Sie sind auf Seite 1von 4

Primary Service Equipment *With MCCBs and ICCBs, the breaker typically is rated for only 80% of its

*With MCCBs and ICCBs, the breaker typically is rated for only 80% of its capacity within a
In some smaller facilities, panel boards may be used as a primary service; but for larger facilities, switchboard or panel board. In this case, you could put no more than 320 amps continuously on
the primary service equipment will be based on a switchboard or switchgear. that breaker. This is a limitation that not everyone is aware of.
*Engineers, architects, contractors, and facility owners often use the terms “switchboard” and *It is possible to specify optional 100%-rated MCCBs and ICCBs in some frame sizes with some cost
“switchgear” interchangeably when referring to 480 V circuit breaker distribution equipment. premium. PCBs are 100%-rated as standard.
*But there are notable differences in configurations, components, standards, applications, *Beyond continuous current, there are important differences when considering short circuits and
reliability, and selection criteria between these two types of power distribution equipment. faults. While beyond the scope of this article, is important to note that PCBs are tested and rated
*There are several notable differences between switchboards and switchgear including physical to higher levels of initial (or asymmetrical) fault than MCCBs or ICCBs. Depending on the engineer’s
size, front or rear access, and how breakers are mounted and removed. detailed calculations, the MCCB’s or ICCB’s listed fault rating may need to be derated.
*The type of breakers used also is a major difference between switchboards and switchgear. The *Beyond a circuit breaker’s ability to withstand and interrupt a maximum short circuit, there are
basic types that we are concerned with, here, are sealed, semi-open, and open types. Specifically, trip levels or regions to consider.
these are called molded-case, insulated-case, and power circuit breakers. *Circuit breakers will open based on various magnitudes and durations of current.
PANEL BOARD is also known as distribution board, breaker panel or electric panel. is a component *These trip levels are expressed as a curve on a graph of current versus time.
of an electricity supply system that divides an electrical power feed into subsidiary circuits, while There are three regions to consider:
providing a protective fuse or circuit breaker for each circuit in a common enclosure  long-time (continuous-current range) faults
SWITCHGEAR is composed of electrical disconnect switches, fuses or circuit breakers used to  short-time faults
control, protect and isolate electrical equipment.  instantaneous fault
SWITCHBOARDS is an apparatus (as in a telephone exchange) consisting of a panel on which are SHORT-TIME REGIONS - The area of difference between MCCBs, ICCBs, and PCBs.
mounted electric switches so arranged that a number of circuits may be connected, combined, and PCBs -have higher short-time ratings, which along with the ability to eliminate the instantaneous
controlled. range, allows PCBs to wait for breakers further downstream in the distribution system to trip and
CIRCUIT BREAKER is an automatic device for stopping the flow of current in an electric circuit as a isolate faults.
safety measure. SELECTIVE OR FULLY COORDINATED SYSTEM -use in large distribution systems where one doesn’t
MOLDED CASE CIRCUIT BREAKER is a type of electrical protection device that is used to protect the want main circuit breakers to trip when a fault occurs on a smaller downstream breaker. This type
electrical circuit from excessive current, which can cause overload or short circuit. MCCBs are the of coordination is more readily achieved with the use of PCBs at main service points.
most commonly used in all types of low-voltage switchboards and panel boards. One will find these SWITCHGEAR AND SWITCHBOARD
breakers in ratings from 15 to 3,000 amps. The breaker mechanism is totally sealed within an *Switchgear is larger than switchboards and requires front and rear access. In addition, the
external molded case. If the breaker has a failure or problem, it must be replaced. These breakers clearance in front must take into account the space needed to draw out a breaker.
typically are bolted onto the bus, or may have plug-in designs. The removal or addition of MCCBs *While not covered in the code when withdrawing a draw out breaker, it may occupy the NEC-
to a switchboard should take place only with the switchboard power turned off required clearances—making egress and access difficult. Rear-connected switchboards, depending
INSULATED CASE CIRCUIT BREAKER is a molded case circuit breaker with an integral 2-step stored- on specified options, also will require similar careful space considerations.
energy mechanism. They have the functionality of an iron-frame breaker, or a low-voltage- *Front-accessible switchboards have the least space requirements and may be located against a
power breaker with a molded plastic instead of an iron frame. ICCBs are a type of MCCB designed wall.
to provide features typically available in PCBs. The internal parts are mostly, but not completely, *Both switchboards and switchgear are code-compliant and proven in the industry.
sealed like those in an MCCB. Typical ratings range from 400 to 5,000 amps. These breakers are ADVANTAGES TO SWITCHGEAR AND REAR- CONNECTED SWITCHBOARDS THAT CAN REDUCE
available as options in switchboards and can be fixed or draw out. Designed to the same standards DOWNTIME AND FAILURES.
as MCCBs, they provide access to replaceable parts, such as contacts. *First, there is the idea of individual compartments for breakers. In the event of a short circuit on a
POWER CIRCUIT BREAKER Typical ratings range from 800 to 5,000 amps. PCBs are designed and breaker, the resulting energy will be contained and isolated from other breakers and from the bus
tested under much different standards than MCCBs or ICCBs. PCBs are connected to the bus in a and cable compartment.
draw out design, allowing the breakers to be withdrawn partially or fully while the entire *Second, the ability to have drawout breakers also permits repair, inspection, and replacement of
switchgear is powered on (see Figure 2). PCBs have numerous components that can be inspected a breaker while the rest of the switchboard or switchgear continues to operate.
and replaced, such as contacts, pole assemblies, and arc chutes. *Third, PCBs, and to a lesser extent ICCBs, have exposed and accessible parts that can be regularly
APPLICATIONS CONSIDERATION inspected and replaced without having to buy an entirely new breaker.
The amount of continuous current that can be put on a 400-amp circuit breaker depends on the *Lastly, PCBs have a more rugged construction and are able to handle more closing and opening
breaker. operations, including faults, and provide for automatic remote control for transfer schemes.
FACTORS TO CONSIDER IN SWITCHGEAR AND SWITCHBOARD SELECTION
INITIAL COSTS – It often play a major role in the selection. The cost differences between a low-end Most panelboards are available in ampere ratings from 100 to 1,200 amps.
switchboard and high-end switchgear can be substantial—as high as two or three times—and must Common Ratings of Panelboard:
be weighed against the long-term issues of maintainability, reliability, and downtime. 100 amps,200 amps,225 amps,400 amps,600 amps,800 amps,1,200 amps
PROJECT TYPE AND COMPLEXITY – It often determine the choice. A simple office facility with no NOTE: If an amperage rating of more than 1,200 amps is needed, switchboards must be specified,
maintenance staff is much different from a manufacturing facility. Recommended applications for as panelboards are not available above 1,200 amps. Commercial and industrial facilities use
switchgear include manufacturing or process facilities with round-the-clock operations, data voltage ratings of 120/208 V, 277/480 V, and 480 V. Residential often will use 120/240 V.
centers, and telecommunication switching sites, airports, convention centers, or skyscrapers. *Panels should have a main breaker (main disconnect) or main lugs only.
HYBRID OR HIGH-END REAR-ACCESS – It is a good choice for medical facilities, laboratories, light *Certain requirements in the code may mandate a main breaker (or disconnect) nearby, such as
manufacturing, and large institutional or commercial facilities. Front-accessible switchboards are when a panelboard is supplied from a transformer per NEC Article 240.21(C).
recommended for basic office and commercial buildings, K-12 schools, warehouses, or retail *Additionally, if the panel is fed from a breaker in an upstream panel, switchboard, or switchgear,
facilities. it is technically protected under code.
BASIC CONFIGURATIONS OF SWITCHBOARD/S AND SWITCHGEAR/S *However, providing a main breaker in some panelboards that are not within sight of their
In its most basic form, a low-voltage switchboard is a common grouping of fixed molded-case upstream protection can provide enhanced safety and maintainability.
“sealed-type” circuit breakers in a common enclosure. The breakers are directly connected to the *Panelboards also offer the choice of bolt-on or plug-on (stab) breaker-to-bus connections.
bus and may be group-mounted or individually mounted in their own compartment within the *A bolt-on breaker connection secures to the panel bus by screws.
entire enclosure. Cable connections are made by an electrician standing in the front of the board. *Stab-on uses a spring-clip-type conductor.
They typically require only front access and may be mounted against a wall. These are often seen *Generally speaking, bolt-on connections are considered more reliable and secure and are
in small- and medium-size commercial or institutional facilities. common in distribution panels.
SWITCHGEAR consists of individually mounted and compartmentalized drawout power, open-type *Plug-on breakers are more common on lighting or branch panels.
circuit breakers. There are physical barriers between the breaker and between the breakers and *In nearly all panelboards, the circuit breakers used are fixed-rated, molded-case thermal magnetic
the bus. Cable connections are made in the rear compartment. They are larger and require front type.
and rear access. These typically have been used in industrial and large commercial and institutional *However, numerous optional breaker types are available. Adjustable magnetic trips are available
facilities. on larger-frame breakers.
Historically, these two simple explanations have helped to highlight the differences between a low- *In addition, adjustable electronic trip breakers are available with various trip settings on most
voltage circuit breaker switchboard and switchgear. Recently, however, the lines have been blurred breakers, providing enhanced selective coordination.
with the availably of rear-connected switchboards that can provide hybrid options of individual *Also, it is possible to specify 100%-rated breakers in larger frames to use the full ampacity of the
compartments and drawout circuit insulated-case semi-open breakers with semi-open or open- rating, rather than the 80% rating standard with most MCCBs.
type power circuit breaker construction. *When a main breaker is used in larger panels, or as a larger branch breaker on a distribution
DISTRIBUTION PANELBOARDS panel, it may be desirable to select 100%-rated and electronic trip features to permit the full rating
In the 2005 and earlier versions of the NEC, panelboards were classified as either lighting and of the panel to be used and improve coordination with upstream panels, switchboards, or
appliance branch-circuit panelboards or power panelboards, based on their content. switchgear.
Specifically, NEC 2005 Article 408.34: Classification of Panelboards contained the following two *Lastly, numerous optional features can be specified for molded-case breakers in special
definitions of panelboard types: applications, such as motor circuit protectors (magnetic only), ground-fault circuit interrupters for
*LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARD. A lighting and appliance branch- wet areas, ground-fault equipment protectors for heat trace, shunt trips for remote control, key
circuit panelboard is one having more than 10% of its overcurrent devices protecting lighting and interlocks and padlocked operators for safety, arc fault circuit interrupters typically for residential,
appliance branch circuits and more.
* POWER PANELBOARD. A power panel board is one having 10% or fewer of its overcurrent *Like switchgear and switchboards, it’s also important to consider whether the main feeder and
devices protecting lighting and appliance branch circuits. branch feeders will be top- or bottom-feed.
One of the reasons is that major electrical-equipment manufacturers typically have several types of *This can affect the panel enclosure and may also necessitate the addition of vertical gutter ways
panel boards with different features, capabilities, and space needs. to accommodate all the branch feeders.
A further benefit to using these terms is when designating panelboards on one-line diagrams, *When laying out floor plans, it’s important to understand that distribution panelboards will
risers, and plans, one can link different types to different specifications. require significantly more space than lighting or branch-circuit panelboards.
A common application approach might be to use the terms distribution or power panels for panels *In addition, distribution panelboards are usually surface-mounted (not recessed), and some may
that feed other panels or large loads, lighting panels for lighting loads and lighting controls, and actually require floor mounting or equipment pads.
receptacle or branch panels for panels that feed outlets or smaller loads. Given the benefits of TRANSFORMERS
using these panel designations, consider the common application issues for these applications. Introduction
In 1820, a Danish physicist, Hans C. Oersted (1777-1851), accidentally discovered an interesting  In simplest form, it consists of two inductive coils which are electrically separated but
phenomenon. Placing a compass near a current- carrying conductor, he noticed that the needle of magnetically linked through a path of low reluctance.
the compass pointed to the conductor rather than north. He was quick to realize that electricity  The two coils posses high mutual inductance. If one coil is connected to a source of
and magnetism was related. This phenomenon is referred to as electromagnetism. alternating voltage, an alternating flux is set up in the laminated core, most of which is
In 1831, the English physicist Michael Faraday explored further Oersted’s discovery of linked with the other coil in which it produces mutually induced e.m.f.
electromagnetism and found that the process could be reversed. Faraday observed that if a  If the second coil circuit is closed, a current flows in it and so electric energy is
conductor was passed through a magnetic field, a voltage will be induced in the conductor and transferred (entirely magnetically) from the first coil to the second coil.
cause a current to flow. This phenomenon is referred to as electromagnetic induction.  The first coil, in which electric energy is fed from the a.c. supply mains, is called primary
ELECTROMAGNETIC INDUCTION winding and the other from which energy is drawn out, is called primary winding.
*The action that causes electrons to flow within a conductor when that conductor is moved TRANSFORMER CONSTRUCTION
through a magnetic field. THE BASIC TRANSFOREMER IS MADE UP OF THE:
*It is the voltage or emf induced or produced in a coil as magnetic lines of force link with the turns CORE, PRIMARY WINDING, SECONDARY WINDING, ENCLOSURE
of coil. *The simple elements of a transformers consist of two coils having mutual inductance and a
The Great Experimenter laminated steel core. The two coils are insulated from each other and the steel core.
*In 1831 MICHAEL FARADAY (1791-1867), a British physicist/chemist often hailed in England as the Other necessary parts are:
father of Electrical Engineering, carried out a number of experiments which are generally accepted  some suitable container for assembled core and windings
as the discovery of electromagnetic induction.  a suitable medium for insulating the core and its winding from its container
*born to James and Margaret Faraday on September 22, 1791.  a suitable bushing (either of porcelain, oil-filled or capacitor-type) for insulating and
*At twenty-two impressed the brilliant professor Humphry Davvy, who made him his research bringing out the terminals of windings out from the tank.
assistant at Count Rumford’s Royal Institution. After two years he was given a promotion and an  The core of transformer is either square or rectangular in size.
apartment at the Royal Institution and in 1821 he married. It is further divided into parts:
*In 1855 he had written three volumes of papers on electromagnetism, the first dynamo, first *Limb – the vertical portion on which coils are wound
transformer and the foundation of electrochemistry, a large amount on dielectrics and even some *Yoke – the top and the horizontal portion of the core
papers in plasma. CORE LAMINATION
*The unit of capacitance is measured in farads , in honor of his work in these areas of science. *is made up of laminations.
Faraday’s Law *Because of laminated type of construction, eddy current losses get minimized.
Michael Faraday carried out an experiment in which he used a coil, a zero center ammeter *Generally high grade silicon steel laminations (0.3 to 0.5 mm thick) are used.
(galvanometer), and a bar permanent magnet *These laminations are insulated from each other by using insulation like varnished.
*When the magnet is moved into a coil the magnetic line of flux cut the turns of the coil. This *Laminations are overlapped so that to avoid the air gap at joints.
action that occurs when the magnetic lines of flux link with a conductor is known as flux linkage. TRANSFORMERS CLASSIFICATION
*When the magnet is stationary within the coil, the magnetic lines are no longer cutting the turns 1. ACCORDING TO THE NUMBER OF PHASES
of the coil, so there is no induced voltage and the meter returns to zero. *single-phase transformer
*When the magnet is pulled back out of the coil, a voltage is induced that causes current to flow in *three-phase transformer
the opposite direction and the meter deflects in the opposite direction. 2. DEPENDING ON THE VOLTAGE LEVEL AT WHICH THE WINDING IS OPERATED
*If the magnet is moved into or out of the coil at a greater speed, the voltage is induced also *Step-up transformer: primary is a low voltage (LV) winding
increases, and therefore so does current. *Step-down transformer: primary is a high voltage (HV) winding
*If the size of the magnet and therefore the magnetic flux strength are increased, the induced 3. DEPENDING UPON CONSTRUCTION
voltage also increases. *Shell type – Core surrounds the considerable part of the winding
*If the number of turns in coil is increased, the induced voltage also increases. *Core type – Winding surrounds the considerable part of the core
WORKING PRINCIPLE OF A TRANSFORMER 4. DEPENDING TO THE COOLING EMPLOYED
*A transformer is a static (or stationary) piece of apparatus by means of which electric power in *Oil – filled self – cooled - ( small and medium size distribution transformer). The assembled
one circuit is transformed into electric power of the same frequency in another circuit. windings and cores of such transformers are mounted in a welded, oil-tight steel tank provided
*It can raise or lower the voltage in circuit. with steel cover. After putting the core at its proper place, the tank is filled with purified, high
 The physical basis of a transformer is mutual induction between two circuit linked by a quality insulating oil.
common magnetic flux.
*Oil – filled water – cooled – a more economical form of construction for such large transformer. 3.The core of a 100-kVA, 11000/550 V, 50 Hz, single phase, core type transformer has a cross-
The windings and core are immersed in the oil, but there is a mounted near the surface of oil, a section of 20 cm x 20 cm. Find (a) the number of H.V. and L.V. turns per phase and (b) the emf per
cooling coil through which a cold water is kept circulating. turn if the maximum core density is not to exceed 1.3 Tesla. Assume a stacking factor of 0.9.
Oil-filled transformers are built for outdoor duty and as these require no housing other than their 4.A single-phase transformer has 400 primary and 1000 turns. The net cross-sectional area of the
own, a great saving is thereby effected. core is 60 cm^2. If the primary winding be connected to a 50 – Hz supply at 520 V, calculate (a) the
*Air – blast type - for voltages below 25, 000 V. The transformer is not immersed in oil, but is peak value of the flux density in the core (b) the voltage induced in the secondary winding.
housed in a thin sheet-metal box open at both ends through which air is blown from the bottom to 5.A 25-kVA transformer has 500 turns on the primary and 50 turns on the secondary winding. The
the top by means of a fan or lower. primary is connected to 300 V, 50 Hz supply. Find the full load primary and secondary currents, the
CORE-TYPE TRANSFORMER secondary emf and the maximum flux in core. Neglect leakage drops and no-load primary current.
*The coils used are form-wound and of the cylindrical type, TRANSFORMER POLARITY
*The general form of these coils may be circular or oval or rectangular. *A transformer may have multiple windings that may be connected either in series to increase the
*On small size core-type transformers, a simple rectangular core is used with cylindrical coils which voltage ratings or in parallel to increase the current rating.
are either circular or rectangular in form. *Transformer polarity refers to the relative direction or polarity of the induced voltage between
*But for large-size core-type transformers, round or circular cylindrical coils are used which are so high-voltage and low voltage terminals of the transformer.
wound as to fit over a cruciform. *An understanding of transformer polarity is essential in making three-phase and single – phase
SHELL-TYPE TRANSFORMERS transformer connection.
*The coils are form-wound but are multi-layer disc type usually wound in the form of pancakes. TRANSFORMER RATINGS
*The different layers of such multi-layer discs are insulated from each other by paper. *The nameplate of a transformer provides information on the apparent power and the voltage-
*shell-type transformer is constructed from a stack of E- and I-shaped laminations. In a shell-type handling capacity of each winding.
transformer, the primary and secondary windings are wound on the same leg of the core, as *For example, the nameplate data of a 5 – kVA, 500/ 250- V, step-down transformer, we conclude
concentric windings, one on top of the other one. the following:
AN IDEAL TRANSFORMER 1. The full-load or nominal power rating of the trans former is 5 kVA
An ideal transformer is one which has no losses. 2. Since it is a step-down transformer, the (nominal) primary is 500 V and the
-Its winding has no ohmic resistance (nominal) secondary voltage is 250 V.
-There is no magnetic leakage 3. The nominal magnitudes of the primary and the secondary currents at full load
-There no core loss are
In other words, an ideal transformer consist of two purely inductive coils wound on a loss-free core I1 = 5000/500 = 10 A
VOLTAGE TRANSFORMATION RATIO I2 = 5000/250 = 20 A
1. The a - ratio can be determine
a = 500/250 = 2
COMMON TRANSFORMER RATIO TRANSFORMER WITH LOSSES BUT NO MAGNETIC LEAKAGE
- When transformer is on no load
- When it is loaded

PRACTICE PROBLEMS:
1.The maximum flux in the core of a 60 cycle transformer flux has 1320 primary turns and 46
secondary turns is 3.76x10^6 Maxwell. Calculate the primary and secondary induced voltage.
2.The maximum flux density in the core of a 250/3000 – volts, 50 – Hz single-phase transformer is
1.2Wb/m^2. If the emf per turn is 8 volt, determine (a) primary and secondary turns and (b) area of
the core.

Das könnte Ihnen auch gefallen