Sie sind auf Seite 1von 7

W ater T alk

Volume 8, Issue 8 August 2008


Zero Blowdown, Reality or Fantasy?
A Critical Look at the Claims and Possibilities

Discussion of Reality constant level. *(If we assume that drift


and or windage is around .1% and delta
With the ever-increasing need to T at 20 degrees the actual rate of loss is
conserve water, the cooling water equivalent to the blowdown rate at 16
customer is being inundated with cycles of concentration.) Happy ending?
promises of water savings by means of NO! By no means was it a happy ending.
“zero blowdown” treatment schemes.
What is zero Blowdown? Zero Windage is water loss from an open
Blowdown refers to a treatment scheme cooling system in the form of fine water
that promises the customer the ability to droplets or spray. The loss in water is
turn off the cooling tower bleed and due to the effect of wind flow across the
literally reduce their blowdown needs to tower or the effect of water droplets
zero, or in other words cycle their water caught in the flow of air through the
without limit. Is this possible? The tower. The amount of water loss can
answer is a qualified yes. vary greatly depending on the type of
tower and the condition of the fill (mist
In naturally soft waters, zero blowdown eliminators.)
can be achieved with proper
considerations for treatment of Type of Tower
corrosion, increased deposition potential Average Windage/Drift Loss D
and microbiological activity. For a Mechanical draft towers
number of years a sort of zero blowdown 0.05% to 0.1%
was and has been common in the east Evaporative condensers
where some common water supplies 0.05% to 0.1%
have been relatively soft. Hardness Atmospheric towers
levels at less than 1 grain i.e. less than With fill
17 ppm of total hardness and low 0.6%
alkalinities seemingly made these waters Without fill
good candidates for zero blowdown 1.5%
programs. In those areas very high
cycles with good water treatment has Windage/drift can be easily calculated
allowed many cooling water users the with the following simple formula:
ability to run at high cycles of
concentration. In many cases, the small W = Average % Loss X Recirculation
amount of drift or windage loss was rate *(% loss expressed as a decimal)
sufficient to keep dissolved solids at a
____________________________________________________________________________________________________________
Water Talk - Monthly Newsletter
*For a mechanical draft tower at 0.1% blowdown? The answer to that question
this would be 0.1. lies not in achieving actual zero
blowdown but in the definition of zero
The maximum cycles of concentration is blowdown as it is used. The current
also easily calculated with the following definition of “Zero Blowdown” is zero
simple formula: Cycles = (0.075 X ∆T + bleed from the tower. In that context
W)/W zero blowdown is achievable but as will
This equation holds true regardless of be shown in the following discussion it
the towers size. For a tower that has a is neither zero or is cheap.
10-degree temp drop this would .
calculate as follows: Achieving Zero Blowdown
Maximum Cycles = ((.075 x 10) +
0.1)/0.1 Hard water- Zero blowdown using hard
Maximum Cycles = (.75 + .1)/.1 water make up is especially difficult and
Maximum Cycles = .85/.1 should never be considered. Many have
Maximum Cycles = 8.5 been lulled into trying it with disastrous
results. Towers fill up with precipitate,
While running these seemingly heat exchangers will plug with both
wonderful programs, intended to save scale and sludgy deposits and tower fill
big bucks in water and chemical, it was will often collapse under the weight of
soon discovered that suspended solids at the entrained deposits. Some have
this level of concentration, even in proposed that a tower can be treated
relatively soft water and even with the using controlled precipitation with pH
windage loss, were a big problem. adjustments and sludge conditioning. It
is a recipe for trouble because it is
Entrained solids from air scrubbing, chemically impossible to keep all of the
precipitates and microbiological deposits solids entrained and soluble. Eventually
became major issues. Heavy deposits in the sludge will collect in all areas of the
the cooling tower basins were breeding system, causing heat transfer and flow
grounds for bacteria, especially sulfate problems, and would have to be
reducers, which caused slime and manually cleaned.
corrosion in the system. It was not
unusual to have the entire fill of a
Using Sodium Zeolite Softened Make
cooling tower collapse under the weight
Up and it’s Associated Costs
of the deposited salts, mud and
microbiological masses. So instead of
zero blowdown users settled for greatly In the search for methods to reduce
reduced blowdown. Between the loss water usage many sites are considering
expected from drift and windage and the use of zeolite softened water as a
greatly reduced blowdown the users means to zero blowdown and water
were able to achieve greater water savings. It is indeed true that by using
savings but not zero blowdown. softened water more cycles of
concentration can be achieved but does
At this point one might ask why would the use of softened water make sense
anyone want to consider zero from an operational and economic stand
point. Considerations for this type of
______________________________________________________________________________________
______________________
Water Talk - Monthly Newsletter
water reduction scheme must include as softener regeneration water and salt
capital costs for buying and installing a requirements.
softener package, which would include
not only the costs of the softeners but the Suggested Operating Conditions for a
infrastructure needed to install and NaCl Regenerated Softener
operate them, ongoing cost of salt and
salt handling, and consideration for brine Ideal service flow rate – 2 gpm
disposal if that is an issue. Backwash rate - 6 gpm per sq ft of
surface for at least 10 min (some can be
For the sake of this discussion we will higher)
assume that the site has excess softener Regenerant flow rate – 1 gpm of 10%
capacity and can support the make up brine solution per cu ft for a minimum of
requirements of a tower that has a 30min to use about 15 lbs of salt per cu
recirculation rate of 10,000 gpm and a ∆ ft
T of 15 degrees. Let’s assume that the Slow rinse rate – 1 gpm per cu ft
tower is older and has a windage or drift Fast rinse flow rate – 1.5 to 2.0 gpm per
loss (W) of .1% cu ft
Total rinse requirements – 50 to 75 gal
The total water requirements will be per cu ft for
as follows:
Given the make up requirement of the
Make up = Evaporation + Bleed + tower we find that we will need to have
Windage a softener that is capable of delivering at
Evaporation = 0.001 x 15 degrees x least 2 to 3 gpm to keep up with our
10,000 x .75* (Assume convection tower evaporation rate. That means we
cooling is 25%) need a softener that has a resin capacity
Evaporation = 113gpm of at least 70 cu ft to satisfy our make up
Windage = Recirculation x 0.001 or flow requirements as well as the
10,000x 0.001 minimum flow requirements of a
Windage = 10gpm softener. To accommodate the resin
Bleed or blowdown = E/Cycles-1 for our needed the size of our softeners bed is 5
example assume cycles to be 3 ft in diameter and has a resin bed that is
Blowdown = 113/2 = 56.5gpm about 4.5 ft deep. Given its size and
Since our bleed will be zero our equation calculated capacity our softener will
becomes, Make up = Evaporation require regeneration about once every 13
+Windage hours per softener to assure soft water is
always available for the tower.
Therefore our softened tower water
make up requirements are 123gpm or Given the above let’s now look at the
about 180,000gpd. Our make up water is total water requirements of regeneration
at 300 ppm as CaCO3 of total hardness. for the above softener.
Given the above let’s now consider what Backwash water = 6gpm x 10min x 15.6
we will need in terms of water sq ft = 936 gal/regen cycle
requirements from our softener as well Regenerant water = 1gpm x 70 cu ft x 30
min = 2100 gal/regen cycle
______________________________________________________________________________________
______________________
Water Talk - Monthly Newsletter
Total rinse water = 60gal x 70 cu ft = about 4500 gallons per load. Since our
4,200gals/regen cycle brine water usage is around 2100 gallons
Total water requirement per regeneration we will need to ship a tanker of brine per
is about 7,300 gallons or approximately day for disposal. The cost is therefore
13,500 per 24 hr day. The blowdown about $500.00 per day. Suddenly zero
water requirements would have been blowdown doesn’t look to good; does it?
about 81,000 gallons therefore we are Moreover, we have not included the
saving nearly 67,500 gallons per day. infrastructure costs of a tank and transfer
At water rates of $2.50 per 1000 gal that pumps for make up water storage or the
is a daily savings of $168.75 per day. costs of spent brine storage and transfer
Not bad! pumps and tank. These costs could
easily add $75 to $100 K of initial
Salt Costs capital costs.

Now let’s consider the cost of salt as part Considering the cost of water, salt, and
of the total savings of zero blowdown. brine disposal we can see that zero
Given salt usage requirements to obtain blowdown using softened water does not
efficient regeneration of 15 lbs of NaCl seem to be an economical alternative to
per cu ft of resin per regeneration we can regular operation. In addition, we have
calculate the amount of salt required per not even considered the costs associated
daily regeneration. That number per 24 with the purchasing and handling of the
hour day is about 1,940 lbs of salt. salt, nor have we considered the costs
associated with the maintenance of the
Salt is available in bag and bulk and softener system, adding in those
varies in price from about $ .03 per lb additional costs would make the zero
for bulk salt to as high as $.20 per lb for bleed option even less attractive. Once
bagged salt; a large user would typically again, it seems that savings touted in a
use bulk salt and pay around $.05/lb, zero bleed programs are more fantasy
unless buying in very large quantities, so than fact.
for a typical day we can expect to spend
about $100 for regeneration costs. The Corrosion Considerations
actual savings from water are
evaporating (no pun intended) and the Several potential corrosion issues need
user is now actually realizing much less consideration when using a soft water
than expected savings for his cooling zero blowdown program. They are,
program. potential corrosion of galvanized towers,
also known as white rust and corrosion
In many areas of the country and of stainless tell due to high levels of
especially in CA there is still another chlorides causing chloride stress
cost associated with the use of softeners cracking.
for water pretreatment, brine disposal. In
southern California brine disposal costs High cycles achieved in softened water
are around $500 per tanker load. zero blowdown programs will also
Considering that a tanker load is limited contribute to the cycling of alkalinity,
to 40,000 lbs we are looking at a limit of resulting in elevated pH, and chlorides.
______________________________________________________________________________________
______________________
Water Talk - Monthly Newsletter
In that high pH water, without the considerable problem with salt
corrosion inhibition of calcium or some deposition on the drift eliminators and
other inhibitor or without acid cooling tower fills. Modern cooling
modification a Zinc Galvanized cooling systems are built for exceptional cooling
tower will experience severe white rust efficiencies. They are smaller than old
attack on the zinc in the cooling tower. conventional towers but exceptionally
Even if a system was previously good at distributing water to create a
passivated, the high alkaline low very large surface area that allows for
hardness water will reverse the rapid evaporation and cooling of the
passivation and cause corrosion of the recycled water. That very design
wetted parts of the galvanized system. characteristic makes this type of towers
Of note is that many owners of very susceptible to deposit build up on
galvanized towers, because of white rust, the louvers and fill of the tower. In a
have switched to stainless cooling softened water system, the deposits are
towers, however the issue of corrosion typically sodium chloride (salt) that
does not go away in softened zero blow builds up in those areas where water
down systems. flow becomes restricted, usually the
outer surfaces of the fill. Because of the
Stainless steel is susceptible to corrosion restricted flows, the deposition occurs
from high concentrations of chlorides in ever more rapidly and impedes the
the grain boundaries of the metal. The airflow and thus evaporation for cooling.
corrosion is especially severe in any area The restricted airflows will decrease the
or equipment that has highly stressed rate of cooling and thus causing
surfaces, such as welds and bends, and decreased rates of heat-transfer, reduced
can become an area of concern under the process efficiency and increased energy
right chemical conditions. It is especially costs. Keeping the fill clean and deposit
important to look at any stainless free is a necessity and becomes an
component in a cooling system that may essential part of the preventative
get hot or has periods of low flow maintenance program.
conditions, (exchangers that stand by,
flat plate exchangers with high heat Demineralization for Zero Blowdown
transfer rates, welded areas of wetted
equipment). It is also important to An alternative to softening is complete
examine welded areas that may demineralization. Like softening it has
experience low flows and even stagnant its associated costs that make that
conditions. The higher levels of approach even less feasible than
chlorides, present in the recirculating softening. Adding to the costs of
water, can and will increase the potential regenerants are the costs of safety and
for corrosion in stainless components. handling when working with caustic and
acid. Adding still the costs of disposal or
Deposition Considerations neutralization to the spent regenerants
makes the approach completely not
Though conventional deposit problems feasible for the application.
from hardness salts are not an issue in Demineralization for zero blowdown is
softened cycled water there is a not an economical alternative.
______________________________________________________________________________________
______________________
Water Talk - Monthly Newsletter
level controls and other infrastructure
Reverse Osmosis (RO) for Zero needed for it would add another $50 to
Blowdown and it’s Costs $75 K to the initial capital cost.

Still another alternative to softening the Still another limitation is the amount of
make up water is using water that has actual useful through put that can be
been purified using reverse osmosis obtained from the unit. Depending on
membranes. Once again the idea sounds water quality an RO unit will have a
feasible but a thorough review of the through put of anywhere from 50% of
method may reveal limitations and costs flow to as high as 90% of flow. What
that need to be considered before this means is that 10 to 50% of the water
deciding whether the method is flow through the RO unit is reject water.
applicable. Using our make up water as source
water without any pretreatment we
In reverse osmosis treatment of raw would fall into the 50% reject category.
water high pressure is used to literally What this means in practical terms is
force filter the raw water through a that we would reject (blowdown) one
membrane to separate the dissolved gallon for every gallon of purified water,
minerals from the bulk water. It is a that means that we would have 180,000
proven method of treatment for all sorts gallons of blowdown everyday. That is
of water and waste waters that can what our blowdown is anyway! So why
provide for very high quality purified bother?
water that, depending on need, can be
used directly or further treated for final We can increase the through put by
use. The RO method is effective but has pretreating the water, with softening, to
a number of limitations. about 75% through put; but we have
already calculated the cost of softening
Reverse osmosis limitations are and that would only add to the already
substantial when considering an unreasonable operating cost. And, we
application. Initial equipment costs are haven’t even considered the, very high,
very high. Our particular application that cost of energy for operating the RO
requires about 120 gpm has an initial system. We could go on and add in the
capital cost of about $100 K for the RO other costs associated with any scheme
unit only. That cost does not include a we wish to consider for pretreatment of
cleaning skid, RO membranes need source water for RO purified water but
regular cleaning, that would add another the bottom line is that RO is not a
$10 K to the cost. Membrane life is practical method of water pretreatment
limited with regular replacement costs of for achieving zero blowdown.
$5 to $10 K per year. The through put
requirements, based on daily variations Water Recycle/Reuse
in evaporation and makeup of the tower,
would necessitate the addition of a bulk There are many opportunities water use
water storage/surge tank to keep flows that are often overlooked by many sites
through the unit from varying to greatly. that allow the user to realize both
A 20K storage tank with transfer pumps, operational savings as well water
______________________________________________________________________________________
______________________
Water Talk - Monthly Newsletter
savings. Many areas of the country are purity source water. Even then the actual
encouraging the use of Utility or Gray reality of zero blowdown is less than
water (water from sewage treatment) for many have promised and claimed. Zero
cooling tower make up. There are of Blowdown really ends up in the category
course considerations for the use of this of “If its sounds to good to be true...”
water but it doesn’t involve much more There are however ways to economically
than a modification to the current achieve the dual goal of reduced water
chemical treatment program used in the consumption and dollar savings that
facility. Cooling tower blowdown, involve more practical and realistic
depending on solids content, has been means to the desired end. Increasing
used alone or blended with other sources cycles thru better chemistry and control
of water as a source for watering the is easily achieved but it requires a higher
lawns and grounds. level of attention to the cooling water
program. Working with experienced and
Case Histories knowledgeable water treaters provides
the means to that end. Still another way
A large auto parts manufacturer in Ohio is to investigate opportunities for water
used their entire waste water flow as a conservation through water reuse and
watering source. Not only did they save recycle.
hundreds of thousands in water and
sewer costs but they had the finest
grounds in the locality.

A large waste to energy plant in Florida


tapped into their community’s Utility
Water main and saved thousands by
using that water for dust control on the
trash piles used for fuel.

Many water recycle/reuse projects may


or may not be easily realized unless
considerations to the logistics,
practicality and economics of reuse and
recycle are fully looked at and analyzed.
However, reuse and recycle may be the
only real path to water savings.

Conclusion

In theory Zero Blowdown means


reduced water consumption by
eliminating water losses but if examined
closely, Zero Blowdown is not a
realizable goal for most cooling towers
unless there is available and cheap high
______________________________________________________________________________________
______________________
Water Talk - Monthly Newsletter

Das könnte Ihnen auch gefallen