#k ffiwffi& On-Site Test

#%xwww Protocols for Commissioning

Gas density relay


Measuri ng instrument type:..__-....... tr DILO SK 509
tr
I nventory no. :_.-._.."..-".. H437022664
SF6 pressure (measured actual value): see table 1

SFo filling pressure (default value) see appendix B

Table 1: SF6 pressures


SFs- filling pressures
Contact / Tu Default Actual
Bay Gas density relay Remarks
signal level at ambient temperature
oc kPa (100 kPa = 1 bar)

=C30 GO 't 1-13 20 620 633 s/N 602495408


21-23 20 600 614
31-33 20 600 615
G2 11-13 20 540 550 s/N 606806401
21-23 20 520 532
G3 11-13 20 540 550 s/N 606806402
21-23 20 520 531

G4 1 1-13 20 540 551 s/N 606806{86


21-23 20 520 534
G6 1 't -13 20 620 632 s/N 602495404
21-23 20 600 614

=C31 GO 1 1-13 20 620 635 s/N 602495459


21-23 20 600 617
31-33 20 600 615
G1 11-13 20 540 549 s/N 606806418
21-23 20 520 529
G2 11-13 20 540 550 s/N 606806-1 16
21-23 20 524 532
G4 11-13 20 540 552 s/N 606806414
21-23 20 520 532
Tu = Ambient temperature (indoor design), temperature of housing (outdoor design)

Note The pressure levels as well as the formula for calculation of the required pressure can
be found in appendix B.

Tested: Mourad REMILI Approved: KM/WSP: qpd-^p


10.a6.2017

Date, Consultant
-Tls*o'nws
1HDG518680Nen 15 / 338