Turbomachinery Instrument Inspection Checklist for Integrity Assurance

Equipment Tag: 3200-P-844 Driver Type: Motor

Manufacturer: Inspected by: Crispin Jee Chen Hung

Service: Extruder Gear Pump Reviewed by:

Criticality: Approval by:

1. BN 3500
Inspection Item Description Finding (OK/Not OK) Recommendations

1. Rack status BN Rack status


- No faults at any module
- Overrides not enabled
- Mode key at RUN
2. Radial vibration probe gap Gap voltage for each radial probe is 10 OK
voltage Vdc (+/- 3%)
3. Axial probes deviation Axial probes reading do not deviate from N/A
each other by more than 0.05 mm

4. Relay configuration for Voting logic is configured: Temperature single


voting implementation - 2oo4 for radial proximity trip initiator
- 2oo2/2oo3 for bearing temperature
(depending on num of sensors)

5. Accelerometer/ Sensor field mounting installation is tight OK


Velomitor mounting and secured
installation

Open
Page 1 of 6
2. Field Instruments (refer attachment)
Inspection Item Description Finding (OK/Not OK) Recommendations

1. Field instrument - Reading is normal with respect to ambient OK


healthiness conditions
- For instrument connected to PRM, no
alarms shown in PRM
2. Machine control and Stroke check performed with expected N/A
shutdown valves results

3. Electronic Governor
Inspection Item Description Finding (OK/Not OK) Recommendations

1. Speed Probes Speed probes are healthy N/A

2. Governor actuator - Stroke check performed with expected N/A


results
- No abnormal deviation observed between
governor command and valve feedback

3. Governor controller No alarm/faults at controller N/A


- check all controller IOs are OK
- all communications are OK

4. Overspeed Protection
Inspection Item Description Finding (OK/Not OK) Recommendations

1. Speed Probes Speed probes not faulty - no intermittent N/A


spikes or speed fluctuations during running
or stop condition
- specific attention to proximity type speed
probes
2. Overspeed controller No alarm/faults observed at controller N/A

Open
Page 2 of 6
Inspection Item Description Finding (OK/Not OK) Recommendations
3. Protech GII module Configuration is as per Vendor datasheet N/A
configuration

4. OSTT Overspeed test completed successfully N/A

5. Anti Surge Controller


Inspection Item Description Finding (OK/Not OK) Recommendations

1. Anti-surge control field - Reading is normal with respect to ambient N/A


instruments conditions
- For instrument connected to PRM, no
alarms shown in PRM

2. Anti-surge controller - No alarm/faults observed at controller N/A


- Controller in AUTO mode

3. Anti-surge valve Stroke check performed with expected N/A


results

4. Surge test Surge test has been completed successfully N/A


and resulting surge line configured

6. General
Inspection Item Description Finding (OK/Not OK) Recommendations

1. Common alarm No common alarms other than those due to OK


auxiliaries not running
2. Logic forcing No logic forcing/bypass in ESD, DCS and OK
antisurge controller
3. Punch List Any pending critical issues captured by UPT OK
during MRT/start-up

Open
Page 3 of 6
Open
Page 4 of 6
Open
Page 5 of 6
Open
Page 6 of 6