Beruflich Dokumente
Kultur Dokumente
P638/EN M/Bc3
Technical Manual
P638/EN M/Da2
Technical Manual
! Warning
When electrical equipment is in operation, dangerous voltage will be present in certain parts of the
equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the device must be isolated. Where stranded conductors
are used, wire end ferrules must be employed.
Proper and safe operation of this device depends on appropriate shipping and handling, proper
storage, installation and commissioning, and on careful operation, maintenance, and servicing.
For this reason only qualified personnel may work on or operate this device.
Any modifications to this device must be in accordance with the manual. If any other modification
is made without the express permission of Schneider Electric, it will invalidate the warranty, and
may render the product unsafe.
Qualified Personnel
are individuals who
are familiar with the installation, commissioning and operation of the device and of the system to which it is being
connected;
are able to perform switching operations in accordance with safety engineering standards and are authorized to
energize and de-energize equipment and to isolate, ground, and label it;
are trained in the care and use of safety apparatus in accordance with safety engineering standards;
are trained in emergency procedures (first aid).
Note:
The operating manual for this device gives instructions for its installation, commissioning, and operation.
However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In
the event of questions or specific problems, do not take any action without proper authorization. Contact the
appropriate Schneider Electric technical sales office and request the necessary information.
Any agreements, commitments, and legal relationships and any obligations on the part of Schneider Electric,
including settlement of warranties, result solely from the applicable purchase contract, which is not affected by the
contents of the operating manual.
Modifications After Going to Press
Contents
3 Operation 3-1
3.1 Modular Structure 3-1
3.2 Operator-Machine Communication 3-3
3.3 Configuration of the Measured (Function Group HMI) 3-4
Value Panels
3.4 Serial interfaces 3-7
3.4.1 PC Link (Function Group PC) 3-7
3.4.2 Rear Port Communications (Function Group COMM1) 3-9
Interface 1
3.4.3 Rear Port Communications (Function Group COMM2) 3-18
Interface 2
3.4.4 Communication interface (Function Groups IEC, 3-21
IEC 61850 GOOSE and GSSE)
3.4.4.1 Communication interface (Function Group IEC) 3-21
IEC 61850
3.4.4.2 Generic Object Oriented (Function Group GOOSE) 3-23
Substation Event
3.4.4.3 Generic Substation State Event (Function Group GSSE) 3-25
3.5 IRIG-B Clock Synchronization (Function Group IRIGB) 3-27
3.6 Configurable Function Keys (Function Group F_KEY) 3-28
3.7 Configuration and Operating Mode (Function Group INP) 3-30
of the Binary Inputs
3.8 Measured Data Input (Function Group RTDmA) 3-32
3.8.1 Direct Current Input 3-33
3.8.2 Input for Connection of a 3-37
Resistance Thermometer
3.9 Configuration, Operating Mode, (Function Group OUTP) 3-38
and Blocking of the Output Relays
3.10 Analog Output Channel (Function Group mA_OP) 3-41
3.10.1 BCD Measured Data Output 3-44
3.10.2 Analog Measured Data Output 3-46
3.10.3 Output of ‘External’ Measured 3-50
Data
3.11 Configuration and Operating Mode (Function Group LED) 3-51
of the LED Indicators
4 Design 4-1
4.1 Designs (Case Types) 4-1
4.2 Dimensional Drawings 4-3
4.2.1 Surface-Mounted Case 4-3
4.2.2 Flush-Mounted Case 4-4
4.3 Modules 4-6
7 Settings 7-1
7.1 Parameters 7-1
7.1.1 Device Identification 7-1
7.1.2 Configuration Settings 7-6
7.1.3 Function Settings 7-51
7.1.3.1 Global 7-51
7.1.3.2 General Functions 7-56
7.1.3.3 Setting Groups 7-67
9 Commissioning 9-1
9.1 Introduction 9-1
9.2 Product Familiarisation 9-1
9.3 Equipment Required for Commissioning 9-2
9.4 Product Checks 9-3
9.5 Setting Checks 9-9
9.6 On-Load Checks 9-13
9.7 Final Checks 9-14
9.8 P638 Commissioning Test Record 9-15
9.9 “As-Fitted” Settings Record 9-23
10 Troubleshooting 10-1
11 Maintenance 11-1
12 Storage 12-1
Appendix AN-1
Contents AN-2
A Glossary A-1
B List of Signals B-1
C Overview of Changes C-1
TERMINOLOGY NOTE:
The P638 menu texts ("Data Model") referred to throughout this manual are regional texts which have been
customised for the UK market. Most diagrams contained in this manual use the same terminology. Some
diagrams however contain standard English menu texts when those were very similar to the "regional" ones
and modifying those diagrams was not deemed essential to comprehension. In those diagrams, references
are made to "Parameter Set(s)": This is the direct equivalent to the regional term "Setting Group(s)".
Similarly, the terms "PSx", "PS1", "PS2", "PS3" and "PS4" are respectively equivalent to "SGx", "SG1",
"SG2", "SG3" and "SG4".
The P638 differential protection device is designed for fast and selective short circuit
protection, ground fault protection, and overload protection of transformers in railway
applications (two-winding arrangement) in railway substations.
The selection of protection functions has been optimised for transformer protection in a
wide range of substations, and at the same time they offer back-up protection for both
incoming and outgoing feeders.
DIF_a, DIF_b Transverse differential protection high and low voltage side
Undervoltage enable
Residual current 1
Voltage 1
By means of a straightforward configuration procedure, the user can adapt the device
flexibly to the scope of protection required in each particular application. The unit’s
powerful programmable logic also makes it possible to accommodate special
applications.
Functions
General Functions
The functions listed in the table above are complete function groups, which may be
individually configured or cancelled (except for ILOCK), depending on the application
(e.g. included in or excluded from the protection device’s configuration).
Unused or de-configured function groups are hidden to the user (except for the
configuration setting), thus simplifying the menu. (An exception is the function MAIN,
which is always visible.) Communication functions and measured value functions may
also be configured or excluded.
This concept provides a large choice of functions and makes wide-ranging application of
the protection device possible, with just one model version. On the other hand simple
and clear settings and adaptations to each protection scheme (and optional control
purposes) can be made.
Global functions
In addition to the features listed above, the P638 differential protection device provides
comprehensive self-monitoring as well as the following global functions:
Design
The P638 protection device is modular in design. The plug-in modules are housed in a
robust aluminium case and electrically interconnected via one analogue module and one
digital module.
The nominal voltage range of the optical coupler inputs is 24 to 250 V DC. The auxiliary
voltage input for the power supply is also designed for an extended range. The nominal
voltage ranges are 48 to 250 V DC and 100 to 230 V AC. There is also a model
available for the lower nominal voltage range of 24 to 36 V DC.
All output relays can be utilized for signalling and command purposes.
The optional PT 100 measuring input is lead-compensated, balanced and linearized for
PT-100 resistance thermometers as per IEC 751.
Two selectable measured variables (cyclically updated measured operating data and
stored measured event data) can be output as a burden-independent direct current via
the two optional 0 to 20 mA outputs. The characteristics are defined via 3 adjustable
interpolation points allowing a minimum output current (4 mA, for example) for slave-side
open-circuit monitoring, knee-point definition for fine scaling, and a limitation to lower
nominal currents (10 mA, for example). Where sufficient output relays are available,
a selectable measured variable can be output in BCD-coded form by contacts.
Interfaces
Local control and display:
Information is exchanged through the local control panel, the PC interface, or the
optional rear communication interfaces. One of the communications interfaces is
designed to conform either to international standard IEC 60870-5-103 or to
IEC 60870-5-101, MODBUS, or DNP 3.0 for integration into a substation control system.
The second communications interface is designed to conform to international standard
IEC 60870-5-103 and intended for remote access, typically by a MODEM link and
MiCOM S1 setting software.
Function keys
With cases 40T and 84T there are six function keys available that offer user-definable
functional assignment. These may be used for easy control operation access.
Information interfaces
Information is exchanged through the user interface (HMI), the PC interface, or two
optional communication interfaces (channel 1 and channel 2).
Using one of the two available communication interfaces (communication protocols per
IEC 870-5-103, IEC 60870-5-101, DNP 3, MODBUS or Courier) the numerical protection
device can be wired either to the substation control system or a telecontrol system.
2 Technical Data
2.1 Conformity
Notice
Applicable to P638, version -302-403/404-610
Declaration of conformity
(As per Article 10 of EC Directive 72/73/EC.) The product designated
Easergy MiCOM P638 Transformer Differential Protection for Railway Applications
has been designed and manufactured in conformance with the European standards
EN 60255-6 and EN 60010-1 and with the ‘EMC Directive’ and the ‘Low Voltage
Directive’ issued by the Council of the European Community.
Installation Position
Vertical ± 30°.
Enclosure Protection
Per DIN VDE 0470 and EN 60529 or IEC 529.
IP 52; IP 20 for rear connection space with flush-mounted case.
Weight
84 TE case: approx. 11 kg
Terminals
PC interface (X6):
EIA RS232 (DIN 41652) connector, type D-Sub, 9-pin.
2.3 Tests
Type tests
All tests per EN 50255-6 or IEC 255-6.
Electromagnetic
compatibility (EMC)
Interference Suppression
Per EN 55022§ or IEC CISPR 22, Class A.
Mechanical robustness 1
Valid for the following case variants:
Flush mounted case, flush-mounting method 1 (without angle brackets and frame)
Vibration Test
Per EN 60255-21-1§ or IEC 255-21-1, test severity class 1.
Frequency range in operation: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g
Frequency range during transport: 10 to 150 Hz, 1 g
Seismic Test
Per EN 60255-21-3 or IEC 60255-21-3, test procedure A, class 1
Frequency range:
5 to 8 Hz, 3.5 mm / 1.5 mm, 8 to 35 Hz, 10 / 5 m/s2, 3 x 1 cycle.
Mechanical robustness 2
Valid for the following case variants:
Flush mounted case, flush-mounting method 2 (with angle brackets and frame)
Surface-mounted case
Vibration Test
Per EN 60255-21-1§ or IEC 255-21-1, test severity class 2.
Frequency range in operation: 10 to 60 Hz, 0.075 mm and 60 to 150 Hz, 1.0 g
Frequency range during transport: 10 to 150 Hz, 2 g
Seismic Test
Per EN 60255-21-3 or IEC 60255-21-3, test procedure A, class 2
Frequency range:
5 to 8 Hz, 3.5 mm / 7.5 mm, 8 to 35 Hz, 20 / 10 m/s2, 3 x 1 cycle.
Voltage Test
Per IEC 255-5.
2.5 kV AC, 1 s.
Direct voltage (2.8 kV DC) must be used for the voltage test of the power supply inputs.
The PC interface must not be subjected to the voltage test.
Environment
Temperatures
Recommended temperature range: -5°C to +55°C (23°F to 131°F)
Storage and transit: -25 °C to +70 °C (-13 °F to +158 °F)
Humidity
75 % relative humidity (annual mean),
56 days at 95 % relative humidity and 40°C, condensation not permissible.
Solar Radiation
Direct solar radiation on the front of the device must be avoided.
Measuring inputs
Current
Nominal current In: 1 and 5 A AC (adjustable)
Nominal burden per phase: < 0.1 VA at In
Load rating:
continuous: 4 In (20 A)
for 10 s: 30 In (150 A)
for 1 s: 100 In (500 A)
Nominal surge current: 250 In
Voltage
Nominal voltage Vn: 50 to 130 V AC (settable)
Nominal burden per phase: < 0.3 VA at Vn = 130 V AC
Load rating: continuous 150 V AC
Frequency
Nominal frequency fn:
16 2/3 Hz, 25 Hz, 50 Hz and 60 Hz (adjustable)
Operating range: 0.95 to 1.05 fn
Special variant:
Vin > Switching threshold: VA 5 mA ± 30 %.
Notes
The standard version of binary signal inputs (opto-couplers) is recommended in most
applications, as these inputs operate with any voltage from 19 V. Special versions with
higher pick-up/drop-off thresholds are provided for applications where a higher switching
threshold is expressly required.
The maximum voltage permitted for all binary signal inputs is 300V DC.
Resistance thermometer
Resistance thermometer: only PT 100 permitted,
Mapping curve as per IEC 751.§
Value range: -40,0 ... +215.0 °C
3-wire configuration: max. 20 per conductor.
Open and short-circuited input permitted.
Open-circuit monitoring: > +215 °C und < -40 °C
Output relays
Binary I/O module X (4H):
with heavy duty contacts, use only for direct voltage/current
Rated voltage: 250 V DC
Continuous current: 10 A
Short-duration current: 250 A for 30 ms,
30 A for 3 s
Making capacity: 30 A
Breaking capacity: 7500 W (resistive load) or 30 A at 250 V DC,
Maximum values: 30 A and 300 V DC
2500 W inductive(L/R 40 ms) or 10 A at 250 V DC,
Maximum values: 10 A and 300 V DC
2.6 Interfaces
PC interface
Transmission rate: 300 to 115,200 baud (adjustable)
Communication interfaces
Communication module A can have two communication channels – depending on the
version.
Channel 1 is designed for twisted pair connection or fiber optic connection, whereas
Channel 2 is intended for twisted pair connection only.
For one channel, interface protocols based on IEC 60870-5-103, IEC 870-5-101,
MODBUS, or DNP 3.0 can be set. The second channel can only be operated using the
interface protocol based on IEC 60870-5-103, as compatible with MiCOM S1.
Wire Leads
Per RS 485 or RS 422, 2 kV isolation
Distance to be bridged:
Point-to-point connection: max. 1200 m
Multipoint connection: max. 100 m
1)
Distance to be bridged given for identical optical outputs and inputs at both ends, a
system reserve of 3 dB, and typical fiber attenuation.
IEC Communication
interface
Wire Leads
IEC 61850-compliant, Ethernet-based communications:
Transmission rate: 10 or 100 Mbit/s
RJ45, 1.5 kV isolation
Maximum distance: 100 m
1) 1)
Distance to be bridged given for identical optical outputs and inputs at both ends, a
system reserve of 3 dB, and typical fiber attenuation.
2-10 P638/EN M/Ca2 // AFSV.12.10182 D /// P638-302-403/404-610
2 Technical Data
(continued)
2.8 Settings
Differential protection
Minimum tripping time:
without inrush stabilization: approx. 0.5 periods
with inrush stabilization: approx. 1.3 periods,
Resetting ratio: 0.95
Time-voltage protection
Shortest tripping time:
V<, V<<: approx. 0.8 periods
V>, V>>: approx. 0.8 periods,
Starting reset time: approx. 1.5 periods,
Starting and measurement resetting ratio (hysteresis):
adjustable from 1 to 10%
2.9 Deviations
Definitions
‘Reference Conditions’
Sinusoidal signals at nominal frequency fn, total harmonic distortion 2 %, ambient
temperature 20°C (68°F), and nominal auxiliary voltage VA,n
‘Deviation’
Deviation relative to the setting under reference conditions.
Inrush Stabilization
(Harmonic Restraint)
Deviation: ± 5 %
Differential protection,
Transverse differential
protection
Differential measuring system
for Id = 0.2 Iref: ± 5 %
Harmonic restraint: ± 10 %
Over-/undervoltage
protection
Operate Values: ± 3 % (in the range 0.6 to 1.4 Vn)
Over-/underfrequency
protection
Operate values f<>: ± 40 mHz
Operate values df/dt: ± 0.1 Hz/s
Thermal overload
protection
Operate values : ± 5 %
PT100 resistance
thermometer
Deviation: ± 2 ° or ± 1 %
20 mA analog measured
data output
Deviation: ± 1 %
Output residual ripple with max. load: ± 1 %
Definitions
‘Reference Conditions’
Sinusoidal signals at nominal frequency fn, total harmonic distortion 2 %, ambient
temperature 20°C (68°F), and nominal auxiliary voltage VA,n.
‘Deviation’
Deviation relative to the setting under reference conditions.
Definite-time stages
Deviation 1 % + 20 ms to 40 ms
Inverse-time stages
Deviation where I 2 Iref: ± 5 % + 10 to 25 ms
For IEC characteristic ‘extremely inverse’ and for thermal overload
characteristics: ± 7.5 % + 10 to 20 ms
Definitions
Reference Conditions
Sinusoidal signals at nominal frequency fn, total harmonic distortion 2 %, ambient
temperature 20°C (68°F), and nominal auxiliary voltage VA,n.
Deviation
Deviation relative to the setting under reference conditions.
Operating Data
Measurement
Measuring Input Currents
Deviation: ± 1 %
Frequency
Deviation: ± 10 mHz
Temperature
Deviation: ± 2 °C
Internal clock
With free running internal clock:
Deviation: < 1 min/month
Overload memory
Number: The 8 most recent overload events
Scope: All signals relevant for an overload event from a total of 1024 different logic
state signals
Depth: 200 entries per overload event
Fault memory
Number: The 8 most recent fault events
Scope: Signals:
All fault-relevant signals from a total of 1024 different logic state signals
Fault values:
Sampled values for all measured currents and voltages
Depth: Signals:
200 entries per fault
Fault values:
max. number of cycles per fault can be set by user; storage capacity with a
total of 32 s is available for all faults, i.e.
2
533 cycles for fn = 16 /3 Hz
800 cycles for fn = 25 Hz
1600 cycles for fn = 50 Hz
1920 cycles for fn = 60 Hz
Currents
Dynamic range: 25 In
Amplitude resolution: 2.0 mA r.m.s. for In = 1 A
10.1 mA r.m.s. for In = 5 A
Voltages
Dynamic range: 150 V AC
Amplitude resolution: 9.2 mV r.m.s.
The following equation is used to calculate the specifications of a current transformer for
the offset maximum primary current:
Vsat Rn R i n In R op R i k I'1, max
with:
Vsat: saturation voltage (IEC knee point)
I'1,max: non-offset maximum primary current, converted to the secondary side
In: rated secondary current
n: rated overcurrent factor
k: over-dimensioning factor
Rn: rated burden
Rop actual connected operating burden
Ri internal burden
The specifications of a current transformer can then be calculated for the minimum
required saturation voltage Vsat as follows:
with:
Pn = Rn In²
Pop = Rop In²
Pi = Ri In²
Theoretically, the specifications of the current transformer could be calculated for lack of
saturation by inserting instead of the required over-dimensioning factor k its maximum
value:
k max 1 T1
with:
: system angular frequency
T1: system time constant
For the maximum fault current with an internal fault, static saturation up to a maximum
saturation factor ‘fS’ of 4 is permissible. This corresponds to an overdimensioning
factor ‘k’ of 0.25.
Current transformers should observe the error limit values for class 5P.
3 Operation
The P638, a numerical device, is part of the Easergy MiCOM 30 family of products.
The device types included in this family are built from identical uniform hardware
modules. Figure 3-1 shows the basic hardware structure of the P638.
The external analog and binary quantities - electrically isolated - are converted to the
internal processing levels by the peripheral modules T, Y and X. Commands and signals
generated by the device internally are transmitted to external destinations via floating
contacts through the binary I/O modules X. The external auxiliary voltage is applied to
the power supply module V, which supplies the auxiliary voltages that are required
internally.
Analog data are transferred from the transformer module T via the analog bus module B
to the processor module P. The processor module contains all the elements necessary
for the conversion of measured analog variables, including multiplexers and
analog/digital converters. The analog data conditioned by the analog I/O module Y is
transferred to the processor module P via the digital bus module. Binary signals are fed
to the processor module by the binary I/O modules X via the digital bus module. The
processor handles the processing of digitized analog variables and of binary signals,
generates the protective trip and signals, and transfers them to the binary I/O modules X
via the digital bus module. The processor module also handles overall device
communication. As an option, communication module A can be mounted on the
processor module to provide serial communication with substation control systems.
The control and display elements of the integrated user interface (HMI) and the
integrated PC interface are housed on control module L.
The following interfaces are available for the exchange of information between the user
and the device:
All settings and signals as well as all measurements and control functions are arranged
within the branches of the menu tree following a scheme that is uniform throughout the
device family. The main branches are:
‘Settings’ branch
All settings are contained in this branch. This branch carries all settings, including the
device identification data, the configuration parameters for adapting the device's
interfaces to the system, and the function parameters for adapting the device functions
to the process. All values in this group are stored in non-volatile memory, which means
that the values will be preserved even if the power supply fails.
‘Measurement + Tests’
branch
This branch carries all information relevant for operation such as measured operating
data and binary signal states. This information is updated periodically and consequently
is not stored. In addition, various controls are grouped here, for example those for
resetting counters, memories and displays.
Settings and signals are displayed either in plain text or as addresses, in accordance
with the user’s choice. The P638's settings and signals are listed in tabular format in
chapters 7, 8 and 10.
The configuration of the user interface (HMI) also permits the installation of Measured
Value 'Panels’ on the LCD display. Different Panels are automatically displayed for
specific system operating conditions. Priority increases from normal operation to
operation under overload conditions to operation during a ground fault to operation
following a short circuit in the system. Thus the P638 provides the measured data
relevant for the prevailing conditions.
The P638 offers Measured Value Panels, which display the measured values relevant at
a given time.
During normal power system operation, the Operation Panel is displayed. As an event
occurs, the display switches to the appropriate Event Panel - provided that measured
values have been selected for the Event Panels. In the event of overload event, the
display will automatically switch to the Operation Panel at the end of the event.
In the event of a fault, the Fault Panel remains active until the LED indicators or the fault
memories are reset.
Operation Panel
The Operation Panel is displayed after the set return time has elapsed, provided that at
least one measured value has been configured.
The user can select which of the measured operating values will be displayed on the
Operation Panel by means of an ‘m out of n’ parameter. If more measured values are
selected for display than the HMI display can accommodate, then the display will switch
to the next set of values at intervals defined by the setting at H M I : P a n e l H o l d -
T i m e or when the appropriate key on the user interface (HMI) is pressed.
LOC: Fct.
Operation Panel
[ 053 007 ]
FT_RC: Record.
in progress
[ 035 000 ]
S1 1 ≥1 C
R1
OL_RC: Record.
in progress ≥1
[ 035 003 ] Operation Panel
GF_RC: Record.
in progress
[ 035 005 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1
MAIN: General
reset EXT
[ 005 255 ]
FT_RC: Reset
record. USER
[ 003 006 ]
1: execute
FT_RC: Reset
record. EXT
[ 005 243 ]
MAIN: Reset LED
306 020
50Z01CXA_EN
Fault panel
The Fault Panel is displayed in place of another data panel when there is a fault,
provided that at least one measured value has been configured. The Fault Panel
remains on display until the LED indicators or the fault memories are reset.
The user can select the measured fault values that will be displayed on the Fault Panel
by setting a 'm out of n' parameter. If more measured values are selected for display
than the HMI display can accommodate, then the display will switch to the next set of
values at intervals defined by the setting at H M I : P a n e l H o l d - T i m e or when the
appropriate key on the user interface (HMI) is pressed.
Selected meas.values
LOC: Hold-time
for Panels
[ 031 075 ]
R
MAIN: General
reset USER
[ 003 002 ]
Fault Panel
1: execute ≥1
MAIN: General
reset EXT
[ 005 255 ]
FT_RC: Reset
record. USER
[ 003 006 ]
1: execute
FT_RC: Reset
record. EXT
[ 005 243 ]
MAIN: Reset LED
306 020
50Z01EJA_EN
Overload Panel
The Overload Panel is automatically displayed in place of another data panel when there
is an overload, provided that at least one measured value has been configured.
The Overload Panel remains on display until the overload event ends, unless a fault
occurs. In this case the display switches to the Fault Panel.
The user can select the measured values that will be displayed on the Overload Panel
by setting a 'm out of n' parameter. If more measured values are selected for display
than the HMI display can accommodate, then the display will switch to the next set of
values at intervals defined by the setting at H M I : P a n e l H o l d - T i m e or when the
appropriate key on the user interface (HMI) is pressed.
LOC: Fct.
Overload Panel
[ 053 005 ]
50Z0140 A_EN
The figure in section 'Configurable Function Keys (Function Group F_KEY)' shows the
operation with function key F1 as an example. Function key F1 is only enabled after the
associated password, as defined at F _ K E Y : P a s s w o r d F u n c t . K e y 1 , has been
entered. After the password has been entered the function key will remain active for the
time period set at F _ K E Y : F c n K e y R e t u r n T i m e . Thereafter, the function key
is disabled until the password is entered again. The same is valid for function keys F2 to
F6.
Further information on function keys and their application can be found in Chapter 3,
section 'Configurable Function Keys (Function Group F_KEY)' and section 'Resetting
Actions' as well as in Chapter 8, section 'Configurable Function Keys F1 to Fx (general)'.
Note: Each of the 6 keys has an LED indicator situated next to it which is freely
configurable, such as the other12 LED indicators, but independent of the configuration of
the function keys (i.e. the function assignment is for red and green light emission).
Configuration of the
READ key
Similar to the setting at H M I : F c t . M e n u J m p L i s t x up to 16 functions may also
be selected from the same menu jump list at H M I : F c t . R e a d K e y . They are
triggered in sequence by repeated pressing of the READ key.
Configuration of the
CLEAR C key
Similar to the setting at M A I N : F c t . A s s i g n . R e s e t x up to 10 reset functions may
be selected from a list at H M I : F c t . R e s e t K e y . These are carried out by pressing
the CLEAR C key.
The P638 has a front port PC link as standard. Optionally the communication module A
providing two communication channels is available. Communication between the P638
and SCADA is through the communication module A. Setting and interrogation is
possible through all P638 interfaces.
Two rear port communications interfaces may be fitted. The settings of rear port
communications interface 1 (COMM1) may be assigned to the physical communications
channels 1 or 2 (see function group "MAIN"). If the COMM1 settings have been
assigned to communications channel 2, then the settings of communications interface 2
(COMM2) will automatically be active for communications channel 1. Communication
channel 2 can only be used to transmit data to and from the P638 if its PC link has been
de-activated. As soon as the PC link is used to transmit data, communication channel 2
becomes "dead".
If tests are run on the P638, the user is advised to activate the test mode. In this way the
PC or the control system will recognize all incoming test signals accordingly (see
function group "MAIN").
Communication between the device and a PC is done through the PC link. In order for
data transfer between the P638 and the PC to function, several settings must be made in
the P638.
There is an operating program available as an accessory for control of the P638 (see
Chapter 13).
PC: Manufacturer
[ 003 183 ]
PC: Select.
Spontan.Sig.
[ 003 189 ]
PC: Sig/Meas.
Val.Block PC: Transm Enab
[ 003 086 ] Cycl Dat
[ 003 084 ]
0
Cycl. Data ILS Tel.
1 [ 003 185 ]
0: No
PC: Delta
1: Yes Meas.v.ILS Tel
[ 003 155 ]
PC: Delta t
MAIN: Prot. Ext.
Disabled [ 003 058 ]
[ 038 046 ]
PC: Time-Out
[ 003 188 ]
PC: Command
Blocking
[ 003 182 ] C
0
1 C
0: No
1: Yes
PC Interface
68Z60ECA_UK
Several interface protocols are available at the rear port communications interface 1.
The following user-selected interface protocols are available for use with the P638:
In order for data transfer to function properly, several settings must be made in the P638.
The rear port communications interface can be blocked through a binary signal input.
In addition, a signal or measured-data block can also be imposed through a binary signal
input.
COMM1: Command
Blocking C
[ 003 174 ]
0
1
COMM1: Sig/Meas.
0: No Val.Block
1: Yes [ 037 075 ]
COMM1: Sig/meas.
Block EXT
[ 037 074 ]
68Z60FFA_UK
3-7 Rear port communications interface 1, settings for the IEC 60870-5-103 interface protocol
0 Communication
interface
1
0: No COMM1: Sig/Meas.
Val.Block
1: Yes [ 037 075 ]
COMM1: Sig/meas.
Block EXT
[ 037 074 ]
3-8 Rear port communications interface 1, settings for the IEC 870-5-101 interface protocol
68Z60FHA_UK
3-9 Rear port communications interface 1, settings for the ILS_C interface protocol
3-10 Rear port communications interface 1, settings for the MODBUS protocol
3-11 Rear port communications interface 1, settings for the DNP 3.0 protocol
3-12 Rear port communications interface 1, settings for the COURIER protocol
Checking spontaneous
signals
For interface protocols based on IEC 60870-5-103, IEC 870-5-101, or ILS_C it is
possible to select a signal for test purposes. The transmission of this signal to the control
station as ‘sig. start‘ or ‘sig. end‘ can then be triggered using setting parameters.
The rear port communications interface 2 supports the interface protocol based on
IEC 60870-5-103.
In order for data transfer to function properly, several settings must be made in the P638.
COMM2: Delta V
68Z60ELA_UK
Checking spontaneous
signals
It is possible to select a signal for test purposes. The transmission of this signal to the
control station as ‘sig. start‘ or ‘sig. end‘ can then be triggered using setting parameters.
The IEC 61850 communication protocol is implemented by these function groups and
the Ethernet module.
Note:
The IEC 61850 Communic. function group is only available as an alternative to function
group COMM1 (hardware ordering option!).
As a further option the P638 now includes an interface protocol according to the Ethernet
based communication standard IEC 61850.
IEC 61850
IEC 61850 was created jointly by users and manufacturers as an international standard.
The main target of IEC 61850 is interoperability of devices. This includes the capability
of two or more intelligent electronic devices (IED), manufactured by the same company
or different companies, to exchange data for combined operation.
Now this new communication standard IEC 61850 has created an open and common
basis for communication from the process control level down to the network control level,
for the exchange of signals, data, measured values and commands.
For a standardized description of all information and services available in a field device a
data model, which lists all visible functions, is created. Such a data model, specifically
created for each device, is used as a basis for an exchange of data between the devices
and all process control installations interested in such information. In order to facilitate
engineering at the process control level a standardized description file of the device,
based on XML, is created with the help of the data model. This file can be imported and
processed further by the relevant configuration program used by the process control
device. This makes possible an automated creation of process variables, substations
and signal images.
The following documentation with the description of the IEC 61850 data model, used
with the P638, is available:
IDC file based on XML in the SCL (Substation Configuration Description Language)
with a description of data, properties and services, available from the device, that are
to be imported into the system configurator.
PICS_MICS_ADL file with the following contents:
PICS (Protocol Implementation Conformance Statement) with an overview of
available services.
MICS (Model Implementation Conformance Statement) with an overview of
available object types.
ADL (Address Assignment List) with an overview of the assignment of parameter
addresses (signals, measuring values, commands, etc.) used by the device with
the device data model as per IEC 61850.
Ethernet Module
The optional Ethernet module provides an RJ45 connection and a fiber optic interface
where an Ethernet network can be connected. The selection which of the two interfaces
is to be used to connect to the Ethernet network is made by setting the parameter
I E C : E t h e r n e t M e d i a . For the optical interface on the Ethernet communications
module the user may either select the ordering option ST connector or SC connector
with 100 Mbit/s and 1300 nm. The RJ45 connector supports 10 Mbit/s and 100 Mbit/s.
The optional Ethernet module additionally provides an RS485 interface for remote
access with the operating program MiCOM S1 (function group COMM2).
Notes: The P638 may only be equipped with the optional Ethernet module as an
alternative to the standard optional communication module. Therefore the
Ethernet based communication protocol IEC 61850 is only available as an
alternative to function group COMM1.
The setting parameters for function groups IEC, GOOSE and GSSE in the device are not
automatically activated. An activation occurs either when the command I E C : E n a b l e
C o n f i g u r a t i o n is executed or automatically when the device is switched online with
MAIN: Enable Configuration.
Client Log-on
Communication in Ethernet no longer occurs in a restrictive master slave system, as is
common with other protocols. Instead server or client functionalities, as defined in the
'Abstract Communication Service Interface' (ACSI, IEC 61870-7-2), are assigned to the
devices. A 'server' is always that device which provides information to other devices.
A client may log-on to this server so as to receive information, for instance 'reports'.
In a network a server can supply any number of clients with spontaneous or cyclic
information.
In its function as server the P638 can supply up to 16 clients with information.
Clock Synchronization
With IEC 61850 clock synchronization occurs via the SNTP protocol, defined as
standard for Ethernet. Here the P638 functions as a SNTP client.
For clock synchronization one can select between the operating modes Broadcast from
SNTP Server or Request from Server. With the first operating mode synchronization
occurs by a broadcast message sent from the SNTP server to all devices in the network,
and in the second operating mode the P638 requests the device specific time signal
during a settable cycle.
Two SNTP servers may be set. In this case, clock synchronization is preferably
performed by the first server. The second server is used only when messages are no
longer received from the first server.
When looking at the source priority for clock synchronization, which is set at the MAIN
function then, by selecting "COMM1", synchronization per IEC 61850 is automatically
active but only if this communication protocol is applied.
Fault Transmission
Transmission of fault files is supported per "File Transfer".
Transmission of "Goose
Messages"
The so-called "Goose Message" is a particular form of data transmission. Whereas
normal server-client-services are transmitted at the MMS and TCP/IP level, the "Goose
Message" is transmitted directly at the Ethernet level with a high transmission priority.
Furthermore these "Goose Messages" can be received by all participants in the
respective sub-network, independent of their server or client function. In IEC 61850
"Goose Messages" are applied for the accelerated transmission of information between
two or more devices. Application fields are, for example, a reverse interlocking, a
transfer trip or a decentralized substation interlock. In future the "Goose Message" will
therefore replace a wired or serial protective interface.
According to IEC 61850 there are two types of "Goose Messages", GSSE and
IEC-GOOSE. The GSSE is used to transmit binary information with a simple
configuration by 'bit pairs', and it is compatible with UCA2. However IEC-GOOSE
enables transmission of all data formats available in the data model, such as binary
information, integer values or even analog measured values. But this will require more
extensive configuration with the help of the data model from the field unit situated on the
opposite side. With IEC-GOOSE the P638 at this time supports sending and receiving of
binary information.
Communication with the
Operating Program
MiCOM S1 via the Ethernet
Interface
Direct access by the operating program MiCOM S1 via the Ethernet interface on the
device may occur through the "tunneling principle". Transmission is carried out by an
Ethernet Standard Protocol, but this is only supported by the associated operating
program MiCOM S1 (specific manufacturer solution). Such transmission is
accomplished over the same hardware for the network, which is used for server-client
communication and "Goose Messages".
Available are all the familiar functions offered by the operating program MiCOM S1 such
as reading/writing of setting parameters or retrieving stored data.
The various settings, measured values and signals for function group IEC are described
in chapters 7 and 8.
The setting parameters for function groups IEC, GOOSE and GSSE in the device are not
automatically activated. An activation occurs either when the command I E C : E n a b l e
C o n f i g u r a t i o n is executed or automatically when the device is switched online with
M A I N : P r o t e c t i o n E n a b l e d . In addition function group IEC must be configured
and enabled.
Sending GOOSE
With GOOSE up to 32 logic binary state signals can be sent. Selection of binary state
signals is made by setting G O O S E : O u t p u t n F c t . A s s i g . (n = 1 to 32).
Assignment of data object indexes to logic state signals is made in the range from 1 to
32 according to the assignment to GOOSE outputs.
GOOSE is automatically sent with each new state change of a configured binary state
signal or an external device. There are numerous send repetitions in fixed ascending
time periods (10 ms, 20 ms, 50 ms, 100 ms, 500 ms, 1000 ms, 2000 ms). If after
2 seconds there is no further state change apparent, GOOSE is then sent cyclically at
2-second intervals.
In order to have unambiguous identification of GOOSE sent, characteristics such as the
Goose ID number, MAC address, application ID and VLAN identifier must be entered
through setting parameters. Further characteristics are the 'Dataset Configuration
Revision' with the fixed value "100" as well as the 'Dataset Reference', which is made up
of the IED name (setting in function group IEC) and the fixed string
"System/LLNO$GooseST".
GOOSE-DataSet: LLN0$GooseST
VLAN Identifier: 0
VLAN Priority: 4
64Z6090B_EN
Receiving GOOSE
With GOOSE up to 16 logic binary state signals and the two-pole contact position signals
from up to 16 external devices can be received. Configuration of the logic state signals
received
(G O O S E : I n p u t n F c t . A s s i g . (n = 1 to 16))
is made on the basis of the selection table of the binary inputs (opto coupler inputs).
Each GOOSE includes time information on the duration of validity of its information.
This corresponds to the double time period to the next GOOSE repetition. If the duration
of validity has elapsed without having received this GSSE again (i.e. because of a
communications fault), the signals received will automatically be set to their respective
default value ( G O O S E : I n p u t n D e f a u l t (n = 1 to 16)).
The various settings, measured values and signals for function group GOOSE are
described in chapters 7 and 8.
The setting parameters for function groups IEC, GOOSE and GSSE in the device are not
automatically activated. An activation occurs either when the command I E C : E n a b l e
c o n f i g u r a t i o n is executed or automatically when the device is switched online with
M A I N : D e v i c e o n - l i n e . In addition the function group IEC must be configured and
enabled.
Sending GSSE
With GSSE up to 32 logic binary state signals can be sent. Selection of binary state
signals is made by setting
G S S E : F c t . A s s i g n m . O u t p . (n = 1 to 32). Each selected state signal is to be
assigned to a bit pair in GSSE (G S S E : O u t p u t n b i t p a i r (n = 1 to 32)), which will
transmit this state signal.
GSSE is automatically sent with each state change of a selected state signal. There will
be multiple send repetitions at ascending time periods. The first send repetition occurs
at the given cycle time set with the parameter G S S E : M i n . c y c l e . The cycles for
the following send repetitions result from a conditional equation with the increment set
with the parameter G S S E : I n c r e m e n t . Should no further state changes occur up to
the time when the maximum cycle time has elapsed (G S S E : M a x . c y c l e ) , then
GSSE will be sent cyclically at intervals as set for the max. cycle time.
In order to have unambiguous identification of a GSSE sent, the IED name is used which
was set in function group IEC.
Receiving GSSE
With GSSE up to 32 logic binary state signals can be received. Configuration of the
logic binary state signals received (G S S E : I n p u t n F c t . A s s i g . , n = 1 to 32) is
made on the basis of the selection table of the binary inputs (opto coupler inputs).
For each state signal to be received, the GSSE message, which will include the required
information, must be selected by setting the IED name (G S S E : I n p u t n I E D
n a m e , n = 1 bis 32) . Selection of information wanted from the selected GSSE will
occur by setting the bit pair (G S S E : I n p u t n B i t P a i r , n = 1 bis 32) .
Each GSSE includes time information on the duration of validity of its information.
This corresponds to the double time period to the next GSSE repetition. If the duration
of validity has elapsed without having received this GSSE again (i.e. because of a
communications fault), the signals received will automatically be set to their respective
default value ( G S S E : I n p u t n D e f a u l t , n = 1 to 32).
The various settings, measured values and signals for function group GOOSE are
described in chapters 7 and 8.
If, for example, a GPS receiver with IRIG-B connection is available, the internal clock of
the P638 can be synchronized to run on GPS time using the optional IRIG-B interface.
It should be noted that the IRIG-B signal holds information on the day only (day of the
current year). Using this information and the year set at the P638, the P638 calculates
the current date (DD.MM.YY).
Ready to synchronize
If the IRIG-B interface is enabled and receiving a signal, the P638 checks the received
signal for plausibility. Implausible signals are rejected by the P638. If the P638 does not
receive a correct signal in the long run, synchronization will not be ready any longer.
The P638 includes six additional function keys that are freely configurable. Function
keys F1 to Fx will only be enabled after the password has been entered at
F_Key: Password Funct.Key x.
Configuration of function
keys with a single function
Each function key may be configured with a single function by selecting a logic state
signal at F _ K E Y : F c t . A s s i g n m . F x (Fx: F1 to F6), but with the exception:
H M I : T r i g . M e n u J m p x E X T (x: 1 or 2). This function is triggered by pressing
the respective function key on the P638.
Configuration of the
function keys with a group
resetting function
Respective binary signal inputs (if previously unavailable) are assigned to all default
reset functions. Instead of a single function each function key may have one of the two
group resetting functions assigned at F _ K E Y : F c t . A s s i g n m . F x (Fx: F1 to F6)
by selecting the listing at M A I N : G r o u p R e s e t x E X T (x: 1 or 2).
By pressing the assigned function key all (up to 10) reset actions selected at
M A I N : F c t . A s s i g n . R e s e t x (x: 1 or 2) are triggered.
Configuration of function
keys with menu jump lists
Instead of a single function each function key may have one of the two menu jump lists
assigned at F _ K E Y : F c t . A s s i g n m . F x (Fx: F1 to F6) by selecting the listing at
H M I : T r i g . M e n u J m p x E X T (x: 1 or 2). The functions of the selected menu
jump list are triggered in sequence by repeated pressing of the assigned function key.
Note: LED indicators including the six positioned directly next to the function keys are
configured independently and in this respect there is no relationship to the respective
function key configuration.
Handling keys
If backlighting for the LC display is switched off it will automatically light up when a
function key or the "READ" key is pressed. The assigned function will only be triggered
when the respective key is pressed a second time. This is also valid for the other keys.
3-18 Configuration and operating mode of function keys. The assigned function is either a single function or a menu jump list.
3.7 Configuration and Operating Mode of the Binary Inputs (Function Group INP)
The P638 has optical coupler inputs for processing binary signals from the system.
The functions that will be activated in the P638 by triggering these binary signal inputs
are defined by the configuration of the binary signal inputs. In order to ensure that
during normal operation the P638 will recognize an input signal, it must persist for at
least 20 ms. With the occurrence of a general starting this time period may have to be
increased to 40 ms under unfavorable conditions.
In this manual, we assume that the required functions (marked 'EXT' in the address
description) have been assigned to binary signal inputs by configuration.
Filter function
An additional filter function may be enabled in order to suppress transient interference
peaks at the logic signal inputs (operating modes Active 'high', filt. or Active 'low', filt.).
With this function enabled a status change at the binary logic input is only signaled when
the input signal remains at a steady signal level during a set number of sampling steps
(sampling step size = period / 20). The number of sampling steps is set at parameter
INP: Filter.
INP: Fct.assignm.
Uxx
[ XXX XXX ]
Function 1 EXT
Function 2 EXT
Function 3 EXT
Function n EXT
2
3
0: active "Low"
1: active "High"
2: active "Low", filt.
3: active "High",filt.
-Uxxx
&
Input signal
&
INP: Control
& U xxx
[ ZZZ ZZZ ]
&
12Z6213 A_EN
The P638 has a measured data input function involving two inputs. Direct current is fed
to the P638 through one of the inputs. The other input is designed for connection of a
resistance thermometer.
The input current IDC is displayed as a measured operating value. The current that is
conditioned for monitoring purposes (IDC,lin) is also displayed as a measured operating
value. In addition, it is monitored by the limit value monitoring function to detect whether
it exceeds or falls below set thresholds (see "Limit Value Monitoring").
When setting the characteristic the user must remember that only a monotone
rising/rising curve sense is allowed (no peak or vee-shapes). If the setting differs, the
signal C H EC K: In va l i d Sc a l i n g ID C will be generated.
IDClin / IDC,nom
1.2
1.1
1
IDClin20
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
IDClin1 0
0 0.1 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.6 IDC/ IDC,nom
IDC1 IDC20
D5Z52KDA
19Z5266A_EN
3-21 Example of the conversion of 4-10 mA input current to 0-20 mA monitored current, IDClin
IDC,lin / IDC,n
0.8
Interpolation points
I DC,lin20 0.7
0.6
IDC,lin4 0.5
0.4
IDC,lin 3 0.3
IDC,lin 2 0.2
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
3-22 Example of a characteristic having five interpolation points (characteristic with zero suppression setting of 0.1 IDC,nom is shown as a broken
line)
Zero suppression
Zero suppression is defined by setting R T D m A: E n a b l e I D C p . u . If the direct
current does not exceed the set threshold, the per-unit input current IDC p.u. and the
current IDClin will be displayed as having a value of ‘0’.
The input current is monitored in order to protect the 20 mA input against overloading.
If it exceeds the set threshold of 24.8 mA, the signal R T D m A: O ve r l o a d 2 0 m A
I n p u t is issued.
Beyond the linearization described above, the user has the option of scaling the
linearized values. Thereby negative values, for example, can be displayed as well and
are available for further processing by protection functions.
This input is designed for connection of a PT 100 resistance thermometer. The mapping
curve R = f(T) of PT 100 resistance thermometers is defined in DIN IEC 751. If the
PT 100 resistance thermometer is connected using the 3-wire method, then no further
calibration is required.
Open-circuit monitoring
If there is an open measuring circuit due to a broken wire, the signal R T D m A: PT 1 0 0
F a u l ty is issued.
The P638 has output relays for the output of binary signals. The binary signal
assignment is freely configured by the user.
OUTP: Outp.rel.
block USER
[ 021 014 ]
0
OUTP: Outp.
1 ≥1 relays blocked
[ 021 015 ]
0: No
OUTP: Block 1: Yes
outp.rel. EXT
[ 040 014 ] ≥1
MAIN: Prot.
ext. disabled
[ 038 046 ]
SFMON: Hardware
fault
304 950
1 ≥1
2
3
4 -K xxx
≥1
5
6
≥1
1: ES updating
2: ES manual reset ≥1
3: ES reset (fault)
4: ES reset (syst.dist)
5: NE updating & ≥1 OUTP: State K xxx
[ zzz zzz ]
6: NE manual reset &
&
& ≥1
OUTP: Fct.
assignm. K xxx & S1 1
[ yyy xxx ]
R1
Signal 1
Signal 2
Signal 3 m out of n
Signal n
≥1 & ≥1
Selected signals
&
FT_RC: Record.
in progress OUTP: Latching
[ 035 000 ] 1 reset
& [ 040 088 ]
FT_RC: System
disturb. runn
[ 035 004 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OUTP: Reset
latch. USER
[ 021 009 ]
0
1 1
100 ms
0: don’t execute
1: execute
OUTP: Reset
latch. EXT
[ 040 015 ]
50Z0141 A_EN
3-26 Configuration, setting the operating mode, and blocking the output relays
Measured values made available by the P638 can be provided in BCD (binary coded
decimal) form through output relays or in analog form as direct current. Output as direct
current can only occur if the device is equipped with analog module Y. BCD-coded
output, however, is possible, regardless of whether the device is equipped with analog
module Y or not.
MEASO: Reset
output USER
[ 037 116 ]
0
1
0: don’t execute
1: execute
MAIN: General
reset USER MEASO: Reset
[ 003 002 ]
meas.val.outp.
1: execute 304 601
MAIN: Reset
indicat. USER
[ 021 010 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
indicat. EXT
[ 065 001 ]
47Z13H6A_EN
The user can select a measured value for output in BCD form by assigning output relays.
The selected measured value is available in BCD-coded form for the duration of the set
hold time m A_ O P: H o l d T i m e O u tp u t BC D . If the selected variable was not
measured, then there is no output of a measured value.
Output of measured
operating values
The selected measured operating value is available for the duration of the set hold time.
After the hold time has elapsed, the current value is saved and the hold time is re-
started. If the hold time has been set to "blocked", the measured operating value that
has been output will be stored until the measured data output function is reset.
Scaling
The resolution for measured data output is defined by setting the scaling factor.
The scaling factor should be selected so that the value 399 is not exceeded by the
maximum measured value to be output. If this should occur or if the measured value is
outside the acceptable measuring range, then the value for "Overflow" (all relays
triggered) is transmitted.
M x ,max
k x ,scal =
scaling factor
where:
Mx,scal: scaled measured value
Mx,max maximum transmitted value for the selected measured value
The user can select two of the measured values available in the P638 for output in the
form of load-independent direct current. Three interpolation points per channel can be
defined for specific adjustments such as adjustment to the scaling of a measuring
instrument. The direct current that is output is displayed as a measured operating value.
The selected measured value is output as direct current for the duration of the set hold
time m A_ O P: H o l d T i m e O u tp u t A- x. If the selected variable was not measured,
then there is no output of a measured value.
Output of measured
operating values
The selected measured operating value is available for the duration of the set hold time.
After the hold time has elapsed, the current value is saved and the hold time is re-
started. If the hold time has been set to "blocked", the measured operating value that
has been output will be stored until the measured data output function is reset.
Configuration of output
relays assigned to the
output channels
The user must keep in mind that direct current output only occurs when the output relays
assigned to the output channels are configured for m A_ O P: Va l u e A- x O u tp u t,
since the output channels would otherwise remain short-circuited (see terminal
connection diagrams).
Scaling
The minimum and maximum values to be transmitted for the selected measured value
and one additional value for the knee point must be scaled to the range limit value of the
measured value. By setting the following parameters the user can obtain an analogue
output characteristic as shown in figure 3-32.
The scaled values that need to be set can be calculated according to the following
formulas:
Formulas Example
Key to the Formulas: Let voltage VAB be selected as the
measured value to be transmitted. Let the
Mx,RL: Range limit of the selected measuring range be 0 to 1.5 Vn.
measured value
When Vn = 100 V, the range limit value in
Mx,min: minimum transmitted value the assumed example is 150 V.
for the selected measured
value Range to be transmitted:
0.02 to 1 Vn = 2 to 100 V
Mx,knee: knee point value transmitted
for the selected measured Knee point:
value 0.1 Vn = 10 V
Mx,knee 10V
Mx,scal,knee = M Mx,scal,knee = 150V = 0.067
x,RL
Mx,max 100V
Mx,scal,max = M Mx,scal,max = 150V = 0.67
x,RL
Ia / mA
20
Max.
output value18
Knee point
16
output value
14
12
10
6
Min.
output value 4
2
0
0 0.02 0.1 1 1.2 1.3 1.4 1.5 Vnom
0,013 0,067 0,667 1,0Mx,scal
D5Z52KFA
19Z5265A_EN
3-32 Example of a characteristic curve for analog output of measured data. In this example the range starting value is = 0; also possible is
directional-signed output (see corresponding example in section BCD Measured Data Output).
Measured data from external devices, which must be scaled to 0 - 100%, can be written
to the following parameters of the P638 using the communications interface.
These "external" measured values are output by the P638 either in BCD data form or as
load-independent direct current, provided that the BCD measured data output function or
the channels of the analog measured data output function are configured accordingly.
The P638 has 23 LED indicators for the indication of binary signals. Four of the LED
indicators are permanently assigned to functions. The other 12 LED indicators are freely
configurable. These freely configurable LEDs will emit either red or green or amber light
(amber is made up of red and green light and may not be configured independently).
H 1 (green) “HEALTHY” Not configurable. H 1 indicates the operational readiness of the device
(supply voltage is present).
H 17 (red) “EDIT MODE” Not configurable. H 17 indicates the input mode. Only when the device
is in this mode, can setting parameters be changed by pressing the “Up“
and “Down“ keys. (See Chapter 6, section 'Display and Keypad')
H 4 (red) “TRIP COMMAND” With the P638 this LED indicator is customarily configured with function
M A I N : G e n T r i p S i g n a l - but the configuration may be modified.
H 4 (green) ---- Function assignment to this green LED indicator is freely configurable.
H 5 to H 16 ---- For each of these LED indicators both colors (red & green) may be
H 18 to H 23 configured freely and independently.
(Note: H10 – H 16 & H 18 – H 23 are not available with case 24T
devices.)
The drawing below shows the layout of the LED indicators situated on the user interface
(HMI).
H4
H3
TRIP
ALARM
F1 H18
H2 OUT OF SERVICE
H1
H17
HEALTHY
EDIT MODE
F2 H19
H5
H6
F3 H20
H7
H8 C
G
H9
H10
G F4 H21
H11
H12
G G F5
G
H13 H22
H14
H15
H16
G F6 H23
12 Z6100B_EN
Therefore the operating modes turn out to be the 23=8 possible combinations of the
following components:
• flashing / continuous,
• energize-on-signal (ES) / normally-energized (NE),
• updating / latching with manual reset,
• energize-on-signal (ES) with reset after new fault (flashing / continuous) and
• energize-on-signal (ES) with reset after new system disturbance (flashing /
continuous),
LED: Operating
mode H xx
[ xxx xxx ]
1
2
3
4
5
6
7
8
9
10
11
-Hxx
12 (red)
1: ES updating ! G !
2: ES manual reset
3: ES reset (fault)
4: ES reset (syst.dist) ≥1
5: NE updating
6: NE manual reset
7: ES updating bl
2: ES manual reset
8: ES manual reset bl
3: ES reset (fault) LED: State H xx
& red
9: ES reset (fault) bl [ zzz zzz ]
10: ES rst (syst.dst) bl &
11: NE updating bl &
12: NE manual reset bl
& S1 1
R1
LED: Fct.assig.
Hxx red
[ yyy yyy ]
Signal 1
Signal 2
Signal 3 m out of n LED: State H xx
Signal n & green
[ zzz zzz ]
&
&
Selected signals
& S1 1
R1
LED: Fct.assig.
Hxx green
[ yyy yyy ]
Signal 1
Signal 2 -Hxx
Signal 3 m out of n (green)
Signal n
&
FT_RC: Record.
in progress
[ 035 000 ] &
FT_RC: System
disturb. runn
[ 035 004 ]
MAIN: General
reset EXT
[ 005 255 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: Reset
LED
306 020
12Z6200 A_EN
The secondary phase currents and the voltage of the system transformers are fed to the
P638 and are, electrically isolated, converted to normalized electronics levels.
The analog quantities are digitized and are thus available for further processing.
Settings that do not refer to nominal quantities are converted by the P638 to nominal
quantities. The user must therefore set the secondary nominal currents and voltages of
the system transformers.
The connection arrangement of the measuring circuits on the P638 must also be set.
Figure 3-35 shows the standard connection. By this setting the phase of the digitised
currents and the voltage is rotated by 180°.
The P638 has an operating data measurement function for the display of currents and
voltages measured as well as quantities derived from these measured values. For the
display of measured values, set lower thresholds need to be exceeded. If these lower
thresholds are not exceeded, the value 'Not measured' is displayed. The following
measured variables are displayed:
The measured data are updated at 1 s intervals. Updating is interrupted if the self-
monitoring function detects a hardware fault.
3-36 Measured operating data for the phase currents, ends a and b
Load Angle
Load angles are only determined, if the associated current and voltage exceed a
minimum threshold.
Frequency
The P638 determines the frequency from the voltage. This voltage needs to exceed a
minimum threshold of 0.65 Vn in order for frequency to be determined.
Cancelling a protection
function
The following conditions must be met before a protection function can be cancelled:
If the above conditions are met, proceed through the Configuration branch of the menu
tree to access the setting relevant for the protection function to be cancelled.
For example, the "LIMIT" function group is cancelled by setting L IM IT : L i m i t
T h r e s h o l d s I < > to 'Disabled'. To re-include the LIMIT function in the device
configuration, the same setting is changed to "Enabled".
Note: If the protection device is disabled using a binary signal input, configured
M AIN : D i s a b l e Pr o te c t. EXT , there will be no
M AIN : Bl o c k e d /F a u l ty signal.
Two multiple blocking conditions may be defined via 'm out of n' settings. The functions
defined by the selection may be blocked using an appropriately configured binary signal
input.
3.12.5 Blocked/Faulty
If the protective functions are blocked, this condition is signaled by a steady light from
yellow LED indicator H 2 on the HMI and also by a signal from the output relay
configured for M AIN : Bl o c k e d /F a u l ty. In addition, the user can select the functions
that will produce the M AIN : Bl o c k e d /F a u l ty signal by setting a ‘m out of n’
parameter. If the "Blocked/Faulty" signal is included in the selection of the output relay
with the assignation "Trip command" a signal with high priority will be generated. The
protection will remain active in this case.
Direction decisions by the definite-time overcurrent protection function (DTOC1) and the
inverse-time overcurrent protection function (IDMT) will issue fault direction signals.
General Start
Starting signals from the differential and transverse differential protection, the phase and
earth fault definite-time overcurrent protection and the inverse-time overcurrent
protection are collectively issued as the "General Start" signal. The number of general
starts is counted.
MAIN: General
Reset USER
[ 003 002 ]
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
68Z6021A_UK
Trip Command
The P638 has the following two channel trip commands available:
Main-Trip command
Re-Trip command
Back-Trip command
The functions to effect a trip can be selected by setting an 'm out of n' parameter
independently for each of the trip commands and each channel. The minimum trip
command time may be set. The trip signals are present only as long as the conditions
for the signal are satisfied.
MAIN: En.Man.Trip
Cmd. EXT
[ 039 053 ]
MAIN: En.Man.
Trip Cmd.USER
[ 003 064 ]
MAIN: Enable
0 Man. Trip Cmd
[ 039 080 ]
1
0: No
1: Yes
MAIN: Man.M-
Trip Cmd1 USER
[ 003 065 ]
0: Don't execute
1: Execute
MAIN: Man.M-Trip
Cmd1 EXT
[ 039 054 ]
MAIN: Man.M-
Trip Cmd2 USER
[ 003 082 ]
0: Don't execute
1: Execute
MAIN: Man.M-Trip
Cmd2 EXT
[ 039 056 ]
MAIN:Man.ReTrip
Cmd1 USER
[ 003 066 ]
0: Don't execute
1: Execute
MAIN: Man.ReTrip
Cmd1 EXT
[ 039 055 ]
MAIN:Man.ReTrip
Cmd2 USER
[ 003 083 ]
0: Don't execute
1: Execute
MAIN: Man.ReTrip
Cmd2 EXT
[ 039 057 ]
MAIN: Man.B-
Trip Cmd1 USER
[ 003 067 ]
0: Don't execute
1: Execute
MAIN: Man.B-Trip
Cmd1 EXT
[ 039 107 ]
MAIN: Man.B-
Trip Cmd2 USER
[ 003 087 ]
0: Don't execute
1: Execute
MAIN: Man.B-Trip
Cmd2 EXT
[ 039 108 ]
68Z6020A_UK
0
1
0: Don't execute
MAIN: General 1: Execute
Reset USER
[ 003 002 ]
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
MAIN: Rst.Co.Cl/
Tr.Cmd EXT
[ 005 210 ]
68Z60A6A_UK
The data stored in the operating data memory, the monitoring signal memory and the
event memories are date- and time-tagged. For correct tagging, the date and time need
to be set at the P638.
Via an appropriately configured binary signal input, the time of different devices may be
synchronized by means of a pulse. The P638 evaluates the rising edge. This will set
the clock to the next full minute, rounding either up or down. If several start/end signals
occur (bouncing of a relay contact), only the last edge is evaluated.
Note: It is not possible to use a signal input on the analog module Y as a minute
pulse input.
Synchronization source
The P638 provides numerous options to synchronize the internal clock:
o Telegram with the time via the communication interface COMM1/IEC (full time)
o Telegram with the time via the communication interface COMM2/PC (full time)
o IRIG-B Signal (IRIGB; time only)
o Minute pulse presented at a binary signal input (MAIN), see figure 3-54 and previous
paragraph
With older device versions these interfaces are of equal priority, i.e. clock
synchronization was carried out regardless of the source. No conflicts have to be taken
into account as long as the synchronization sources (communication master, IRIG-B and
minute impulse signal sources) are at the same time. But if the sources are at different
times, unwanted step changes in the internal clock can occur. On the other hand
redundant time synchronization is often used so as to sustain time synchronization via
IRIG-B interface even if and while the SCADA communication is out of service.
With the current device versions a primary and a backup source for time synchronization
may now be set, where both provide the four options listed in the above.
M A I N : Prim.Source TimeSync
M A I N : BackupSourceTimeSync
With this feature synchronization occurs continuously from the primary source as long as
time synchronization telegrams or minute pulses are received within a time-out period
set at M A I N : T i m e s y n c . t i m e - o u t . The backup source is required if after the set
time-out there is no synchronization through the primary source.
When selecting the time telegram via IEC as the primary source the device will expect
time synchronization telegrams from server SNTP2 after server SNTP 1 has become
defective, before it will switch over to the backup source.
Time synchronization occurs solely from the primary source when the time-out stage is
blocked.
Stored data such as event logs, measured fault data etc, can be cleared in several ways.
The following mechanisms are available:
Automatic resetting of the event signals provided by LED indicators (given that the
LED operating mode has been set accordingly) and of the display of measured event
data on the front panel LCD whenever a new event occurs. In this case only the
displays on the front panel LCD are cleared but not the internal memories such as the
fault memory.
Resetting of LED indicators and measured event data displayed on the front panel
LCD by pressing the "CLEAR" key C located on the front panel. By selecting the
required function at H M I : F c t . R e s e t K e y further memories may be assigned
which will then also be cleared when the "CLEAR" key is pressed.
Selective resetting of a particular memory type (e.g. only the fault memory) via setting
parameters. (For this example: Navigate to menu point
O S C I L : R e s e t R e c o r d . U S E R and set to 'Execute', see also the exact step-
by-step description in Chapter 6 "User Interface (HMI)", section 'Reset'.)
Selective resetting of a particular memory type (e.g. only the fault memory) through
appropriately configured binary signal inputs. (For this example: Assign parameter
O S C I L : R e s e t R e c o r d . E X T to the relevant binary signal input e.g.
I N P : F c t . U 6 0 1 A s s i g n .)
Group resetting by setting parameters, by navigating to menu point
M A I N : G r o u p R e s e t x U S E R and setting it to 'Execute'. For this the relevant
memories (i.e. those to be reset) must be assigned to parameter
MAIN: Fct.Assign. Reset x.
Group resetting through appropriately configured binary signal inputs. (That is assign
parameter M A I N : G r o u p R e s e t . x E X T to the relevant binary signal input,
e.g. I N P : F c t . U 6 0 1 A s s i g n . after memories to be reset have been assigned
to parameter M A I N : F c t . A s s i g n . R e s e t x .)
General resetting by setting parameters (menu point
M A I N : G e n e r a l R e s e t U S E R ). All memories, counters, events etc. are reset
without any special configuration options.
Should several resetting actions have been configured for one particular memory then
they all have equal priority.
In the event of a cold restart, namely simultaneous failure of both internal battery and
substation auxiliary supply, all stored signals and values will be lost.
Further resetting possibilities are basically not distinct resetting actions but make access
especially easy to one of the resetting actions described above i.e. by configuring them
to a function key.
MAIN: General
reset USER
[ 003 002 ]
0
1 1: execute
0: don't execute
1: execute
MAIN: Reset
indicat. USER
[ 021 010 ]
0
1
0: don't execute
1: execute
≥1 MAIN: Reset LED
306 020
MAIN: Reset
indicat. EXT
[ 065 001 ]
12Z6115 A_EN
3-55 General reset, LED reset and measured event data reset from the user interface (HMI)
m out of n
MAIN: Group
reset 1 USER
[ * ]
0
1 ≥1 &
0: don't execute
1: execute
MAIN: Group
reset 1 EXT
[ * ]
MAIN: Fct.assign.
reset 1
[ * ]
m out of n
12Z61RMB_EN
3-56 "CLEAR" key on the user interface (HMI) and, as an example, group resetting of the operating data recording (e.g. as an example for the
reset signal OP_RC: Reset record. EXT); further examples for resetting signals generated in this way are:
- [005 240] MT_RC: Reset Record. EXT
- [005 241] OL_RC: Reset Record. EXT
- [005 243] OSCIL: Reset Record. EXT
- [005 247] CBM_1: Reset Meas.Val. EXT
- [007 111] CBM_2: Reset Meas.Val. EXT
- [005 210] MAIN: Rst.Co.Cl/Tr.Cmd EXT
- [005 255] MAIN: General Reset EXT
- [036 087] mA_OP: Reset Output EXT
- [038 061] THERM: Reset Replica EXT
- [040 015] OUTP: Reset Latch. EXT
- [040 138] MAIN: Reset latch.trip EXT
- [065 001] MAIN: Reset Indicat. EXT
Depending on the design version of the communications module A there are up to two
communications channels available (see "Technical Data"). These physical
communications channels may be assigned to communications interfaces COMM1 and
COMM2.
If tests are run on the P638, the user is advised to activate the test mode so that all
incoming signals via the serial interfaces using protocols according to IEC will be marked
accordingly.
With the P638, four independent setting groups may be pre-set. The user may switch
between setting groups during operation without interrupting the protection function.
If, after the supply voltage is turned on, no logic level of ' 1 ' is present at any of the
binary signal inputs selected for the setting group selection, then the setting group
selected using the function parameter will become active once the stored time has
elapsed. The previous setting group remains active while the stored hold timer stage is
running.
Setting group selection may also occur during a general starting condition.
When subset selection is handled via binary signal inputs, a maximum inherent delay of
approximately 100 ms must be taken into account.
Settings for which only one address is given in the following sections are equally
effective for all four setting groups.
Comprehensive monitoring routines in the P638 ensure that internal faults are detected
and do not lead to maloperations.
Cyclic tests
After start-up has been successfully completed, cyclic self-monitoring tests will be run
during operation. In the event of a positive test result, a specified monitoring signal will
be issued and stored in a non-volatile memory – the monitoring signal memory – along
with the assigned date and time (see also Monitoring Signal Recording).
The self-monitoring function monitors the built-in battery for any drop below the minimum
acceptable voltage level. If the associated monitoring signal is displayed, then the
battery should be replaced within a month, since otherwise there is the danger of data
loss if the supply voltage should fail. Chapter 11 gives further instructions on battery
replacement.
Peripheral fault
By setting a 'm out of n' parameter a peripheral fault can issue an alarm in addition to
self-monitoring signals.
Signalling
The monitoring signals are also signalled via the output relay configured
C H EC K: Al a r m . The output relay operates as long as an internal fault is detected.
Device response
The response of the P638 is dependent on the type of monitoring signal. The following
responses are possible:
Signaling Only
If there is no malfunction associated with the monitoring signal, then only a signal is
issued, and there are no further consequences. This situation exists, for example,
when internal data acquisition memories overflow.
Selective Blocking
If a fault is diagnosed solely in an area that does not affect the protective functions,
then only the affected area is blocked. This would apply, for example, to the
detection of a fault on the communication module or in the area of the PC interface.
Warm Restart
If the self-monitoring function detects a fault that might be eliminated by a system
restart – such as a fault in the hardware –, then a procedure called a warm restart is
automatically initiated. During this procedure, as with any start-up, the computer
system is reset to a defined state. A warm restart is characterized by the fact that no
stored data and, in particular, no setting parameters are affected by the procedure. A
warm restart can also be triggered manually by control action. During a warm restart
sequence the protective functions and the communication through serial interfaces
will be blocked. If the same fault is detected after a warm restart has been triggered
by the self-monitoring system, then the protective functions remain blocked but
communication through the serial interfaces will usually be possible again.
Cold Restart
If a corrupted setting group is diagnosed during the checksum test, which is part of
the self-monitoring procedure, then a cold restart is carried out. This is necessary
because the protection device cannot identify which parameter in the subset is
corrupted. A cold restart causes all internal memories to be reset to a defined state.
This means that all the protection device settings are also erased after a cold restart.
In order to establish a safe initial state, the default values have been selected so that
the protective functions are blocked. Both the monitoring signal that triggered the
cold restart and the value indicating parameter loss are entered in the monitoring
signal memory.
The default for this timer stage is ‘Blocked’ e.g. blocking of the protection device with two
identical faults occurs independent of the time evolved since the first fault monitoring
signal was issued.
The behavior caused by sporadic faults could lead to an unwanted blocking of the device
if the monitoring signal memory has not been reset in the interim, for example, because
the substation is difficult to reach in wintertime or display and clearing of the monitoring
signal memory via the communication interfaces was not enabled. To defuse this
problem it is suggested to set the function parameter to a specific time duration period so
that blocking will only occur if the same fault occurs again within this time period.
Otherwise, the device will continue to operate normally after a warm restart.
MT_RC: Operat.
Data Record.
[ 003 024 ]
Operating Memory
MAIN: Oper.-
relev. 306
signal
024
1
0: Don’t execute
1: Execute
12Z61CMB_UK
3-61 Operating data recording and counter for signals relevant to system operation
The monitoring signals generated by the self-monitoring function are recorded in the
monitoring signal memory. The memory buffer allows for a maximum of 30 entries.
If more than 29 monitoring signals occur without interim memory clearance, the
C H EC K: O ve r fl o w M T _ R C signal is entered as the last entry. Monitoring signals
prompted by a hardware fault in the unit are always entered in the monitoring signal
memory. Monitoring signals prompted by a peripheral fault can be entered into the
monitoring signal memory, if desired. The user can select this option by setting an 'm
out of n' parameter (see 'Self-Monitoring').
If at least one entry is stored in the monitoring signal memory, this fact is signaled by the
yellow LED indicator H 3 (labeled 'ALARM') on the local control panel. Each new entry
causes the LED to flash (on/off/on....).
The monitoring signal memory can only be cleared manually by a control action. Entries
in the monitoring signal memory are not cleared automatically, even if the corresponding
test in a new test cycle now shows the device to be healthy. The contents of the
monitoring signal memory can be read from the local control panel or through the PC or
communication interface. The time and date information assigned to the individual
entries can be read out through the PC or communication interface or from the local
control panel.
SFMON: Hardware
fault
304 950
Select monit.
signal
MT_RC: Reset
record. USER
[ 003 008 ]
CT30 SFMON: Overflow
≥1 MT_RC
[ 090 012 ]
0
MT_RC: No. monit.
1 ≥1 signals
[ 004 019 ]
0: don't execute
1: execute
MT_RC: Reset
record. EXT
[ 005 240 ]
12Z6155A_EN
Overload Duration
In the event of an overload, the P638 determines the overload duration. The overload
duration is defined as the time between the start and end of the OL_ R C : R e c o r d . i n
Pr o g r e s s signal.
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OL_RC: Reset
record. EXT
[ 005 241 ]
OL_RC: Reset
record. USER
[ 100 003 ]
1: execute
50Z0137A_EN
OL_RC: Record.
in progress C
[ 035 003 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1
MAIN: General
reset EXT
[ 005 255 ]
OL_RC: Reset
record. EXT
[ 005 241 ]
OL_RC: Reset
record. USER
[ 100 003 ]
1: execute
12Z6238A_EN
OL_RC: Record. in
Progress
[ 035 003 ]
THERM: Starting
k*Iref>
[ 041 108 ] +
R OL_RC: No.
Overload
[ 004 101 ]
MAIN: General
Reset USER
[ 003 002 ]
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
OL_RC: Reset
Record. EXT
[ 005 241 ]
OL_RC: Reset
Record. USER
[ 100 003 ]
1: Execute
64Z70DXA_UK
Time tagging
The date that is assigned to each overload event by the internal clock is stored.
The overload start or end signals are likewise time-tagged by the internal clock. The
date and time assigned to an overload event when the event begins can be read out
from the overload memory on the local control panel or through the PC and
communication interfaces. The time information (relative to the onset of the overload
event) can be retrieved from the overload memory or through the PC or communication
interfaces.
Overload logging
Protection signals during an overload event are logged in chronological order with
reference to the specific event. A total of eight overload events, each involving a
maximum of 200 start or end signals, can be stored in the non-volatile overload
memories. After eight overload events have been logged, the oldest overload log will be
overwritten, unless memories have been cleared in the interim. If more than 199 start or
end signals have occurred during a single overload event, then OL_ R C : O ve r l . M e m .
O ve r fl o w will be entered as the last signal.
In addition to the signals, the measured overload data will also be entered in the
overload memory.
The overload recordings can be read from the user interface (HMI) or through the PC or
communication interfaces.
OL_RC: Record. C
in progress
[ 035 003 ]
OL_RC: Overload
n
Measured value 1 recording n
0
1 ≥1
MAIN: General
reset USER 0: don't execute
[ 003 002 ] 1: execute
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OL_RC: Reset
record. EXT
[ 005 241 ]
12Z6117 A_EN
When there is a primary system fault, the P638 collects the following measured fault
data:
Running time
Fault duration
Fault currents (short-circuit currents)
Fault voltage (short-circuit voltage)
Differential currents of the two measuring systems
Second harmonic of the differential current
Restraining currents of the two measuring systems
MAIN: General
Reset USER
[ 003 002 ]
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
64Z70DMA_UK
The difference in time between the start of the fault and the fault data acquisition time is
also displayed.
1 2 3 4 5 6 7
DIFF: I0 Filt a
Enab SGx
[ * ]
0
1
0: No
1: Yes
C C2,4
Iam,A,a C1,3
Iam,0,a
Iam,C,a
Iam,A,a-Iam,0,a 1
Iam,C,a-Iam,0,a 3
1 … 2 Is,1,a
DIFF: I0 Filt b
Enab SGx 3 … 4 Is,2,a
[ * ]
0
1
0: No
1: Yes
C C2,4
Iam,A,b C1,3
Iam,0,b
Iam,C,b
Iam,A,b-Iam,0,b 1
Iam,C,b-Iam,0,b 3
1 … 2 Is,1,b
3 … 4 Is,2,b
68Z6034A_UK
Fault currents and voltage are displayed as per-unit quantities referred to In and Vn.
OSCIL: Record. in
Progress
[ 035 000 ]
FT_DA: Save C C
measured values
305 052
FT_DA: Fault
IN Current N p.u.
[ 004 107 ]
R
FT_DA: Fault
IA,b Curr.IA,b p.u.
[ 004 118 ]
R
FT_DA: Fault
IC,b Curr.IC,b p.u.
[ 004 119 ]
R
FT_DA: Fault
V voltage p.u.
[ 004 108 ]
R
MAIN: General
Reset USER
[ 003 002 ]
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
Acquisition of the
differential and restraining
currents
The P638 stores the differential and restraining current data determined at the
acquisition time by the differential protection. Moreover, the component values for the
second harmonic of the differential current are stored.
Differential and restraining currents are stored as per-unit quantities referred to Iref.
OSCIL: Record.
in Progress
[ 035 000 ]
FT_DA: Save C C
measured values
305 052
FT_DA: Diff
DIFF: Id,1 Current 1
303 303
[ 005 082 ]
R
FT_DA: Diff
DIFF: I(2*fn),1 Current 1 (2fn)
303 301
[ 005 084 ]
R
FT_DA: Restrain
DIFF: IR,1 Current 1
303 305 [ 005 083 ]
R
FT_DA: Diff
DIFF: Id,2 Current 2
303 304 [ 006 082 ]
R
FT_DA: Restrain
DIFF: IR,2 Current 2
303 306
[ 006 083 ]
R
MAIN: General
Reset USER
[ 003 002 ]
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
In addition, the user can set a logical "OR" combination of logic signals ('m out of n'
parameter) whose appearance will trigger fault recording.
Fault counting
Faults are counted and identified by sequential numbers.
OSCIL: Trigger
USER
[ 003 041 ]
0
1
0: Don't execute
1: Execute
OSCIL: Fct
Assig. Trigger
[ 003 085 ]
Signal 1
Signal 2
m out of n
Signal 3
Signal n
OSCIL: Record.
in Progress
Selected signals [ 035 000 ]
OSCIL: System
Disturb. Runn
OSCIL: I>, End a [ 035 004 ]
[ 016 014 ]
OSCIL: I>
IA,a Triggered, End a
[ 035 014 ]
IC,a
OSCIL: IN>
[ 016 017 ]
OSCIL: IN>
IN Triggered
[ 035 017 ]
OSCIL: Id>
[ 016 018 ]
OSCIL: Id>
DIFF: Id,1 Triggered
303 303 [ 035 018 ]
DIFF: Id,2
303 304
OSCIL: No. of
MAIN: General + Faults
Reset USER [ 004 020 ]
[ 003 002 ]
1: Execute ≥1 R
MAIN: General
Reset EXT OSCIL: No. System
[ 005 255 ] + Disturb.
OSCIL: Reset [ 004 010 ]
Record. USER R
[ 003 006 ]
1: Execute
OSCIL: Reset
Record. EXT
[ 005 243 ]
68Z6031A_UK
Time tagging
The date that is assigned to each fault by the internal clock is stored. A fault’s individual
start or end signals are likewise time-tagged by the internal clock. The date and time
assigned to a fault when the fault begins can be read out from the fault memory on the
front panel user interface (HMI) or through the PC and communication interfaces.
The time information (relative to the onset of the fault) that is assigned to the signals can
be retrieved from the fault memory or through the PC or communication interfaces.
Fault recordings
Protection signals during a fault, including the signals during the settable pre-fault and
post-fault windows, are logged in chronological order with reference to the specific fault.
A total of eight faults, each involving a maximum of 200 start or end signals, can be
stored in the non-volatile fault memories. After eight faults have been recorded, the
oldest fault recording will be overwritten, unless memories have been cleared in the
interim. If more than 199 start or end signals have occurred during a single fault, then
O SC IL : F a u l t M e m . O ve r fl o w will be entered as the last signal. If the time and
date are changed during the pre-fault time, the signal O S C I L : F a u l t y T i m e T a g
is generated.
In addition to the fault signals, the RMS measured fault data will also be entered in the
fault memory.
The fault recordings can be read from the user interface (HMI) or through the PC or
communication interfaces.
FT_RC: Record. C
in progress
[ 035 000 ]
FT_RC: Fault mem.
Signal 1 + CT200 overflow
1 [ 035 001 ]
Signal 2 1 R
Signal 3 1
Signal n 1
FT_RC: Fault
recording n
1 [ * ]
FT_RC: Pre-fault
time
[ 003 078 ]
FT_RC: Post-
fault time
[ 003 079 ]
n FT_RC: Fault
recording n
Fault memory n
1 003 000
2 033 001
3 033 002
MAIN: General
reset USER &
[ 003 002 ]
1: execute R
MAIN: General
reset EXT
[ 005 255 ]
FT_RC: Reset
record. EXT
[ 005 243 ]
FT_RC: Reset
record. USER
[ 003 006 ]
0
1 1: execute
0: don’t execute
1: execute
12Z6161 B_EN
The signals are recorded before, during and after a fault. The times for recording before
and after the fault can be set. A maximum time period of 32 s - independent of
frequency - is available for recording. This period can be divided among a maximum of
eight faults. The maximum recording time per fault can be set. If a fault, including the
set pre-fault and post-fault times, lasts longer than the set maximum recording time, then
recording will terminate when the set maximum recording time is reached.
The pre-fault time is exactly adhered to if it is shorter than the set maximum recording
time. Otherwise the pre-fault time is set to the maximum recording time minus a
sampling increment, and the post-fault time is set to zero.
If the maximum recording time of 32 s is exceeded, the analog values for the oldest fault
are overwritten, but not the binary values. If more than eight faults have occurred since
the last reset, then all data for the oldest fault are overwritten.
The analog waveform data of the fault record can only be read out through the PC or
communication interfaces.
When the supply voltage is interrupted or after a warm restart, the values of all faults
remain stored.
OSCIL: Trigger
[ 037 076 ] C
OSCIL: Record.
in Progress OSCIL: Max
[ 035 000 ] Record Time
[ 003 075 ]
OSCIL: Pre-Fault
Time
[ 003 078 ]
OSCIL: Post-
Fault Time
[ 003 079 ]
IN
Analog channel 6
R
V Analog channel 7
R
OSCIL: Reset
Record. USER
[ 003 006 ]
1: Execute ≥1
MAIN: General
Reset USER
[ 003 002 ]
1: Execute
MAIN: General
Reset EXT
[ 005 255 ]
OSCIL: Reset
Record. EXT
[ 005 243 ]
68Z6030A_UK
The differential protection functionality provided by the P638 was designed to protect
transformers in a two-phase system. For such an application amplitude matching is
required. This is achieved simply by setting the reference power (generally the nominal
power of the transformer), and the primary and secondary nominal voltages of the
transformer.
Vector group matching is not generally necessary with transformers situated in railway
substations. Should this be required, however, the P638 can be configured in such a
way that the phase of one side of the transformer is rotated by 180°.
For transformers with grounded mid-point tapping, the P638 provides optional zero-
sequence current filtering for both voltage levels.
In the descriptions in the following sections, it is assumed that the current transformers
are connected to the P638 in the standard configuration (see figure "Connecting the
P638 measuring circuits" in section 'Conditioning of the Measured Variables' in
Chapter 3).
It is further assumed that the ‘a’ end refers to the high voltage side of the transformer.
Enabling or disabling
differential protection
You can enable or disable differential protection using setting parameters. Furthermore,
you can do this separately for each setting group. For differential protection to operate,
the matching factors must be within their permissible ranges.
1 2 3 4 5 6 7
DIFF: General
Enable USER
[ 019 080 ]
0
1 DIFF: Enabled
& [ 041 210 ]
0: No
1: Yes
DIFF: Ready
& [ 041 216 ]
DIFF: Enable
SGx DIFF: Not Ready
[ * ] [ 041 217 ]
0
1
0: No
1: Yes
Amplitude matching
In order to set amplitude matching for the protected object, a reference power needs to
be defined. Normally this is the rated power of the transformer. The reference current is
then calculated by the P638 using the set reference power and the set transformer
primary and secondary nominal voltages.
Sref S ref
I ref ,a = I ref , b =
Vn ,a Vn , b
The P638 calculates the matching factors using the reference currents and the set
primary nominal currents of the system transformers.
Calculation of the matching factors:
I n ,a I n ,b
k am,a = k am,b =
I ref ,a I ref ,b
The P638 checks that the matching factors are within the permissible range of
0.5 ≤ k am, x ≤ 5 . In addition the ratios kam,a/kam,b and kam,b/kam,a must not exceed the
value of 3. Should the P638 calculate matching factors which do not satisfy the above
conditions, an alarm will be issued and differential protection will be automatically
blocked.
The measured values of the phase currents at either end of the protected object are
multiplied by the relevant matching factors. These are then available for further
processing. Consequently, all threshold values and measured values are always in
relation to the relevant reference currents rather than to the transformer nominal currents
or the nominal currents of the device.
1 2 3 4 5 6 7
DIFF: Vn prim.,
End a
[ 019 017 ]
DIFF: Vn prim.,
End b
[ 019 018 ]
DIFF: Rated Ref
Power Sref
[ 019 016 ]
DIFF: Enabled C
[ 041 210 ]
MAIN: In CT.
prim.,End a
[ 019 020 ]
MAIN: In CT.
prim.,End b
[ 019 021 ]
MAIN: Protection
active C
306 001
DIFF: Ready
[ 041 216 ] & C
MAIN: Protect.
Not Ready
[ 004 060 ]
kam,a * IA,a Iam,A,a
IA,a
68Z6033A_UK
Zero-sequence current
filtering
On transformers with grounded mid-point tapping on one winding and an asymmetrical
load, a zero-sequence current flows through this grounded mid-point tapping. This zero-
sequence current is superimposed on both phase currents and will corrupt differential
and restraining currents. In order to prevent this problem the P638 provides both
measuring circuits (end ‘a’ and end ‘b’) with zero-sequence current filtering, which may
be enabled or disabled.
The P638 calculates the zero-sequence currents using the following formula:
1
I am ,0 ,y = ⋅ ( I am ,A ,y − I am ,C ,y )
2
y: measuring system 1 or 2
The determined zero-sequence current is subtracted from the phase currents. These
corrected phase currents are then used to determine the differential and restraining
currents.
1 2 3 4 5 6 7
DIFF: I0 Filt a
Enab SGx
[ * ]
0
1
0: No
1: Yes
C C2,4
Iam,A,a C1,3
Iam,0,a
Iam,C,a
Iam,A,a-Iam,0,a 1
Iam,C,a-Iam,0,a 3
1 … 2 Is,1,a
DIFF: I0 Filt b
Enab SGx 3 … 4 Is,2,a
[ * ]
0
1
0: No
1: Yes
C C2,4
Iam,A,b C1,3
Iam,0,b
Iam,C,b
Iam,A,b-Iam,0,b 1
Iam,C,b-Iam,0,b 3
1 … 2 Is,1,b
3 … 4 Is,2,b
68Z6034A_UK
Tripping Characteristic
The differential and restraining current values for each measurement system are derived
from the amplitude matched and zero-sequence compensated currents. The following
equations are valid only for uniformly orientated current phasors relative to the protected
object. That means, the current phasors in each end, must point either towards the
protected object or away from it.
I d , y = I s , y ,a + I s, y, b
The differential and restraining currents are displayed as measured operating data,
provided that the set thresholds are exceeded.
The P638 tripping characteristic has two knee-points. The first knee-point is dependent
on the setting D I F F : I d i f f > S G x and is determined by the intersection with the
tripping characteristic for single-side feed. The second knee of the tripping characteristic
is defined by the setting D I F F : I R , m 2 S G x .
The characteristic equations for the three different ranges are given below. Figure 3-77
shows the tripping characteristics.
Id I diff >
=
I ref I ref
Id I I diff >
= m1 ⋅ R + ⋅ ( 1 − 0.5 ⋅ m1 )
I ref I ref I ref
Id I I diff >
= m2 ⋅ R + ⋅ ( 1 − 0.5 ⋅ m1 ) + I R ,m 2 ⋅ ( m1 − m2 )
I ref I ref I ref
where:
Iref: Reference current
m1: gradient of characteristic for the range 0.5 ⋅ I diff > < I R ≤ I R ,m 2 (configurable)
m2: gradient of characteristic for the range I R ,m 2 < I R (configurable)
If the differential current is above the configured threshold D I F F : I d i f f > > S G x , the
P638 will trip without taking the inrush stabilization into account. Furthermore, if the
differential current exceeds the adjustable threshold D I F F : I d i f f > > > S G x , the
restraining current and the saturation discriminator are also no longer taken into account.
25
Id/Iref
Tripping area
m1=m2=1.
20
Fault current characteristic for
single-side feed
15
10
m2=0.4
Idiff>=2. m1=0.2
Blocking area
Idiff>=0. 0
0 5 10 15
IR/Iref
IRm2 = 1. IRm2 = 10 Q9Z5005A
Inrush Stabilization
(Harmonic Restraint)
When an unloaded transformer is energized, the inrush current could reach values that
exceed the transformer nominal current several times over. It takes some time for the
current to assume its steady state value. Since the high inrush current flows on the
connected side only, the tripping characteristic of the P638 may give rise to a trip unless
stabilizing action is taken. The inrush current has a high proportion of harmonics of
twice the system frequency. This provides a mechanism to provide stabilization against
tripping due to the inrush current.
The P638 filters the differential current. The fundamental wave I(f0) and second
harmonic components I(2*f0) of the differential current are thus determined. Tripping is
blocked if the ratio I(2*f0) / I(f0) exceeds a specific adjustable value in at least one
measuring system. There will be no blocking if the differential current exceeds the set
threshold D I F F : I d i f f > > S G x .
Saturation discriminator
Up to a certain limit, stability in the event of external faults is ensured by means of the
restraining action. Due to the double-knee-point (triple-slope) tripping characteristic, the
stabilization is particularly pronounced for high currents. However, as an additional
safeguard for through-currents with transformer saturation, the P638 is provided with a
saturation discriminator.
The saturation discriminator monitors the occurrence of the differential current after each
zero-crossing of the restraining current. For internal faults, the differential current
appears after a zero crossing together with the restraining current. In the case of
through-currents with transformer saturation, however, a differential current will not
appear until the transformer starts to saturate. Accordingly, a blocking signal is
generated by monitoring the level of the differential current and comparing it with the
restraining current, thus the desired stabilization is achieved. Blocking is restricted to the
measuring system where an external fault was detected. There will be no blocking if the
differential current exceeds the set threshold D I F F : I d i f f > > S G x .
As an additional protection feature against winding and ground faults the P638 provides
transverse differential protection for transformer ends a and b.
All transverse differential protection threshold values are based on nominal currents of
the protection device.
Enabling or disabling
transverse differential
protection
Transverse differential protection may be disabled or enabled using setting parameters.
Enabling can be done separately for each setting group.
Tripping Characteristic
Transverse and restraining currents are calculated by the transverse differential
protection by using the two-phase current values.
I trans, z = I A , z − I C, z
I R ,z = 0.5 ⋅ ( I A ,z + I C,z )
z: End a or b
The ripping characteristic has two slopes. The first knee is dependent on the setting
D I F _ z : I t r a n s > S G x and is on the intersection with the line m1 ⋅ I R ,z . The
characteristic equations for the different ranges are given below. Figure 3-82 shows the
tripping characteristic.
I trans >
Characteristic equation for the range 0 < I R ,z ≤ :
m1
I trans >
Characteristic equation for the range < I R ,z :
m1
I trans,z I
= m1 ⋅ R ,z
I nom I nom
25
Itrans/Inom
Tripping area
20
15
m1=1.5
10
Itrans>/m1=5
Itrans>/m1=0,066 m1=0.2
Blocking
0
0 5 10 15
IR/Inom
Q9Z5010A
Enabling or disabling
DTOC protection
DTOC protection can be disabled or enabled using a setting parameter. Enabling can
be done separately for each setting group.
1 2 3 4 5 6 7
DTOC1: General
Enable USER
[ 031 135 ]
0
1 DTOC1: Enabled
& [ 035 102 ]
0: No
1: Yes
DTOC1: Enable
SGx
[ * ]
0
1
0: No
1: Yes
DTOC2: General
Enable USER
[ 031 136 ]
0
1 DTOC2: Enabled
& [ 035 132 ]
0: No
1: Yes
DTOC2: Enable
SGx
[ * ]
0
1
0: No
1: Yes
Inrush restraint
Triggering of the overcurrent protection functions can optionally be blocked, together
with the differential protection function, during inrush occurrences. In this case the signal
from the inrush stabilization function of the differential protection is used as a blocking
criterion. Therefore when the differential protection of the P638 is disabled, then the
overcurrent stages will always operate without inrush stabilization. Blocking of the inrush
stabilization is released when at least one phase current exceeds the set threshold
DTOC1: I>lift Rush Rest.SGx.
1 2 3 4 5 6 7
DTOC1: Inrush
Stab ="on"SGx
[ * ]
0
1
0: No
1: Yes
DTOC1: I>lift
Rush Rest.SGx
[ * ]
DTOC1: IC
402 411 DTOC1: Harm.Block.
& 2 Trigg.
310 031
DTOC1: Inrush
DIFF: Harm.Block. 1 Stabil.Trigg.
Trigg. [ 035 127 ]
[ 041 118 ]
DIFF: Harm.Block. 2
Trigg.
[ 041 119 ]
DTOC2: Inrush
Stab ="on"SGx
[ * ]
0
1
0: No
1: Yes
DTOC2: Inrush
Stabil.Trigg.
[ 035 157 ]
DTOC2: I>lift
Rush Rest.SGx
[ * ]
DTOC2: IC
402 421 DTOC2: Harm.Block.
& 2 Trigg.
310 033
68Z6011A_UK
3-86 Inrush restraint of the definitive-time overcurrent protection functions DTOC1 and DTOC2
Definite-time overcurrent
protection 1
(incl. short-circuit direction
determination)
Depending on the setting the phase currents on the high and low voltage sides are
monitored by the definite-time overcurrent protection function to detect when they
exceed the set thresholds. The timer stages connected in series to the triggers can be
blocked by way of appropriately configured binary signal inputs.
When the current thresholds I> or I>> are triggered and if the measured voltage level is
within the limits set by Vmin and V< then the fault angle ϕ is calculated and the short-
circuit (fault) direction is determined. The short-circuit characteristic is defined by the
angles β and γ. The program decides that the fault direction is 'Forward' when the
calculated angle ϕ lies within the range given by γ = ϕ = β.
Another setting is used to determine whether a failure of the voltage measuring circuit
will either lead to the overcurrent protection operating non-directionally or to it becoming
blocked.
The direction determination and the starting of the respective stage are only enabled if
the measured voltage value is below a settable undervoltage threshold V<. Setting the
undervoltage threshold V< to 'Blocked' will disable this voltage scan and direction
determination and starting are permanently enabled.
1 2 3 4 5 6 7
DTOC1: Timer
Start tI> SGx
[ * ]
1
2
1: With Starting
2: With Direction
DTOC1: Blocking
tI> EXT
[ 035 120 ]
DTOC1: I>
DTOC1: Enabled SGx
[ 035 102 ] & [ * ]
MAIN: Protection
active C1,2
306 001
DTOC1: Harm.Block.
1 Trigg. C1 DTOC1: tI>
310 039 C SGx
[ * ]
DTOC1: Harm.Block.
2 Trigg. C2
310 031
DTOC1: tI> Elapsed
& [ 035 098 ]
DTOC1: IA
402 410
DTOC1: Starting
DTOC1: IC & I>
[ 035 108 ]
402 411
1
2
1: With Starting
2: With Direction
DTOC1: Blocking tI>>
EXT
[ 035 121 ] DTOC1: Phase A
Triggered
[ 035 104 ]
DTOC1: I>>
SGx DTOC1: Phase C
[ * ] Triggered
[ 035 105 ]
C1,2
C1 DTOC1: tI>>
C SGx
[ * ]
C2
DTOC1: tI>> Elapsed
& [ 035 099 ]
DTOC1: Starting
& I>>
[ 035 109 ]
&
Setting DTOC1: Timer DTOC1: I> DTOC1: tI> DTOC1: Timer DTOC1: I>> DTOC1: tI>>
Start tI> SGx SGx SGx Start tI>> SGx SGx SGx
Group 1 071 146 076 051 076 057 072 245 076 052 076 058
Group 2 071 147 077 051 077 057 073 044 077 052 077 058
Group 3 071 148 078 051 078 057 074 044 078 052 078 058
Group 4 071 149 079 051 079 057 075 044 079 052 079 058
68Z6012A_UK
When a permanent current enable value is exceeded and if the measured voltage level
is greater or equal to the enable voltage threshold value Vmin then the load angle ϕ is
calculated and the load flow direction is determined according to the selected short-
circuit characteristic.
The load flow direction is displayed as long as no short circuit condition is present, which
is identified by triggering of DTOC stages and the undervoltage enable.
1 2 3 4 5 6 7
DTOC1: Direction
Measurem.
[ 031 131 ] &
1: Enabled
MAIN: M.c.b. Trip V
EXT
[ 004 061 ]
DTOC1: V ≥ Vmin (I>) DTOC1: Beta
(I>) SGx
402 418 [ * ]
DTOC1: Gamma
(I>) SGx
[ * ]
≥ 0.05 In
C
30 ms 0 DTOC1: Fault
Reverse direction I>> Reverse
& [ 035 148 ]
DTOC1: I>>
Triggered
310 035 &
DTOC1: V < U< (I>>)
403 411
Definite-time overcurrent
protection 2
Depending on the setting the phase currents on the high and low voltage sides are
monitored by the definite-time overcurrent protection function to detect when they
exceed the set thresholds. Their starting can optionally be blocked together with the
inrush stabilization function of the differential protection. In this case the signal from the
inrush stabilization function of the differential protection is used as a blocking criterion.
Therefore when the differential protection of the P638 is disabled, then the overcurrent
stages will always operate without inrush stabilization. Blocking of the inrush
stabilization is released when at least one phase current exceeds the set threshold
D T O C 2 : I > l i f t R u s h R e s t . S G x . The timer stages connected in series to the
triggers can be blocked by way of appropriately configured binary signal inputs.
1 2 3 4 5 6 7
DTOC2: Blocking
tI> EXT
[ 035 150 ]
DTOC2: I>
SGx
[ * ]
C1,2
DTOC2: Harm.Block.
1 Trigg. C1
310 032
DTOC2: I>>
SGx
[ * ]
C1,2
C1
DTOC2: tI>>
C2 C SGx
[ * ]
DTOC2: Starting
I>>
[ 035 139 ]
68Z6014A_UK
1 2 3 4 5 6 7
DTOCN: General
Enable USER
[ 031 138 ]
0
1 DTOCN: Enabled
& [ 035 192 ]
0: No
1: Yes
DTOCN: Enable
SGx
[ * ]
0
1
0: No
1: Yes
3-93 Disabling or enabling the definite-time overcurrent protection function for residual current
The residual current is monitored to detect when the set thresholds are exceeded. The
arithmetical mean and the instantaneous value of the residual current are monitored in
parallel to the high-current stage . Depending on the time of fault occurrence and
current value, the monitoring reaction time to the arithmetical mean value has the
duration of 0.5 to 1 cycles. The reaction time to the instantaneous value is less than the
duration of 0.1 cycles.
In addition to the high-current stage the residual current is monitored by two stages
whether it exceeds the set threshold values.
After the set time delays have elapsed, a trip signal is issued. The elapsing of the time-
delays may be blocked using an appropriately configured binary signal input.
DTOCN: Enabled
[ 035 192 ] & t 0 DTOCN: Trip
Signal tIN>H
MAIN: Protection DTOCN: IN>H [ 035 198 ]
active C SGx
306 001 [ * ]
DTOCN: Starting
Instantaneous value IN>H
IN [ 035 195 ]
AR_MV (Average)
68Z6026A_UK
Inverse time overcurrent protection may optionally be operated with short-circuit direction
determination.
Disabling or enabling
IDMT protection
IDMT protection can be disabled or enabled using a setting parameter. Enabling can be
done separately for each setting group.
1 2 3 4 5 6 7
IDMT: General
Enable USER
[ 017 096 ]
0
1 IDMT: Enabled
& [ 040 100 ]
0: No
1: Yes
IDMT: Enable
SGx
[ * ]
0
1
0: No
1: Yes
GROUP: Group y
Active
[ * ]
Time-dependent
characteristics
The user can select from a large number of characteristics (see table below).
The tripping characteristics available for selection are shown in figures 3-96 to 3-99.
1000 1000
100 100
k=10
10 10 k=10
t/s k=1
t/s
1 1
k=1
k=0,1
0,1 k=0,05 0,1
k=0,1
k=0,05
0,01 0,01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/IB I/IB
S8Z50K1B S8Z50K2B
1000 1000
100 100
k=10
10 10
k=1
t/s k=10
t/s
1 1
k=0,1
k=0,05
k=1
0,1 0,1
k=0,1
0,01 k=0,05 0,01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/IB I/IB
S8Z50K3B S8Z50K4B
1000 1000
100 100
10 k=10 10
k=10
t/s t/s
1 k=1 1
k=1
I/IB I/IB
S8Z50K5C S8Z50K6C
1000
100
10
t/s
k=10
1
k=1
0,1
k=0,1
0,01 k=0,05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/IB
S8Z50K7C
Characteristic No. 7
1000 1000
100 100
10 10
t/s k=10
t/s
1 1
k=10
k=1
0,1 0,1
k=1
k=0,1 k=0,1
0,01 k=0,05 0,01
k=0,05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/IB I/IB
S8Z50K8C S8Z50K9C
1000
100
k=10
10
t/s k=0,1
1
k=1
0,1 k=0,05
0,01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/IB
S8Z50KAC
Characteristic No. 10
1000 1000
100 100
k=10
k=10
10 10
k=0,1
k=0,05 k=0,1
0,1 0,1
k=0,05
0,01 0,01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/IB I/IB
S8Z50KBB S8Z50KCB
Inrush restraint
Triggering of the inverse-time overcurrent protection functions can optionally be blocked,
together with the differential protection function, during inrush occurrences. In this case
the signal from the inrush stabilization function of the differential protection is used as a
blocking criterion. Therefore when the differential protection of the P638 is disabled,
then the overcurrent stages will always operate without inrush stabilization. Blocking of
inrush stabilization is released when at least one phase current exceeds the set
threshold ID M T : I > l i f t R u s h R e s t . S G x .
1 2 3 4 5 6 7
IDMT: I>lift
Rush Rest.SGx
[ * ]
IDMT:
IDMT: IA Harm.Block. 1
& Trigg.
307 101 310 036
IDMT: IC
307 103
IDMT:
Harm.Block. 2
& Trigg.
310 037
IDMT: Inrush
DIFF: Harm.Block. 1 Stabil.Trigg.
Trigg. [ 040 118 ]
[ 041 118 ]
DIFF: Harm.Block. 2
Trigg.
[ 041 119 ]
68Z6016A_UK
Direction determination
Short-circuit direction determination is enabled with IDMT : D i r e c t i o n M e a s u r e m .
When the inverse-time overcurrent protection is triggered and if the measured voltage
level is within the limits set by Vmin and V< then the fault angle ϕ is calculated and the
short-circuit (e.g. fault) direction is determined. The short-circuit characteristic is defined
by the angles β and γ. The program decides that the fault direction is 'Forward' when the
calculated angle ϕ lies within the range given by γ = ϕ = β.
Direction determination and starting of the respective stage are only enabled if the
measured voltage value is below a settable undervoltage threshold V<. Setting the
undervoltage threshold V< to 'Blocked' will disable this voltage scan, and direction
determination and starting are permanently enabled.
1 2 3 4 5 6 7
1
1.05 * Iref
2
1: With Starting
2: With Direction
IDMT: Enabled
[ 040 100 ] &
MAIN: Protection
active C1,2
306 001
IDMT: Harm.Block.
1 Trigg. C1
310 036
IDMT: Harm.Block.
2 Trigg. C2
310 037 IDMT: Starting
Iref>
& [ 040 080 ]
IDMT: IA
307 101
&
IDMT: IC
307 103
IDMT: Forward
trip
307 104
IDMT: Block.
tIref> EXT
[ 040 101 ] IDMT: Charac-
teristic SGx
[ * ]
Setting IDMT: kt Time
IDMT: Characteristic SGx Dial/TMS SGx
[ * ]
0: Definite Time IDMT: Min. Trip
1: IEC Standard Inverse Time SGx
2: IEC Very Inverse [ * ]
3: IEC Extr. Inverse IDMT: Hold Time
4: IEC Long Time Inv. SGx
5: IEEE Moderately Inv. [ * ]
6: IEEE Very Inverse IDMT: Release
7: IEEE Extremely Inv. C SGx
8: ANSI Normally Inv. [ * ]
9: ANSI Short Time Inv.
10: ANSI Long Time Inv. C
11: RI-Type Inverse
12: RXIDG Inverse
IDMT: Memory
Clear
IP, max / Iref,P [ 040 110 ]
Setting IDMT: Hold Time
IDMT: Release SGx Running
[ 040 053 ]
1: Instantaneous IDMT: tIref>
2: Delayed as per Char. Elapsed
[ 040 082 ]
IDMT: Trip
& Signal tIref>
[ 040 084 ]
&
Setting IDMT: Charac- IDMT: kt Time IDMT: Min. Trip IDMT: Hold Time IDMT: Release
teristic SGx Dial/TMS SGx Time SGx SGx SGx
Group 1 072 056 072 053 072 077 072 071 072 059
Group 2 073 056 073 052 073 077 073 071 073 059
Group 3 074 056 074 052 074 077 074 071 074 059
Group 4 075 056 075 052 075 077 075 071 075 059
68Z6017A_UK
When a permanent current enable value is exceeded and if the measured voltage level
is greater or equal to the enable voltage threshold value Vmin then the load angle ϕ is
calculated and the load flow direction is determined according to the selected short-
circuit characteristic.
The load flow direction is displayed as long as no short circuit condition is present, which
is identified by triggering of IDMT stages and the undervoltage enable.
1 2 3 4 5 6 7
IDMT: Direction
Measurem.
[ 017 109 ] & Setting IDMT: Beta IDMT: Gamma
1: Enabled SGx SGx
MAIN: M.c.b. Trip Group 1 072 046 072 047
V EXT
[ 004 061 ] Group 2 073 046 073 047
IDMT: Beta
IDMT: V ≥ Vmin SGx
Group 3 074 046 074 047
307 107 [ * ] Group 4 075 046 075 047
IDMT: Gamma
SGx
[ * ]
≥ 0.05 In
C
Holding time
Depending on the current flow magnitude the P638 determines the tripping time and a
timer stage is started. The setting for the holding time defines the period for the elapsed
IDMT starting time to be stored after the starting has dropped out. If the starting returns
while the hold time elapses, the new starting time is added to the stored time. If the sum
of the starting times reaches the tripping time determined by the P638 then the
appropriate signal is issued. Should starting not recur during the hold time period then,
depending on the setting, the memory storing the accumulated starting times value will
either be cleared without delay or according to the set characteristic. In figure 3-106 the
effect of the holding time is shown by the example of a phase current stage.
3-106 The effect of the holding time illustrated for the phase current stage as an example
Case A: The determined tripping time is not reached.
Case B: The determined tripping time is reached.
Disabling or enabling
thermal overload protection
Thermal overload protection may be disabled or enabled using setting parameters.
Enabling can be carried out separately for each setting group.
Operating modes
Two operating modes can be selected for thermal overload protection.
Relative Replica
Absolute Replica
Either operating mode can be enabled or disabled individually. Only one of the
operating modes at a time may be enabled for thermal overload protection. However, if
both operating modes are enabled at the same time, an error message is generated by
the P638 and thermal overload protection is blocked.
Relative replica
The rated operating current of the protected object and its overload tolerance for
maximum coolant (ambient) temperature are the basis of the relative thermal replica.
In the 'Relative replica' operating mode, the following settings have to be made for
thermal overload protection:
In the 'Absolute replica' operating mode, the following parameters have to be set for
thermal overload protection:
Tripping characteristics
Current I is used to track a first-order thermal replica as specified in IEC 255-8.
The following parameters will govern the tripping time: In addition to the operating mode
specific settings the tripping time is governed by the following parameters:
2
⎛ I ⎞
⎜⎜ ⎟⎟ − Θ P
t = τ ⋅ ln ⎝ KWx ⋅ I B
f ⎠
2
⎛ I ⎞ ⎛ Θ a − Θ a,max ⎞
⎜⎜ ⎟⎟ − ∆ϑ Aus ⋅ ⎜1 − ⎟
⎜ Θ ⎟
⎝ fKWx ⋅ I B ⎠ ⎝ max − Θ a,max ⎠
The tripping threshold ∆ϑtrip is set to a fixed value of 100 % ( = 1 ) if the operating mode
is 'Absolute replica'.
θtrip / %
10000
200
1000
110
τ/min
50
100
200
110
10 1000
50
t/min 200
1
110
50 30
0.1
0.01 1
0 1 2 3 4 5 6 7 8 9 10 11
0.00
I/Iref
D5Z50BE
3-109 Tripping characteristics of thermal overload protection (tripping characteristics apply to Θ P = 0 % and identical settings for the maximum
permissible coolant and object temperatures)
Influence of coolant
temperature
To permit ambient temperature correction, the analog I/O module Y must be fitted.
There are two possible means available to measure coolant temperatures:
RTDmA: O v e r l o a d 2 0 m A I n p u t
RTDmA: O p e n C i r c . 2 0 m A i n p .
RTDmA: P T 1 0 0 O p e n C i r c u i t
The thermal model uses these signals as a criterion to determine a fault in the coolant
temperature measurement. A fault at the selected measuring point will lead to the
issuance of the signal T H ER M : C T A Er r o r .
All relevant parameters for coolant temperature acquisition are hidden if the analog
module Y has not been fitted to the P638. The tripping time is calculated by including
the setting for T H E R M : D e f a u l t C T A m b S G x .
Minimum coolant
temperature
A setting for a minimum coolant temperature is provided for catenary sections where
coolant temperatures may differ strongly from measured values. For instance in winter
months the temperature measured in a tunnel will be higher than the ambient
temperature measured at the feeder point. In such cases the measured coolant
temperature is limited to a low value set at T H ER M : M i n i m u m T e m p e r a t.SG x.
Thermal overload
protection operation
without coolant
temperature acquisition
In order to guarantee thermal overload protection, without considering an offset because
of a variable coolant temperature, it is recommended to set the parameter
T H ER M : D e fa u l t C T Am b SG x to the maximum permitted coolant temperature.
1 2 3 4 5 6 7
THERM: Select
CT AmbientSGx
[ * ]
0
1 ≥1 THERM: with CTA
303 201
2
0: Default Temp.
Value
1: From PT 100
2: From 20 mA
input
THERM: Enabled ≥1
[ 040 068 ] & ≥1 THERM: CTA Error
[ 039 111 ]
RTDmA: Enabled
[ 035 008 ] CHECK: CTA Error
& [ 098 034 ]
RTDmA: PT100 Faulty
[ 041 190 ]
&
RTDmA: Overload 20mA Input ≥1
[ 041 191 ]
RTDmA: Open Circ. 20mA
inp.
[ 041 192 ]
THERM: CTA Error EXT
[ 038 062 ]
THERM: Funct.
f.CTA fail.SGx
[ * ]
0
THERM: Block.by
1 & CTA Fail305 200
2
0: Default Temp.
Value
1: Last Meas.
Temperat
2: From 20 mA
input
Alarm
Depending on the selected operating mode, a warning signal can be set at one of the
following parameters:
Additionally, a pre-trip time limit can be set; when the time left until tripping falls below
this pre-trip limit, a warning will be issued.
Trip
The trip threshold is set according to the selected operating mode with the following
parameters:
If a trip command is issued, the trip signal is maintained until the status of the thermal
replica has decreased by the value T H E R M : T r i p H y s t e r e s i s S G x , at least for
a fixed time of 5s.
Cooling
If the current falls below the default threshold of 0.1 Iref, the buffer is discharged with the
set time constant T H E R M : T i m . C o n s t 2 ( C o o l ) S G x . This element in the
thermal model takes account of the cooling characteristics of the equipment.
C
THERM: Starting
THERM: I AR_MV k*Iref>
305 202 (Average) [ 041 108 ]
THERM: Iref
SGx <0.1 Iref
[ * ] C
THERM: Start THERM: Tim.Const
Fact.OL_RC SGx C 1(Heat)SGx
[ * ] [ * ]
THERM: Tim.Const
kP*Iref 2(Cool)SGx
C [ * ]
MAIN: Protection
active & THERM: Default
306 001 C CT Amb SGx
THERM: Enabled [ * ]
[ 040 068 ] THERM: O/T
& C f.Iref
[
Pers. SGx
* ]
THERM: Not THERM: Alarm
Ready Temp. SGx
[ 040 035 ] C [ * ]
THERM: Max Perm
C Obj Tmp.SGx
THERM: Absolute [ * ] THERM: Within
Replica Pre-trip Time
[ 022 065 ] THERM: Max Perm [ 041 109 ]
C Cool
[
TmpSGx
* ] CHECK: Setting
0 THERM: T> Alarm Error THERM
C Reset,% SGx [ 098 035 ]
[ * ]
1 THERM: Setting
THERM: T> Trip Error,Block.
0: No C Reset,% SGx [ 039 110 ]
[ * ]
1: Yes THERM: Alarm
THERM: Minimum [ 039 025 ]
C Temperat.SGx
[ * ] THERM: Trip
THERM: Relative THERM: Trip Signal
Replica Hysteresis SGx [ 039 020 ]
[ 022 064 ] [ * ]
THERM: Reclosure
THERM: Pre-Trip Blocked
0 Alarm SGx [ 039 024 ]
[ * ]
1 THERM: Memory
Clear
0: No [ 039 112 ]
C
1: Yes
Setting THERM: Tim.Const THERM: Tim.Const THERM: O/T THERM: Alarm THERM: Max Perm THERM: Max Perm
1(Heat)SGx 2(Cool)SGx f.Iref Pers. SGx Temp. SGx Obj Tmp.SGx Cool TmpSGx
Group 1 072 187 072 188 072 167 072 153 072 182 072 185
Group 2 073 187 073 188 073 167 073 153 073 182 073 185
Group 3 074 187 074 188 074 167 074 153 074 182 074 185
Group 4 075 187 075 188 075 167 075 153 075 182 075 185
Setting THERM: T> Alarm THERM: T> Trip THERM: Default THERM: Minimum THERM: Trip THERM: Pre-Trip
Reset,% SGx Reset,% SGx CT Amb SGx Temperat.SGx Hysteresis SGx Alarm SGx
Group 1 072 184 072 181 072 186 076 178 072 183 072 191
Group 2 073 184 073 181 073 186 077 178 073 183 073 191
Group 3 074 184 074 181 074 186 078 178 074 183 074 191
Group 4 075 184 075 181 075 186 079 178 075 183 075 191
68Z6051A_UK
Reset
The thermal replica may be reset either using a setting parameter or an appropriately
configured binary signal input. Resetting is possible even when thermal overload
protection is disabled. Thermal overload protection can be blocked using an
appropriately configured binary signal input.
The P638 provides a two-stage time-voltage protection function for over- and
undervoltage monitoring.
Disabling or enabling
V<> protection
V<> protection can be disabled or enabled using a setting parameter. Enabling can be
carried out separately for each setting group.
Voltage monitoring
The P638 checks the voltage to determine whether it exceeds or falls below set
thresholds. The triggers are followed by timer stages that can be blocked using
appropriately configured binary signal inputs.
If the decisions of undervoltage monitoring are to be included in the trip commands, then
it is recommended that transient signals be used. Otherwise the trip command would
always be present when the system voltage were disconnected, and thus it would not be
possible to reclose the circuit breaker.
The P638 checks the voltage selected to detect whether the frequency exceeds or falls
below set thresholds. The frequency is determined from the difference in time between
the zero crossings of the voltage. The over-/ underfrequency protection function has
four stages. The first stage will serve as an example to illustrate the operation of over-/
underfrequency protection.
Conditioning of the
Measured Values
The over-/underfrequency protection function filters the fundamental with the nominal
frequency from the voltage.
Operating modes of
frequency protection
For each stage of the over-/ underfrequency protection function, the user can select
between the following operating modes:
Frequency monitoring
Frequency monitoring combined with instantaneous rate of change (dt/dt) monitoring
Frequency monitoring combined with average rate of change (∆f/∆t) monitoring
Frequency monitoring
Depending on the setting, the P638 checks the frequency to detect whether it exceeds or
falls below set thresholds. If an operate threshold in excess of the set nominal frequency
is set, the P638 checks whether the frequency exceeds the operate threshold. If an
operate threshold below the set nominal frequency is set, the P638 checks whether the
frequency falls below the operate threshold. If it exceeds or falls below the set threshold,
a set timer stage is started. The timer stage can be blocked by way of an appropriately
configured binary signal input.
Frequency monitoring
combined with
instantaneous rate of
change (dt/dt) monitoring
In this operating mode of the over-/ underfrequency protection function, the frequency is
additionally monitored for attaining the set frequency gradient (as well as for exceeding
or falling below the set threshold). Monitoring for overfrequency is combined with
monitoring for a frequency increase; monitoring for underfrequency is combined with
monitoring for a frequency decrease. If both operate conditions are satisfied, a set timer
stage is started. The timer stage can be blocked by way of an appropriately configured
binary signal input.
Frequency monitoring
combined with average
rate of change (∆f/∆t)
monitoring
The frequency gradient can differ for system disturbances in individual substations and
may vary in time due to power swings. Therefore it makes sense to take the mean value
of the frequency gradient into account for load-shedding systems.
Monitoring of the mean value of the frequency gradient starts concurrently with
underfrequency pick-up. If the frequency decreases by the set value ∆f within the set
time ∆t then the ∆t/∆f monitoring function operates without delay and generates a trip
signal. If a frequency change does not lead to an operate decision of the monitoring
function then the ∆t/∆f monitoring function will be blocked until the underfrequency
monitoring function drops out. The trip signal can be blocked by way of an appropriately
configured binary signal input.
3-119 Operation of frequency monitoring combined with rate of change (∆f/∆t) monitoring
3.29 Circuit Breaker Failure Protection (Function Groups CBF_1 and CBF_2)
The P638 provides two main-trip circuits. Each of these main-trip circuits is provided
with its own circuit breaker protection function.
Disabling or enabling
circuit breaker failure
protection
Circuit breaker failure protection may be disabled or enabled using setting parameters.
Moreover, enabling can be done separately for each setting group.
CBF_y: General
Enable USER
[ * ]
0
1 CBF_y: Enabled
[ * ]
0: No
1: Yes
CBF_y: Enable
SGx
[ * ]
0
1
0: No
1: Yes
y: System 1 y: System 2
y: System 1
Setting CBF_1: Enable
SGx
Group 1 072 110
Group 2 073 110
Group 3 074 110
Group 4 075 110
y: System 2
Setting CBF_2: Enable
SGx
Group 1 072 120
Group 2 073 120
Group 3 074 120
Group 4 075 120
Q9Z5014 C_UK
Circuit breaker protection is started by the main-trip command. This command then
starts timer stages. Once they have elapsed, and unless the current monitored by the
circuit breaker failure protection function has fallen below the set threshold, re-trips will
result or a superior level protection unit is triggered. Only the fundamental of the current
is monitored. Current values to be monitored (end a or end b) may be set.
Additionally, the circuit breaker auxiliary contact can be monitored. This is only possible
if a binary signal input has been set to C B F _ y : C B C l o s e d S i g . E X T . The
pickup of the circuit breaker auxiliary contact starts a timer stage. If, after this timer
stage has elapsed, the current value monitored exceeds the set threshold, then the
signal C B F _ y : C B S u p e r v . S i g n a l is issued. Auxiliary contact supervision is only
active for the set operative time.
CBF_y: Imin<
Triggered
402 455
CBF_y: Enabled C
[ * ]
CBF_y: Timer
tBF2 Running
[ * ]
MAIN: CB Failure
[ 036 017 ]
CBF_y: tImin<
SGx
[ * ] CBF_y: CB
Superv. Signal
[ * ]
CBF_y: CB Closed
Sig. EXT
[ * ]
CBF_y: tOp
SGx
[ * ]
y: System 1 y: System 2
CBF_y: Timer
y: System 1 y: System 2 tBF1 Running 036 066 036 111
CBF_y: Enabled 040 055 040 048 CBF_y: Back-Trip 039 023 040 104
Signal
MAIN: Main-Trip 039 011 039 058 CBF_y: Failure 036 056 036 106
Command y Re-Trip
MAIN: Parallel 037 019 037 022 CBF_y: Timer 036 110 036 112
Trip y EXT tBF2 Running
CBF_y: CB Closed 036 107 036 108 CBF_y: CB 039 000 039 039
Sig. EXT Superv. Signal
y: System 1
Setting CBF_1: tBF1 Init CBF_1: tBF2 Init CBF_1: tImin< CBF_1: tOp
M-Trip SGx ReTrip SGx SGx SGx
Group 1 072 115 072 116 072 113 072 114
Group 2 073 115 073 116 073 113 073 114
Group 3 074 115 074 116 074 113 074 114
Group 4 075 115 075 116 075 113 075 114
y: System 2
Setting CBF_2: tBF1 Init CBF_2: tBF2 Init CBF_2: tImin< CBF_2: tOp
M-Trip SGx ReTrip SGx SGx SGx
Group 1 072 125 072 126 072 123 072 124
Group 2 073 125 073 126 073 123 073 124
Group 3 074 125 074 126 074 123 074 124
Group 4 075 125 075 126 075 123 075 124
68Z60ANA_UK
The P638 provides two independent trip circuits. Each of these trip circuits is equipped
with its own circuit breaker monitoring function. This function supports state-controlled
maintenance of circuit breakers.
Enable/disable circuit
breaker monitoring
Circuit breaker monitoring functions may be disabled or enabled by setting parameters.
1 2 3 4 5 6 7
CBM_1: General
Enable USER
[ 022 010 ]
0
1 CBM_1: Enabled
[ 044 130 ]
0: No
1: Yes
CBM_2: General
Enable USER
[ 007 170 ]
0
1 CBM_2: Enabled
[ 007 113 ]
0: No
1: Yes
68Z6040A_UK
Variants
The wear condition of a circuit breaker may be determined by a variety of methods:
CB wear characteristic
Circuit breaker manufacturers usually provide wear characteristics showing the
maximum number of permissible CB operations as a function of the ruptured current.
Figure 3-125 displays the wear characteristics for a circuit breaker with a nominal current
of 2000 A and a rated ruptured current of 63 kA. The mean ruptured current is 48 kA.
1 2 3 4 5 6 7
100000
Number of remaining CB operations
10000
1000
100
10
0,1
0.1 1 10 100
Ruptured current in kA
68Z6041A_UK
The knee points shown in figure 3-125 are needed to set the circuit breaker wear
characteristic :
n (I nom,CB )
nrem (Inom,CB ) = nrem,0 (Inom,CB ) −
n (Id ,CB )
Where:
1 2 3 4 5 6 7
CBM_1: Select
Meas. Input
[ 022 178 ]
1
2
1: End a C1,3
2: End b
C2,4
IA,a 1
IC,a 3
IA,b 2
IC,b 4
1 ... 2 CBM_1: IA
310 040
3 ... 4 CBM_1: IC
310 041
CBM_2: Select
Meas. Input
[ 007 216 ]
1
2
1: End a C1,3
2: End b
C2,4
1 ... 2 CBM_2: IA
310 042
3 ... 4 CBM_2: IC
310 043
68Z6042A_UK
3-126 Selecting the measured variables for the circuit breaker monitoring functions
Operating modes
You select the condition for which the function will be triggered by setting the
parameters: C B M _ 1 : O p e r a t i n g m o d e or C B M _ 2 : O p e r a t i n g m o d e .
The following correction values can be set to determine the exact trip time:
C B M _ 1 : C o r r . A c q u . t . T r i p or C B M _ 2 : C o r r . A c q u . t . T r i p
A positive correction time value can be set for the delay period between the trip
command and the opening of the CB contacts.
C B M _ 1 : C o r r . A c q u . t . C B S i g . or C B M _ 2 : C o r r . A c q u . t . C B S i g .
A positive or negative correction time value can be set for leading or lagging auxiliary
contacts.
The cycle is started by a trigger criterion. The end of a cycle is defined when the
remaining time of a power cycle has elapsed after the last detected current zero
crossing. The signals C B M _ 1 : C u r r . F l o w E n d e d x or
C B M _ 2 : C u r r . F l o w E n d e d x are generated (x = A or C).
The maximum cycle time duration is defined at 220 milliseconds. The start of the cycle
time is corrected by the configurable correction times. A fault on a CB pole is assumed if
further current zero crossings are detected after the maximum cycle time has elapsed.
Measured values from the respective CB tripping are cancelled and the signal
C B M _ 1 : t m a x > x or C B M _ 2 : t m a x > x is issued (x = A or C).
1 2 3 4 5 6 7
CBM_1: Blocked
[ 044 199 ]
CBM_1: Enabled C
[ 044 130 ] &
MAIN: CBM_1: Operating
Protection Mode
active [ 022 007 ]
306 001
1
2
3
1: With Trip Cmd. Only
2: With CB Sig.EXT Only
3: CB Sig. EXT or Trip
C1,2
CBM_1: Corr.
C1 Acqu.t. Trip
[ 022 153 ]
CBM_1: Corr.
C2 Acqu.t.CB Sig.
[ 022 018 ]
MAIN: Main-Trip
Signal 1
[ 039 101 ] 1
MAIN: Re-Trip
Signal 1
[ 039 103 ]
MAIN: CB1 Trip EXT 2
[ 044 131 ] C
CBM_1: tmax> x
[ * ]
220 ms 0 CBM_1: Cycle
1 … 2 Running x
& [ * ]
< 0.05 In
CBM_1: Ix
CBM_1: Curr. Flow
A: 310 040 Ended x
C: 310 041 [ * ]
68Z6043A_UK
Pole-selective measured
values and counter values
Depending on the set operating mode, the P638 evaluates the conductor currents
separately and establishes a wear state for each circuit breaker or CB pole.
The following measured values are presented pole-selectively, and per-unit values refer
to the CB nominal current:
Primary ruptured currentThis value is used to evaluate wear with reference to the CB
wear characteristic.
Per-unit ruptured current
Square of the per-unit ruptured current
Sum of the per-unit ruptured currents
Sum of the squares of the per-unit ruptured currents
Current-time integral of the per-unit ruptured current
Sum of the current-time integrals of the per-unit ruptured currents
The ruptured current is derived from the r.m.s. current value during the function cycle.
The integral of the current-time area is calculated during the function cycle. An example
of a current-time integral calculation is shown in figure 3-128.
1 2 3 4 5 6 7
Current-time integral
1 cycle
MAIN: Main-Trip
Command x
68Z6044A_UK
3-128 Calculation of the pole-selective current-time integrals when CBM is triggered by the respective main-trip command
Note: You may only set new measurement and counter values if the default values
are not set to 'Blocked'.
The stored value will remain unchanged if the default value is set to 'Blocked'.
Execution of the set command initializes all default values in the P638 to
'Blocked'.
1 2 3 4 5 6 7
CBM_1: In,CB
[ 022 012 ]
MAIN: In CT.
prim.,End a
[ 019 020 ]
MAIN: In CT.
prim.,End b
[ 019 021 ]
CBM_1: Perm. CB
Op. In,CB
[ 022 013 ]
fnom
CBM_1: Ix CBM_1: Med.
Curr. Itrip,CB
A: 310 040 [ 022 014 ]
C: 310 041
CBM_1: Perm. CB
C Op. Imed,CB
[ 022 015 ]
CBM_1: Set
–Itrip x CBM_1: Itrip x
[ * ] R [ * ]
CBM_1: ΣItrip x
S [ * ]
CBM_1: ΣItrip**2 x
S [ * ]
CBM_1: ΣI*t x
S [ * ]
CBM_1: No. of CB
Oper. x
S [ * ]
CBM_1: Remain. No.
CB op. x
S [ * ]
Phase x CBM_1: Cycle CBM_1: Set No. CBM_1: Set CBM_1: Set CBM_1: Vorg. CBM_1: Vorg.
/ Current Running x CB Oper. x Remain. CB Op. x –Itrip x ΣItrip**2 x ΣI*t x
Ix
A / IA 044 205 022 131 022 134 022 137 022 140 022 143
C / IC 044 207 022 133 022 136 022 139 022 142 022 145
Note: You may only set new measurement and counter values if the default values
are not set to 'Blocked'.
The stored value will remain unchanged if the default value is set to "blocked".
Execution of the set command initializes all default values in the P638 to
'Blocked'.
1 2 3 4 5 6 7
CBM_1: Remain
No. CB Op. <
[ 022 020 ]
CBM_1: Sig. Rem. No.CB
CBM_1: Remain. op.<
No. CB op. A [ 044 136 ]
[ 008 014 ]
CBM_1: Remain.
No. CB op. C
[ 008 016 ]
CBM_2: Remain
No. CB Op. <
[ 007 180 ]
CBM_2: Sig. Rem.
CBM_2: Remain. No.CB op.<
No. CB op. A [ 007 118 ]
[ 007 144 ]
CBM_2: Remain.
No. CB op. C
[ 007 145 ]
68Z6046A_UK
Each switching operation will increment the CB Activity counter. The number of CB
operations made for each CB contact is displayed. A threshold value can be set with the
parameters C B M _ 1 : N o . C B O p e r a t i o n s > or
C B M _ 2 : N o . C B O p e r a t i o n s > . An alarm is issued if the number of CB
operations exceeds this threshold.
1 2 3 4 5 6 7
CBM_1: No. CB
Operations >
[ 022 019 ]
CBM_1: Sig. No. CB Op.
CBM_1: No. of [ 044 135 ]
CB Oper. A
[ 008 011 ]
CBM_1: No. of
CB Oper. C
[ 008 013 ]
CBM_2: No. CB
Operations >
[ 007 179 ]
CBM_2: Sig. No. CB Op.
CBM_2: No. of CB [ 007 117 ]
Oper. A
[ 007 142 ]
CBM_2: No. of CB
Oper. C
[ 007 143 ]
68Z6047A_UK
Monitoring ruptured
currents
In addition to the evaluation of the CB wear state and activity, the P638 provides the
possibility of accumulating and displaying ruptured current values and the square of
these values.
1 2 3 4 5 6 7
&
CBM_1: Blocking
EXT
[ 044 128 ]
CBM_1: Blocking
USER
[ 022 150 ]
0
1
0: No
1: Yes
&
CBM_2: Blocking
EXT
[ 007 112 ]
CBM_2: Blocking
USER
[ 007 171 ]
0
1
0: No
1: Yes
68Z6048A_UK
LIMIT: General
Enable USER
[ 014 010 ]
0
1 LIMIT: Enabled
& [ 040 074 ]
0: No
1: Yes
LIMIT: Enable
SGx
[ * ]
0
LIMIT: Starting
1 IDC,lin>
[ 040 180 ]
0: No
1: Yes
LIMIT: LIMIT:
IDC,lin> tIDC,lin>
MAIN: [ 014 110 ] [ 014 112 ]
Protection
active
306 001 LIMIT:
MESSE: Curr. tIDC,lin>
IDC,lin. p.u. Elapsed
[ 004 136 ] [ 040 182 ]
LIMIT: Starting
IDC,lin>>
Setting LIMIT: Enable [ 040 181 ]
SGx
Group 1 072 240
LIMIT: IDC,lin>> LIMIT:
Group 2 073 240 tIDC,lin>>
Group 3 074 240 [ 014 111 ] [ 014 113 ]
Group 4 075 240
LIMIT:
tIDC,lin>>
Elapsed
[ 040 183 ]
LIMIT: Starting
IDC,lin<
[ 040 184 ]
LIMIT: tIDC,lin<
Elapsed
[ 040 186 ]
LIMIT: Starting
IDC,lin<<
[ 040 185 ]
LIMIT:
tIDC,lin<<
Elapsed
[ 040 187 ]
68Z6054A_UK
The device features limit value monitoring functions to monitor current flow in
transformer ends a and b.
Current monitoring
The maximum current is monitored with two stages to detect when it exceeds the set
thresholds. If the thresholds are exceeded, a signal is issued after a set time period has
elapsed.
LIMIT: Enabled
[ 040 074 ] LIMIT: Iz> LIMIT: tIz>
C SGx SGx
MAIN: Protection [ * ] [ * ]
active
306 001
IA,z
t 0 LIMIT: tIz>
Imax Elapsed
[ * ]
IC,z
t 0 LIMIT: tIz>>
Elapsed
[ * ]
z: End a z: End b
Current monitoring
The residual current is monitored with two stages to detect when it exceeds the set
thresholds. If any of the thresholds are exceeded a signal is issued after a set time
period has elapsed.
t 0 LIMIT: tIN>
IN Elapsed
[ 040 153 ]
t 0 LIMIT: tIN>>
Elapsed
[ 040 154 ]
68Z6056A_UK
The device checks the voltage to detect whether it exceeds or falls below set thresholds.
In addition the device features a frequency monitoring function.
Voltage magnitude
monitoring
The voltage is monitored by two stages to determine whether it exceeds or falls below
set thresholds. If it exceeds or falls below the thresholds a signal is issued once a set
time period has elapsed.
MAIN: Protection
active
306 001
t 0 LIMIT: tV>
V Elapsed
[ 040 140 ]
t 0 LIMIT: tV<
Elapsed
[ 040 142 ]
t 0 LIMIT: tV>>
Elapsed
[ 040 141 ]
LIMIT: tV>>&tV<<
Elapsed
LIMIT: V<< LIMIT: tV<< [ 040 145 ]
C SGx SGx
[ * ] [ * ]
t 0 LIMIT: tV<<
Elapsed
[ 040 143 ]
68Z6057A_UK
Frequency monitoring
The voltage frequency is monitored with two stages to detect whether it exceeds or falls
below set thresholds. If it exceeds or falls below the thresholds a signal is issued once a
set time period has elapsed.
MAIN: Protection
active
306 001
t 0 LIMIT: tf>
MAIN: Frequency f Elapsed
[ 004 040 ] [ 040 196 ]
t 0 LIMIT: tf>>
Elapsed
[ 040 197 ]
t 0 LIMIT: tf<
Elapsed
[ 040 198 ]
t 0 LIMIT: tf<<
Elapsed
[ 040 199 ]
68Z6058A_UK
Programmable (or user-configurable) logic enables the user to link binary signals within
a framework of Boolean equations.
Binary signals in the P638 may be linked by logical 'OR' or 'AND' operations or by
additional NOT operations by setting L O G IC : F c t. As s i g n m . O u tp . n , where n = 1
to 32. The Boolean equations need to be defined without the use of brackets.
The following rule applies to the operators: ‘NOT’ before ‘AND’ before ‘OR’.
Logical operations can be controlled through the binary signal inputs in different ways.
The binary input signals L O G IC : I n p u t n E X T (n = 1 to 16) have an updating
function, whereas the input signals L O G IC : Se t n EXT (n = 1 to 8) are latched.
The logic can only be controlled from the binary signal inputs configured for
L O G IC : Se t n EXT if the corresponding reset input L O G IC : R e s e t n EXT ) has
been configured for a binary signal input. If only one or neither of the two functions is
configured, then this is interpreted as ‘Logic externally set’. If the input signals of the two
binary signal inputs are implausible (such as when they both have a logic value of ‘1’),
then the last plausible state remains stored in memory.
When using the programmable logic, the user must carry out a functional type test to
conform with the requirements of the relevant protection/control application. In particular,
it is necessary to verify that the requirements for the implementation of logic linking (by
setting) as well as the time performance during device startup, during operation and
when there is a fault (device blocking) are fulfilled.
3-140 Control of logic operations using setting parameters or stored input signals
The output signal of one equation can be processed as the input signal for another
higher-order equation, and this makes it possible to have a sequence of interlinked
Boolean equations. The equations are processed according to their order sequence.
It should be noted that in the case of overlapping equations, the result is provided by the
highest-order equation.
The output signal of each equation is fed to a separate timer stage with two timer
elements and a choice of operating modes. This offers the possibility of assigning a
freely configurable time characteristic to the output signal of each Boolean equation. In
the Minimum Dwell operating mode, the setting of timer stage t2 has no effect.
Figures 3-142 to 3-146 show the time characteristics for the various timer stage
operating modes.
Note: If the device is switched to "offline" the equations are not processed and all
outputs are set to the '0' logic level.
4 Design
The P638 is available in different types of cases and with different combinations of
modules.
The P638 – like all other devices in the Easergy MiCOM 30 family – is equipped with the
standard user interface (HMI). The user interface is covered with a tough film so that the
specified degree of IP protection will be maintained. In addition to the essential control
and display elements, a parallel display consisting of a total of 17 LED indicators is also
incorporated. The meaning of the various LED indications is shown in plain text on a
label strip.
The PC interface (9-pin D-Sub female connector) is located under the hinged cover at
the bottom of the user interface.
Electrical connections are made via plug-in threaded terminal blocks. The threaded
terminal blocks in the surface-mounted case are accessible from the front of the device
after unscrewing the crosshead screws on the sides (see Figure 4-1, c) and removing
the user interface (HMI). The user interface (HMI) can then be secured by inserting the
tabs in the slots in the left side wall (see Figure 4-1, d). The flush-mounted case is
connected at the back of the case.
4-1 Surface-mounted case, removal of user interface (HMI), illustrated here for a device with graphic display in a 84TE case
Aus-Kommando Mi COM P6 3 8
Warnung
Block./ Stör ung Pa ra me te r
Betr ieb
Änderungsmod
.
147,5
177,5
184,5
434,8 257,1
464,0
481,6
Aus- Kommando
War nung
Mi COM P6 3 8
Block /S
. törung Pa r ame te r
Betr ieb
Änder ungsmod.
177,5
434,8 227,9
253,6
284,9
259,0
25,9
159,0
168,0
5,0
5,0
410,0
4-3 Flush-mounted 84TE case with panel opening, flush-mount method 1 (without angle brackets)
Note: The device has increased mechanical robustness if flush-mount method 2 (with angle brackets and frame, shown in next
drawing) is used for the flush-mounted case.
Aus- Kommando
War nung
Mi COM P6 3 8
Block./ Störung Pa r ame te r
Betr ieb
Änder ungsmod
.
101,6
177,5
434,8 227,9
253,6
464,0
481,6
6,4
101,6
186,5
445,9
464,0
4-4 Flush-mounted 84TE case with panel opening, flush-mount method 2 (with angle brackets and frame)
Note: The device has increased mechanical robustness if flush-mount method 2 (with angle brackets and frame, shown in this
drawing) is used for the flush-mounted case.
4.3 Modules
The P638 is constructed from standard hardware modules. The following table gives an
overview of the modules relevant for the P638
(*: modules that are not shown in the location diagrams, {: optional, z: standard
equipment,
: depending on order).
{
A 9650 356 A ff Communication module 2 (wire connection) 4T
A 9651 427 E ff Ethernet module (for 100 Mbit/s Ethernet, glass fiber, 4T {
SC connector and RJ45 wire)
A 9651 471 E ff Ethernet module (for 100 Mbit/s Ethernet, glass fiber, 4T {
ST connector and RJ45 wire)
The location of the individual modules and the position of the threaded terminal blocks in
the P638 are shown in the location figures and terminal connection diagrams at the end
of Chapter 5.
Only qualified personnel, familiar with the "Warning" page at the beginning of this
manual, may work on or operate this device.
The instructions given in the "Protective and Operational Grounding" section should be
noted. In particular, check that the protective ground connection is secured with a tooth
lock washer, as per the diagram "Installing the protective grounding conductor terminal".
If a cable screen is added to this connection or removed from it, then the protective
grounding should be checked again.
The SC connector and RJ45 wire of the Ethernet module cannot be connected at the
same time. (The selection for I E C : E t h e r n e t M e d i a should be noted.)
All P638 units are packaged separately in their own cartons and shipped inside outer
packaging. Use special care when opening cartons and unpacking units, and do not use
force. In addition, make sure to remove supporting documents and the type
identification label supplied with each individual device from the inside carton.
The design revision level of each module included in the unit when shipped can be
determined from the list of components (assembly list). This list should be carefully
saved.
After unpacking each unit, inspect it visually to make sure it is in proper mechanical
condition.
If the P638 needs to be shipped, both inner and outer packaging must be used. If the
original packaging is no longer available, make sure that packaging conforms to
DIN ISO 2248 specifications for a drop height ≤ 0.8 m.
The nominal data and design type of the P638 can be determined by checking the type
identification label (see Figure 5-1). One rating label is located under the hinged cover
at the top of the user interface (HMI). Another copy of the type identification label is
affixed to the outside of the P638 packaging.
Specification F 6.xxxxxx.y
EN 60255-6 / IEC 255-6
The P638 design version can be determined from the order number. A breakdown of the
order number is given in Chapter 14 of this manual.
The P638 is designed to conform to DIN 57 435 Part 303. Therefore it is important when
choosing the installation location to make certain that it provides the operating conditions
as specified in above DIN norm sections 3.2 to 3.4. Several important conditions are
listed below.
Climatic conditions
Ambient temperature: -5 °C to +55 °C [+23 °F to +131 °F]
Relative humidity: The relative humidity must not result in the formation of
either condensed water or ice in the P638.
Ambient air: The ambient air must not be significantly polluted by dust,
smoke, gases or vapors, or salt content.
Mechanical conditions
Vibration stress: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g
Electromagnetic conditions
Appropriate measures taken in substations must correspond to the best of modern
practices.
5.4 Installation
The dimensions and mounting dimensions for surface-mounted cases are given in
Chapter 4. When the P638 is surface-mounted on a panel, the leads to the P638 are
normally run along the front side of the mounting plane. If the wiring is to be at the rear
an opening can be provided above and below the surface-mounted case, as shown in
Figure 5-2. Figure 5-2 shows only the lower opening. The same considerations also
apply to the upper opening.
5-2 Opening for running the wiring to the 84TE surface-mounted case (dimensions in mm)
If the units are to be installed in accordance with flush-mount method 1 (without the
angle brackets and frame), follow the steps described below.
Before the P638 can be installed in the control panel, the user interface (HMI) must be
removed. The procedure is as follows:
Remove the hinged covers at the top and bottom of the user interface. (Open the
hinged covers by flipping them up or down 180°. Hold them in the middle and bend
them slightly. The side mountings of the covers can then be disengaged.)
Remove the M3 screws (see Figure 5-3).
Remove the user interface.
Then remove the lower M4 screws and loosen the upper M4 screws (see Figure 5-3).
Insert the P638 into the panel opening from the rear so that the upper M4 screws fit into
the corresponding slots. Then tighten all the M4 screws. After this, replace the user
interface (HMI).
Note: If the front panel thickness is ≥ 2 mm, longer M3 and M4 bolts must be used.
Longer screws are enclosed within the device packing.
3 mm
M4
M3
12Y6182 B_EN
5-3 Mounting the 84TE case in a control panel, flush-mount method 1 (without angle brackets and frame)
The P638 has increased mechanical robustness if either the surface-mounted case or – for the flush-mounted case – flush-mount
method 2 (with angle brackets and frame see figure 5-5) is used.
When installing units into a panel in accordance with flush-mount method 2, proceed as
follows:
Remove the screws as shown in Figure 5-4, c and mount the enclosed angle
brackets using these same screws.
Slide the unit into the panel opening from the front.
Secure the device to the control panel by using the enclosed M6 screws (see
Figure 5-5).
Assemble the cover frame and snap it onto the mounting bolts.
Angle brackets
M6
B6
6.4
M6 x 15
Height: 204 mm
Frame for the
80 mm
W idt h: 2 n ted cas e
s h-m o u
40T E flu
12Y6183 B_EN
5-5 Installation of a case into a control panel, flush-mount method 2 (with angle brackets and frame).
Example for a device in a 40TE case.
The device has an increased mechanical robustness, if flush-mount method 2 (with angle brackets and frame, shown on this page) is
used for the flush-mounted cases.
The 84TE flush-mounted cases – with angle brackets mounted – are also suitable for
installation in enclosures or cubicles equipped with a 19" mounting rack.
In addition, a protective ground connection at the terminal contact on the power supply
module (identified by the letters "PE" on the terminal connection diagram) is also
required for proper operation of the device. The cross-sectional area of this ground
conductor must also conform to applicable national standards. A minimum cross section
of 1.5 mm2 is required.
19Y5220A_EN
The protective ground conductor must always be connected to the protective grounding conductor terminal in order to guarantee the
safeguard provided by the design.
5.6 Connection
The P638 must be connected in accordance with the terminal connection diagram
indicated on the type identification label. The terminal connection diagram is included in
the supporting documents supplied with the device. Connection diagrams relevant for
the P638 can be found at the end of this chapter.
Copper leads having a 2.5 mm2 cross-section are generally suitable as the connecting
leads between the current transformers and the P638. To reduce CT knee-point voltage
requirements, it may be necessary to install shorter copper conductors with a greater
cross section between the system current transformers and the current inputs on the
P638. Copper leads having a 1.5 mm2 cross section are adequate for connecting the
binary signal inputs, the signaling and triggering circuits, and the power supply input.
All connections run into the system must always have a defined potential. Connections
that are pre-wired but not used should preferably be grounded when binary inputs and
output relays are isolated. When binary inputs and output relays are connected to a
common potential, the pre-wired but unused connections should be connected to the
common potential of the grouped connections.
Power supply
Before connecting the auxiliary voltage VA for the P638 power supply, it must be ensured
that the nominal value of the auxiliary device voltage corresponds with the nominal value
of the auxiliary system voltage.
Current-measuring inputs
When connecting the system transformers, it must be ensured that the secondary
nominal currents of the system and the device correspond.
The secondary circuit of live system current transformers must not be opened! If the
secondary circuit of a live CT is opened, there is the danger that the resulting voltages
will endanger personnel and damage the insulation.
The threaded terminal block for system current transformer connection is not a shorting
block! Therefore always short-circuit the system current transformers before loosening
the threaded terminals.
A
C
IA
IC
IN
Operation busbar
Return busbar
68Z50APA _UK
Connecting a resistance
thermometer
If the analogue I/O module Y is fitted, a resistance thermometer can be connected.
This analogue I/O module input is designed to connect a PT 100 resistance
thermometer. The PT 100 should be connected using the 3-wire method (see
Figure 5-9). No supply conductor compensation is required in this case.
P638
The terminal connection diagrams give a polarity for connection of the binary signal
inputs. However, this is only a recommendation. Connection to binary inputs can be
made as desired.
PC interface
The PC interface is provided in order to operate the unit from a personal computer (PC).
Communication interfaces
Communication interfaces are provided for permanent connection of the unit to a control
system for substations or to a central substation unit. Depending on the type,
communication interface 1 on the device is connected either by a special fiber-optic
connector or a RS 485 interface with twisted pair copper wires. Connection to channel 2
is always by way of an RS 485 interface.
The selection and assembly of a properly cut fiber-optic connecting cable requires
special knowledge and expertise and is therefore not covered in this operating manual.
The fiber-optic interface may only be connected or disconnected when the supply voltage
for the unit is shut off.
The RS 485 interface available on the P638 was designed so that data transfer in a full
duplex transmission mode is possible using a 4-wire data link between devices.
However, communication through the RS 485 interface is always in the half-duplex mode
of operation. To connect the RS 485 communication interface the following must be
observed:
Always use twisted-pair shielded cables only, the kind used for telecommunications
systems.
At least one symmetrically twisted core pair will be required.
Strip cable cores and cable shield right at the connection point and connect properly
in accordance with specifications.
Ground all shields at both ends (large-area grounding).
Ground free (unshielded) cores at one end only.
As another option, a 2-wire or 4-wire connection is also possible. For the 4-wire
connection, a cable with two symmetrically twisted core pairs is required. A 2-wire data
link is shown in Figure 5-10, and a 4-wire data link is shown in Figure 5-11 as an
example for channel 2 on the communication module. If channel 1 of the communication
module is designed as an RS 485 interface, then the same arrangement would apply.
2-wire connection:
Transmitter and receiver must be bridged in all units that have a full-duplex interface as
part of their electrical system – like the P638, for example. In the two units that form the
physical ends of the line, the pair of leads must be terminated by a 200-to-220 Ω resistor.
With the P638, as with most Schneider Electric units, a 220 Ω resistor is integrated into
the RS 485 interface and can be connected by a wire jumper. An external resistor is
therefore not necessary.
4-wire connection:
Transmitter and receiver must be bridged in the unit that forms one physical end of the
line. The receivers of the slaves that have a full-duplex interface as part of their
electrical system (like the P638, for example) are connected to the transmitter of the
communication master, and the transmitters of the slaves are connected to the receiver
of the master. Units that only have a half-duplex interface are connected to the
transmitter of the communication master. In the last physical participant (master or
slave) of the communication link, the transmitter and receiver must each be terminated
by a 200-to-220 Ω resistor. With the P638, as with most Schneider Electric units, a
220 Ω resistor is integrated into the RS 485 interface and can be connected by a wire
jumper. An external resistor is therefore not necessary. The second resistor must be
connected externally to the device (resistor order number see Chapter 13).
P139
P139
P139
P139
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
P A T Y X X X X X V
CH1 5I 4I 6I 6I 6I 6I 4I
CH2 1U 8O 8O 8O 8O 6O 8O
alt. alt.
A X
ETH
CH2 4H
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
P A T Y X X X X X V
CH1 5I 4I 6I 6I 6I 6I 4I
CH2 1U 8O 8O 8O 8O 6O 8O
alt. alt.
A X
ETH
CH2 4H
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
Ring Pin Voltage measuring Ring Pin Ring Pin Ring Pin
X041 X041 inputs X_ 1 X_ 1 Output relays X_1 X_ 1 Output relays X_ 1 X_1 Measuring outputs
1 1 1 1 1 1
13 1 V T5 2 2 K_01 2 2 K_01 2 2 K_01
16 4 3 3 3 3 3 3 valid
4 4 4 4
5 5 5 5 4 4 U
Current measuring 6 6 K_02 6 6 K_02 5 5
inputs 7 7 7 7
#
X042 6 6
8 8 8 8 0 ..20 mA U_08
1 1 1IA T11 9 9 K_03 9 9 K_03 7 7
2 2 8 8 K_02
3 3 1IC T13 X_ 2 X_ 2 9 9 valid
4 4 10 1 10 1
11 2 K_04 11 2 K_04 X_ 2
5 5 IN T4 12 3 K_05 12 3 K_05 10 1
U
6 6 13 4 K_06 13 4 K_06 11 2
14 5 K_07 14 5 K_07 #
12 3
15 6 15 6 0 ..20 mA U_09
X052 16 7 K_08 16 7 K_08
17 8 17 8
9 1 2IA T21 Signal and
10 2 Signal inputs Signal inputs measuring inputs
11 3 2IC T23 18 9 Vin 18 9
V in 13 4
Vin U_01
12 4 U_01 U_01 14 5
X_ 3 X_ 3 15 6
Vin U_02
19 1 19 1 16 7
20 2 20 2 17 8
Vin V in Vin U_03
21 3 U_02 21 3 U_02
22 4 22 4 18 9
Vin V in Vin U_04
U_03 U_03
23 5 23 5 X_ 3
Vin V in
24 6 U_04 24 6 U_04 19 1
25 7 20 2
U
V in U_05
Power supply U_05 21 3 0..20 mA
#
25 7 + Vaux 26 8
V in
22 4 U
26 8 - U100 27 9 U_06 23 5 PT100
U_06
27 9 PE 24 6 #
X10 RJ45
X// Y
1 X_ 3 X_3
2 D2[ R] 19 1 1) 19 1 K_03
COMM2
3
U20 20 2 K_04 20 2 +
4
wire link 21 3
21 3
5 D1[ T] 22 4 1) 22 4
X10
X//Y 23 5 K_05 23 5
1
RS 485 24 6 24 6
2 D2[ R]
25 7 25 7
3
IRIG-B U20 26 8 K_06 26 8 K_04
4
time synchronization D1[ T] 27 9 27 9 +
5
X11
1 # U21 RS 485
#
Control through the PC interface is also possible. This requires a suitable PC and
operating program (MiCOM S1).
Then there are seven keys with permanently assigned functions situated below the LCD
and there are six additional freely configurable function keys on the right side of the LCD.
Furthermore the HMI is provided with 17 LED indicators, aligned vertically, and situated
on the left side of the LCD and there are six additional LED indicators situated on the
right side of the six freely configurable function keys.
6-1 View of the front panel user interface (HMI) and layout of the LED indicators
Display levels
All data relevant for operation and all device settings are displayed on two levels.
At the 'Panel level', data such as measured operating values are displayed in panels that
provide a quick overview of the current state of the bay. The menu tree level below the
panel level allows the user to select all data points (settings, signals, measured
variables, etc.) and to change them, if appropriate. To access a selected event
recording from either the panel level or from any other point in the menu tree, press the
READ key .
Display Panels
The P638 can display 'Measured Value Panels' which are selected automatically by the
device according to system conditions.
Selected measured values are displayed on the Measured Value Panels. The system
condition determines which Panel is called up (examples are the Operation Panel and
the Fault Panel). Only the Measured Value Panels relevant for the particular design
version of the given device and its associated range of functions are actually available.
The Operation Panel is always available.
Keys
‘Up’ and ‘Down’ Keys
G
/
Panel Level:
The ‘up’/‘down’ keys switch between the Measured Value Panels.
Menu Tree Level:
Press the ‘up’ and ‘down’ keys to navigate up and down through the menu tree in a
vertical direction. If the unit is in input mode, the ‘up’ and ‘down’ keys have a different
function.
Input mode:
Settings can only be changed in the input mode, which is signaled by the LED
indicator labeled EDIT MODE. Press the ‘up’ and ‘down’ keys in this mode to change
the setting value.
(‘Up’ key: the next higher value is selected.
‘Down’ key: the next lower value is selected.)
With list settings, press the ‘up’ and ‘down’ key to change the logic operator of the
value element.
ENTER Key
G
Panel Level:
Press the ENTER key at the Panel level to go to the menu tree.
Menu Tree Level:
Press the ENTER key to enter the input mode. Press the ENTER key a second time
to accept the changes as entered and exit the input mode. The LED indicator labeled
EDIT MODE signals that the input mode is active.
CLEAR Key C
Press the CLEAR key to reset the LED indicators and clear all measured event data.
The records in the recording memories are not affected by this action.
Input mode:
Press the CLEAR key to reject the changes entered and exit the input mode.
READ Key
Press the READ key to access a selected event recording from either the Panel level
or from any other point in the menu tree.
Function Keys F1 to F6
By pressing a function key the assigned function is triggered. More details on
assigning functions to function keys can be found in section "Configurable Function
Keys (Function Group F_KEY)" in Chapter 3. More details on handling function keys
can be found in this Chapter, in section 6.4 "Configurable Function Keys F1 to Fx
(general)".
The following tables, which show the individual control steps, specify the displays that
can be changed by pressing specific keys. A small black square to the right of the
ENTER key indicates that the LED indicator labeled EDIT MODE is on. The examples
shown here do not necessarily apply to the device type described in this manual; they
merely serve to illustrate the control principles involved.
XYYY
After the set "hold" time has elapsed (setting in menu tree: 'Set/Conf/HMI'), the display
will automatically switch to the Panel level if a Measured Value Panel has been
configured.
If none of the control keys is pressed, the display illumination will switch off once the set
"hold" time has elapsed (‘Backlight time’ setting in the menu tree at ‘Set/Conf/HMI’). The
backlight is turned on again by pressing one of the control keys. In this case, the control
action that is normally triggered by the key will not be executed. Reactivation of the
backlight is also possible using a binary input.
If continuous illumination is desired, the user can set the ‘Backlight time’ function to
‘blocked’.
If they have not been configured as control keys, function keys F1 to Fx are enabled only
after the password for function keys has been entered.
It is assumed for the remainder of this section that the function key F1 is enabled only
after the password (as assigned at F _ K E Y : P a s s w o r d F u n c t . K e y 1 ) has been
entered. After the password has been entered the function key will remain active for the
time period set at F _ K E Y : F c n K e y R e t u r n T i m e . Thereafter, the function key
is disabled until the password is entered again.
For this example it is further assumed that the password for the function keys is the
factory-set password. If the user has changed the password (see the chapter entitled
"Changing the Password"), the following description will apply accordingly.
'Left'
G
*
'Down' G
G
*
'Right' GG
'Up’ G
The measured values that will be displayed on the Measured Value Panels can first be
selected in the menu tree under Set/Conf/HMI. The user can select different sets of
measured values for the Operation Panel, the Overload Panel, the Ground Fault Panel,
and the Fault Panel. Only the Measured Value Panels relevant for the particular design
version of the given device and its associated range of functions are actually available.
The menu for the Operation Panel is always present. The remarks in "Setting a List
Setting" apply to this selection. If the M A I N : D i s a b l e d setting has been selected for
a given panel, then that panel is disabled.
The Measured Value Panels are called up according to system conditions. If, for
example, the device detects an overload or a ground fault, then the corresponding
Measured Value Panel will be displayed as long as the overload or ground fault situation
exists. Should the device detect a fault, then the Fault Panel is displayed and remains
active until the measured fault values are reset, by pressing the CLEAR key, for
example.
The menu tree begins with the device type at the top, then branches out below into the
three main folders entitled ‘Settings’, ‘Measurements + Tests’ and ‘Fault + Event
Records’, which form the first folder level. Up to two further folder levels follow so that
the entire folder structure consists of three main branches and a maximum of three
folder levels.
At the bottom of each branch of folders, below the folder levels, are the various function
groups in which the individual data points (settings) are combined.
PX yyy
Unit
type
Oper/
Folder Cyclic measurements
level 2
Oper/Cycl/
Folder Meas. operating data
level 3
Oper/Cycl/Data/
Function MAIN
groups
Oper/Cycl/Data/MAIN
Data Date
points 01.01.99 dd.mm.yy
The display on the user interface (HMI) can be switched between address mode and
plain text mode. In the address mode the display shows settings, signals, and measured
values in numerically coded form, that is, as addresses. In plain text mode the settings,
signals, and measured values are displayed in the form of plain text descriptions.
In either case, control is guided by the menu tree. The active branch of the menu tree is
displayed in plain text in both modes. In the following examples, the display is shown in
plain text mode only.
Although it is possible to select any data point in the menu tree and read the associated
value by pressing the keys, it is not possible to switch directly to the input mode. This
safeguard prevents unintended changes in the settings.
This setup is designed to prevent accidental output and applies even when the global
change-enabling function has been activated. The following example is based on the
factory-set password. If the password has been changed by the user (see section
entitled 'Changing the Password'), the following description will apply analogously.
M+T/C+Test/HMI
Setting Change enabl
appear in the fourth line of the display. No
********
No
*
‘right’ G
M+T/C+Test/HMI
Setting Change enabl
G
No
*
‘up’ G
M+T/C+Test/HMI
Setting Change enabl
G
No
*
‘down’ G
M+T/C+Test/HMI
The display will change as shown in the Setting Change enabl
G
G
M+T/C+Test/HMI
labeled EDIT MODE will light up. This Setting Change enabl
indicates that the setting can now be changed No
by pressing the ‘up’ or ’down’ keys.
G
Yes
G
M+T/C+Test/HMI
Setting Change enabl
indicator will go out. The unit is enabled for Yes
further setting changes.
The same procedure applies to any setting change unless the global change-enabling
function has been activated. This method is recommended for a single setting change
only. If several settings are to be changed, then the global change-enabling function is
preferable. In the following examples, the global change-enabling function has been
activated.
Automatic return
The automatic return function prevents the change-enabling function from remaining
activated after a change of settings has been completed. Once the set return time (menu
tree ‘Set/Conf/HMI’) has elapsed, the change-enabling function is automatically
deactivated, and the display switches to a Measured Value Panel corresponding to the
current system condition. The return time is restarted when any of the control keys is
pressed.
Forced return
The return described above can be forced from the user interface (HMI) by first pressing
the ‘up’ key and then holding it down while pressing the CLEAR key.
Note: It is important to press the ‘up’ key first and release it last in order to avoid
unintentional deletion of stored data.
Even when the change-enabling function is activated, not all settings can be changed.
For some settings it is also necessary to disable the protective function (menu tree:
Set/Func/Glob/MAIN, 'Protection Enabled'). Such settings include the configuration
settings, by means of which the device interfaces can be adapted to the system.
If all the conditions for a value change are satisfied (see above), the desired setting can
be entered.
G
50000 s
G
Set/Conf/HMI
Auto Return Time
labeled EDIT MODE will light up. The last digit 50000 s
of the value is highlighted by a cursor
(underlined).
50000 s
50010 s
meantime the device will continue to operate
with the old value.
Set/Conf/HMI
Auto Return Time
labeled EDIT MODE will go out and the device 50010 s
will now operate with the new value. Press the
keys to select another setting for a value
change.
Using list settings, the user is able to select several elements from a list in order to
perform tasks such as defining a trip command or defining the measurements that will be
displayed on Measured Value Panels. As a rule, the selected elements are linked by an
‘OR’ operator. Other operators (NOT, OR, AND, NOT OR and NOT AND) are available
in the LOGIC function group for linking the selected list items. In this way binary signals
and binary input signals can be processed in a Boolean equation tailored to meet user
requirements. For the DNP 3.0 communication protocol, the user defines the class of a
setting instead of assigning operators. The definition of a trip command shall be used
here as an illustration.
#01 DIST
and fourth lines, respectively. The symbol Trip signal Z1/t1
‘#01’ in the display indicates the first item of the
selection. If 'MAIN: Disabled’ appears for the
first item, then this means that no function
assignment has been made yet.
OR #02 DIST
Trip signal Z2/t2L
Set/Func/Glob/MAIN
Main-Trip 'OR' gate
list. The LED indicator labeled EDIT MODE #02 DIST
will light up. Trip signal Z2/t2L
#02 DIST
mode. Trip zone 4
OR #02 DIST
only the ‘OR’ operator can be selected. There Trip zone 4
is no limitation on the selection of classes.
G
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
will go out. The assignment has been made. OR #02 DIST
The unit will now operate with the new settings. Trip zone 4
G
8 If you wish to reject the new setting while C Par/Func/Glob/MAIN
Fct.assign.trip cmd.
you are still entering it (LED indicator labeled OR #02 DIST
EDIT MODE is on), press the CLEAR key. The Trip zone 2
LED indicator labeled EDIT MODE will go out.
Memories can be read out after going to the corresponding entry point. This does not
necessitate activating the change-enabling function or even disabling the protective
functions. Inadvertent clearing of a memory at the entry point is not possible.
G
Enabled USER
No
G
Enabled USER
order. Once the end of the operating data Yes
memory has been reached, pressing the ‘left’
key again will have no effect.
Enabled USER
No
point.
G
Checksum error param
point.
G
Event
In this example it is the 22nd fault since the last 22
reset.
Running time
signals in chronological order. The time shown 0.17 s
in the second line is the time, measured from
the onset of the fault, at which the value was
measured or the binary signal started or G
Fault recording 1
ended. 0 ms FT_RC
G
Record. in progress
Once the end of the fault has been reached Start
(after the ‘right’ key has been pressed
repeatedly), pressing the ‘right’ key again will
have no effect.
G
Fault recording 1
241 ms FT_RC
G
Record. in progress
End
Record. in progress
Start
01.01.99 10:00:33
6.6.7 Resetting
All information memories – including the event memories and the monitoring signal
memory – as well as the LED indicators can be reset manually. In addition, the LED
indicators are automatically cleared and initialized at the onset of a new fault – provided
that the appropriate operating mode has been selected – so that they always indicate the
latest fault.
The LED indicators can also be reset manually by pressing the CLEAR key, which is
always possible in the standard control mode. This action also triggers an LED indicator
test and an LCD display test. The event memories are not affected by this action, so that
inadvertent deletion of the records associated with the reset signal pattern is reliably
prevented.
Because of the ring structure of the event memories, the data for eight consecutive
events are updated automatically so that manual resetting should not be necessary, in
principle.
If the event memories need to be cleared, however, as would be the case after functional
testing, this can be done after selecting the appropriate setting. An overview of all
resetting actions can be found in section "Resetting Actions" in Chapter 3.
The resetting procedure will now be illustrated using the fault memory as an example.
In this example the global change-enabling function has already been activated.
10
Execute
Certain actions from the local HMI, such as a manual trip command for testing purposes,
can only be carried out by entering a password (see section "Change-Enabling
Function").
This setup is designed to prevent accidental output and applies even when the global
change-enabling function has been activated. The password consists of a pre-defined
sequential key combination entered within a specific time interval. If the password has
been changed by the user (see section entitled 'Changing the Password'), the following
description will apply accordingly.
Don't execute
*
‘right’ G
Oper/CtrlTest/MAIN
Man. trip cmd. USER
G
Don't execute
*
‘up’ G
Oper/CtrlTest/MAIN
Man. trip cmd. USER
G
Don't execute
*
‘down’ G
Oper/CtrlTest/MAIN
The display will change as shown in the Man. trip cmd USER
G
Oper/CtrlTest/MAIN
labeled EDIT MODE will light up. This Man. trip cmd. USER
indicates that the setting can now be changed Don't execute
by pressing the ‘up’ or ’down’ keys.
G
Execute
G
Oper/CtrlTest/MAIN
Man. trip cmd. USER
indicator labeled EDIT MODE will go out. The Don't execute
unit will execute the command.
The password consists of a combination of keys that must be entered sequentially within
a specific time interval. The ‘left’, ’right’, ‘up’ and ‘down’ keys may be used to define the
password and represent the numbers 1, 2, 3 and 4, respectively:
3
G
1 2
G
The password can be changed by the user at any time. The procedure for this change is
described below. The starting point is the factory-set password.
G
Par/Conf/LOC
Password
appear in the fourth line of the display. ********
********
G
********
change as shown in the column on the right. *
G
Par/Conf/LOC
G Password
********
*
G
Par/Conf/LOC
Password
G
********
*
G
Par/Conf/LOC
Password
G
********
*
Par/Conf/LOC
Password
indicator labeled EDIT MODE will light up. The _
third line shows an underscore character ( _ )
as the prompt for entering a new password.
G
*
followed by the DOWN key.
G
Par/Conf/LOC
Password
G
**
G
Par/Conf/LOC
Password
appear in the third line, and a cursor **
(underscore) in the fourth line prompts the user _
to enter the new password again.
G
**
*
G
Par/Conf/LOC
Password
G
**
**
Par/Conf/LOC
Password
password has been re-entered correctly, the ********
LED indicator labeled EDIT MODE goes out
and the display appears as shown on the right.
The new password is now valid.
Par/Conf/LOC
Password
incorrectly, the LED indicator labeled EDIT **
MODE remains on and the display shown on _
the right appears. The password needs to be
re-entered. It is also possible to cancel the
change in password by pressing the CLEAR
key (see Step 8).
Operation from the user interface (HMI) without password protection is also possible.
To select this option, immediately press the ENTER key a second time in steps 4 and 6
without entering anything else. This will configure the HMI without password protection,
and no control actions involving changes will be possible until the global change-
enabling function has been activated (see section entitled ‘Change-Enabling Function’).
If the configured password has been forgotten, it can be called up on the LCD display as
described below. The procedure involves turning the device off and then on again.
G
TEST
directional keys (‘left’, ‘right’, ‘up’ and ‘down’) at
the same time and hold them down.
Password
startup, the password is displayed.
G
1234
7 Settings
7.1 Parameters
The P638 must be adjusted to the system and to the protected equipment by appropriate
settings. This section gives instructions for determining the settings, which are located in
the folder entitled ‘Settings’ in the menu tree. The sequence in which the settings are
listed and described in this chapter corresponds to their sequence in the menu tree.
The units are supplied with a factory-set configuration. After a cold restart the P638 will
be blocked so that all settings must be re-entered.
The device identification settings are used to record the ordering information and the
design version of the P638. They have no effect on the device functions. These settings
should only be changed if the design version of the P638 is modified.
Setting for the change level of the data model text. This display cannot be
altered.
DVICE: Text Vers Data Model 002 121
Using the ‘text replacement tool’ provided by the operating program, the
user can change the setting descriptors (plain text designations) and load
them into the device. These user-specific data models obtain a setting
which is defined by the setting of the data model created by the user and
displayed at this location. Standard data models have the identifier ‘0’
(factory-set default).
DVICE: Serial Number 002 124
The Serial Number is the serial number of the device. This display cannot
be altered.
DVICE: AFS Order No. 001 000
Order numbers for the device. This number cannot be altered by the user.
DVICE: Order Ext. No. 1 000 003
Item number of the module inserted in the respective slot. The display
always shows the actual component configuration at any given time.
DVICE: Module Vers. Slot 1 086 193
Index letter specifying the version of the module inserted in the respective
slot.
DVICE: Variant of Module A 086 047
MAC address for the network hardware of the Ethernet module. This
address is introduced during manufacture and can only be read.
DVICE: Variant of Module L 086 048
When set to 'Yes' it is apparent that the device is fitted with the user
interface (HMI).
The password to be used for changing settings from the user interface
(HMI) can be defined here. Further information on changing the password
is given in Chapter 6.
HMI: Fct. Reset Key 005 251 Fig. 3-56
Selection of specified counters or event logs that are reset by pressing the
RESET key on the user interface.
HMI: Fct. Read Key 080 110
Selection of the event log that will be displayed when the READ key is
pressed.
HMI: Fct. Menu Jmp List 1 030 238
Setting for the time period for which a panel is displayed before the unit
switches to the next panel. This setting is only relevant if more values are
selected than can be shown on the LC-Display.
HMI: Auto Return Time 003 014 Fig. 3-2
If the user does not press a key on the user interface (HMI) during this set
time period, the change-enabling function is deactivated.
HMI: Backlight Time 003 023
If the user does not press a key on the user interface during this set time
period, then the backlighting of the LCD display is switched off, and any
switchgear selection that might have been made is cancelled.
Set the same parity that is set at the interface of the PC connected to the
P638.
PC: Spontan. Sig. Enable 003 187 Fig. 3-5
Enable for the cyclic transmission of measured values via the PC interface.
PC: Cycl. Data ILS Tel. 003 185 Fig. 3-5
All measured values are transmitted again via the PC interface after this
time period has elapsed – provided that transmission has not been
triggered by the other delta conditions.
PC: Time-Out 003 188 Fig. 3-5
Setting for the time that will elapse after the last telegram traffic via the PC
interface before the second communication channel of communication
module A is activated.
Enabling additional settings that are relevant for the protocol based on
IEC 870-5-101.
COMM1: Addit. ILS Enable 003 217 Fig. 3-6
Enabling additional settings that are relevant for the ILS protocol.
COMM1: MODBUS Enable 003 220 Fig. 3-6
In the DNP 3.0 protocol, a 16-bit address is used to identify devices. The
address that can be set here is the higher-order octet, whereas the address
set at C O M M 1 : O c t e t c o m m . a d d r e s s is the lower-order octet of the
DNP address.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Test Monitor On 003 166 Fig. 3-7,
3-8,3-9,3-10,
3-11,3-12
Setting specifying whether data shall be recorded for service activities.
COMM1: Manufacturer 003 161 Fig. 3-7,
3-8, 3-9
Setting for the name of the manufacturer.
Note: This setting can be changed to ensure compatibility.
This setting is hidden unless an IEC 870-5 protocol is enabled.
Setting for the length of the common address for identification of telegram
structures.
Note:
This setting is hidden unless the IEC 870-5-101 protocol is enabled.
'ASDU': Application Service Data Unit
COMM1: Octet 2 Addr. ASDU 003 194 Fig. 3-8
Setting for the length of the common higher-order address for identification
of telegram structures.
Note:
This setting is hidden unless the IEC 870-5-101 protocol is enabled.
'ASDU': Application Service Data Unit
COMM1: Addr. Length Inf.Obj 003 196 Fig. 3-8
Setting for the length of the higher-order address for information objects.
Note: This setting is hidden unless the IEC 870-5-101 protocol is
enabled.
Setting for the transmission direction. Normally this value will be set to '1' at
the control center and to '0' at the substation.
Note: This setting is hidden unless the IEC 870-5-101 protocol is
enabled.
COMM1: Mon.Time to Acknowl. 003 228 Fig. 3-8
Setting for the maximum time that will elapse until the status signal for the
acknowledgment command is issued.
Note: This setting is hidden unless the IEC 870-5-101 protocol is
enabled.
Number of bits that must pass between the receipt of the 'request' and the
start of sending the 'response'.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Phys. Char. Timeout 003 242 Fig. 3-11
Number of bits that may be missing from the telegram before receipt is
terminated.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
Setting for the time period within which the master must acknowledge at the
link layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Link Max. Retries 003 245 Fig. 3-11
Number of repetitions that are carried out on the link layer if errors have
occurred during transmission (such as failure to acknowledge).
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Appl Confirm.Timeout 003 246 Fig. 3-11
Setting for the time period within which the master must acknowledge at the
application layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Appl Need Time Del. 003 247 Fig. 3-11
Time interval within which the slave requests time synchronization cyclically
from the master.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./Cl. Bin. Inputs 003 232 Fig. 3-11
Selection of data points and data classes for object 1 – binary inputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./Cl. Bin.Outputs 003 233 Fig. 3-11
Selection of data points and data classes for object 10 – binary outputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./Cl. Bin. Count. 003 234 Fig. 3-11
Selection of data points and data classes for object 20 – binary counters.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
Selection of data points and data classes for object 30 – analog inputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./Cl. Analog Outp 003 236 Fig. 3-11
Selection of data points and data classes for object 40 – analog outputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ph-Ph Meas V.(DNP3) 003 250 Fig. 3-11
Cycle time at the conclusion of which the selected measured values are
again transmitted.
Note: This setting is hidden unless the Courier protocol is enabled.
Setting the same parity that is set at the interface of the control system
connected to the P638.
COMM2: Dead Time Monitoring 103 176 Fig. 3-14
The time between two polling calls from the communication master must be
less than the time set here.
COMM2: Positive Ackn. Fault 103 203
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
'ASDU': Application Service Data Unit
COMM2: Manufacturer 103 161 Fig. 3-14
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
'ASDU': Application Service Data Unit
All measured values are transmitted again via the communication interface
after this time period has elapsed – provided that transmission has not been
triggered by the other delta conditions.
IEC 61850 Communication IEC: IEC 61850 Communic. 056 059 Page: 3-22
Name of the device (IED has server function). This device name serves as
device identification in the IEC 61850 system, it is included in the Logical
Device Name in the IEC data model and must therefore be unambiguous.
All devices logged-on to the network should have non-recurring IED names.
IEC: TCP Keep-Alive Timer 104 062
The subnet mask defines which part of the IP address is addressed by the
sub-network and which part by the device that is logged-on to the network.
Note:
In the S&R 103 operating program, the complete IP address is displayed at
I E C : S u b n e t m a s k . The device’s front panel display only displays the IP
address distributed to these four data model addresses.
IEC: Gateway Address 104 011
Device (IED) poll cycle time for time synchronization when operating mode
is set to Request from Server.
IEC: SNTP Server 1 IP 104 202
Time difference between UTC and local time at the devices' substation
(IED).
IEC: Diff. Dayl.Sav. Time 104 207
These three settings define the date (e.g. at what day of the year) for
switching from standard time over to daylight saving time. Available for
I E C : D a y l . S a v . T i m e S t a r t are the values 'first', 'second', 'third',
'fourth', and 'last'. For I E C : D a y l . S a v . T i m e s t . d the seven
weekdays are available so that for example a setting like "on the last
Sunday in March" may be used.
IEC: Dayl.Sav.t.St.0:00 + 104 223
This defines the time difference and the time of day (on the specific
changeover day) when the clock is to be switched to daylight saving time.
The time is given in the number of minutes after midnight, e.g. when the
clock changeover to 3:00 AM always occurs at 2:00 AM, then the value to
be entered at I E C : D a y l . s a v . t . s t . 0 : 0 0 + is 120 [minutes] and at
I E C : D i f f . d a y l . s a v . t i m e it is 60 [minutes].
IEC: Dayl.Sav.Time End 104 225
This setting defines the date and time of day for the clock changeover from
daylight saving time to standard time. The setting is similar to that for the
clock changeover to daylight saving time.
IEC: Update Measurements 104 229
Setting to calculate the filter value for all IP Report Control Blocks (RCB).
Should a change occur in one of the IP measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • s e t t i n g I E C : D e a d B a n d I P
Setting to calculate the filter value for all IN Report Control Blocks (RCB).
Should a change occur in one of the IN measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • s e t t i n g I E C : D e a d B a n d I N
IEC: Dead Band VPP 104 232
Setting to calculate the filter value for all VPP Report Control Blocks (RCB).
Should a change occur in one of the VPP measured values, which is
greater than the filter value, the RCB is again sent to all clients. The filter
value for each measured value is calculated according to this formula:
step size measured value • s e t t i n g I E C : D e a d B a n d V P P
IEC: Dead Band VPG 104 233
Setting to calculate the filter value for all VPG Report Control Blocks (RCB).
Should a change occur in one of the VPG measured values, which is
greater than the filter value, the RCB is again sent to all clients. The filter
value for each measured value is calculated according to this formula:
step size measured value • s e tti n g IEC : Dead Band VPG
IEC: Dead Band f 104 234
Setting to calculate the filter value for all f Report Control Blocks (RCB).
Should a change occur in one of the f measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • s e t t i n g I E C : D e a d B a n d f
IEC: Dead Band P 104 235
Setting to calculate the filter value for all P Report Control Blocks (RCB).
Should a change occur in one of the P measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • s e t t i n g I E C : D e a d B a n d P
IEC: Dead Band Phi 104 236
Setting to calculate the filter value for all f Report Control Blocks (RCB).
Should a change occur in one of the φ measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • s e t t i n g I E C : D e a d B a n d P h i
IEC: Dead Band Z 104 237
Setting to calculate the filter value for all Z Report Control Blocks (RCB).
Should a change occur in one of the Z measured values, which is greater
than the filter value, the RCB is again sent to all clients. The filter value for
each measured value is calculated according to this formula:
step size measured value • s e tti n g IEC : Dead Band Z
IEC: Dead Band Min/Max 104 238
Setting to calculate the filter value for all min/max Report Control Blocks
(RCB). Should a change occur in one of the min/max measured values,
which is greater than the filter value, the RCB is again sent to all clients.
The filter value for each measured value is calculated according to this
formula:
step size measured value • s e tti n g IEC : Dead Band Min/Max
Setting to calculate the filter value for all ASC Report Control Blocks (RCB).
Should a change occur in one of the ASC measured values, which is
greater than the filter value, the RCB is again sent to all clients. The filter
value for each measured value is calculated according to this formula:
step size measured value • s e tti n g IEC : Dead Band ASC
IEC: Dead Band Temp. 104 240
Setting to calculate the filter value for all temperature Report Control Blocks
(RCB). Should a change occur in one of the temperature measured values,
which is greater than the filter value, the RCB is again sent to all clients.
The filter value for each measured value is calculated according to this
formula:
step size measured value • s e tti n g IEC : Dead Band Temp.
IEC: Dead Band 20ma 104 241
Setting to calculate the filter value for all 20mA Report Control Blocks
(RCB). Should a change occur in one of the 20mA measured values, which
is greater than the filter value, the RCB is again sent to all clients. The filter
value for each measured value is calculated according to this formula:
step size measured value • s e tti n g IEC : Dead Band 20ma
IEC: Update Cycle Energy 104 060
Cycle time to send energy value by Report Control Block (RCB). No RCB
transmission with setting to blocked!
Goose ID being sent by this device (IED). GOOSE includes a Dataset with
32 binary and configurable virtual outputs and 10 two-pole states to the
maximum of 10 monitored external devices
VLAN identifier of GOOSE being sent by this device (IED). The VLAN
identifier makes it possible to have switches in the network filter messages,
if the switches support such a function. Because so-called multicast MAC
addresses are applied, switches are unable to filter messages in the
network if they do not include a VLAN identifier.
GOOSE: VLAN Priority 106 007 Fig. 3-16
Goose ID for GOOSE, which is to be received by this device (IED) for the
virtual binary GOOSE input.
Default for the virtual binary GOOSE input. The state of a virtual two-pole
GOOSE input will revert to default as soon as the continuously monitored
communication link to a GOOSE sending device (IED situated on the
opposite side) is in fault or has disappeared altogether.
Minimum value for the GSSE repetition cycle time in ms. The repetition
cycle time for a GSSE message is calculated, according to a standard, with
this formula:
Repetition cycle time = Min. cycle + (1 + (increment/1000))N-1 [ms]
The repetitions counter N will be restarted at count 1 after each state
change of a GSSE bit pair.
GSSE: Max. Cycle 104 053 Page: 3-25
Maximum value for the GSSE repetition cycle time in s. For the formula to
calculate the repetition cycle time see Min. cycle. Should the calculated
value for the repetition cycle time be equal to or greater than the set max.
value then the GSSE message will be sent repeatedly at the set max. value
time.
GSSE: Increment 104 054
Increment for the GSSE repetition cycle. For the formula to calculate the
repetition cycle time see Min. cycle.
Setting with which GSSE bit pair the configured binary signal of the virtual
GSSE outputs is to be transmitted. A GSSE is always transmitted
consisting of a fixed number of 96 bit pairs, of which a maximum of 32 are
used by this device (IED) during a send operation.
Setting which GSSE bit pair is assigned to which virtual GSSE input.
A GSSE is always received consisting of a fixed number of 96 bit pairs, of
which a maximum of 32 are processed by this device (IED).
IED name for the virtual GSSE input used to identify a GSSE received.
Default for the virtual binary GSSE input. The state of a virtual two-pole
GSSE input will revert to default as soon as the continuously monitored
communication link to a GSSE sending device (IED situated on the opposite
side) is in fault or has disappeared altogether.
Once the password has been entered, the function keys remain active for
no longer than this time period. When this time period has elapsed the
password must again be entered.
Binary input
The P638 has optical coupler inputs for processing binary signals from the system.
The number and connection schemes for the available binary inputs are shown in the
terminal connection diagrams.
The P638 identifies the installed modules during startup. If a given binary I/O module is
not installed or has fewer binary signal inputs than the maximum number possible at this
slot, then the configuration addresses for the missing binary signal inputs are
automatically hidden in the menu tree.
When configuring binary inputs, one should keep in mind that the same function can be
assigned to several signal inputs. Thus one function can be activated from several
control points having different signal voltages.
In order to ensure that the device will recognize the input signals, the triggering signals
must persist for at least 30 ms.
The operating mode for each binary signal input can be defined. The user can specify
whether the presence (active ‘high’ mode) or absence (active ‘low’ mode) of a voltage
shall be interpreted as the logic ‘1’ signal.
Input filter which is activated when either the mode "Active ‘High’, Filt." or
Active ‘Low’, Filt." has been selected for I N P : O p e r . M o d e U x x x .
In order to suppress transient interference peaks at the logic signal inputs it
is suggested to adjust this setting to 6 [steps]. For further information see
Chapter 3.
INP: Fct. U 601 Assign 152 091 Fig. 3-19,
3-29, 3-41
INP: Fct. U 602 Assign 152 094
Setting for the minimum current that must flow in order for the P638 to
display a measured value > 0 (zero suppression).
RTDmA: IDC< Open Circuit 037 191 Fig. 3-23
If the input current falls below the set threshold, the P638 will issue an ‘open
circuit’ signal.
RTDmA: IDC 1 037 150 Fig. 3-23
Setting for the input current that will correspond to a linearized value that
has been set accordingly.
Setting for the linearized current that will correspond to an input current that
has been set accordingly.
RTDmA: Scaled Val. IDC,lin1 037 192 Fig. 3-24
Binary output
The P638 has output relays for the output of binary signals. The number and connection
schemes for the available output relays are shown in the terminal connection diagrams.
The P638 identifies the installed modules during startup. If a given binary I/O module is
not installed or has fewer output relays than the maximum number possible at that slot,
then the configuration addresses for the missing output relays are automatically hidden
in the menu tree.
The contact data of the relay used permit the use as command relay and as signal relay.
For multiply contacts, a signal can be assigned to several output relays simultaneously.
An operating mode can be defined for every output relay. Depending on the set
operating mode, the output relay is in closed circuit operation or in open circuit operation,
latching or not. The setting of the operating mode defines when the latch will be
cancelled for latched output relays.
Setting for the time period for transmission of the selected measured value
in BCD form.
mA_OP: Scale BCD 016 082 Fig. 3-31
Scaling factor setting for the measured value to be transmitted in BCD form.
The scaling factor is calculated according to the following formula:
Mx,max
scaling factor = M
x,scal
where:
Mx,scal: scaled measured value
Mx,max maximum transmitted value for the selected measured value
mA_OP: Fct. Assignm. A-1 053 000 Fig. 3-33
Setting for the time period for output of the selected measured value.
mA_OP: Scaled Min. val. A-1 037 104 Fig. 3-33
Setting for the minimum scaled measured value to be output. The value to
be set is calculated according to the following formula:
Mx,min
Mx,scal,min = M
x,RL
where:
Mx,min: minimum transmitted value
for the selected measured value
Mx,RL: range limit of the selected measured value
Setting for the scaled measured value for output that defines the knee point
of the characteristic. The value to be set is calculated according to the
following formula:
Mx,knee
Mx,scal,knee = M
x,RL
where:
Mx,knee: knee point value to be transmitted for selected measured value
Mx,RL: range limit of the selected measured value
mA_OP: Scaled Max. val. A-1 037 106 Fig. 3-33
Setting for the output current that is output for measured values smaller
than or equal to the minimum measured value setting.
Setting for the output current that is output if the measured value is on the
knee point of the characteristic.
mA_OP: AnOut Max. val. A-1 037 109 Fig. 3-33
with:
Mx,min. ... Mx,max. : measured values to be issued
mA_OP: Output Value 1 037 120 Fig. 3-33
LED indicator
The P638 has a total of 17 LED indicators. LED H1 is not configurable. It indicates the
working readiness of the device (supply voltage exists). LEDs H 2 and H 3 are also not
configurable. They indicate "Blocked/faulty" (H 2) and "Alarm" (H 3). LED H 17 indicates
that the user is in the "EDIT MODE".
An operating mode can be defined for each LED indicator. Depending on the set
operating mode, the LED indicator is in closed or in open circuit operation, latching or
not. The setting of the operation mode also defines for latched LED indicators when the
latch will be cancelled.
Selection of the primary source for date and time synchronization. Available
are COMM1, COMM2/PC, IRIG-B or a binary input for minute signal pulses.
MAIN: BackupSourceTimeSync 103 211
Selection of the backup source for date and time synchronization. Available
are COMM1, COMM2/PC, IRIG-B or a binary input for minute signal pulses.
The backup source is used when there is no synchronization generated by
the primary source after M AIN : T i m e s yn c . ti m e - o u t has elapsed.
MAIN: Time Sync. Time-Out 103 212
The user specifies the channel for which disturbance waveforms are
recorded. The figure shown illustrates an overview of the assignment.
Cancelling protection
functions
By means of a configuration procedure, the user can adapt the device functions flexibly
to the scope of protection functions required in each particular h.v. system.
The following conditions must be met before a protection function can be cancelled:
None of the signals of the protection function may be linked to other signals.
protection, end a Cancelling function group DIF_a or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
protection, end b Cancelling function group DIF_b or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
protection, channel 1 Cancelling function group CBF_1 or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
protection, channel 2 Cancelling function group CBF_2 or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
7.1.3.1 Global
This prevents any settings or commands from being sent to the relay from
the PC interface.
PC: Sig/Meas. Val.Block 003 086 Fig. 3-5
Communication interface 1 COMM1: USER Command Block 003 172 Fig. 3-6
This prevents any settings or commands from being sent to the relay from
the COMM1 interface.
COMM1: USER Sig/Meas Block 003 076 Fig. 3-7,
3-8, 3-9
When signal and measured value blocking user is activated, no signals or
measured data are transmitted through communication interface COMM1.
Communication interface 2 COMM2: USER Command Block 103 172 Fig. 3-14
This prevents any settings or commands from being sent to the relay from
the COMM2 interface.
COMM2: USER Sig/Meas Block 103 076 Fig. 3-14
Binary output OUTP: USER Outp Rel Block 021 014 Fig. 3-26
When the test mode user is activated, signals or measured data for PC and
communication interfaces are labeled 'test mode'.
MAIN: Frequency fn 010 030 Fig. 3-40,
3-120
Setting for the nominal frequency of the protected system.
MAIN: In CT. prim.,end a 019 020 Fig. 3-36
Setting for the primary nominal current of the main current transformer of
end a or b .
Setting for the primary nominal current of the main current transformer for
measurement of residual current.
MAIN: Vn V.T. prim. 010 002 Fig. 3-38
Setting for the primary nominal voltage of the system transformer for
measurement of phase-to-ground and phase-to-phase voltages.
MAIN: In Device, end a 010 024 Fig. 3-35
Setting for the nominal device current of the measuring inputs for end a or
b.
MAIN: IN,n device 010 026 Fig. 3-35
Setting for the secondary nominal current of the system transformer for
measurement of residual current. This also corresponds to the nominal
device current.
MAIN: Vn VT. Sec. 010 009 Fig. 3-35
Setting for the secondary nominal voltage of the voltage transformer for
measurement of phase-to-ground and phase-to-phase voltages.
MAIN: Wdng a CT Orientat'n 010 140 Fig. 3-35
The vector sum of the phase currents of ends a and b is governed by the
connection of the measuring circuits. If the connection is as shown in
Chapter 5, then the setting must be 'Standard'. If the connection direction is
reversed then the setting must be 'Reversed'.
MAIN: VT Orientation 010 158 Fig. 3-35
Setting for the minimum current that must be exceeded so that measured
operating values of the phase currents and, if applicable, derived currents
are displayed.
MAIN: Minimum IN Meas'mt 011 031 Fig. 3-37
Setting for the minimum current that must be exceeded so that the
measured operating value of the residual current is displayed.
MAIN: Minimum V Meas'mt 011 032 Fig. 3-38
Setting for the minimum voltage that must be exceeded so that measured
operating values of the phase-to-ground voltages, phase-to-phase voltages,
and, if applicable, derived voltages are displayed.
MAIN: Fct.Assign. Reset 1 005 248 Fig. 3-56
Setting group selection GROUP: Control via USER 003 100 Fig. 3-59
The setting of this timer stage is relevant only if setting group selection is
carried out via the binary signal inputs. Any voltage-free pause that may
occur during selection is bridged. If, after this time period has elapsed, no
binary signal input has yet been set, then the setting group selected from
the user interface (HMI) shall apply.
Selection of the signals whose appearance shall result in the signals ‘Alarm
(LED)’ and ‘Alarm (relay) and in the activation of the LED indicator labeled
‘ALARM’. Signals caused by faulty hardware and leading to blocking of the
device are not configurable. They always result in the above signals and
indication.
CHECK: Mon.Sig. Retention 021 018 Page: 3-86
Fault recording OSCIL: Fct Assig. Trigger 003 085 Fig. 3-71
This setting defines the signals that will trigger disturbance recording.
OSCIL: I>, end a 016 014 Fig. 3-71
This setting defines the threshold value of the phase current in end A of the
transformer that will trigger disturbance recording.
OSCIL: I>, end b 016 015 Fig. 3-71
This setting defines the threshold value of the phase current in end B of the
transformer that will trigger disturbance recording.
OSCIL: Id> 016 018 Fig. 3-71
This setting defines the threshold value of the differential current that will
trigger disturbance recording.
OSCIL: IN> 016 017 Fig. 3-71
This setting defines the threshold value of the residual current that will
trigger disturbance recording.
Setting for the time during which data will be recorded before the onset of a
fault (pre-fault recording time).
OSCIL: Post-Fault Time 003 079 Fig. 3-73
Setting for the time during which data will be recorded after the end of a
fault (post-fault recording time).
OSCIL: Max Record Time 003 075 Fig. 3-73
Setting for the maximum recording time per fault. This includes pre-fault
and post-fault recording times.
Setting for the minimum current that must be exceeded in order for the
measured operating values of the differential currents to be displayed.
DIFF: Minimum IR Meas'mt 011 042 Fig. 3-78
Setting for the minimum current that must be exceeded in order for the
measured operating values of the restraining currents to be displayed.
Differential protection DIFF: General Enable USER 019 080 Fig. 3-74
Setting for the rated reference power. Normally this is the rated power of
the transformer.
DIFF: Ref. Curr. Iref,a 019 023 Fig. 3-75
Transverse differential DIF_a: General Enable USER 019 081 Fig. 3-81
protection, end a Disabling/enabling of the transverse differential protection end a.
Transverse differential DIF_b: General Enable USER 019 082 Fig. 3-81
protection, end b Disabling/enabling of the transverse differential protection end b.
Definite-time overcurrent DTOC1: General Enable USER 031 135 Fig. 3-84
Definite-time overcurrent DTOC2: General Enable USER 031 136 Fig. 3-84
Definite-time overcurrent DTOCN: General Enable USER 031 138 Fig. 3-93
Inverse-time overcurrent IDMT: General Enable USER 017 096 Fig. 3-95
Thermal overload protection THERM: General Enable USER 022 050 Fig. 3-107
Time-voltage protection V<>: General Enable USER 023 030 Fig. 3-113
Over-/ Underfrequency f<>: General Enable USER 023 031 Fig. 3-116
Setting for the evaluation time. The operate conditions must be met for the
duration of the set evaluation time so that a signal is issued.
f<>: Undervolt. Block. V< 018 200 Fig. 3-118
Setting for the threshold for undervoltage blocking. If it falls below the set
threshold, the over-/under frequency protection is blocked.
Circuit breaker failure CBF_1: General Enable USER 022 100 Fig. 3-121
protection, channel 1 Disabling or enabling the circuit breaker failure protection function,
channel 1.
CBF_1: Select Meas. Input 022 102 Fig. 3-123
Circuit breaker failure CBF_2: General Enable USER 022 101 Fig. 3-121
protection, channel 2 Disabling or enabling the circuit breaker failure protection function,
channel 2.
CBF_2: Select Meas. Input 022 103 Fig. 3-123
Circuit Breaker Monitoring, CBM_1: General Enable USER 022 010 Fig. 3-124
Setting for start criteria for circuit breaker condition monitoring. To evaluate
all trip commands issued by the protection device "With Trip Cmd. Only"
must be selected. For further evaluation of operational trip commands the
additional CB auxiliary contact "CB Sig. EXT or Trip" is used.
CBM_1: In,CB 022 012 Fig. 3-129
Setting for the warning stage threshold for the number of remaining CB
operations at CB nominal current.
Setting for the warning stage threshold for the accumulated ruptured current
values.
CBM_1: –Itrip**2> 022 081
Setting for the warning stage threshold for the second power of the
accumulated ruptured current values.
CBM_1: –I*t> 022 096
Setting for the warning stage threshold for the sum of the current-time
integral of the ruptured currents.
CBM_1: Corr. Acqu.t. Trip 022 153 Fig. 3-127
Correction of the delay period between the forming of the device internal trip
command and the actual opening of the CB contacts.
CBM_1: Corr. Acqu.t.CB Sig. 022 018 Fig. 3-127
Circuit Breaker Monitoring, CBM_2: General Enable USER 007 170 Fig. 3-124
Setting for start criteria for circuit breaker condition monitoring. To evaluate
all trip commands issued by the protection device "With Trip Cmd. Only"
must be selected. For further evaluation of operational trip commands the
additional CB auxiliary contact "CB Sig. EXT or Trip" is used.
CBM_2: In,CB 007 173
Setting for the warning stage threshold for the number of remaining CB
operations at CB nominal current.
CBM_2: –Itrip> 007 181
Setting for the warning stage threshold for the accumulated ruptured current
values.
CBM_2: –Itrip**2> 007 182
Setting for the warning stage threshold for the second power of the
accumulated ruptured current values.
CBM_2: –I*t> 007 183
Setting for the warning stage threshold for the sum of the current-time
integral of the ruptured currents.
CBM_2: Corr. Acqu.t. Trip 007 184
Correction of the delay period between the forming of the device internal trip
command and the actual opening of the CB contacts.
CBM_2: Corr. Acqu.t.CB Sig. 007 185
Limit value monitoring LIMIT: General Enable USER 014 010 Fig. 3-133
Setting for operate threshold IDC,lin> for monitoring the linearized direct
current.
LIMIT: IDC,lin>> 014 111 Fig. 3-133
Setting for operate threshold IDC,lin>> for monitoring the linearized direct
current.
LIMIT: tIDC,lin> 014 112 Fig. 3-133
Setting for operate threshold IDC,lin< for monitoring the linearized direct
current.
LIMIT: IDC,lin<< 014 115 Fig. 3-133
Setting for operate threshold IDC,lin<< for monitoring the linearized direct
current.
LIMIT: tIDC,lin< 014 116 Fig. 3-133
These settings define the static input conditions for the logic function.
LOGIC: Fct.Assignm. Outp. 1 030 000 Fig. 3-141
LOGIC: Fct.Assignm. Outp. 2 030 004
These settings define the operating modes for the output timer stages.
These settings assign the function of a binary input signal to the output of
the logic equation.
These settings assign the function of a binary input signal to the output of
the logic equation.
Differential protection DIFF: Enable SGx 072 152 073 152 074 152 075 152 Fig. 3-74
This setting defines the threshold value of the differential current with which
inrush stabilization becomes ineffective.
Note: If the threshold exceeds its normal setting, the P638 may not
start if there are internal faults with transformer saturation.
DIFF: Idiff>>> SGx 072 144 073 144 074 144 075 144 Fig. 3-78
This setting defines the threshold value of the differential current that will
trigger the differential protection regardless of hold time, inrush stabilization
and saturation detection.
Note: If the threshold is set too low, the P638 may start if there are
external faults with transformer saturation.
DIFF: m1 SGx 072 145 073 145 074 145 075 145 Fig. 3-78
Knee point from which the characteristic runs with a set gradient of m2.
DIFF: Inrush 2nd HarmonSGx 072 159 073 159 074 159 075 159 Fig. 3-79
Note: The zero current filter may not be enabled if the P638 has to
work in end a with transverse differential protection.
DIFF: I0 Filt b Enab SGx 071 060 071 061 071 062 071 063 Fig. 3-68,
3-76
Disabling/enabling of the zero current filter of end b.
Note: The zero current filter may not be enabled if the P638 has to
work in end b with transverse differential protection.
Transverse differential DIF_a: Enable SGx 072 130 073 130 074 130 075 130 Fig. 3-81
protection, end a
This setting defines the setting group in which transverse differential
protection is enabled.
DIF_a: Itrans> SGx 072 131 073 131 074 131 075 131 Fig. 3-83
Transverse differential DIF_b: Enable SGx 072 134 073 134 074 134 075 134 Fig. 3-81
protection, end b
This setting defines the setting group in which transverse differential
protection is enabled.
DIF_b: Itrans> SGx 072 135 073 135 074 135 075 135 Fig. 3-83
Definite-time overcurrent DTOC1: Enable SGx 076 050 077 050 078 050 079 050 Fig. 3-84
protection 1
This setting defines the setting group in which definite-time overcurrent
protection is enabled.
DTOC1: I> SGx 076 051 077 051 078 051 079 051 Fig. 3-87
This setting defines whether the stage timer tI> is started when the current
thresholds I> are triggered or, additionally, with direction signaling.
DTOC1: Inrush Stab ="on"SGx 076 063 077 063 078 063 079 063 Fig. 3-86
Setting for the current threshold to be exceeded for the inrush stabilization
to become ineffective.
DTOC1: Beta (I>) SGx 076 068 077 068 078 068 079 068 Fig. 3-88
Angles β and γ set the range in which the I> starting signal logic determines
that the direction is 'Forward'.
DTOC1: Gamma (I>) SGx 076 073 077 073 078 073 079 073 Fig. 3-88
Angles β and γ set the range in which the I> starting signal logic determines
that the direction is 'Forward'.
DTOC1: Direction (I>) SGx 076 080 077 080 078 080 079 080 Fig. 3-90
Setting for the measuring direction for which a tI> trip signal is sent: forward,
reverse or non-directional.
DTOC1: V< (I>) SGx 076 131 077 131 078 131 079 131 Fig. 3-90
The tI> trip signal is enabled only if the voltage is lower than the set value.
If it has been set to 'Blocked' the enabling is permanently active.
DTOC1: Vmin (I>) SGx 076 157 077 157 078 157 079 157 Fig. 3-90
A direction decision of the I> overcurrent stage is possible only if the short
circuit voltage is higher than this set value.
DTOC1: Mode V<Vmin (I>) SGx 076 113 077 113 078 113 079 113 Fig. 3-90
This setting defines whether, for a short circuit voltage which is lower than
Vmin, the I> overcurrent stage should operate non-directional or should be
blocked.
DTOC1: Mode w/o V (I>) SGx 076 128 077 128 078 128 079 128 Fig. 3-90
This setting defines whether, for a voltage measuring circuit failure, the I>
overcurrent stage should operate non-directional or should be blocked.
DTOC1: Timer Start tI>> SGx 072 245 073 044 074 044 075 044 Fig. 3-87
This setting defines whether the stage timer tI>> is started when the current
thresholds I>> are triggered or, additionally, with direction signaling.
DTOC1: Beta (I>>) SGx 076 069 077 069 078 069 079 069 Fig. 3-88
Angles β and γ set the range in which the I>> starting signal logic
determines that the direction is 'Forward'.
DTOC1: Gamma (I>>) SGx 076 074 077 074 078 074 079 074 Fig. 3-88
Angles β and γ set the range in which the I>> starting signal logic
determines that the direction is 'Forward'.
DTOC1: Direction (I>>) SGx 076 088 077 088 078 088 079 088 Fig. 3-91
Setting for the measuring direction for which a tI>> trip signal is issued:
forward, reverse or non-directional.
DTOC1: V< (I>>) SGx 076 150 077 150 078 150 079 150 Fig. 3-91
The tI>> trip signal is enabled only if the voltage is lower than the set value.
If it has been set to "blocked" the enabling is permanently active.
DTOC1: Vmin (I>>) SGx 076 158 077 158 078 158 079 158 Fig. 3-91
A direction decision of the I>> overcurrent stage is possible only if the short
circuit voltage is higher than this set value.
DTOC1: Mode V<Vmin(I>>) SGx 076 127 077 127 078 127 079 127 Fig. 3-91
This setting defines whether, for a short circuit voltage which is lower than
Vmin, the I>> overcurrent stage should operate non-directional or should be
blocked.
DTOC1: Mode w/o V (I>>) SGx 076 129 077 129 078 129 079 129 Fig. 3-91
This setting defines whether, for a voltage measuring circuit failure, the I>>
overcurrent stage should operate non-directional or should be blocked.
Definite-time overcurrent DTOC2: Enable SGx 076 070 077 070 078 070 079 070 Fig. 3-84
protection 2
This setting defines the setting group in which definite-time overcurrent
protection 2 is enabled.
DTOC2: I> SGx 076 071 077 071 078 071 079 071 Fig. 3-92
Definite-time overcurrent DTOCN: Enable SGx 076 110 077 110 078 110 079 110 Fig. 3-93
protection
This setting defines the setting group in which definite-time overcurrent
protection for residual current is enabled.
DTOCN: IN>H SGx 076 111 077 111 078 111 079 111 Fig. 3-94
Inverse-time overcurrent IDMT: Enable SGx 072 000 073 000 074 000 075 000 Fig. 3-95
protection
This setting defines the setting group in which IDMT protection is enabled.
IDMT: Inrush Stab ="on"SGx 072 129 073 129 074 129 075 129 Fig. 3-101
IDMT: Min. Trip Time SGx 072 077 073 077 074 077 075 077 Fig. 3-102
This setting defines whether the stage timer tIref> is started when the IDMT
protection is triggered or, additionally, with direction signaling.
IDMT: Beta SGx 072 046 073 046 074 046 075 046 Fig. 3-103
Angles β and γ set the range in which the inverse-time overcurrent starting
signal logic determines that the direction is 'Forward'.
IDMT: Gamma SGx 072 047 073 047 074 047 075 047 Fig. 3-103
Angles β and γ set the range in which the inverse-time overcurrent starting
signal logic determines that the direction is 'Forward'.
IDMT: Direction (I>) SGx 072 048 073 048 074 048 075 048 Fig. 3-105
Setting for the measuring direction for which a tIref> trip signal is sent:
forward, reverse or non-directional.
IDMT: V< SGx 072 081 073 081 074 081 075 081 Fig. 3-105
The tIref> trip signal is enabled only if the voltage is lower than the set value.
If it has been set to "blocked" the enabling is permanently active.
IDMT: Vmin SGx 072 133 073 133 074 133 075 133 Fig. 3-105
This setting defines whether, for a short circuit voltage which is lower than
Vmin, the definite-time overcurrent protection should operate non-
directional or should be blocked.
IDMT: Mode w/o Voltage SGx 072 119 073 119 074 119 075 119 Fig. 3-105
This setting defines whether, in case of voltage measuring circuit failure, the
definite-time overcurrent protection should operate non-directional or should
be blocked.
Thermal overload protection THERM: Enable SGx 072 175 073 175 074 175 075 175 Fig. 3-107
This setting defines the setting group in which thermal overload protection is
enabled.
THERM: Iref Rating SGx 072 179 073 179 074 179 075 179 Fig. 3-111
THERM: Tim.Const 1(Heat)SGx 072 187 073 187 074 187 075 187 Fig. 3-111
Setting for the thermal time constants of the protected object with current
flow (heating time constant).
THERM: Tim.Const 2(Cool)SGx 072 188 073 188 074 188 075 188 Fig. 3-111
Setting for the thermal time constants of the protected object without current
flow (cooling time constant).
Note:
This setting option is only relevant when machines are running. In all other
cases, time constant 2 must be set equal to time constant 1.
THERM: O/T f.Iref Pers. SGx 072 167 073 167 074 167 075 167 Fig. 3-111
Selecting if and how the coolant temperature is measured: Via the PT100,
the 20 mA input or Tx (x = 1 to 9).
THERM: Default CT Amb SGx 072 186 073 186 074 186 075 186 Fig. 3-111
Setting for the default coolant temperature to be used for calculation of the
trip time if coolant temperature is not measured.
THERM: Funct.f.CTA Fail.SGx 076 177 077 177 078 177 079 177 Fig. 3-110
The setting defines how the thermal overload protection function will
continue to operate in the event of faulty coolant temperature acquisition.
User can select between 'Default Temp. Value', 'Last Meas.Temperat.' and
'Blocking'.
THERM: Minimum Temperat.SGx 076 178 077 178 078 178 079 178 Fig. 3-111
An alarm will be raised in advance of the trip. The time difference between
the alarm and the trip time is set here.
Time-voltage protection V<>: Enable SGx 076 000 077 000 078 000 079 000 Fig. 3-113
This setting defines the setting group in which V<> protection is enabled.
V<>: V> SGx 076 003 077 003 078 003 079 003 Fig. 3-114
Setting for the time limit of the signals generated by the undervoltage
stages.
V<>: Hyst. V<> Meas. SGx 076 048 077 048 078 048 079 048 Fig. 3-114
Setting for the hysteresis of the trigger stages for monitoring measured
voltages.
Over-/ Underfrequency f<>: Enable SGx 018 196 018 197 018 198 018 199 Fig. 3-116
Protection
This setting defines the setting group in which over-/underfrequency
protection is enabled.
f<>: Oper. Mode f1 SGx 018 120 018 121 018 122 018 123 Fig. 3-120
f<>: Oper. Mode f2 SGx 018 144 018 145 018 146 018 147
f<>: Oper. Mode f3 SGx 018 168 018 169 018 170 018 171
f<>: Oper. Mode f4 SGx 018 192 018 193 018 194 018 195
f<>: f3 SGx 018 148 018 149 018 150 018 151
f<>: f4 SGx 018 172 018 173 018 174 018 175
f<>: tf3 SGx 018 152 018 153 018 154 018 155
f<>: tf4 SGx 018 176 018 177 018 178 018 179
f<>: df3/dt SGx 018 156 018 157 018 158 018 159
f<>: df4/dt SGx 018 180 018 181 018 182 018 183
f<>: Delta f3 SGx 018 160 018 161 018 162 018 163
f<>: Delta f4 SGx 018 184 018 185 018 186 018 187
f<>: Delta t3 SGx 018 164 018 165 018 166 018 167
f<>: Delta t4 SGx 018 188 018 189 018 190 018 191
Circuit breaker failure CBF_1: Enable SGx 072 110 073 110 074 110 075 110 Fig. 3-121
protection, channel 1
This setting defines the setting group in which breaker failure protection is
enabled.
CBF_1: tBF1 Init M-Trip SGx 072 115 073 115 074 115 075 115 Fig. 3-122
Setting for the monitoring time of the main-trip command before issuing a
re-trip.
CBF_1: tBF2 Init ReTrip SGx 072 116 073 116 074 116 075 116 Fig. 3-122
Setting for the monitoring time of the re-trip command before issuing a
back-trip.
CBF_1: Imin< SGx 072 112 073 112 074 112 075 112 Fig. 3-123
Setting for the Imin< current threshold. Current falling below this threshold
will be interpreted as breaker opening, and reset the CBF timers.
CBF_1: tImin< SGx 072 113 073 113 074 113 075 113 Fig. 3-122
Circuit breaker failure CBF_2: Enable SGx 072 120 073 120 074 120 075 120 Fig. 3-121
protection, channel 2
This setting defines the setting group in which breaker failure protection is
enabled.
CBF_2: tBF1 Init M-Trip SGx 072 125 073 125 074 125 075 125 Fig. 3-122
Setting for the monitoring time of the main-trip command before issuing a
re-trip.
CBF_2: tBF2 Init ReTrip SGx 072 126 073 126 074 126 075 126 Fig. 3-122
Setting for the monitoring time of the re-trip command before issuing a
back-trip.
CBF_2: Imin< SGx 072 122 073 122 074 122 075 122 Fig. 3-123
Setting for the Imin< current threshold. Current falling below this threshold
will be interpreted as breaker opening, and reset the CBF timers.
CBF_2: tImin< SGx 072 123 073 123 074 123 075 123 Fig. 3-122
Limit value monitoring LIMIT: Enable SGx 072 240 073 240 074 240 075 240 Fig. 3-133
This setting defines the setting group in which the limit value monitoring
function is enabled.
LIMIT: Ia> SGx 072 221 073 221 074 221 075 221 Fig. 3-135
LIMIT: f> SGx 072 211 073 211 074 211 075 211 Fig. 3-138
The P638 generates a large number of signals, processes binary input signals, and
acquires measured data during fault-free operation of the protected object as well as
fault-related data. A number of counters are maintained for statistical purposes.
This information can be read out from the integrated user interface. All this information
can be found in the ‘Measurements + Tests’ and ‘Fault + Event Record’ folders in the
menu tree.
8.1 Operation
Measured data input RTDmA: Current IDC 004 134 Fig. 3-23
Date display.
Note: The date can also be set here.
MAIN: Time 003 091 Fig. 3-54
Thermal overload protection THERM: Status Therm.Replica 004 016 Fig. 3-111
If, on the other hand, the coolant temperature and the maximum permissible
coolant temperature have been set to the same value, then the coolant
temperature is not taken into account and the characteristic is a function of
the current only. The additional reserve amounts to zero in this case.
Substation Event
GOOSE: Output 2 State 106 012
Status Events
GSSE: Output 2 State 104 103
This display appears regardless of the binary signal input mode set.
Communication interface 1 COMM1: Command Block. EXT 003 173 Fig. 3-6
COMM1: Sig/meas. Block EXT 037 074 Fig. 3-7, 3-8,
3-9
COMM1: Command Blocking 003 174 Fig. 3-6
COMM1: Sig/Meas. Val.Block 037 075 Fig. 3-7, 3-8,
3-9
COMM1: IEC 870-5-103 003 219 Fig. 3-7
COMM1: IEC 870-5-101 003 218 Fig. 3-8
COMM1: IEC 870-5,ILS 003 221 Fig. 3-9
COMM1: MODBUS 003 223 Fig. 3-10
COMM1: DNP3 003 230 Fig. 3-11
COMM1: COURIER 103 041 Fig. 3-12
Display when an Ethernet module has not initiated properly, i.e. if the MAC
address is missing or there is a non-plausible setting parameter!
Binary output OUTP: Block Outp.Rel. EXT 040 014 Fig. 3-26
OUTP: Reset Latch. EXT 040 015 Fig. 3-26
OUTP: Outp. Relays Blocked 021 015 Fig. 3-26
OUTP: Latching Reset 040 088 Fig. 3-26
Measured data output mA_OP: Outp. Enabled EXT 036 085 Fig. 3-29
mA_OP: Reset Output EXT 036 087 Fig. 3-30
mA_OP: Enabled 037 102 Fig. 3-28
mA_OP: Output Reset 037 117 Fig. 3-30
mA_OP: Valid BCD Value 037 050 Fig. 3-31
mA_OP: 1-dig. Bit 0 (BCD) 037 051 Fig. 3-31
mA_OP: 1-dig. Bit 1 (BCD) 037 052 Fig. 3-31
mA_OP: 1-dig. Bit 2 (BCD) 037 053 Fig. 3-31
mA_OP: 1-dig. Bit 3 (BCD) 037 054 Fig. 3-31
mA_OP: 10-dig. Bit 0 (BCD) 037 055 Fig. 3-31
mA_OP: 10-dig. Bit 1 (BCD) 037 056 Fig. 3-31
mA_OP: 10-dig. Bit 2 (BCD) 037 057 Fig. 3-31
mA_OP: 10-dig. Bit 3 (BCD) 037 058 Fig. 3-31
mA_OP: 100-dig. Bit 0 (BCD) 037 059 Fig. 3-31
mA_OP: 100-dig. Bit 1 (BCD) 037 060 Fig. 3-31
mA_OP: Value A-1 Valid 069 014 Fig. 3-33
mA_OP: Value A-1 Output 037 118 Fig. 3-33
mA_OP: Value A-2 Valid 069 015
Main function MAIN: Enable Protect. EXT 003 027 Fig. 3-41
MAIN: Group Reset 1 EXT 005 209 Fig. 3-56
MAIN: Rst.Co.Cl/Tr.Cmd EXT 005 210 Fig.*: 3-56
MAIN: Group Reset 2 EXT 005 252 Fig. 3-56
MAIN: General Reset EXT 005 255 Fig. 3-2
MAIN: Disable Protect. EXT 003 026 Fig. 3-41
MAIN: Time Switching EXT 003 096 Fig. 3-54
MAIN: Blocking 1 EXT 040 060 Fig. 3-42
MAIN: Blocking 2 EXT 040 061 Fig. 3-42
MAIN: Parallel Trip 1 EXT 037 019 Fig. 3-122
MAIN: Parallel Trip 2 EXT 037 022 Fig. 3-122
MAIN: Reset Latch.Trip EXT 040 138 Fig. 3-50
MAIN: Trip Cmd. Block. EXT 036 045 Fig. 3-51
MAIN: M.c.b. Trip V EXT 004 061 Fig. 3-88,
3-90, 3-91,
3-103, 3-105,
3-113
MAIN: En.Man.Trip Cmd. EXT 039 053 Fig. 3-49
MAIN: Man. M-Trip Cmd1 EXT 039 054 Fig. 3-49
MAIN: Man. M-Trip Cmd2 EXT 039 056 Fig. 3-49
MAIN: Man. ReTrip Cmd1 EXT 039 055 Fig. 3-49
MAIN: Man. ReTrip Cmd2 EXT 039 057 Fig. 3-49
MAIN: Man. B-Trip Cmd1 EXT 039 107 Fig. 3-49
MAIN: Man. B-Trip Cmd2 EXT 039 108 Fig. 3-49
MAIN: CB1 Trip EXT 044 131
Setting group selection GROUP: Control Via User EXT 036 101 Fig. 3-59
GROUP: Activate Grp 1 EXT 065 002 Fig. 3-59
GROUP: Activate Grp 2 EXT 065 003 Fig. 3-59
GROUP: Activate Grp 3 EXT 065 004 Fig. 3-59
GROUP: Activate Grp 4 EXT 065 005 Fig. 3-59
GROUP: Control Via User 036 102 Fig. 3-59
GROUP: Ext.Sel. Settg. Grp 003 061 Fig. 3-59
GROUP: Grp1 Activated Ext. 036 094 Fig. 3-59
GROUP: Grp2 Activated Ext. 036 095 Fig. 3-59
GROUP: Grp3 Activated Ext. 036 096 Fig. 3-59
GROUP: Grp4 Activated Ext. 036 097 Fig. 3-59
GROUP: Actual Setting Group 003 062 Fig. 3-59
GROUP: Group 1 Active 036 090 Fig. 3-59
GROUP: Group 2 Active 036 091 Fig. 3-59
GROUP: Group 3 Active 036 092 Fig. 3-59
GROUP: Group 4 Active 036 093 Fig. 3-59
Operating data recording OP_RC: Reset Record. EXT 005 213 Fig. 3-56
Monitoring signal recording MT_RC: Reset Record. EXT 005 240 Fig.*: 3-56
Overload recording OL_RC: Reset Record. EXT 005 241 Fig.*: 3-56
OL_RC: Record. in Progress 035 003 Fig. 3-65
OL_RC: Overl. Mem. Overflow 035 007 Fig. 3-66
Fault recording OSCIL: Reset Record. EXT 005 243 Fig.*: 3-56
OSCIL: Trigger EXT 036 089 Fig. 3-71
OSCIL: Trigger 037 076 Fig. 3-71
OSCIL: I> Triggered, End a 035 014 Fig. 3-71
OSCIL: I> Triggered, End b 035 015 Fig. 3-71
OSCIL: Id> Triggered 035 018 Fig. 3-71
OSCIL: IN> Triggered 035 017 Fig. 3-71
OSCIL: Record. in Progress 035 000 Fig. 3-71
OSCIL: System Disturb. Runn 035 004 Fig. 3-71
OSCIL: Fault Mem. Overflow 035 001 Fig. 3-72
OSCIL: Faulty Time Tag 035 002
Definite-time overcurrent DTOC1: Blocking tI> EXT 035 120 Fig. 3-87
protection 1 DTOC1: Blocking tI>> EXT 035 121 Fig. 3-87
DTOC1: Enabled 035 102 Fig. 3-84
DTOC1: Starting I> 035 108 Fig. 3-87
DTOC1: Starting I>> 035 109 Fig. 3-87
DTOC1: tI> Elapsed 035 098 Fig. 3-87
DTOC1: Phase A Triggered 035 104 Fig. 3-87
DTOC1: tI>> Elapsed 035 099 Fig. 3-87
DTOC1: Trip Signal tI> 035 114 Fig. 3-87
DTOC1: Trip Signal tI>> 035 115 Fig. 3-87
DTOC1: Phase C Triggered 035 105 Fig. 3-87
DTOC1: Inrush Stabil.Trigg. 035 127 Fig. 3-86
DTOC1: Dir.Meas. I> Blocked 035 080 Fig. 3-90
DTOC1: Meas. I> Non-Direct. 035 077 Fig. 3-90
DTOC1: Fault I> Forward 035 137 Fig. 3-88
DTOC1: Power Flow I> Forw. 035 223 Fig. 3-88
DTOC1: Fault I> Reverse 035 140 Fig. 3-88
DTOC1: Power Flow I> Rev. 035 224 Fig. 3-88
DTOC1: Dir.Meas. I>> block. 035 133 Fig. 3-90
DTOC1: Meas. I>> Non-direct 035 078 Fig. 3-91
DTOC1: Fault I>> Forward 035 147 Fig. 3-88
DTOC1: Power Flow I>> Forw. 035 227 Fig. 3-88
DTOC1: Fault I>> Reverse 035 148 Fig. 3-88
DTOC1: Power Flow I>> Rev. 035 228 Fig. 3-88
Definite-time overcurrent DTOC2: Blocking tI> EXT 035 150 Fig. 3-92
protection 2 DTOC2: Blocking tI>> EXT 035 151 Fig. 3-92
DTOC2: Enabled 035 132 Fig. 3-84
DTOC2: Starting I> 035 138 Fig. 3-92
DTOC2: Starting I>> 035 139 Fig. 3-92
DTOC2: Starting Phase A 035 134 Fig. 3-92
DTOC2: Starting Phase C 035 135 Fig. 3-92
DTOC2: Trip Signal tI> 035 144 Fig. 3-92
DTOC2: Trip Signal tI>> 035 145 Fig. 3-92
DTOC2: Inrush Stabil.Trigg. 035 157 Fig. 3-86
Definite-time overcurrent DTOCN: Block. tIN>H EXT 035 201 Fig. 3-94
protection DTOCN: Enabled 035 192 Fig. 3-93
DTOCN: Starting IN>H 035 195 Fig. 3-94
DTOCN: Trip Signal tIN>H 035 198 Fig. 3-94
Inverse-time overcurrent IDMT: Block. tIref> EXT 040 101 Fig. 3-102
protection IDMT: Enabled 040 100 Fig. 3-95
IDMT: Starting Iref> 040 080 Fig. 3-102
IDMT: Phase A Triggered 038 117 Fig. 3-102
IDMT: tIB> Elapsed 040 082 Fig. 3-102
IDMT: Phase C Triggered 038 118 Fig. 3-102
IDMT: Trip Signal tIref> 040 084 Fig. 3-102
IDMT: Hold Time Running 040 053 Fig. 3-102
IDMT: Inrush Stabil.Trigg. 040 118 Fig. 3-101
IDMT: Buffer Empty 040 110 Fig. 3-102
IDMT: Dir. Meas. Blocked 041 006 Fig. 3-105
IDMT: Meas.Non-Directional 041 007 Fig. 3-105
IDMT: Fault Forward 041 008 Fig. 3-103
IDMT: Power Flow Forward 041 017 Fig. 3-103
IDMT: Fault Reverse 041 009 Fig. 3-103
IDMT: Power Flow Reverse 041 018 Fig. 3-103
Thermal overload protection THERM: Replica Block EXT 041 074 Fig. 3-107
THERM: CTA Error EXT 038 062 Fig. 3-110
THERM: Reset Replica EXT 038 061 Fig. 3-112
THERM: Enabled 040 068 Fig. 3-107
THERM: Not Ready 040 035 Fig. 3-107
THERM: Reclosure Blocked 039 024 Fig. 3-111
THERM: Starting k*Iref> 041 108 Fig. 3-111
THERM: Trip Signal 039 020 Fig. 3-111
THERM: Reset Replica 039 061 Fig. 3-112
THERM: Buffer Empty 039 112 Fig. 3-111
THERM: CTA Error 039 111 Fig. 3-110
THERM: Within Pre-trip Time 041 109 Fig. 3-111
THERM: Alarm 039 025 Fig. 3-111
THERM: Setting Error,Block. 039 110 Fig. 3-111
Time-voltage protection V<>: Blocking tV> EXT 041 068 Fig. 3-114
V<>: Blocking tV>> EXT 041 069 Fig. 3-114
V<>: Blocking tV< EXT 041 070 Fig. 3-115
V<>: Blocking tV<< EXT 041 071 Fig. 3-115
V<>: Enabled 040 066 Fig. 3-113
V<>: Ready 042 003 Fig. 3-113
V<>: Not Ready 042 004 Fig. 3-113
V<>: Starting V> 041 030 Fig. 3-114
V<>: Starting V>> 041 096 Fig. 3-114
V<>: Starting V< 041 037 Fig. 3-115
V<>: Starting V<< 041 099 Fig. 3-115
V<>: tV> Elapsed 041 034 Fig. 3-114
V<>: tV>> Elapsed 041 035 Fig. 3-114
V<>: tV< Elapsed 041 041 Fig. 3-115
V<>: tV< Elapsed & Vmin 041 026 Fig. 3-115
V<>: tV< Elaps. Transient 042 023 Fig. 3-115
V<>: tV<< Elapsed 041 042 Fig. 3-115
V<>: tV<< Elapsed & Vmin 041 066 Fig. 3-115
V<>: tV<< Elapsed Trans. 042 025 Fig. 3-115
V<>: Fault V< 041 110 Fig. 3-115
V<>: Fault V<< 041 112 Fig. 3-115
V<>: tV</<< Elaps. Trans. 042 007 Fig. 3-115
Circuit breaker failure CBF_1: CB Closed Sig. EXT 036 107 Fig. 3-122
protection, channel 1 CBF_1: Enabled 040 055 Fig. 3-121
CBF_1: CB Superv. Signal 039 000 Fig. 3-122
CBF_1: Failure Main-Trip 039 021 Fig. 3-122
CBF_1: Failure Re-Trip 036 056 Fig. 3-122
CBF_1: Re-Trip Signal 039 022 Fig. 3-122
CBF_1: B-trip Signal 039 023 Fig. 3-122
CBF_1: Timer tBF1 Running 036 066 Fig. 3-122
CBF_1: Timer tBF2 Running 036 110 Fig. 3-122
CBF_1: CB Failure 006 051
Circuit breaker failure CBF_2: CB Closed Sig. EXT 036 108 Fig. 3-122
protection, channel 2 CBF_2: Enabled 040 048 Fig. 3-121
CBF_2: CB Superv. Signal 039 039 Fig. 3-122
CBF_2: Failure Main-Trip 036 059 Fig. 3-122
CBF_2: Failure Re-Trip 036 106 Fig. 3-122
CBF_2: Re-Trip Signal 040 089 Fig. 3-122
CBF_2: B-trip Signal 040 104 Fig. 3-122
CBF_2: Timer tBF1 Running 036 111 Fig. 3-122
CBF_2: Timer tBF2 Running 036 112 Fig. 3-122
CBF_2: CB Failure 006 052
Circuit Breaker Monitoring, CBM_1: Reset Meas.Val. EXT 005 247 Fig.*: 3-56
Channel 1 CBM_1: Blocking EXT 044 128 Fig. 3-132
CBM_1: Enabled 044 130 Fig. 3-124
CBM_1: Blocked 044 199 Fig. 3-132
CBM_1: Setting Error CBM_1 044 204 Page: 3-171
CBM_1: Cycle Running A 044 205 Fig. 3-127
CBM_1: Cycle Running C 044 207 Fig. 3-127,
3-129
CBM_1: Sig. No. CB op. > 044 135 Fig. 3-131
CBM_1: Sig. Rem. No.CB op.< 044 136 Fig. 3-130
CBM_1: Signal –Itrip> 044 137
Circuit Breaker Monitoring, CBM_2: Reset Meas.Val. EXT 007 111 Fig.*: 3-56
Channel 2 CBM_2: Blocking EXT 007 112 Fig. 3-132
CBM_2: Enabled 007 113 Fig. 3-124
CBM_2: Blocked 007 116 Fig. 3-132
CBM_2: Setting Error CBM_2 007 126 Page: 3-171
CBM_2: Cycle Running A 007 114
Trigger for the transmission of the selected signal (as signal ‘start‘).
COMM1: Test Spont.Sig. End 003 186 Fig. 3-13
Trigger for the transmission of the selected signal (as signal ‘end‘).
Trigger for the transmission of the selected signal (as signal ‘start‘).
COMM2: Test Spont.Sig. End 103 186 Fig. 3-15
Trigger for the transmission of the selected signal (as signal ‘end‘).
Bar with state bits for all GSSE inputs, showing if the respective GSSE
sending device has logged-on and is transmitting free of fault (input 1 to
16).
GSSE: Enroll. IEDs Flags H 105 161
Bar with state bits for all GSSE inputs, showing if the respective GSSE
sending device has logged-on and is transmitting free of fault (input 17 to
32).
GSSE: Tx Message Counter 105 162
State of the continuous counter sequence for the message counter sent
with each GSSE.
State of the continuous counter sequence for state changes sent with each
GSSE.
GSSE: No. Reject. Messages 105 167
Setting for which GSSE sending device the following statistics information is
to be displayed.
GSSE: IED Receiv. Messages 105 172
State of the continuous counter sequence for the message counter received
with each GSSE.
GSSE: IED Rx Last Message 105 174
State of the continuous counter sequence for state changes received with
each GSSE.
GSSE: IED Missed Messages 105 175
Number of GSSE received after the validity time period has elapsed. This
counter is reset by G S S E : R e s e t S t a t i s t i c s .
Binary output OUTP: Reset Latch. USER 021 009 Fig. 3-26
The output relay selected for testing is triggered for the duration of the set
time ( O U T P : H o l d - T i m e f o r t e s t ).
Setting for the time period for which the selected output relay is triggered for
functional testing.
mA_OP: Reset Output USER 037 116 Fig. 3-30
Main function MAIN: General Reset USER 003 002 Fig. 3-55
The counters for counting the close and trip commands are reset.
MAIN: Group Reset 1 USER 005 253 Fig. 3-56
A trip command is issued from the front panel HMI for the 100 ms. This
setting is password-protected (see section entitled 'Password-Protected
Control Operations' in Chapter 6).
MAIN: Man.M-Trip Cmd2 USER 003 082 Fig. 3-49
A trip command is issued from the front panel HMI for the 100 ms. This
setting is password-protected (see section entitled 'Password-Protected
Control Operations' in Chapter 6).
MAIN: Man.ReTrip Cmd1 USER 003 066 Fig. 3-49
A trip command is issued from the user interface (HMI) for the 100 ms. This
setting is password-protected (see section entitled 'Password-Protected
Control Operations' in Chapter 6).
Note: This command is not executed unless the manual trip has been
configured as re-trip command.
MAIN: Man.ReTrip Cmd2 USER 003 083 Fig. 3-49
A trip command is issued from the user interface (HMI) for the 100 ms. This
setting is password-protected (see section entitled 'Password-Protected
Control Operations' in Chapter 6).
Note: This command is not executed unless the manual trip has been
configured as a re-trip command 2.
A trip command is issued from the user interface (HMI) for the 100 ms. This
setting is password-protected (see section entitled 'Password-Protected
Control Operations' in Chapter 6).
Note: This command is not executed unless the manual trip has been
configured as a back-trip command.
MAIN: Man.B-Trip Cmd2 USER 003 087 Fig. 3-49
A trip command is issued from the user interface (HMI) for the 100 ms. This
setting is password-protected (see section entitled 'Password-Protected
Control Operations' in Chapter 6).
Note: This command is not executed unless the manual trip has been
configured as a back-trip command 2.
MAIN: Warm Restart 003 039
A warm restart is carried out. The device functions as it does when the
power supply is turned on.
MAIN: Cold Restart 000 085
Operating data recording OP_RC: Reset Record. USER 100 001 Fig. 3-61
The operating data memory and the counter for operation signals are reset.
Monitoring signal recording MT_RC: Reset Record. USER 003 008 Fig. 3-62
Overload recording OL_RC: Reset Record. USER 100 003 Fig. 3-66
To manually trigger fault recording from the user interface for a "fault"
window of 500 ms.
OSCIL: Reset Record. USER 003 006 Fig. 3-72
Thermal overload protection THERM: Reset Replica USER 022 061 Fig. 3-112
Set the limit values for the ruptured currents and their squares. (An alarm is
displayed if these limit values are exceeded.)
Set the limit values for the ruptured currents and their squares. (An alarm is
displayed if these limit values are exceeded.)
Operating data recording OP_RC: Operat. Data Record. 003 024 Fig. 3-61
Monitoring signal recording MT_RC: Mon. Signal Record. 003 001 Fig. 3-62
Main function MAIN: No. General Start. 004 000 Fig. 3-45
Operating data recording OP_RC: No. Oper. Data Sig. 100 002 Fig. 3-61
Monitoring signal recording MT_RC: No. Monit. Signals 004 019 Fig. 3-62
Number of faults.
OSCIL: No. System Disturb. 004 010 Fig. 3-71
Circuit Breaker Monitoring, CBM_1: No. of CB Oper. A 008 011 Fig. 3-129
Overload data acquisition OL_DA: Overload Duration 004 102 Fig. 3-63
Display of the load current used by the thermal overload protection function
to calculate the tripping time.
OL_DA: Object Temp. THERM 004 035 Fig. 3-64
Fault data acquisition FT_DA: Fault Duration 008 010 Fig. 3-67
9 Commissioning
9.1 Introduction
Easergy MiCOM P638 transformer protection relays are fully numerical in their design,
implementing all protection and non-protection functions in software. The relays employ
a high degree of self-checking and, in the unlikely event of a failure, will give an alarm.
As a result of this, the commissioning tests do not need to be as extensive as with
non-numeric electronic or electro-mechanical relays.
Extracting the settings applied to the relay using appropriate setting software
(preferred method – using MiCOM S1)
Via the operator interface
Unless previously agreed to the contrary, the customer will be responsible for
determining the application-specific settings to be applied to the relay and for testing of
any scheme logic applied by external wiring and/or configuration of the relay’s internal
programmable scheme logic.
Before carrying out any work on the equipment, the user should be familiar with
the contents of the Technical Data section and the ratings on the equipment’s
rating label.
The Easergy MiCOM P638 relay must not be disassembled in any way during
commissioning.
Settings
When commissioning a P638 relay for the first time, sufficient time should be
allowed to become familiar with the method by which the settings are applied.
With the secondary front cover in place all keys except the key are accessible. With
the cover fitted, no protection or configuration settings can be changed.
Removing the secondary front cover allows access to all keys so that settings can be
changed, LED’s and alarms reset, and fault and event records cleared. However, for
setting and configuration cells, the appropriate password has to be entered before
changes can be made.
Reference to Menu
Addresses
To simplify the specifying of menu cell locations in these Commissioning Instructions,
they will be given in the form [menu address: FUNCTION GROUP, Cell Description].
For example, the cell for selecting the menu language (first cell in the function group) is
located in the menu under Parameters… Config Parameters… Local HMI (abbreviated
LOC) so it would be given as [003.020: Config/LOC, Language].
THESE INSTRUCTIONS ASSUME THAT THE MENU LANGUAGE WILL BE CHANGED
FROM THE FACTORY SUPPLIED REFERENCE TO THE ENGLISH 2nd LANGUAGE,
set at address 003.020.
When using MiCOM S1 software, the toolbar command Edit… Find… can be used to
jump directly to a chosen address.
Module Positions
Each internal circuit board/module has its connections terminated at a block on the rear
of the relay. The slot position of each module is numbered from 01 to 20, with slot 01 on
the left, and slot 20 at the right (viewed from rear). Each module also has a generic
alpha identifier: A, T, V, X, Y used in documentation, used to abbreviate its purpose (e.g.
V denotes a power supply module).
Terminal References
All terminals are prefixed by identifier X, and then a numeric location. The first two digits
of the location denote the module slot position as described above. Thus, X20nn would
be connection number “nn” for the terminal block in slot 20.
Minimum Equipment
Required
Multifunctional current and voltage injection test set.
Multimeter with suitable ac current range, and ac and dc voltage ranges of 0 – 300V.
Optional Equipment
Multi-finger test plug type P992 (if test block type P991 installed) or MMLB (if using
MMLG blocks)
An electronic or brushless insulation tester with a dc output not exceeding 500V (for
insulation resistance testing when required).
A portable PC, with appropriate MiCOM S1 software (this enables the rear
communications port to be tested, if this is to be used, and will also save considerable
time during commissioning).
These product checks cover all aspects of the relay which should be checked to ensure
that it has not been physically damaged prior to commissioning, is functioning correctly
and all input quantity measurements are within the stated tolerances.
If the application-specific settings have been applied to the relay prior to commissioning,
it is advisable to make a copy of the settings so as to allow their restoration later. This
could be done by:
Obtaining a setting file on a diskette from the customer (this requires a portable PC
with appropriate setting software for transferring the settings from the PC to the relay)
Extracting the settings from the relay itself (this again requires a portable PC with
appropriate setting software)
The current and voltage transformer connections must be isolated from the relay for
these checks. If a P991 or MMLG test block is provided, the required isolation can easily
be achieved by inserting test plug type P992 / MMLB which effectively open-circuits all
wiring routed through the test block.
Before inserting the test plug, reference should be made to the scheme (wiring) diagram
to ensure that this will not potentially cause damage or a safety hazard. For example,
the test block may be associated with protection current transformer circuits. It is
essential that the sockets in the test plug that correspond to the current transformer
secondary windings be shorted. In the case of an MMLB test plug, the user must make
the shorts manually on the plug BEFORE it is inserted into the MMLG test block.
Warning: Never open circuit the secondary circuit of a current transformer since the
high voltage produced may be lethal and could damage insulation.
Warning: For pin terminal relays, never disconnect the T module terminal block - it is
NOT a shorting block, and CT connections will be open circuited.
If a test block is not provided, the voltage transformer supply to the relay should be
isolated by means of the panel links or connecting blocks. The line current transformers
should be short-circuited and disconnected from the relay terminals. Where means of
isolating the auxiliary supply and trip circuit (e.g. isolation links, fuses, MCB, etc.) are
provided, these should be used. If this is not possible, the wiring to these circuits will
have to be disconnected and the exposed ends suitably terminated to prevent them from
being a safety hazard.
Visual Inspection
Carefully examine the relay to see that no physical damage has occurred since
installation.
The rating information given under the top access cover on the front of the relay should
be checked to ensure it is correct for the particular installation.
Ensure that the case earthing connection, is used to connect the relay to a local earth
2
bar using a conductor of minimum cross-sectional area 2.5mm . The case earth should
be verified, made tight to the side of the case by nut/bolt.
Isolate all wiring from the earth and test the insulation with an electronic or brushless
insulation tester at a dc voltage not exceeding 500V. Terminals of the same circuits
should be temporarily connected together.
On completion of the insulation resistance tests, ensure all external wiring is correctly
reconnected to the relay.
External Wiring
Check that the external wiring is correct to the relevant relay diagram or scheme
diagram. The relay diagram number appears on the rating label under the top access
cover on the front of the relay, written in the form P638.4xx.
If a P991 or MMLG test block is provided, the connections should be checked against
the scheme (wiring) diagram. Check the wiring against the schematic diagram for the
installation to ensure compliance with the customers' normal practice.
Auxiliary supply
The P638 relay can be operated from either a dc only or an ac/dc auxiliary supply
depending on the relay’s nominal supply rating. The incoming voltage must be within the
operating range specified in Table 9-1.
Without energising the relay measure the auxiliary supply to ensure it is within the
operating range.
It should be noted that the P638 relay can withstand an ac ripple of up to 12% of the
upper rated voltage on the dc auxiliary supply.
Do not energise the relay using the battery charger with the battery disconnected
as this can irreparably damage the relay’s power supply circuitry.
Energise the relay only if the auxiliary supply is within the specified operating ranges,
and also the power supply protective earth/ground connection is connected. The ground
conductor is connected to terminal X2027 (ring terminal relay) or X2039 (pin terminal
relay), and the minimum wire cross section is 1.5mm2. If a test block is provided, it may
be necessary to link across the front of the test plug to connect the auxiliary supply to the
relay.
The current and voltage transformer connections must remain isolated from the relay for
these checks. The trip circuit should also remain isolated to prevent accidental operation
of the associated circuit breaker.
Power-Up Verification
On application of the supply voltage, the P638 will start-up. During start-up LEDs will
flash, and the display will show a sequence of arrows on the LCD display >>>>>. After
approximately 15s the display will stabilise showing “P438”, and the relay is ready.
Verify that the “HEALTHY” LED is illuminated.
If no settings have previously been applied to the relay, the “OUT OF SERVICE” LED
may also be showing.
To allow the relay’s time and date to be maintained from an external IRIG-B source cell
[056.072: Settings/Configuration/IRIGB, IRIG-B Time Synch] must be set to ‘Enabled’
and [023.200: Settings/Configuration/IRIGB, General Enable USER] must be set to ‘Yes’.
Ensure the relay is receiving the IRIG-B signal by checking that cell [023.202:
Measurements/Log.State signals/IRIGB, IRIG-B Ready] reads ‘Yes’.
Once the IRIG-B signal is active, adjust the time offset of the universal co-ordinated time
(satellite clock time) on the satellite clock equipment so that local time is displayed.
To test this, remove the IRIG-B signal, then remove the auxiliary supply from the relay.
Leave the relay de-energised for approximately 30 seconds. On re-energisation, the
date and time in cells 003.090 and 003.091 should be correct.
Set the date and time to the correct local time and date using cells [003.091:
Measurements/Analogue Readings/MAIN, Time] and [003.090: Measurements/Analogue
Readings/MAIN, Date].
In the event of the auxiliary supply failing, the time and date will be maintained.
Therefore, when the auxiliary supply is restored, the time and date will be correct and not
need to be set again.
To test this, remove the auxiliary supply from the relay for approximately 30 seconds.
On re-energisation, the date and time in cells 003.090 and 003.091 should be correct.
Check that on pressing the ) key ALL LED indicators momentarily light and then
extinguish.
Input Opto-Isolators
(Binary Status Inputs)
This test checks that all the opto-isolated inputs on the relay are functioning correctly.
The opto-isolated inputs should be energised one at a time, as per the external wiring
diagram. Ensure correct polarity, with the positive battery voltage applied to the lowest
numbered terminal, and negative to the highest number for the input concerned (e.g.
Opto input U201 for the ring terminal relay should be energised at terminals X2013 (+ve)
and X2014 (-ve)).
If possible, the voltage applied to the opto should be generated by operation of the item
of plant which that opto normally monitors. e.g. If an opto input is assigned to 52b
(circuit breaker open), then correct wire routing and indication is best ascertained by
movement of the real contacts, or a test short connected across them.
Opto inputs are polarity-sensitive, and DC rated only. Do not energise from an
alternating current supply.
The status of each opto-isolated input can be viewed in the Measurements & Tests
subheading in the menu, under Measurements/I.O.Status Monitor, example cell for opto
Output Relays
This test checks that all the output relays are functioning correctly. It can also be used to
verify that output contact wiring is routed to the correct location, via the panel/cubicle
wiring.
Connect a continuity tester across the terminals corresponding to the output relay being
tested, as given in the external connection diagram.
The output relays should be energised one at a time. The means of operating contacts
is within the Control and Testing sub-heading in the menu, via the heading
Measurements and Tests. The user first selects which contact should be operated, at
cell [153.086: Control and Testing/OUTP, Relay assign. f test]. The contact to be
operated is selected by scrolling down the list and selecting Configure.
Once configured, stepping down to the next cell in the menu [003.043: OUTP, Relay
Test] allows the user to apply the test by selecting ‘Execute’. With default settings, the
selected contact will be operated for 1 second. Operation will be confirmed by the
continuity tester operating for a normally open contact and ceasing to operate for a
normally closed contact. Measure the resistance of the contacts in the closed state
Note: It should be ensured that thermal ratings of anything connected to the output
relays during the contact test procedure is not exceeded by the associated
output relay being operated for too long. It is therefore advised that the time
between application and removal of contact test is kept to the minimum.
Rear Communications
Port(s): COMM1 and
COMM2 (If Used)
This test should only be performed where the relay is to be accessed from a remote
location and will vary depending on the communications standard being adopted.
It is not the intention of the test to verify the operation of the complete system from the
relay to the remote location, just the relay’s rear communications port and any protocol
converter necessary.
IEC60870-5-103
Communications COMM1
Connect a portable PC running the appropriate IEC60870-5-103 Master Station software
to the relay’s EIA(RS)485 port via a EIA(RS)485 to EIA(RS)232 interface converter. It is
strongly recommended that MiCOM S1 software is used for this test, as it uses the –103
protocol for its communication.
Where the communication is –103 protocol over fibre optic, the appropriate fibre link will
need to be made and tested.
Ensure that the Relay/Octet communication address, Baud rate, and Parity settings in
the COMM1 Configuration sub-heading are set to match the Master Station set-up.
Check that communications with this relay can be established.
Ensure that the Relay/Octet communication address, Baud rate, and Parity settings in
the COMM1 Configuration sub-heading are set to match the Master Station set-up.
Ensure that the Relay/Octet communication address, Baud rate, and Parity settings in
the COMM1 Configuration sub-heading are set to match the Master Station set-up.
IEC60870-5-103
Communications COMM2
This test is only valid for relays having a second communications port fitted, COMM2.
Connect a portable PC running MiCOM S1 software to the relay’s EIA(RS)485 port via a
EIA(RS)485 to EIA(RS)232 interface converter. If the second port is being used for an
off-site MODEM link, remote access can be tested at this stage.
Ensure that the Relay/Octet communication address, Baud rate, and Parity settings in
the COMM1 Configuration sub-heading are set to match the Master Station set-up.
Must show an ambient air temperature as expected for the weather conditions.
Apply Application-Specific
Settings
There are two methods of applying the settings to the relay:
Transferring them from a pre-prepared setting file to the relay using a portable PC
running the appropriate software via the relay’s front EIA(RS)232 port, located under
the bottom access cover, or rear communications port. This method is preferred for
transferring function settings as it is much faster and there is less margin for error
If a setting file has been created for the particular application and provided on a diskette,
this will further reduce the commissioning time and should always be the case where
application-specific programmable scheme logic is to be applied to the relay.
Current Inputs
This test verifies that the accuracy of current measurement is within the acceptable
tolerances.
All relays will leave the factory set for operation at a system frequency of 50 Hz.
If operation at 16⅔ Hz, 25 Hz or 60 Hz is required then this must be set in cell
[010.030: Function Settings/Global/MAIN, Frequency fn].
Apply current equal to the line current transformer secondary winding rating to each
current transformer input in turn, checking its magnitude using a multimeter. The
corresponding reading can then be checked under Measurements/Analogue Readings.
When reading the per unit (p.u.) measurements of current, the relevant reading should
be 1 (unity).
The measurement accuracy of the relay is ±1%. However, an additional allowance must
be made for the accuracy of the test equipment being used.
Voltage Input
Apply voltage equal to the line voltage transformer secondary winding rating to the VT
input, checking its magnitude using a multimeter. The corresponding reading can then
be checked under Measurements/Analogue Readings. When reading the per unit (p.u.)
measurements of voltage, the relevant reading should be 1 (unity).
The measurement accuracy of the relay is ±0.5%. However, an additional allowance
must be made for the accuracy of the test equipment being used.
9.5 Setting Checks
The setting checks ensure that all of the application-specific relay settings (i.e. both the
relay’s function and programmable scheme logic settings), for the particular installation,
have been correctly applied to the relay.
Note (1): The trip circuit should remain isolated during these checks to prevent
accidental operation of the associated circuit breaker.
Note (2): If the user wishes the relay to be incapable of tripping the circuit breaker by
means of inhibiting the trip output contact(s), this can be set at:
To determine that the primary protection function of the relay, differential protection,
can trip according to the correct application settings
To verify correct setting of any backup overcurrent protection
To verify correct assignment of the trip contacts, by monitoring the response to a
selection of fault injections
The customer’s desired setting group to be left in-service after testing is used. This
is generally Settings Group SG1, and verification that the relay has the correct group
applied should be done by reading cell [003.062: Measurements/Log.State
Signals/GROUP, Actual Setting Group]
To enable the protection elements, ensure that the Protection is “Enabled” at cell
[003.030: Function Settings/Global/MAIN, Protection Enabled]
Checking differential
sensitivity
For single-side infeeding to an in-zone fault, the fault current characteristic crosses the
first knee of the tripping characteristic of the P638, so that an injection test will find the
Idiff> setting [072.142].
The current I to which the P638 responds for single-side feeding is calculated as follows:
z: Ends a or b
Idiff>: Set differential minimum sensitivity
Inom,z: Nominal CT current of the P638 for ends a or b
kz: Amplitude matching factor for end a or b [address 004.105 and 004.106]
The differential and restraining currents formed by the P638 are displayed as measured
operating data. They aid in assessing whether the connection of the P638 to the system
current transformers is correct. The display of differential and restraining currents is
prevented, however, if they fall below minimum thresholds that can be set by the user.
Connect the test equipment to the relay via the test block(s) taking care not to open-
circuit any CT secondary. If MMLG type test blocks are used, the live side of the test
plug must be provided with shorting links before it is inserted into the test block.
Apply a current slightly less than the Idiff> setting to the HV side CT input only (this CT is
usually the input designated as „end a“). Observe that no trip should occur, and the red
Trip LED remains extinguished.
Ramp up the current until a trip occurs and the Trip LED illuminates.
Record the current at which the relay tripped. The measured current should be within +/-
10% of the Idiff> setting (relay accuracy 5%, plus test set accuracy 5%).
Checking differential
through stability
The previous procedure should be repeated, but now to simulate current flowing through
the transformer to an out-of-zone external fault. Select an HV side (end A) CT current
equal to Inom, and an LV side (end B) current equal to: Inom x Ka / Kb .
Apply the fault currents for approximately one second. It should be observed that if both
CTs are in the correct orientation that no trip should occur.
Apply the fault current for 100ms – check and record the tripping time.
Checking transverse
differential sensitivity
These tests are performed on a per winding basis, depending on whether the DIF_a, or
DIF_b elements are enabled. The tripping sensitivity for the transverse differential
protection of either winding with a single end infeed is given by:
z: End a or b
Itrans>: Set operate value
Inom,z: CT nominal current rating for ends a or b
First start with winding (end) „a“ if enabled. Apply a current slightly less than the Itrans>
setting to one phase CT input only. Observe that no trip should occur, and the red Trip
LED remains extinguished.
Ramp up the current until a trip occurs and the Trip LED illuminates.
Record the current at which the relay tripped. The measured current should be within +/-
10% of the Itrans> setting (relay accuracy 5%, plus test set accuracy 5%).
Checking transverse
differential through stability
The previous procedure should be repeated, but with an equal and opposite current
flowing in the CT at the other end of the winding. The injection simulates current flowing
into the winding at one end, and out at the other – if the CT orientations are correct, no
trip will occur.
Apply the fault currents for approximately one second. No trip should occur.
Repeat the transverse differential tests for the second winding, if necessary.
The settings applied should be carefully checked against the required application-
specific settings to ensure that they are correct, and have not been mistakenly altered
during the injection test.
Extract the settings from the relay using a portable PC running MiCOM S1 software
via the front EIA(RS)232 port, located under the bottom access cover, or rear
communications port. Compare the settings transferred from the relay with the
original written application-specific setting record. (For cases where the customer
has only provided a printed copy of the required settings but a portable PC is
available)
Step through the settings using the relay’s operator interface and compare them with
the original application-specific setting record
Note that address “y” is the required setting group “x”, plus one
Confirm the external wiring to the current and voltage inputs is correct
Directionality check for any directionalised IDMT or DTOC1 elements
However, these checks can only be carried out if there are no restrictions preventing the
energisation of the plant being protected.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring
that has been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the relay in order to
perform any of the foregoing tests, it should be ensured that all connections are replaced
in accordance with the relevant external connection or scheme diagram.
Current Connections
For each current input to the relay, verify that the analogue reading is as expected.
When reading the per unit (p.u.) measurements of current, the relevant reading should
be 1 (unity) when the line current is equal to the [In C.T. Prim.] setting in A.
Firstly the actual direction of power flow on the system must be ascertained, using
adjacent instrumentation or protection already in-service, or a knowledge of the
prevailing network operation conditions.
Check the [005.014] and [005.016] load angle readings to check they are as
expected. In general, the end „a“ load angle for a transformer subjected to traction
loading would be expected to be small (within the range +/- 45o).
Remove all test or temporary shorting leads, etc. If it has been necessary to disconnect
any of the external wiring from the relay in order to perform the wiring verification tests, it
should be ensured that all connections are replaced in accordance with the relevant
external connection or scheme diagram.
If a P991/MMLG test block is installed, remove the P992/MMLB test plug and replace the
cover so that the protection is put into service.
Date: Engineer:
S/Station Circuit:
System Frequency:
This section should be completed to allow future identification of protective devices that have been commissioned using
equipment that is later found to be defective or incompatible but may not be detected during the commissioning
procedure.
Product Checks
Tick as Appropriate
Tick as Appropriate
Tick as Appropriate
Tick as Appropriate
Tick as Appropriate
Tick as Appropriate
Tick as Appropriate
Tick as Appropriate
Tick as Appropriate
Current Inputs
ΙN A p.u. na
Voltage Input
VT Ratio / (prim/sec)
V V p.u.
Tick as Appropriate
Tick as Appropriate
On-Load Checks
Tick as Appropriate
Tick as Appropriate
Final Checks
Tick as Appropriate
Date Date
Safe electronic storage, under the control of the customer’s quality system, will permit
easy re-use and/or modification of settings in the future.
10 Troubleshooting
This chapter describes problems that might be encountered, their causes, and possible
methods for eliminating them. It is intended as a guide only, and in cases of doubt it is
better to return the P638 to the manufacturer. Please follow the packaging instructions
in the section entitled "Unpacking and Packing" in Chapter 5 when returning equipment
to the manufacturer.
Problem:
Before checking further, disconnect the P638 from the power supply.
If the fuse is defective, it should not be replaced without determining the cause of
failure. If a fuse is replaced without eliminating the problem, there is the danger
that the damage will spread.
Required Fuses:
Identify the specific problem by reading out the monitoring signal memory (see
section "Monitoring Signal Memory Readout" in Chapter 6). The table below lists
possible monitoring or alarm indications (provided that a configuration setting has
been entered at C H E C K : F c t As s i g n . F a u l t, the faulty area, the P638
response, and the mode of the output relay configured for 'Alarm' and
'Blocked/Faulty'.
Key:
-: No reaction and/or no output relay triggered.
Updating: The output relay configured for 'Alarm' starts only if the monitoring
signal is still present.
1)
: The 'Blocked/Faulty' output relay only operates if the signal has been
configured at M A I N : F c t A s s i g n F a u l t .
2)
: The 'Alarm' output relay only operates if the signal has been
configured at C H EC K: F c t. As s i g n . Al a r m .
CHECK: Cold Restart 093 024
A cold restart has been carried out on account of a checksum error in the
memory (NOVRAM).
The +15 V internal supply voltage has dropped below a minimum value.
The +24 V internal supply voltage has dropped below a minimum value.
The checksum feature of analog I/O module Y has detected a fault in the
data transmission of the Dual-Port-RAM.
Undefined interrupt.
Faulty test pattern in the RAM. This can occur, for example, if the processor
module or the power supply module is removed from the bus module
(digital). This fault is only detected during device start-up. After the fault is
detected, the software initializes the RAM. This means that all records are
deleted.
Software overload.
Incorrect or invalid software for analog I/O module has been downloaded.
An invalid characteristic has been set for the circuit breaker monitoring
function.
The maximum number of the circuit breaker operations has been exceeded.
The maximum opening time of a circuit breaker contact has been exceeded.
Disconnection is not determined for this CB pole.
An invalid characteristic has been set for one of the analog output channels
of analog I/O module Y.
An invalid characteristic has been set for the analog input channel of analog
I/O module Y.
The P638 has detected an open circuit in the connection of the resistance
thermometer.
The P638 has detected an open circuit in the connection of the 20 mA input.
11 Maintenance
Only qualified personnel, familiar with the "Warning" page at the beginning of this
manual, may work on or operate this device.
The P638 is a low-maintenance device. The components used in the units are selected
to meet exacting requirements. Recalibration is not necessary.
Maintenance procedures in
the power supply area
Electrolytic capacitors are installed in the power supply area because of dimensioning
requirements. The useful life of these capacitors is significant from a maintenance
standpoint. When the equipment is operated continuously at the upper limit of the
recommended temperature range (+55°C or 131°F), the useful life of these components
is 80,000 hours, or more than 9 years. Under these conditions, replacement of the
electrolytic capacitors is recommended after a period of 8 to 10 years. When the
operating temperatures are approx. +45°C inside the devices, the required maintenance
interval can be increased by about 1 year.
The P638 is equipped with a lithium battery for non-volatile storage of fault data and for
keeping the internal clock running in the event of failure of the auxiliary power supply.
Loss of capacity due to module-internal self-discharging amounts to less than 1% per
year over a period of availability of 10 years. Since the terminal voltage remains virtually
constant until capacity is exhausted, usefulness is maintained until a very low residual
capacity is reached. With a nominal capacity of 850 mAh and discharge currents of only
a few µA during device storage or in the range of the self-discharge current during
device operation, the result is a correspondingly long service life. It is therefore
recommended that the lithium battery only be replaced after the maintenance interval
cited above.
Always turn off the power (supply voltage) before removing a hardware module.
The power supply must be turned off for at least 5 s before power supply module V is
removed. Otherwise there is the danger of an electric shock.
Electrolytic capacitor:
on power supply module V.
Lithium battery:
on power supply module V.
There is a danger of explosion if the electrolytic capacitor and battery are not properly
replaced. Always check to make sure that the polarity of the electrolytic capacitor and the
battery is correct.
After the maintenance procedures described above have been completed, new
commissioning tests as described in Chapter 9 must be carried out.
The P638 incorporates in its system a very extensive self-monitoring function for
hardware and software. The internal structure guarantees, for example, that
communication within the processor system will be checked on a continuing basis.
Nonetheless, there are a number of sub-functions that cannot be checked by the self-
monitoring feature without injection testing from the device terminals. The respective
device-specific properties and settings must be observed in such cases.
In particular, none of the control and signaling circuits that are run to the device from the
outside are checked by the self-monitoring function.
The best way to carry out a static test of the analog input circuits is to check the primary
measured operating data using the operating data measurement function or to use a
suitable testing instrument. A "small" measured value (i.e. 0.5 In) and a "large"
measured value (i.e. 4 In) should be used to check the measuring range of the A/D
converter. This makes it possible to check the entire dynamic range.
The dynamic test is not absolutely necessary, since only the stability of a few passive
components is checked. Based on reliability analysis, the statistical expectation is that
only one component in 10 years in 1000 devices will be outside the tolerance range.
Additional analogue testing is not necessary, in our opinion, since information processing
is completely numerical and is based on the measured analogue voltage values. Proper
operation was checked in conjunction with type testing.
Binary outputs
With respect to binary outputs, the integrated self-monitoring function includes even two-
phase triggering of the relay coils of all the relays. There is no monitoring function for
the external contact circuit. In this case, the all-or-nothing relays must be triggered by
way of device functions or integrated test functions. For these testing purposes,
triggering of the output circuits is integrated into the software through a special control
function (‘M+T/C+Test/’ folder).
Before starting the test, open any triggering circuits for external devices so that no
inadvertent switching operations will take place.
Serial interfaces
The integrated self-monitoring function for the PC or communication interface also
includes the communication module. The complete communication system, including
connecting link and fiber-optic module (if applicable), is always totally monitored as long
as a link is established through the control program or the communication protocol.
12 Storage
If the units are stored without being connected to auxiliary voltage, then the electrolytic
capacitors in the power supply area need to be recharged every 4 years. Recharge the
capacitors by connecting auxiliary voltage to the P638 for approximately 10 minutes.
If the units are stored during a longer time, the battery of the power supply module is
used for the continuous buffering of the event data in the working memory of the
processor module. Therefore the battery is permanently required and discharges
rapidly. In order to avoid this continuous discharge, it is recommended to remove the
power supply module from the mounting rack during long storage periods. The contents
of the event memory should be previously read out and stored separately!
The P638 is supplied with standard labeling for the LED indicators. LED indicators that
are not already configured and labeled can be labeled using the label strips supplied.
Affix the label strips to the front of the unit at the appropriate location.
The label strips can be filled in using a Stabilo brand pen containing water-resistant ink
(Type OH Pen 196 PS).
P638
PCS Cell No. 1234 5 6 7 8 9 10 11 12, 13 15 16 18
Transformer Differential Protection P638- N N N N N N N AA A A A
Transformer Differential Protection P638- 0 -302 -4xx -610 -46x -9x x -8xx
Basic device:
Basic device 84TE, pin-terminal connection, 7 -403
Basic device 84TE, ring-terminal connection, 8 -404
basic complement with 4 binary inputs, 8 output relays
and 6 function keys
Current transformer:
Inom = 1 A / 5 A (T11;T13 / T21;23 / T4)
2) 9
Voltage transformer:
Vnom = 50 ... 130 V (1-pole) 1
Language:
English (German)
4) Without order extension No.
Px40 English (English)
4) On request -800
German (English)
4) -801
French (English)
4) On request -802
Spanish (English)
4) On request -803
A Glossary
B Signal List
C Overview of Changes
Contents
A Glossary A-1
A1 Function Groups A-1
A2 Modules A-2
A3 Symbols A-3
A4 Examples of Signal Names A-10
A5 Symbols Used A-11
A1 Function Groups
A2 Modules
A: Communication module
B: Bus module
L: HMI module
P: Processor module
T: Transformer module
V: Power supply module
X: Binary I/O module
Y: Analog I/O module
A3 Symbols
Graphic symbols for block diagrams
Binary elements in compliance with DIN 40900 part 12, September 1992, IEC 617-12:
modified 1991
Analog information processing according to DIN 40900 Part 13, January 1981;
To document the linking of analog and binary signals, additional symbols have been
used, taken from several DIN documents.
As a rule, direction of the signal flow is from left to right and from top to bottom. Other
flow directions are marked by an arrow. Input signals are listed on the left side of the
signal flow, output signals on the right side.
Note:
This rule does not necessarily apply to configurations
with two or more signal flow directions, such as for
symbols with a control block and an output block.
Components of a symbol
A symbol consists of a contour or contour combination
and one or more qualifiers.
Control block
A control block contains an input function common to
several symbols. It is used for the collective setting of
several trigger elements, for example.
Output block
An output block contains an output function common
to several symbols.
D5Z08X6B
State input
Only the state of the binary input variable is read.
Negation of an output
The value up to the boundary line is negated at the
output.
Negation of an input
The input value is negated before the boundary line.
AND element
The output variable will be 1 only if all input variables
are 1.
OR element
The output variable will be 1 only if at least one input
variable is 1.
Threshold element
The output variable will be 1 only if at least two input
variables are 1. The number in the symbol may be
replaced by any other number.
(m out of n) element
The output variable will be 1 only if at least one input
variable is 1.
Delay element
The transition from value 0 to 1 at the output occurs
after a time delay of t1 relative to the corresponding
transition at the input.
The transition from value 1 to 0 at the output occurs
after a time delay of t2 relative to the corresponding
transition at the input.
Monostable flip-flop
The output variable will be 1 if the input variable
changes to 1. The output variable will remain 1 for
100 ms, regardless of the duration of the input value
1 (non-retriggerable).
Analog-digital converter
An analog input signal is converted to a binary
signal.
Subtractor
The output variable is the difference between the
two input variables.
A summing element is obtained by changing the
minus sign to a plus sign at the symbol input.
Memory, general
Storage of a binary or analog signal.
Non-stable flip-flop
When the input variable changes to 1, a pulse
sequence is generated at the output.
Amplifier
The output variable is 1 only if the input variable is
also 1.
Counter
At the + input the input variable transitions from 0 to
1 are counted and stored in the function block.
At the R(eset) input a transition of the input variable
from 0 to 1 resets the counter to 0.
Electromechanical drive
in general, here a relay, for example.
Input transducer
with conductor and device identifiers
(according to DIN EN 60445)
Change-over contact
with device identifier
Special symbol
Output relay in normally-energized arrangement
(‘closed-circuit operation’).
PC interface
with pin connections
Multiplier
The output variable is the result of the multiplication
of the two input variables.
Divider
The output variable is the result of the division of
the two input variables.
Comparator
The output variable becomes 1 only if the input
variable(s) are equal to the function in the function
block.
Formula block
The output variable becomes 1 only if the input
variable(s) satisfy the equation in the function block
OSCIL: Fault recording n Internal signal names are not coded by a data model
305 100
address. In the block diagrams they are marked with a
diamond. The small figure underneath the signal
name represents a code that is irrelevant to the user.
The internal signal names used and their origins are
listed in Appendix B.
DIST: VNG>> triggered Signal names coded by a data model address are
[ 036 015 ] represented by their address (shown in square
brackets). Their origin is given in Chapters 7 and 8.
MAIN: General Reset A specific setting to be used later on is shown with its
[ 003 002 ] signal name, address, and the setting preceded by
1: Execute the setting arrow.
A5 Symbols Used
Symbol Meaning
t Time duration
V Complex voltage
I Electrical current
I Complex current
Z Complex impedance
f Frequency
δ Temperature in °C
Σ Sum, result
α Angle
τ Time constant
This section incorporates Section 8 of EN 60870-5-101 (1996), which includes a general definition of the telecontrol
interface for substation control systems.
B 2.1 Interoperability
This application-based standard (companion standard) specifies parameter sets and other options from which subsets
are to be selected in order to implement specific telecontrol systems. Certain parameters such as the number of bytes
(octets) in the COMMON ADDRESS of the ASDU are mutually exclusive. This means that only one value of the defined
parameter is allowed per system. Other parameters, such as the listed set of different process information in the
command and monitor direction, permit definition of the total number or of subsets that are suitable for the given
application. This section combines the parameters given in the previous sections in order to facilitate an appropriate
selection for a specific application. If a system is made up of several system components supplied by different
manufacturers (“equipment stemming”), then it is necessary for all partners to agree on the selected parameters.
Note: The overall definition of a system may also require individual selection of certain parameters for specific
parts of a system such as individual selection of scaling factors for individually addressable measured
values.
1
See National Preface of EN 60870-5-101.
P638/EN M/Aa2 // AFSV.12.10180 D /// P638-302-403/404-610 B-3
Appendix B - Signal List
(continued)
1
See National Preface of EN 60870-5-101.
2
The transmission rates for control direction and monitor direction must be identical.
B-4 P638/EN M/Aa2 // AFSV.12.10180 D /// P638-302-403/404-610
Appendix B - Signal List
(continued)
Frame format FT 1.2, single character 1, and the fixed time-out interval are used exclusively in this companion
standard.
x Two octets 2
1
See National Preface of EN 60870-5-101.
2
Balanced only.
P638/EN M/Aa2 // AFSV.12.10180 D /// P638-302-403/404-610 B-5
Appendix B - Signal List
(continued)
Mode 1 (least significant octet first), as defined in clause 4.10 of IEC 870-5-4, is used exclusively in this companion
standard.
x Three octets
1
See National Preface of EN 60870-5-101.
B-6 P638/EN M/Aa2 // AFSV.12.10180 D /// P638-302-403/404-610
Appendix B - Signal List
(continued)
<14> = Measured value, short floating point value with time tag M_ME_TC_1
x <18> = Packed start events of protection equipment with time tag ME_EP_TB_1
x <19> = Packed output circuit information of protection equipment with time tag M_EP_TC_1
1
Incorrectly identified with control direction in IEC 870-5-101.
P638/EN M/Aa2 // AFSV.12.10180 D /// P638-302-403/404-610 B-9
Appendix B - Signal List
(continued)
1
The command procedure is formally processed, but there is no change in the local time in the station.
B-10 P638/EN M/Aa2 // AFSV.12.10180 D /// P638-302-403/404-610
Appendix B - Signal List
(continued)
<122> = Call directory, select file, call file, call section F_SC_NA_1
1
B 2.1.5 Basic Application Functions
x Remote initialization
x Global
x Group 5 x Group 11
x Clock synchronization
1
See National Preface of EN 60870-5-101.
B-12 P638/EN M/Aa2 // AFSV.12.10180 D /// P638-302-403/404-610
Appendix B - Signal List
(continued)
Direct set point command transmission Select and execute set point command
x No additional definition
Persistent output
x Threshold value
Smoothing value
This section incorporates Section 8 of IEC 60870-5-103, including definitions applicable to the P638.
B 3.1 Interoperability
x EIA RS 485
Note: EIA RS 485 defines the loads in such a way that 32 of them can be operated on one line. For detailed information
see EIA RS 485, Section 3.
x Glass fiber
x Plastic fiber
x F-SMA connector
BFOC/2.5 connector
x 9 600 bit/s
x 19,200 bit/s
Mode 1 (least significant octet first) as defined in clause 4.10 of IEC 60870-5-4 is used exclusively in this companion
standard.
x <3> Reset CU
<5> Power on
x <36>1 Trip circuit supervision 041 200 CHECK: Relay Kxx Faulty
1
The message content is formed from the OR operation of the individual signals
B-18 P638/EN M/Aa2-S // AFSV.12.10180 D /// P638-302-403/404-610
Appendix B - Signal List
(continued)
<69> Trip A
<70> Trip B
<71> Trip C
<78> Level 1
<79> Level 2
<80> Level 3
<81> Level 4
<82> Level 5
<83> Level 6
<128> CB ‘on’ by AR
<130> AR blocked
<144> Measurand I
<145> Measurands I, V
<146> Measurands I, V, P, Q
x <23>1 Activate characteristic 1 003 060 GROUP: Setting Grp Sel USER
x <24>2 Activate characteristic 2 003 060 GROUP: Setting Grp Sel USER
x <25>3 Activate characteristic 3 003 060 GROUP: Setting Grp Sel USER
x <26>4 Activate characteristic 4 003 060 GROUP: Setting Grp Sel USER
1
Switches GROUP: Setting Grp Sel USER to "Setting Group SG1"
2
Switches GROUP: Setting Grp Sel USER to "Setting Group SG2"
3
Switches GROUP: Setting Grp Sel USER to "Setting Group SG3"
4
Switches GROUP: Setting Grp Sel USER to "Setting Group SG4"
B-24 P638/EN M/Aa2-S // AFSV.12.10180 D /// P638-302-403/404-610
Appendix B - Signal List
(continued)
x Test mode
x Disturbance data
Generic services
x Private data
B 3.1.3.6 Miscellaneous
Measured values are transmitted both with ASDU 3 and ASDU 9. As defined in Sec. 7.2.6.8, the maximum MVAL can
be either 1.2 or 2.4 times the rated value. In ASDU 3 and ASDU 9, different ratings may not be used; in other words,
there is only one choice for each measurand.
Current L2
Current L3
Voltage L1-E
Voltage L2-E
Voltage L3-E
Active power P
Reactive power Q
Frequency f
Voltage L1-L2
Version Changes
P638-301-401/402-601 First delivery version
Release: 24/09/2002
P638-301-401/402-602 Hardware No modifications
Release: 20/01/2003 Diagram No modifications
Software
DVICE Bug fixing:
The device was blocked following a start-up if either one of the
protections V<> or f<> were enabled, due to erroneous hardware self-
identification.
PC The configuration option for cyclic telegrams with measured operating
values was modified in such a way that non-supported ASDUs per IEC
where removed from the selection table.
The selection table position “Spontaneous signal enable” (address
003.177) was expanded by the setting options “VDEW Only“ and
“VDEW + Selected Sig.”.
These configuration settings used to generate cyclic telegrams are not
supported and were therefore removed from the data model:
003 055 C O M M 1 : D e l t a V
003 056 C O M M 1 : D e l ta I
003 057 C O M M 1 : D e l t a f
003 059 C O M M 1 : D e l t a P
COMM1 The selection table position “Spontaneous signal enable” (address
003.177) was expanded by the setting options “VDEW Only“ and
“VDEW + Selected Sig.”.
These configuration settings used to generate cyclic telegrams are not
supported and were therefore removed from the data model:
003 050 C O M M 1 : D e l t a V
003 051 C O M M 1 : D e l t a I
003 052 C O M M 1 : D e l t a f
003 054 C O M M 1 : D e l t a P
COMM2 The configuration option for cyclic telegrams with measured operating
values was modified in such a way that non-supported ASDUs per IEC
where removed from the selection table.
These configuration settings used to generate cyclic telegrams are not
supported and were therefore removed from the data model:
103 050 C O M M 1 : D e l ta V
103 051 C O M M 1 : D e l ta I
103 052 C O M M 1 : D e l ta f
103 054 C O M M 1 : D e l ta P
CBF_1 The setting "Select meas. input" was removed from the setting groups
and included in "Main Function" (similar to DTOC, IDMT, THERM).
CBF_2 The setting "Select meas. input" was removed from the setting groups
and included in "Main Function" (similar to DTOC, IDMT, THERM).
Version Changes
P638-301-401/402-602-701 Hardware No modifications
Release: 26/09/2003 Diagram No modifications
Software
THERM Bug fixing:
A setting error (if present) is now only signaled when the respective
function is enabled (e.g. 040 068 T H ER M : E n a b l e d = 'Yes').
The status signal 040 068 T H ER M : E n a b l e d is now independent
from the simultaneous (prohibited) enabling of the relative and absolute
replicas
(setting 022 064 T H ER M : R e l a ti ve R e p l i c a = 'Yes'
AND 022 065 T H ER M : Ab s o l u te R e p l i c a = 'Yes')
The coordination of the operate delay for the monitoring signal for the
measured data input 040 190 R T D m A: PT 1 0 0 F a u l t y = 'Yes' and
the plausibility check of the coolant temperature acquisition, integrated in
the thermal overload protection, have now been improved. This
measure prevents the danger of incorrect tripping when an open wire is
present.
P638-301-401/402-603 Hardware No modifications
Release: 10/12/2003 Diagram No modifications
Software
THERM Bug fixing:
In case the overload protection is blocked (setting 072 178
T H ER M : Bl k fo r C T A F a i l SG 1 = 'Yes') because of a faulty coolant
temperature acquisition then the trip signal is not reset if this fault
occurred simultaneously to the trip signal.
In case of a fault in the coolant temperature acquisition the thermal
modeling will then be continued on the basis of the measured current
alone. All THERM signals will be reset (except CTA fault signals) and all
THERM measured values (except the status of the thermal replica) will
be set to 'Not Measured'.
IDMT Bug fixing:
The minimum voltage for the directional operation
(072 133 ID M T : Vm i n SG 1 ) can now no longer be set to 'Blocked'.
OP_RC The list of possible entries has been modified such that all LIMIT stages
do no longer enter starting signals, but only the signal 'timer stage
elapsed'.
Version Changes
P638-302-403/404-610 Hardware Now the new text display panel is available featuring 6 function keys that
offer user-definable functional assignment and a total of 23 multi-colored
Release: 15/08/2008
LED indicators. 18 of these red and green LED indicators offer user-
definable functional assignment (amber/yellow is present when both red
and green colors are illuminated simultaneously).
Furthermore there is an optional binary I/O module X (4H), with 4 high-
break contacts available.
As ordering options for input switching thresholds, further input switching
thresholds (e.g. 18V, 73V, 90V, 146V, 155V) are now available in
addition to the 24V standard variant.
A further new option is an Ethernet communication board providing the
communications protocol per IEC 61850.
Diagram The updated terminal connection diagrams now include the connections
of the new binary output module fitted with 4 high-break contacts.
Software
DVICE The previous menu point 000 001 D VIC E: O r d e r N o . is replaced by
001 000 D VIC E: AFS Order No.
001 200 D V I C E : P C S O r d e r N o .
The following device menu points have been added:
001 201 D VIC E: L o c a ti o n
002 059 D V I C E : D M I E C 6 1 8 5 0 V e r s i o n
002 131 D V I C E : S W V e r s i o n D H M I
002 132 D V I C E : S W V e r s i o n D H M I D M
PC, The values AREVA and AREVA D can now be selected as the
COMM1, manufacturer. This is relevant for the following menu points:
COMM2 003 183 P C : M a n u f a c t u r e r
003 161 C O M M 1 : M a n u f a c t u r e r
103 161 C O M M 2 : M a n u f a c t u r e r
(Remark: With the P638, as with all MiCOM P railway protection relays,
the manufacturer’s name is only visible in COMM1 when the setting at
address 003 215 C O M M 1 : IEC 8 7 0 - 5 E n a b l e d is set to 'Yes'.)
Version Changes
IEC, The communications protocol per IEC 61850 has been implemented.
GOOSE, An active monitoring of the communications links to logged-on clients
GSSE has been implemented with setting:
104 062 T C P K e e p - A l i v e T i m e r
(This active monitoring replaces the passive monitoring at setting
104 050 IEC : In a c ti vi ty ti m e r .)
Implementation of an automatic switchover to daylight saving time,
activated by setting 104 219 IEC : Sw i tc h .d a yl .s a v.ti m e .
Switchover times for the automatic switch to daylight saving time are
governed by the following settings:
104 220 IEC : D a yl .Sa v.T i m e Sta r t
104 221 IEC : D a yl .Sa v.T i m e St. d
104 222 IEC : D a yl .Sa v.T i m e St. m
104 223 IEC : D a yl .Sa v. t . S t . 0 : 0 0 +
104 225 IEC : D a yl .Sa v.T i m e En d
104 226 IEC : D a yl .Sa v.T i m e En d d
104 227 IEC : D a yl .Sa v.T i m e En d m
104 228 IEC : D a yl .Sa v. t . E n d 0 : 0 0 +
Instead of setting a router address and target network so as to establish
a communications link to a client situated exterior to the local network,
now only the setting of the gateway address is required via:
104 011 IEC : G a te w a y Ad d r e s s .
F_KEY This new function group is now available and can be used to configure
function keys situated on the front panel user interface (HMI).
LED Configuration capabilities for the LED indicators (e.g. multi-colored and
increased numbers) have been adapted to the hardware.
INP In order to comply with standard IEC 60255-22-7, class A the setting
010 220 IN P: F i l te r is now available.
Version Changes
MAIN A primary and a backup source for time of day synchronization may now
be set.
Version Changes
CHECK A number of device bugs previously led to a blocking with the second
entry to the monitoring signal memory (i.e. if the recurring fault was
already stored in the monitoring signal memory – see Chapter 10 in the
Technical Manual). This reaction was changed in such a manner that
device blocking will only occur if a renewed appearance of the same
device fault lies within a set "memory retention time" (021 018
C H E C K : M o n . S i g . R e t e n t i o n ). This makes it possible to tolerate
sporadic faults, resulting from control actions, without having to clear the
monitoring signal memory in the interim.
The significance of the time stamp was modified to accommodate this
new feature. The time stamp now represents the last appearance of the
fault.
In the course of platform harmonization, the configuration table of the
user-defined alarm condition has been supplemented by the
instantaneous outputs 30 to 32 and the timed outputs 30 to 32 (t) of the
programmable logic:
098 053 CHECK: Output 30 ↔ 042 090 LOGIC: Output 30
098 054 CHECK: Output 30 (t) ↔ 042 091 LOGIC: Output 30 (t)
098 055 CHECK: Output 31 ↔ 042 092 LOGIC: Output 31
098 056 CHECK: Output 31 (t) ↔ 042 093 LOGIC: Output 31 (t)
098 057 CHECK: Output 32 ↔ 042 094 LOGIC: Output 32
098 058 CHECK: Output 32 (t) ↔ 042 095 LOGIC: Output 32 (t)
These LOGIC outputs can be included in the list of alarm signals by
selection at C H EC K: F c t As s i g n . Al a r m and they are also recorded
in the monitoring signal memory.
These signals can be used to create an alarm signal under complex
application conditions. This signaling has no influence on the device's
operation (i.e. no warm restart or blocking).
The following new menu points / self-checking points have been added:
098 020, 098 078 C H E C K : S e t t i n g E r r o r C B M _ x (x=1, 2)
098 066, 098 079 C H E C K : C B x N o . C B O p . > (x=1, 2)
098 067, 098 085 C H E C K : C B x R e m . N o . C B o p . < (x=1, 2)
098 068, 098 086 C H E C K : C B x Σ I t r i p > (x=1, 2)
098 069, 098 087 C H E C K : C B x Σ I t r i p * * 2 > (x=1, 2)
098 070, 098 088 C H E C K : C B x t m a x> A (x=1, 2)
098 077, 098 090 C H E C K : C B x t m a x> C (x=1, 2)
FT_DA The following English menu point has been renamed (without changing
the German menu point text):
006 083 F T _ D A : R e s t r a i n C u r r e n t 2
(was previously: R e s tr a i n C u r r e n t 1 )
DIFF There is now a zero current filter available for the low voltage side of the
transformer.
THERM The further operation may now be selected when there is a CTA failure.
076 177 T H E R M : F u n c t . f . C T A F a i l . S G x
A minimum coolant temperature may be set for the power feed of
catenary sections situated in long tunnels:
076 178 T H E R M : M i n i m u m T e m p e r a t . S G x
The following setting has been deleted:
072 178 T H E R M : B l k f o r C T A F a i l S G x
Version Changes
DTOC_1, The menu points
IDMT 071 146 D T O C 1 : T i m e r S t a r t t I > S G x
072 245 D T O C 1 : T i m e r S t a r t t I > > S G x
006 061 I D M T : T i m e r S t . t I r e f > S G x
can be used to define whether the respective stage timer is started when
the protection is triggered or, additionally, with direction signaling.
The load flow direction can now be determined when the short-circuit
direction determination has been enabled.
The following menu points have been renamed:
035 104 D T O C 1 : P h a s e A T r i g g e r e d
(previously: D T O C 1 : S t a r t i n g P h a s e A )
035 105 D T O C 1 : P h a s e C T r i g g e r e d
(previously: D T O C 1 : S t a r t i n g P h a s e C )
038 117 I D M T : P h a s e A T r i g g e r e d
(previously: I D M T : S t a r t i n g I r e f > ,A )
038 117 I D M T : P h a s e C T r i g g e r e d
(previously: I D M T : S t a r t i n g I r e f > ,C )
DTOCN The text in all menu points has been changed (if present) from "IN>" and
"tIN>" to "IN>H" and "tIN>H" where the letter "H" stands for "high
current". For example:
076 111 D T O C N : I N > H S G 1
(previously: D T O C N : IN> SG1)
CBF_1, The following signals are now available:
CBF_2
006 051 C BF _ 1 : C B F a i l u r e and
006 052 C BF _ 2 : C B F a i l u r e
The previous signals C BF _ x: C B F a i l u r e have all been renamed.
The new text is:
039 000 C BF _ 1 : C B S u p e r v . S i g n a l
039 039 C BF _ 2 : C B S u p e r v . S i g n a l
CBM_1. Circuit breaker monitoring (triggering circuits 1 and 2) is now available
CBM_2 with two new function groups.
LIMIT The previous function groups LIM_a, LIM_b, LIM_c and LIM_V have
been united in one single function group "LIMIT". Except for the
renaming of menu points, for example
072 221 LIM_a: I> SG1 → 072 221 LIMIT: Ia> SG1
this does not mean that associated functionalities have been changed.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P638/EN M/Da2 // AFSV.12.10183 D /// P638-302-403/404-610 06/2016
Easergy MiCOM P638
P638/EN AD/Bb2
Upgrade Documentation
P638, Changes in software version -610 to -611
In the new versions of the Transformer Differential Protection Device for Railway
Applications Easergy MiCOM P638, several enhanced features and changes on
existing features have been included. These are described with reference to the
documentation listed below:
References
Released Version Documentation
15.08.2008 P638 -302 -403/404 -610 Technical Manual
P638/EN M/Da2
1 Overview
Version Changes
P638-302-403/404-611 Hardware New Schneider-Electric design for the local control panel (HMI).
Diagram No change
Release: 23.02.2011 Software
PC The following menu point has been removed:
P C : N a m e o f m a n u f a c t u r e r (003 183)
Note:
Compatibility even with older versions of the operating program
continues to be guaranteed.
COMM1 The data point C O M M 1 : M O D B U S p r o t . v a r i a n t (003 214) may
now be used to select between the MODBUS protocol variants Private
and Compatible.
The protocol variant Compatible corresponds to the MODBUS
implementation in the MiCOM Px20 and Px40 protection devices.
The protocol variant Private corresponds to the first implementation of
the MODBUS protocol.
Note:
As before this setting is hidden unless the MODBUS protocol is enabled.
COMM1, The menu points C O M M 1 : N a m e o f m a n u f a c t u r e r (003 161)
COMM2 and C O M M 2 : N a m e o f m a n u f a c t u r e r (103 161) can no longer
be set by using a selection list but, for reasons of compatibility, they may
now be defined as free text. The default is SE but, in individual cases, it
may become necessary to enter texts differing from the default.
Notes:
These parameters can only be set using the operating program and it is
not possible to set them locally using the integrated local control panel
(HMI).
The maximum text length is 8 characters and designations exceeding
this will be truncated.
The parameter C O M M 1 : N a m e o f m a n u f a c t u r e r is hidden
unless an IEC 60870-5 protocol is enabled.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P638/EN AD/Bb2 // AFSV.12.11031 D /// P638-302-403/404-611 06/2016
Easergy MiCOM P638
P638/EN AD/Bc3
Upgrade Documentation
2 P638/EN AD/Bc3 // AFSV.12.11431 D /// P638-303-405/406-612
P638, Changes in Software Version -611 to -612
References
Released Version Documentation
2008-08-15 P638 -302 Technical Manual
-403/404 P638/EN M/Da2
-610
2011-02-23 P638 -302 Upgrade Documentation
-403/404 P638/EN AD/Bb2
-611
1 Overview
Version Changes
P638 -303 Hardware The P638 is now fitted with an improved power supply module.
-405/406 Note that the voltage range has changed for DC input:
-612 • For the DC / AC variant, the range is now
Release: 2012-12-01 60 … 250 VDC / 100 ... 230 VAC
(previously 48 … 250 VDC / 100 ... 230 VAC).
• For the DC-only variant, the range is now
24 … 60 VDC
(previously 24 VDC).
A new communication module (“REB” = “Redundant Ethernet
Board”) is now available as an ordering option. This module
can be used for redundant communication via IEC 61850 and
may be fitted to slot 2, as an alternative to the other
communication modules. The following communication
protocols are supported:
• SHP (Self-Healing Protocol).
• RSTP (Rapid Spanning Tree Protocol).
• DHP (Dual-Homing Protocol).
A detailed description of the module and the appropriate
network connections is available as a separate document
(“Redundant Ethernet Board, Application Guide”).
The binary module X(6I 3O) with 6 binary signal inputs and 3
output relays is now optionally available and may be fitted to
slot 18.
Diagram The diagrams have been adapted to the new selection of
modules:
• P638 -405: Case 84TE, pin-terminal connection
• P638 -406: Case 84TE, ring-terminal connection
Software Note:
Software version P638 -612 is compatible with all previous
hardware releases.
IEC Bug fixing:
• In a few cases a data change report was not transferred
when a cyclic report was generated at the same time.
• Operate signals OpIn are available now in the Logical
Nodes RBRF1 and RBRF2.
DIFF The restrictions for setting the amplitude matching factors
have been relaxed as follows:
• 0.5 ≤kam,x ≤16 (instead of: kam,x ≤5)
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P638/EN AD/Bc3 06/2016
Customer Care Centre
http://www.schneider-electric.com/ccc
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P638/EN M/Bc3 Version: -610 -611 -612 06/2016