Generator set specification

Model : C25D5P
Duty : Prime
Power Rating kVA/kWe: 25/20
No of Phases : 3 phase
Output Voltage 415
Power Factory 0,8 (lagging)
Current (3 Phase/1 Phase) (A) 35
Frequency (Hz) and RPM 50 Hz, 1500 RPM
Engine Spesifiaction
Make Cummins
Model X2.7T-G1
MoEF Certified Power (hp) 32
Required Power for Rated Kva (hp) 31,6
Cooling Liquid cooled (EG Compleat 50:50)
Aspiration turbo changed
No of Cylinders 3, in – line
Bore (mm) x Stroke (mm) 95 x 127
Compression ratio 18 3:1
Displacement (liter) 2.7
Fuel High Speed Diesel
Fuel consumption @75% load with radiator and fan 4.76
(litre/hr)
Fuel consumption @100% load with radiator and fan 6.29
(litre/hr)
Performance class of generator set ISO 8528-5 G2
Starting system 12 V DC Electrical
Lube Oil spesification Ch4 15W40
Lube Oil sump capacity, High-Low level ( litre) 7.3-3.2
Total lubrication system capacity (litre) 8
Lube oil Consumption @full load (litre/hr) 0.01
Total coolant capacity (litre) 11
Exhaust pipe size (inch) 2.5
Total wet weight (engine+radiator) * (kg) 322
Length x Width x Height (Engine) (mm) 701x600x889
Mean Piston Speed (m/s) 6.35
Combustion air intake @100% load (±5%) (cfm) 67
Exhaust Temperature (°C) 463
Alternator Specification
Make Stamford (CGT)
Alternator frame PT144E
Enclosure IP23
Voltage regulation (Max) ±1%
Class of insulation H class
Winding Pitch 2/3
Stator Winding Double layer Lap
Rotor Dynamically Balanced
Waveform distortion/total harmonic distortion no load <1.5% non distoring balanced linier load
<5%
Maximum unbalanced load across phases Less than or equal to 25%
Telephonic harmonic factor <2%

Conformance Standard

1. IS/IEC 60034-1
2. IS 1460
3. ISO 9001

Typical Enclosed Genset Dismensions

 Genset Model : C25D5P


 Rating (kVA) : 25
 Length (mm) : 2400
 Width (mm) : 950
 Height (mm) : 1400
 Wet Weight (kg) : 1090
 Standard Fuel tank Capacity (liter) : 70