects edits to the Add-On Instruction, but the
Edited Date attribute is the same, the Add-On Instruction is not imported.

When importing Add-On Instructions directly or as references, consider


these guidelines.

Topic Consideration
Tag Data Imported tags that reference an Add-On Instruction in the import file may be affected if the
Add-On Instruction is not imported as well. In this case, the imported tag’s data may be
converted if the existing Add-On Instruction’s data structure is different. Tag data may be
lost.
If an existing Add-On Instruction is overwritten, project tag data may be converted if the
Add-On Instruction’s data structure is different. Tag data may be lost.
See Import Configuration for more information.
Logic Imported logic that references the Add-On Instruction in the import file may be affected if
the Add-On Instruction is not imported. If an existing Add-On Instruction is used for the
imported logic reference and the parameter list of the Add-On Instruction in the project is
different, the project may not verify or it may verify but not work as expected.
If an existing Add-On Instruction is overwritten, logic in the project that references the
Add-On Instruction may be affected. The project may not verify or may verify but not work as
expected.
See Import Configuration for more information.
Add-On Instructions While An Add-On Instruction cannot be overwritten during import while online with the controller,
Online though a new Add-On Instruction may be created while online.

58 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export Add-On Instructions Chapter 6

Topic Consideration
Final Name Change If the Final Name of an Add-On Instruction is modified during import configuration, the edit
date of the imported Add-On Instruction is updated. In addition, all logic, tags, user-defined
data types, and other Add-On Instructions in the import file that reference the Add-On
Instruction are updated to reference the new name. As a result, the edit date of any Add-On
Instruction that references the Add-On Instruction is updated.
Add-On Instructions that are sealed with an instruction signature cannot be renamed during
import.
User-Defined data types Add-On Instructions cannot overwrite user-defined data types. Add-On Instructions and
user-defined data types require unique names.
Instruction Signature When importing an Add-On Instruction with an instruction signature into a project where
referenced Add-On Instructions or user-defined data types are not available, consider
removing the signature.
Overwrite an Add-On Instruction that has an instruction signature by importing another
Add-On Instruction with the same name into an existing routine. Add-On Instructions that
are sealed with an instruction signature cannot be renamed during import.
Safety Add-On Instructions Importing a safety Add-On Instruction into a standard project is not allowed.
Importing a safety Add-On Instruction into a safety project that has been safety-locked or
one that has a safety task signature is not allowed.
Import a safety Add-On Instruction while online.
Class, instruction signature, signature history, and safety instruction signature, if it exists,
remain intact when an Add-On Instruction with an instruction signature is imported.

Important: Importing an Add-On Instruction created in version 18.00.00 or later of the application, into an earlier
project that does not support Add-On Instruction signatures causes the Add-On Instruction to lose
attribute data and the instruction may no longer verify.

See also

Import Configuration on page 59

Import configuration When selecting a file to import, use the Import Configuration dialog box to
choose how the Add-On Instruction and referenced components are
imported.

If no issues exist, select OK to complete the import.

If the Add-On Instruction collides with an Add-On Instruction in the project:

• Rename it by typing a new, unique name in the Final Name field.


• Choose Overwrite from the Operation menu.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 59


Chapter 6 Import and export Add-On Instructions

• Choose Use Existing from the Operation menu.

Tip: Rename an Add-On Instruction only if it has not been sealed with an instruction signature.
To rename an Add-On Instruction that has been source-protected, use the source key.

Use the Collision Details button to view the Property Compare tab, which
shows the differences between the two instructions, and the Project
References tab, which shows where the existing Add-On Instruction is used
and how the arguments are updated to locations where the existing Add-On
Instruction is called.

To update an instruction to a later revision, import it from an .l5x file or copy


Update an Add-On it from an existing project. Update an Add-On Instruction only when offline.
Instruction to a later
To update an Add-On Instruction to a later revision using import:
revision using import
1. Select the Add-On Instruction folder and choose Import Add-On
Instruction.

2. Select the file with the Add-On Instruction and select Open.

3. From the Operation list on the Import Configuration dialog box,


choose Overwrite.

60 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export Add-On Instructions Chapter 6

4. Select Collision Details to see any differences in the Add-On


Instruction definition, and to see any changes that will be made to the
logic where the Add-On Instruction is called.

Differences listed in the Property Compare tab are shown in bold in


the Name column.

Tip: The Compare dialog box compares metadata for each instruction definition, such as
description, revision, or edited date. For effective revision control, enter a detailed revision
note in the Add-On Instructions Definition dialog box. To open the dialog box, right-click
an Add-On Instruction and select Open Definition.

The Project References tab shows a list of locations where the


Add-On Instruction is called, and for each location, shows how the
arguments in the Add-On Instruction will be updated to adapt to the
new parameters.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 61


Chapter 6 Import and export Add-On Instructions

Important: Beginning with version 18.00.00, when changing the parameters of an


Add-On Instruction (add, delete, or move), each location where the
Add-On Instruction is called is modified so that the existing arguments
continue to match their previous parameters. Importing and Overwriting
an existing Add-On Instruction may cause changes to the existing logic
that uses the Add-On Instruction.

Important: If the logic calling the Add-On Instruction is within a source-protected routine, and the key is not
available, the arguments are not shown or updated. Instead, the Location will be identified as
Source Not Editable.

For more information on updates to arguments, see Logix 5000 Controllers


Add-On Instructions.

See also

Logix 5000 Controllers Add-On Instructions

62 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Chapter 7

Import and export tag-based alarms and alarm


definitions

Introduction This chapter explains export and import of tag-based alarms and alarm
definitions.

Tag-based alarms and alarm definitions can be exported to an XML file for
Create export files offline editing, and they are exported to the .l5x file as part of a program,
routine, user-defined data type, or Add-On Instruction export.

To create export files (tag-based alarms):

1. On the main menu, select Tools > Export > Alarms or Tools >
Export > Alarm Definitions to open the Export Alarms and Alarm
Definitions dialog box.

2. Select a destination for the file and adjust the file name if necessary.

3. Click Save.

Tip: To open an XML file in an Excel spreadsheet, open it as an XML table. After editing,
select XML data as the file type in the Save as dialog box.

Keep these considerations in mind when editing alarms and alarm definitions
in an XML file or in a spreadsheet:

• One message is exported for each alarm or alarm definition.

Delete alarms and alarm definitions from the XML file, but those items are
not removed from the Logix Designer project when importing the modified
XML file.

Import alarms and alarm After exporting alarms or alarm definitions to an XML file, import the file
into a project.
definitions
Keep these consideration in mind when importing alarms and alarm
definitions from an XML file:

• If alarms and alarm definitions are deleted from the XML file, those
items are not removed from the Logix Designer project when
importing the modified XML file.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 63


Chapter 7 Import and export tag-based alarms and alarm definitions

To import tag-based alarms and alarm definitions:

1. On the main menu, select Tools > Import > Alarms or Tools >
Import > Alarm Definitions to open the Import Alarms and Alarm
Definitions dialog box.

2. In the Import dialog box, select the file and select Open to open
the Collision Handling dialog box.

3. On the Collision Handling dialog box, select the method the Logix
Designer application should use in case of differences or duplication
between the imported alarms and alarms that exist in the project.

The table describes the handling options.


Option Description
Create New Alarms & New alarms in the XML file are created in the project, and existing alarms in
Overwrite Existing Alarms the project are overwritten with the same alarms in the XML file.
This is the default option.
Create New Alarms & Preserve New alarms in the XML file are created in the project, but existing alarms in
Existing Alarms the project are not overwritten with the same alarms in the XML file.
Skip New Alarms & Overwrite New alarms in the XML file are not created in the project, and existing alarms
Existing Alarms in the project are overwritten with the same alarms in the XML file.

Import considerations Keep these considerations in mind when importing an XML file containing
alarms or alarm definitions:

• The import file must be an XML file. If the import file is not an XML
file, try opening the file in Excel and, in the Open XML dialog box,
select As an XML table. Then save the file as an XML file by
selecting XML data as the file type in the Save as dialog box.
• The XML file must be in the same alarm format as the exported file. If
it was corrupted somehow or incorrectly edited after it was exported,
try exporting the alarm list again and import the resulting XML file.
• The XML file must contain only the attributes that are recognized as
attributes of an alarm or an alarm definition, such as AckRequired,
Latched, and Severity. If an XML file is edited incorrectly after export,
an attribute might be altered to make it unrecognizable, or an unknown
attribute might be added. Remove or correct any unrecognized
attributes in the XML file.
• The XML file must contain only the elements that are recognized as
elements of an alarm or an alarm definition. If an XML file is edited
incorrectly after export, an attribute might be altered to make it
unrecognizable, or an unknown element might be added. In the alarm
import XML file, elements appear in angle brackets, such as
<Message>, <AlarmClass>, and <HMIGroup>. Remove or correct any
unrecognized elements in the XML file.

64 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Import and export tag-based alarms and alarm definitions Chapter 7

Keep the following consideration in mind when copying and pasting an


Add-On Instruction in a project:

• When an Add-On Instruction (AOI) tag is copied and pasted in a


project, alarm definitions associated with the tag are not included.
After you copy and paste an AOI tag, open the Alarm Definition list
and copy and paste the alarm definition for the tag. Follow these steps:

1. In the Controller Organizer, right-click Alarms and select Edit


Alarm Definitions.

2. Right-click the alarm definition for the AOI tag and select Copy.

3. Right-click again and select Paste. The alarm definition is pasted


into the list with _000 added to the alarm name.

4. Double-click the copy of the alarm definition to open the Alarm


Definition Properties dialog box.

5. In the Input box, change the input tag to the AOI tag that you
copied and pasted.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 65


Chapter 8

Additional considerations for tags

This chapter explains import and export of referenced tags.


Introduction
Tip: Starting with version 24.00.00 of Logix Designer application, use program
parameters to share data between programs in much the same way
controller-scoped tags are used. Program parameters are imported and
exported in the same way as tags in most instances. For more information
on program parameters, refer to 1756-PM021, Logix 5000 Controllers
Program Parameters Programming Manual.

Export considerations Tags are not exported to an .l5x file themselves, but they are exported to the
.l5x file as part of a program, equipment phase, or Add-On Instruction export
(program-scoped tags with a program export, equipment phase-scoped tags
with an equipment phase export, and parameters and local tags with an
Add-On Instruction export).

Tags may also be exported to an .l5x file as references from another


component being exported (controller-scoped tag references with a program
or equipment phase export or program-scoped and controller-scoped tag
references with a rung or routine export). The definitions for the referenced
tags are exported to the .l5x file by default if they exist in the project.

When exporting logic, especially if it is intended for general use, be aware


that logic that references a bit member of a tag or member of a user-defined
data type tag cannot be replaced during import to reference another bit or
user-defined data type member. To connect the logic reference to another bit
or member of a tag, consider editing the logic before export so the reference
is to a full tag name (and alias if need be) so that the reference can be
connected to the desired tag on import.

When importing a program, the program-scoped tags are imported with the
Import considerations program automatically (the same as they are for equipment phase). When
importing an Add-On Instruction, the parameters and local tags are imported
with the Add-On Instruction automatically.

During program or equipment phase imports, referenced controller-scoped


tags may also be imported. For routine and rung imports, referenced tags
may be imported as well. Configure how referenced tags are imported during
import configuration. By default, referenced tags that collide with project
components are not imported.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 67


Chapter 8 Additional considerations for tags

Keep the following considerations in mind when importing tags.

Topic Consideration
Tag data Imported tags that reference an Add-On Instruction or user-defined data type in the import
file may be affected if the Add-On Instruction or user-defined data type is not imported as
well. In this case, the imported tag’s data may be converted if the existing data structure is
different and tag data may be lost.
If an existing Add-On Instruction or user-defined data type is overwritten, project tag data
may be converted if the data structure is different and tag data may be lost.
If the data is not convertible, it is overwritten with the default values for the type. When
array dimensions are changed, existing array members retain their values and descriptions
and new members have the default values and description (usually 0 and no description).
Consumed tags Consumed tags cannot be imported from an .l5x file. They are converted to base tags and a
warning appears in the Errors or Warning pane during initial parsing of the .l5x file.
Tag values while online When importing into a controller while online, if existing tags are being overwritten by
imported tags, the tag values are not written to the controller. Tag values are written only to
the offline project. The tag values in the controller maintain their current values but other
tag attributes are written to the controller.
Values for tags that are created during import are written to the controller. However,
existing tag values are never overwritten in the online controller.
Prevent tag values from being overwritten in the offline project by selecting Preserve
existing tag values in offline project on the Import Configuration dialog box.
Tag values while offline Prevent tag values from being overwritten in the offline project by selecting Preserve
existing tag values in offline project on the Import Configuration dialog box.

Tag attributes while online Tag attributes (for example, External Access, Constant, and Style) are written to the online
project and the offline project.
If existing tags are to be overwritten with new attributes that are incompatible with existing
user logic, the import is not allowed.
Tag scope An import tag maintains the scope of the tag as it was when exported if the tag initially
collides with another scoped tag in the project. In that case, an attention (red) flag appears
on the tag indicating the scope collision. However, If changing the Final Name of a tag so
that it subsequently collides with a tag of another scope in the project, the imported tag is
changed to the scope of the existing tag.
Resolve the attention flag that appears on initial collision due to a scope issue by changing
the Final Name to avoid the collision with that tag or, if the import component is routine or
rungs, change the scope of the import tag by selecting the tag row and selecting Toggle
Tag Scope.

68 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Chapter 9

Additional considerations for data exchange

Import or export hardware diagrams to or from a standard file type to share


Data exchange with other data between different software applications.
software applications
Import and export in the Logix Designer application support these file
formats:

• Web Ontology Language (OWL) uses an .rdf file to exchange data.


Recommended for the most rich data exchange with all Rockwell
Automation specific features identified for data exchange. The RDF
(Resource Description Framework) serves for data representation,
OWL (Web Ontology Language) builds on RDF and defines the
dictionary. Both are open standards for data exchange. They are used
as a basis for a Rockwell Automation specific data format.
Tip: When exchanging data between Rockwell Automation software applications,
always use the RDF file type.

• AutomationML (AML) uses an .aml file to exchange data.


AML is an open industry standard format dedicated to automation
usage. The AML specification includes a set of data structures
implemented in the application. This implementation enables
interoperability with other software applications that use the
AutomationML Automation Project Configuration format, such as
EPLAN Electric.
Some Rockwell Automation devices are only partially supported by the
AML format because they include capabilities that are not within the
scope of the current AML standard. When a product is partially
supported, it can be imported or exported, but may require some
additional configuration to reconfigure the unsupported features. Check
the Errors window in the Logix Designer application for details.

See also

Data exchange device support tables on page 72

Data exchange file type capabilities and limitations on page 70

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 69


Chapter 9 Additional considerations for data exchange

Data exchange file type AutomationML (AML) is an XML-based data format for storing
automation-related data. Import and export AML and RDF within the Logix
capabilities and limitations Designer application.

Current Logix Designer application supported devices are:

• Chassis
• Controllers
• Controllers with Ethernet
• I/O modules
• ControlNet communication modules
• Ethernet communication module
• Motion modules
• Redundancy modules
• Specialty modules
• Ethernet switches
• Servo drives
• Ethernet network (one only)
• Ethernet connection
• ControlNet network (trunk) (multiple)
• PowerFlex devices

Some devices are not supported by AML or RDF data exchange with the
Logix Designer application and, if they are present, are omitted from the
export file. These devices are:

• CompactLogix L2x, L3x, L4x, -L37ERMO, and -L37ERMOS


controllers
• HMI devices
• Classic profiles (profiles that do not have a Module Definition dialog
box) (excluding controllers)
• Devices not included:

70 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Additional considerations for data exchange Chapter 9

• 1734 Address Reserve module (1734-ARM)


• 1756 Redundancy modules (1756-RM2)
• 1794 Extended-Local I/O adapter (1794-FLA)
• Unmanaged switches (1783-US)
• Generic switch
• Generic computer
• Flex Terminal Base Unit device (1794-TB, 1797-TB)
• Power Supply devices
• End Cap and cable devices
• Stratix expansion module switches (1783-MX, 1783-MS, 1783-RMS)
• PowerFlex Peripheral modules
• Other trunks

Some devices cannot be exported to AML. These devices are:

• CompactExtensionConnection (indicating a multi-part chassis)


• FlexLogixTrunk
Important: Attempting to export a hardware diagram that includes either of these
devices results in an error and the export does not succeed.

Device properties

AML and RDF support storing a subset of device and tag properties. This
table identifies the properties that are stored for data exchange with the Logix
Designer application:

Device Property
All GUID
Name
Chassis, Modules in Chassis, Independent physical devices Catalog number
Position
Firmware version
IP address
Description

Unsupported properties are omitted in an AML export. Some properties can


be calculated and restored upon import and others must be explicitly
configured after import. Unsupported properties are:

• LeftRackSize and RightRackSize properties of CompactLogix chassis.


If possible this data is calculated during post-processing and restored
during import.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 71


Chapter 9 Additional considerations for data exchange

• Redundancy
• Safety Level
• Servo drive grouping
• Stratix expansion module owner assignment. If possible this data is
calculated during post-processing and restored during import.

See also

Data exchange with other software applications on page 69

Data exchange device support tables on page 72

AutomationML web site (https://www.automationml.org)

Data exchange device Use the tables in this section to determine which form of data exchange is
supported by a Logix Designer application device. Devices included in a
support tables project that are not supported cannot be imported from or exported to an
RDF or AML file.

See also

Data exchange with other software applications on page 69

Data exchange file type capabilities and limitations on page 70

1715 Data exchange is not supported for 1715 communication, and digital and
analog input and output devices.

1719 Data exchange is not supported for 1719 communication, and digital and
analog, input and output devices.

1732 Data exchange is not supported for 1732 safety, communication, and digital
and analog input and output devices.

1734 POINT I/O Data exchange support for 1734 POINT I/O safety, communication,
specialty, and digital and analog input and output devices:

1734 POINT I/O safety, communication, specialty, digital, and analog

Catalog Number or Product Family RDF support AML


support
1734-232ASC Yes Yes
1734-485ASC Yes Yes
1734-4IOL No No
1734-8CFG Yes Yes
1734-8CFGDLX Yes Yes
1734-ACNR Yes Yes
1734-AENT Yes Yes

72 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Additional considerations for data exchange Chapter 9

Catalog Number or Product Family RDF support AML


support
1734-AENTR Yes Yes
1734-ARM Yes Yes
1734-DIN Yes Yes
1734-EP24DC Yes Yes
1734-EPAC Yes Yes
1734-FPD Yes Yes
1734-IA11-2 No No
1734-IA11-8 No No
1734-IA16-2 No No
1734-IA2 Yes Yes
1734-IA4 Yes Yes
1734-IB2 Yes Yes
1734-IB4 Yes Yes
1734-IB4D Yes Yes
1734-IB8 Yes Yes
1734-IB8S Yes Yes
1734-IE2C Yes Yes
1734-IE2V Yes Yes
1734-IE4C Yes Yes
1734-IE4S Yes Yes
1734-IE8C Yes Yes
1734-IJ Yes Yes
1734-IK Yes Yes
1734-IM2 Yes Yes
1734-IM4 Yes Yes
1734-IR2 Yes Yes
1734-IR2E Yes Yes
1734-IT2I Yes Yes
1734-IV2 Yes Yes
1734-IV4 Yes Yes
1734-IV8 Yes Yes
1734-MODULE No No
1734-OA2 Yes Yes
1734-OA4 Yes Yes
1734-OB2 Yes Yes
1734-OB2E Yes Yes
1734-OB2EP Yes Yes
1734-OB4 Yes Yes
1734-OB4E Yes Yes
1734-OB8 Yes Yes

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 73


Chapter 9 Additional considerations for data exchange

Catalog Number or Product Family RDF support AML


support
1734-OB8E Yes Yes
1734-OB8S Yes Yes
1734-OE2C Yes Yes
1734-OE2V Yes Yes
1734-OE4C Yes Yes
1734-OV2E Yes Yes
1734-OV4E Yes Yes
1734-OV8E Yes Yes
1734-OW2 Yes Yes
1734-OW4 Yes Yes
1734-OX2 Yes Yes
1734sc-IE2CH No No
1734sc-IE4CH No No
1734sc-IF4U No No
1734sc-OE2CIH No No
1734-SSI Yes Yes
1734-VA11-2 No No
1734-VA11-3 No No
1734-VA11-8 No No
1734-VA16-2 No No
1734-VA16-4 Yes Yes
1734-VHSC24 Yes Yes
1734 POINT I/O power supplies Yes Yes

1738 Data exchange is not supported for 1738 communication, specialty, and
digital and analog input and output devices.

1746 Data exchange is not supported for 1746 specialty, and digital and analog
input and output devices.

1747 Data exchange is not supported for 1747 communication devices.

1753 Data exchange is not supported for 1753 GuardPLC devices.

1756 ControlLogix Data exchange support for 1756 ControlLogix devices:

1756 ControlLogix

Catalog Number or Product Family RDF support AML


support
1756 ControlLogix all chassis Yes3 Yes3

74 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Additional considerations for data exchange Chapter 9

Catalog Number or Product Family RDF support AML


support
1756 ControlLogix all motion modules Partial Partial
1756 ControlLogix all specialty modules Partial Partial
1756 ControlLogix all redundancy modules Partial 2
Partial2
1756 generic module Partial Partial
1756-A10 Yes3 Yes3
1756-A13 Yes 3
Yes3
1756-A17 Yes3 Yes3
1756-A4 Yes3 Yes3
1756-A4LXT Yes3 Yes3
1756-A5XT Yes3 Yes3
1756-A7 Yes3 Yes3
1756-A7LXT Yes3 Yes3
1756-CFM No No
1756-CN2 Yes Yes
1756-CN2R Yes Yes
1756-CNB ControlLogix communication module Partial Partial
1756-CNBR Yes Yes
1756-DHRIO ControlLogix communication module No No
1756-DMA30 No No
1756-DMA31 No No
1756-DMA50 No No
1756-DMB30 No No
1756-DMD30 No No
1756-DMF30 No No
1756-DNB No No
1756-EN2F Yes Yes
1756-EN2T Yes Yes
1756-EN2TP Yes Yes
1756-EN2TR Yes Yes
1756-EN2TSC ControlLogix communication module Partial Partial
1756-EN3TR Yes Yes
1756-ENBT Yes Yes
1756-ENET No No
1756-EWEB ControlLogix communication module No No
1756-HIST1G Yes Yes
1756-HIST2G Yes Yes
1756-HSC No No
1756-HYD02 No No
1756-IA16 ControlLogix digital I/O module Partial Partial
1756-IA16I Yes Yes

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 75


Chapter 9 Additional considerations for data exchange

Catalog Number or Product Family RDF support AML


support
1756-IA32 Yes Yes
1756-IA8D Yes Yes
1756-IB16 Yes Yes
1756-IB16D Yes Yes
1756-IB16I Yes Yes
1756-IB16IF ControlLogix module Partial Partial
1756-IB16ISOE Yes Yes
1756-IB32 Yes Yes
1756-IC16 Yes Yes
1756-IF16 Yes Yes
1756-IF16H Yes Yes
1756-IF16IH No No
1756-IF4FXOF2F Yes Yes
1756-IF6CIS No No
1756-IF6I No No
1756-IF8 Yes Yes
1756-IF8H Yes Yes
1756-IF8I ControlLogix module Partial Partial
1756-IF8IH ControlLogix module Partial Partial
1756-IG16 Yes Yes
1756-IH16I Yes Yes
1756-IH16ISOE Yes Yes
1756-IM16I Yes Yes
1756-IN16 Yes Yes
1756-IR12 No No
1756-IR6I No No
1756-IRT8I ControlLogix module Partial Partial
1756-IT16 No No
1756-IT16I No No
1756-IT6I2 No No
1756-IV16 Yes Yes
1756-IV32 Yes Yes
1756-L1 Yes Yes
1756-L53 Yes Yes
1756-L55 Yes Yes
1756-L60M03SE Yes Yes
1756-L60M03SE SERCOS No No
1756-L61 Yes Yes
1756-L61S Yes Yes
1756-L62 Yes Yes

76 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Additional considerations for data exchange Chapter 9

Catalog Number or Product Family RDF support AML


support
1756-L62S Yes Yes
1756-L63 Yes Yes
1756-L63S Yes Yes
1756-L64 Yes Yes
1756-L65 Yes Yes
1756-L71 Yes Yes
1756-L71S Yes Yes
1756-L72 Yes Yes
1756-L2S Yes Yes
1756-L3 Yes Yes
1756-L73S Yes Yes
1756-L4 Yes Yes
1756-L5 Yes Yes
1756-L7SP Yes Yes
1756-L81E ControlLogix controller Partial Partial
1756-L81ES ControlLogix controller Partial1
Partial1
1756-L82E ControlLogix controller Partial Partial
1756-L82ES ControlLogix controller Partial1 Partial1
1756-L83E ControlLogix controller Partial Partial
1756-L83ES ControlLogix controller Partial1
Partial1
1756-L84E ControlLogix controller Partial Partial
1756-L84ES ControlLogix controller Partial1
Partial1
1756-L85E ControlLogix controller Partial Partial
1756-L8SP ControlLogix controller Partial Partial
1756-LCE ControlLogix controller Partial Partial
1756-LSC8XIB8I ControlLogix specialty module Partial Partial
1756-LSP ControlLogix safety controller Yes Yes
1756-M02AE No No
1756-M02AS No No
1756-M03SE No No
1756-M08SE No No
1756-M08SEG No No
1756-M016SE No No
1756-MODULE No No
1756-OA16 Yes Yes
1756-OA16I Yes Yes
1756-OA8 Yes Yes
1756-OA8D Yes Yes
1756-OA8E Yes Yes
1756-OB16D Yes Yes

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 77


Chapter 9 Additional considerations for data exchange

Catalog Number or Product Family RDF support AML


support
1756-OB16E Yes Yes
1756-OB16I Yes Yes
1756-OB16IEF ControlLogix digital I/O module Partial Partial
1756-OB16IEFS ControlLogix digital I/O module Partial Partial
1756-OB16IS Yes Yes
1756-OB32 Yes Yes
1756-OB8 Yes Yes
1756-OB8EI Yes Yes
1756-OB8I No No
1756-OC8 Yes Yes
1756-OF4 Yes Yes
1756-OF6CI No No
1756-OF6VI No No
1756-OF8 Yes Yes
1756-OF8H Yes Yes
1756-OF8I ControlLogix analog I/O module Partial Partial
1756-OF8IH ControlLogix analog I/O module Partial Partial
1756-OG16 Yes Yes
1756-OH8I Yes Yes
1756-ON8 Yes Yes
1756-OV16E Yes Yes
1756-OV32E Yes Yes
1756-OW16I Yes Yes
1756-OX8I Yes Yes
1756-PA72 Yes Yes
1756-PA75 Yes Yes
1756-PA75R Yes Yes
1756-PAR Yes Yes
1756-PAR2 Yes Yes
1756-PAXT Yes Yes
1756-PB72 Yes Yes
1756-PB75 Yes Yes
1756-PB75R Yes Yes
1756-PBR Yes Yes
1756-PBR2 Yes Yes
1756-PBXT Yes Yes
1756-PLS No No
1756-PPMPC No No
1756-RIO ControlLogix communication module Partial Partial
1756-RM* No No

78 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Additional considerations for data exchange Chapter 9

Catalog Number or Product Family RDF support AML


support
1756sc-CTR8 No No
1756sc-CT32 No No
1756sc-IF8H No No
1756sc-IF8U No No
1756sc-OF8H No No
1756-SYNCH ControlLogix communication module No No
1
Safety level properties not supported.
2
Other networks trunk not supported
3
Chassis power supply configuration not included.
*
All devices of type

1757 Data exchange is not supported for 1757 devices.

1768 CompactLogix Data exchange support for 1768 CompactLogix devices:

1768 CompactLogix

Catalog Number or Product Family RDF support AML


support
1768 CompactLogix controllers, banks, power supplies and modules Yes Partial1
1768-L43 CompactLogix modules No No
1768-L43 DIN rail No No
1768-L43S No No
1768-L43S DIN rail No No
1768-L45 CompactLogix modules No No
1768-L45 DIN rail No No
1768-L45S No No
1768-L45S DIN rail No No
1768-CNB CompactLogix modules No No
1768-CNBR CompactLogix modules No No
1768-DIN CompactLogix modules Yes Yes
1768-ENBT CompactLogix modules No No
1768-EWEB CompactLogix modules No No
1768-M04SE CompactLogix modules No No
1768-MODULE CompactLogix generic module No No
1768-PA3 Yes Yes
1768-PB3 Yes Yes
1
Configuration relationships calculated during post-processing. Confirm that the configuration is correct before
committing the project.
2
RightRackSize property not supported.

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 79


Chapter 9 Additional considerations for data exchange

1769 Data exchange support for 1769 CompactLogix devices:

1769 CompactLogix

Catalog Number or Product Family RDF support AML


support
1769 CompactLogix controllers, banks, and modules Partial1 Partial1
1769 CompactLogix all digital I/O modules Partial1 Partial1
1769 CompactLogix all analog I/O modules Partial1 Partial1
1769 CompactLogix all specialty modules Partial1 Partial1
1769 CompactLogix generic module Partial1
Partial1
1769-L16ER-BB1B CompactLogix controller Partial1 Partial1
1769-L18ER-BB1B CompactLogix controller Partial1 Partial1
1769-L18ERM-BB1B CompactLogix controller Partial1 Partial1
1769-L19ER-BB1B CompactLogix controller Partial1 Partial1
1769-L20 No No
1769-L23* CompactLogix controllers Partial1 Partial1
1769-L24* CompactLogix controllers Partial1
Partial1
1769-L27ERM-QBFC1B CompactLogix controllers Partial1 Partial1
1769-L30* CompactLogix controllers Partial1 Partial1
1769-L31 CompactLogix controllers No No
1769-L32C CompactLogix controllers No No
1769-L32E CompactLogix controllers No No
1769-L33* CompactLogix controllers Partial1 Partial1
1769-L35CR CompactLogix controller No No
1769-L35E CompactLogix controller No No
1769-L36* CompactLogix controllers Partial1
Partial1
1769-L37* CompactLogix controllers Partial1 Partial1
1769-L38* Yes Yes
1769-L40 No No
1769-MODULE No No
1769sc-IF4IH No No
1769sc-IF8U No No
1769sc-IR6I No No
1769sc-IT6I No No
1769sc-OF4IH No No
1769-SDN CompactLogix communication module No No
1769-AENTR CompactLogix communication module Partial1 Partial1
*
All devices of type
1
Configuration relationship between controller and its owned I/O or other types of modules not supported.

80 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Additional considerations for data exchange Chapter 9

1771 Data exchange is not supported for 1771 devices.

1783 Stratix Data exchange support for 1783 Stratix devices:

1783 Stratix

Catalog Number or Product Family RDF support AML


support
1783 Stratix 2000 switches Yes Yes
1783 Stratix 5400 switches Partial1 Partial1
1783 Stratix 5700 switches Partial1 Partial1
1783-BMS06* Yes Yes
1783-BMS010* Yes Yes
1783-BMS12T4E2CGL Stratix 5700 switch Partial1
Partial1
1783-BMS12T4E2CGNK Stratix 5700 switch Partial1 Partial1
1783-BMS12T4E2CGP Stratix 5700 switch Partial1 Partial1
1783-BMS20* Yes Yes
1783-BMS4S2SGA Stratix 5700 switch Partial1
Partial1
1783-BMS4S2SGL Stratix 5700 switch Partial1 Partial1
1783 Stratix 6000 switches Partial1 Partial1
1783 Stratix 8000 switches Partial1 Partial1
1783 Stratix 8300 switches Partial1 Partial1
1783-EMS04T Partial2 Partial2
1783-EMS08T Partial2 Partial2
1783 Ethernet Taps Partial1 Partial1
1783-HMS16T4CGN Yes Yes
1783-HMS16TG4CGN Yes Yes
1783-HMS16TG4CGR Yes Yes
1783-HMS4* Yes Yes
1783-HMS8* Yes Yes
1783-IMS28* No No
1783-LMS5 No No
1783-LMS8 No No
1783-MS06T Yes Yes
1783-MS06T plus 4-Port Expansion Module No No
1783-MS06T plus 4-Port in Expansion Modules 1 and 8-Port in Expansion Modules 2 No No
1783-MS06T plus 8-Port in Expansion Module 1 and 4-Port Expansion Modules 2 No No
1783-MS06T plus two 4-Port Expansion Modules No No
1783-MS10T Yes Yes
1783-MS10T plus 4-Port Expansion Module No No
1783-MS10T plus 4-Port Expansion Module 1 and 8-Port in Expansion Module 2 No No
1783-MS10T plus 8-Port in expansion module 1 and 4-Port in Expansion Module 2 No No
1783-MS10T plus two 4-Port Expansion Modules No No

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 81


Chapter 9 Additional considerations for data exchange

Catalog Number or Product Family RDF support AML


support
1783-MX04* Partial3 Partial3
1783-MX08* Partial3 Partial3
1783-NATR No No
1783-RMS06T Yes Yes
1783-RMS06T plus 4-Port Expansion Module No No
1783-RMS06T plus 4-Port in Expansion Modules 1 and 8-Port in Expansion Modules 2 No No
1783-RMS06T plus 8-Port in Expansion Module 1 and 4-Port Expansion Modules 2 No No
1783-RMS06T plus two 4-Port Expansion Modules No No
1783-RMS10T Yes Yes
1783-RMS10T plus 4-Port Expansion Module No No
1783-RMS10T plus 4-Port Expansion Module 1 and 8-Port in Expansion Module 2 No No
1783-RMS10T plus 8-Port in expansion module 1 and 4-Port in Expansion Module 2 No No
1783-RMS10T plus two 4-Port Expansion Modules No No
1783-US03T01F Partial2
Partial2
1783-US06T01F Partial2 Partial2
1783-US5T Partial2 Partial2
1783-US8T Partial2 Partial2
1783-WAPxK9 No No
1783-ZMS16TA No No
1783-ZMS24TA No No
1783-ZMS4T4E2TGN No No
1783-ZMS4T4E2TGP No No
1783-ZMS8T8E2TGN No No
1783-ZMS8T8E2TGP No No
1783-ZMS8TA No No
1
Configuration relationships are not supported. Relationship will be calculated by post-processing during import.
2
Connections only
3
Stratix expansion module
*
All devices of type

1784 Data exchange is not supported for 1784 devices.

1785 Data exchange is not supported for 1785 devices.

1788 Data exchange is not supported for 1788 devices.

1789 Data exchange is not supported for 1789 devices.

1791DS Data exchange is not supported for 1791DS devices.

82 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Additional considerations for data exchange Chapter 9

1791ES Data exchange is not supported for 1791ES devices.

1794 FLEX I/O Data exchange support for 1794 FLEX I/O devices:

1794 FLEX I/O

Catalog Number or Product Family RDF support AML


support
1794 FLEX I/O DIN, power supplies and modules Partial1 Partial1
1794-ASB No No
1794-IF4ICF FLEX I/O module Partial 1
Partial1
1794-IF8IHNF FLEX I/O module Partial1 Partial1
1794-FLA No No
1794-IB8S No No
1794-IE8H Yesl 2
Yesl2
1794-IJ2I No No
1794-L33 No No
1794-L34 No No
1794-OE8H/A Yesl 3
Yesl3
1794-PS1 Yes4 Yes4
1794-PS13 Yes4 Yes4
1794-PS3 Yes4 Yes4
1794TB* Yes5 Yes5
1
Configuration relationship between controller and owned IO modules not supported.
2
As 1794-IE8H/B
3
As 1794-OE8H/B
4
Power Supply ignored
5
Yes Flex Terminal Base unit ignored
*
All devices of type

1797 Data exchange support for 1797 devices:

1797

Catalog Number or Product Family RDF support AML


support
1797-ACNR15 Yes Yes
1797-IBN16 No No
1797-IE8* No No
1797-IJ2 No No
1797-IRT8 No No
1797-OB4D No No
1797-OE8 No No

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 83


Chapter 9 Additional considerations for data exchange

Catalog Number or Product Family RDF support AML


support
1797-PS* Yes1 Yes1
1797-TB* Yes2 Yes2
*
All devices of type
1
Power Supply ignored
2
Terminal Base Unit ignored

1799 Data exchange is not supported for 1799 devices.

193/592 Data exchange is not supported for 193/592 devices.

20-750 Data exchange support for 20-750 devices:

20-750

Catalog Number or Product Family RDF support AML


support
20-750-ENETR* Yes Yes
20-750-S* Ye Yes
20-750-S1* Yes Yes
*
PowerFlex peripheral

5069 CompactLogix Data exchange support for 5069 CompactLogix devices:

5069 CompactLogix

Catalog Number or Product Family RDF support AML


support
5069 CompactLogix controllers, banks and modules Partial1 Partial1
5069-AENTR Partial2 Partial2
5069-AEN2TR communication module Partial2 Partial2
5069-ARM Yes Yes
5069-ECR Yes 3
Yes3
5069-FPD Yes4 Yes4
5069 CompactLogix digital I/O modules Partial2 Partial2
5069 CompactLogix analog I/O modules Partial 2
Partial2
5069 CompactLogix specialty modules Partial2 Partial2
5069-L306* controllers Yes Yes
5069-L3100* controllers Yes Yes
5069-310* controllers Yes Yes
5069-L320ER* controllers Partial 2
Partial2

84 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Additional considerations for data exchange Chapter 9

Catalog Number or Product Family RDF support AML


support
5069-L330ER* controllers Yes Yes
5069-L340ER* controllers Yes Yes
5069-L350ER* controllers Yes Yes
5069-L380ER* controllers Yes Yes
5069-L460ERMW controllers Yes Yes
5069-SERIAL No No
1
DIN description not supported.
2
Configuration relationships not supported. Relationship calculated by post-processing during import.
3
End cap ignored.
4
Power Supply ignored.
*
All devices of type

5094 Data exchange is not supported for 5094 devices.

ArmorPoint Data exchange is not supported for ArmorPoint devices.

ArmorStart Data exchange is not supported for ArmorStart devices.

Communication Data exchange is not supported for these communication devices.

Communication

Catalog Number or Product Family RDF support AML


support
100-1167-001 No No
1440-ACNR No No
2PCA-7844-B101 No No
56AMXN No No
ACT350 EtherNet/IP No No
ACT350-2P EtherNet/IP No No
Bus Module No No
Checker 4G1 No No
Checker 4G7 No No
CompactBus No No
CONTROLNET-MODULE No No
DACS EtherNet/IP Adapter No No
DataMan 200 Series No No
DataMan 500 Series No No
DataMan 8000 Series No No
DriveLogix5730 Ethernet Port No No
E1 Plus No No

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 85


Chapter 9 Additional considerations for data exchange

Catalog Number or Product Family RDF support AML


support
EA3600 EtherNet/IP No No
EtherNet/IP No No
ETHERNET-BRIDGE No No
ETHERNET-MODULE No No
EX250-S* No No
EX260-SEN* No No
EX500-GEN1 No No
FlexBus No No
HMS-EN2MB-R No No
HMS-EN2PB-R No No
HMS-EN2SE-R No No
IB-E01 No No
IB-E03B No No
IB-E04F No No
ILX34-AENWG No No
ILX69-PBM No No
ILX69-PBS No No
IND131 EtherNet/IP No No
IND560 EtherNet/IP No No
IND570 EtherNet/IP No No
IND780 ControlNet No No
IND780 EtherNet/IP No No
In-Sight 1700 Series No No
In-Sight 3400 Series No No
In-Sight 5000 Series No No
In-Sight Micro Series No No
Link_OS_Printer No No
LMDrive No No
MVI56* No No
MVI69* No No
OCP-ETG No No
OCX-* No No
PCIe-ETAP No No
PCI-ETAP No No
RA56-ESA No No
RIO-ADAPTER No No
SLP85xD No No
SST-ESR2-C* No No
SST-PB3*-CPX No No
SST-PFB/PB3-CLX-RLL No No

86 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Additional considerations for data exchange Chapter 9

Catalog Number or Product Family RDF support AML


support
SST-SR4-CLX-RLL No No
STB3574 EtherNet/IP No No
Stratix 8000* No No
Stratix 8300* No No
SWG70 No No
Thyro* No No
WHA-GW No No
WMF No No
*
All devices of type

DPI to EtherNet/IP Data exchange is not supported for DPI to EtherNet/IP devices.

Drive Data exchange is not supported for these drives.

Drives

Catalog Number or Product Family RDF support AML


support
1305-ACDrive-CN1 No No
1305-ACDrive-EN1 No No
1336E-IMPACTDrive-CN1 No No
1336E-IMPACTDrive-EN1 No No
1336F-PLUSIIDrive-CN1 No No
1336F-PLUSIIDrive-EN1 No No
1336R-REGENBrake-CN1 No No
1336R-REGENBrake-EN1 No No
1336S-PLUSDriveLG-CN1 No No
1336S-PLUSDriveLG-EN1 No No
1336S-PLUSDriveSM-CN1 No No
1336S-PLUSDriveSM-EN1 No No
1336T No No
1336T-FORCEDriveCNA-CN1 No No
1336T-FORCEDriveCNA-EN1 No No
1336T-FORCEDrivePLC-CN1 No No
1336T-FORCEDrivePLC-EN1 No No
1336T-FORCEDriveStd-CN1 No No
1336T-FORCEDriveStd-EN1 No No
1394C-SJT05-D No No
1394C-SJT10-D No No
1394C-SJT22-D No No

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 87


Chapter 9 Additional considerations for data exchange

Catalog Number or Product Family RDF support AML


support
1395 No No
1397DigitalDCDrive-CN1 No No
1397DigitalDCDrive-EN1 No No
150-SMC Flex-C No No
150-SMC Flex-E No No
150-SMC Flex-ER No No
150-SMC Flex-Q No No
150-SMCDialogPlus--CN1 No No
150-SMCDialogPlus--EN1 No No
2098-DSD* No No
2099-BM* No No
2364F-RGU* No No
8720MC* No No
Drives AOP Infrastructure No No
FLEX-MODULE No No
Generic SERCOS Drive No No
GV3000 No No
Multi-Drive-25-COMM-E2P No No
Rockwell Automation UDC AOP Infrastructure No No
SMC-50* No No
WebPak 3000 No No
*
All devices of type

Embedded Data exchange support for embedded devices:

Embedded

Catalog Number or Product Family RDF support AML


support
Embedded Compact, analog, output No No
Embedded Point I/O Yes Yes
Embedded Compact, specialty No No
Embedded Compact, digital, input, output No No
Embedded HSC Yes Yes
Embedded IF4XOF2 Yes Yes
Embedded IQ16F Yes Yes
Embedded 0B16 Yes Yes

88 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Additional considerations for data exchange Chapter 9

Energy Management Products Data exchange is not supported for energy management products.

HMI Data exchange is not supported for HMI devices.

Kinetix Data exchange support for Kinetix devices:

Kinetix

Catalog Number or Product Family RDF support AML


support
2093-AC05* No No
2093-AM* No No
2094-AC* No No
2094-AM* No No
2094-BC* No No
2094-BM* No No
2094-EN02D-M01* No No
2094-SE02F-M00-S0/2094-AC* No No
2094-SE02F-M00-S0/2094-AM* No No
2094-SE02F-M00-S0/2094-BC* No No
2094-SE02F-M00-S0/2094-BM* No No
2094-SE02F-M00-S1/2094-AC* No No
2094-SE02F-M00-S1/2094-AM* No No
2094-SE02F-M00-S1/2094-BC* No No
2094-SE02F-M00-S1/2094-BM* No No
2094--SEPM-B24-S No No
Kinetix 300 servo drives Partial1 Partial1
Kinetix 350 servo drives Partial1
Partial1
Kinetix 5500 servo drives Partial1 2 Partial1 2
Kinetix 5700 servo drives Partial1 2 Partial1 2
MDx-SB1003P-Qxx* No No
*
All devices of type
1
Configuration relationships not supported. Relationship calculated by post-processing during import.
2
Motion group property not supported by AML.

Motion Data exchange is not supported for these motion devices.

Motion

Catalog Number or Product Family RDF support AML


support
2094-SEPM-B24-S No No
842-CM-M No No

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 89


Chapter 9 Additional considerations for data exchange

MPI to EtherNet/IP Data exchange is not supported for MPI to EtherNet/IP devices.

PowerFlex Data exchange support for PowerFlex devices:

PowerFlex

Catalog Number or Product Family RDF support AML


support
22C... No No
22N... No No
25* Yes Yes
PowerFlex 523 drives Partial12
Partial1 2
PowerFlex 525 drives Partial1 3 Partial1 3
PowerFlex 527-STO CIP Safety drive Partial1 Partial1
PowerFlex 700 No No
PowerFlex 753 drives Partial14
Partial1 4
PowerFlex 755 drives Partial1 5 Partial1 5
DriveLogix 57* No No
PowerFlex 4 Class Multi* No No
PowerFlex 400* No No
PowerFlex 40* No No
PowerFlex 4* No No
PowerFlex 523-C No No
PowerFlex 523-E* Yes Yes
PowerFlex 525-C No No
PowerFlex 525-E* Yes Yes
PowerFlex 527-STO CIP Safety Yes Yes
PowerFlex 70 ED* No No
PowerFlex 700 AC* No No
PowerFlex 700 Vector* No No
PowerFlex 7000* No No
PowerFlex 700* No No
PowerFlex 70* No No
PowerFlex 753-CNETC No No
PowerFlex 753-ENETR Yes Yes
PowerFlex 753-NET-C No No
PowerFlex 753-NET-E Yes Yes
PowerFlex 753-NET-Q No No
PowerFlex 755 HiPwr-PMM-EENET No No
PowerFlex 755 HiPwr-CNETC No No
PowerFlex 755 HiPwr-EENET Yes Yes

90 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Additional considerations for data exchange Chapter 9

Catalog Number or Product Family RDF support AML


support
PowerFlex 755 HiPwr-ENETR Yes Yes
PowerFlex 755 HiPwr-NET-C No No
PowerFlex 755 HiPwr-NET-E Yes Yes
PowerFlex 755 HiPwr-NET-Q No No
PowerFlex 755 PMM-EENET No No
PowerFlex 755-CNETC No No
PowerFlex 755-EENET* Yes Yes
PowerFlex 755-ENETR Yes Yes
PowerFlex 755 HiPwr-EENET-CM* Yes Yes
PowerFlex 755-NET-C No No
PowerFlex 755-NET-E Yes Yes
PowerFlex 755-NET-Q No No
PowerFlex 755T* No No
PowerFlex 755 DC FC* No No
PowerFlex 755 DC* No No

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 91


Chapter 9 Additional considerations for data exchange

Catalog Number or Product Family RDF support AML


support
*
All devices of type
1
Configuration properties not fully supported.
2
PowerFlex 523-E2P drive imports as a type PowerFlex 523-E drive but includes the PowerFlex 523-E2P description in
the configuration properties.
3
PowerFlex 525-E drive imports as a type PowerFlex 523-E drive and includes the PowerFlex 523-E description in the
configuration properties.
PowerFlex 525-E2P drive imports as a type PowerFlex 525-EENET drive but includes the PowerFlex 525-E2P
description in the configuration properties.
PowerFlex 525-EENET-Multi drive imports as a type PowerFlex 525-EENET drive but includes the PowerFlex
525-EENET-Multi description in the configuration properties.
4
PowerFlex 753-NET-E drive imports as a type PowerFlex 753-ENETR drive but includes the PowerFlex 753-NET-E
description in the configuration properties.
5
PowerFlex 755 HiPwr-ENETR2 drive imports as a type PowerFlex 755 HiPwr-EENET drive but includes the PowerFlex
755 HiPwr-ENETR description in the configuration properties.
PowerFlex 755 HiPwr-NET-E drive imports as a type PowerFlex 755 HiPwr-EENET drive but includes the PowerFlex
755 HiPwr-NET-E description in the configuration properties.
PowerFlex 755-EENET drive imports as a type PowerFlex 755 HiPwr-EENET drive but includes the PowerFlex
755-EENET description in the configuration properties.
PowerFlex 755-ENETR drive imports as a type PowerFlex 755 HiPwr-EENET drive but includes the PowerFlex
755-ENETR description in the configuration properties.
PowerFlex 755-EENET-CM drive imports as a type PowerFlex 755 HiPwr-EENET drive but includes the PowerFlex
755-EENET-CM description in the configuration properties.
PowerFlex 755-EENET-CM -S drive imports as a type PowerFlex 755 HiPwr-EENET drive but includes the PowerFlex
755-EENET-CM-S description in the configuration properties.
PowerFlex 755-EENET-CM-S1 drive imports as a type PowerFlex 755 HiPwr-EENET drive but includes the PowerFlex
755-EENET-CM-S1 description in the configuration properties.
PowerFlex 755-HiPwr-EENET-CM drive imports as a type PowerFlex 755 HiPwr-EENET drive but includes the
PowerFlex 755-HiPwr-EENET-CM description in the configuration properties.
PowerFlex 755-HiPwr-EENET-CM-S drive imports as a type PowerFlex 755 HiPwr-EENET drive but includes the
PowerFlex 755-HiPwr-EENET-CM-S description in the configuration properties.
PowerFlex 755-HiPwr-EENET-CM-S1 drive imports as a type PowerFlex 755 HiPwr-EENET drive but includes the
PowerFlex 755-HiPwr-EENET-CM-S1 description in the configuration properties.
PowerFlex 755-NET-E drive imports as a type PowerFlex 755 HiPwr-EENET drive but includes the PowerFlex
755-NET-E description in the configuration properties.

Specialty Data exchange is not supported for these specialty devices.

Specialty

Catalog Number or Product Family RDF support AML


support
124x No No
1440-DYN02-01RJ No No
1444-DYN04-01RA No No
1642 No No
2198-ABQE No No
3202 No No
3204 No No

92 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Additional considerations for data exchange Chapter 9

Catalog Number or Product Family RDF support AML


support
3401 - 3401L No No
3601 No No
3602 - 3602D No No
48MS-SN1PF1-M2 No No
48MS-SN1PF2-M2 No No
56RF-IN-IP* No No
5XRF_IN_IP No No
7662 No No
842E-M No No
842E-S No No
A3XX No No
ACU No No
AX8 No No
FANUC CNC* No No
FANUC Robot No No
FANUC Robt R30iB Plus No No
HI1734-WS No No
HI1756-xDF No No
HI1756-xFC No No
HI1756-xWS No No
HI1769-xFC No No
HI1769-xWS No No
Liquiline_CA80xx No No
Liquiline_CM44x No No
Liquistation_CSFxx No No
Memograph_M_RSG45 No No
Onyx-S/SC2 No No
Promag* No No
Promass* No No
* All devices of type

Other Data exchange support for other devices:

Other

Catalog Number or Product Family RDF support AML


support
Logix Designer projects Partial1 Partial1
Generic switches Yes Yes
Ethernet switches - Generic Yes Yes

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 93


Chapter 9 Additional considerations for data exchange

Catalog Number or Product Family RDF support AML


support
Generic computers Partial2 Partial2
PanelView Plus graphic terminals Yes Yes
MobileView mobile terminals Yes Yes
FactoryTalk View applications or servers No No
Graphics No No
Files No No
Text Boxes No No
Shapes No No
Links No No
Combination Generator Control Module No No
Combination Generator Control Module, 2-Port No No
Powermonitor1000 No No
1557... No No
20-COMM-E Yes 3
Yes3
22-COMM-E Yes3 Yes3
2706-PENETX No No
440C-CR30-22BBB No No
CEP7-ETN No No
CIP-MODULE No No
DEVICENET-SAFETYMODULE No No
DPI-DRIVE-PERIPHERAL-MODULE No No
DSI-DRIVE-PERIPHERAL_MODULE No No
Emulate 5570 No No
ETHERNET-SAFETYMODULE No No
ETHERNET-SAFETY-STANDARD-MODULE No No
FLEX_MODULE No No
Generic Computer Yes 4
Yes4
Generic Switch Yes5 Yes5
L2yEmbedded Analog_IO Yes6 Yes6
L2yEmbedded Counters Yes7 Yes7
L2yEmbedded Discrete_IO Yes8 Yes8
Logix Block No No
MDCOMM-ENET No No
RHINOBP-DRIVE-PERIPHERAL-MODULE Yes 3
Yes3
RIO-MODULE No No
RSLinx No No
SCANport-DRIVE-PERIPHERAL-MODULE No No
VersaView CE* No No
Other Networks Yes No

94 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018


Additional considerations for data exchange Chapter 9

Catalog Number or Product Family RDF support AML


support
1
Project must not include any unsupported devices. Data imported subject to the limitations on included devices.
2
The computer name property of the generic computer object not supported for AML export or import. Assigns a
default name to the generic computer object during import that can be updated after the import is complete.
3
PowerFlex peripheral.
4
Computer ignored.
5
Connections only.
6
As 1.10.164
7
As 1.109.71
8
AS 1.7.64

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 95


Index
description
A export 19
Add-On Instruction 55
export 19
E
import 24
alarms 63 equipment phase 51
attention flags 41 export 19
export considerations 67
import 24
B import considerations 58
backward compatibility 45 export
Add-On Instruction 55
component description 19
C components 13, 19
canceled import 42 considerations 17
collision equipment phase 51
import 59, 60 L5X 13, 19
communication timeouts 20, 58 local tag 67
compare instructions 60 parameter 67
component program 51
configuration 59 routine 49
export 13, 19 rungs 47
import 13, 24 tag 67
configuration user-defined data type 53
attention flags 41 user-defined string type 53
components 59 export considerations
example 40 equipment phase 67
import 38, 59 local tag 67
options 25, 58 parameter 67
references 38 program 67
undefined references 41 routine 67
Connections grid 36 rungs 67
considerations security 19
export 17 tag 67
import 58 user-defined data type 67
motion 22 user-defined string type 67
online import 20 exportIXexport 55
safety 23
security 19, 23
F
failed import 42
D find
data exchange 13 text 44
data exchange file type capabilities and limitations 70 use wildcards 44
support tables 72, 74, 79, 80, 81, 82, 83, 84, 85, 87, 88, 89, 90, 92, 93
with other software applications 69
Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 97
Index

I multiple components 23, 29

import
Add-On Instruction 55 O
canceled 42 online import 20
components 13, 24
configuration 38, 59
considerations 58 P
equipment phase 51 parameter
failed 42 export considerations 67
L5X 13, 24 import considerations 58
local tag 67 program 51
multiple components 29 export 19
parameter 67 export considerations 67
program 51 import 24
routine 49 import considerations 58
rungs 47 Project References tab 60
tag 67 Property Compare tab 60
user-defined data type 53
user-defined string type 53
Import Configuration dialog box 60 R
import considerations references
equipment phase 58 configuration 38
local tag 58 undefined 41
multiple components 23 replace
parameter 58 text 44
program 58 routine 49
routine 58 export 19
rungs 58 export considerations 67
security 23 import 24
tag 58 import considerations 58
user-defined data type 58 rungs 47
user-defined string type 58 export 19
importIXimport 58 export considerations 67
import 24
import considerations 58
L
L5X
export 13, 19 S
import 13, 24 safety 23
local tag safety Add-On Instruction
export considerations 67 import 58
import considerations 58 safety task signature 58
search and replace 44
security 19, 23
M
motion 22
98 Rockwell Automation Publication 1756-PM019I-EN-E - December 2018
Index

T
tag 67
export considerations 67
import considerations 58
tooltip
attention flags 41
trend
export 19
import 24

U
undefined references 41
update Add-On Instruction revision 60
user-defined data type 53
export 19
export considerations 67
import 24
import considerations 58
user-defined string type 53
export 19
export considerations 67
import 24
import considerations 58
UTF-8 file format 13

W
wildcards 44

X
XML files 13

Rockwell Automation Publication 1756-PM019I-EN-E - December 2018 99


Rockwell Automation support
Rockwell Automation provides technical information on the web to assist you in using its products.
At http://www.rockwellautomation.com/support you can find technical and application notes, sample code, and links to software service
packs. You can also visit our Support Center at https://rockwellautomation.custhelp.com for software updates, support chats and forums,
technical information, FAQs, and to sign up for product notification updates.

In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more information, contact your
local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/services/online-phone.

Installation assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can
contact Customer Support for initial help in getting your product up and running.

United States or Canada 1.440.646.3434


Outside United States or Canada Use the Worldwide Locator available at http://www.rockwellautomation.com/locations, or contact your local Rockwell
Automation representative.

New product satisfaction return


Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility.
However, if your product is not functioning and needs to be returned, follow these procedures.

United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to
your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.

Documentation feedback