1 Phase DIN Rail Meter

USER MANUAL FOR 1 PHASE DIN RAIL METER

Doc.No.4D060283 Rev.0 L&T Electrical & Automation


FEATURES & TECHNICAL SPECIFICATIONS

FEATURES

Terminal sealing provision


Terminal cover
Display

Pulse LED

Optical
communication

Push button

Terminal sealing provision

 LCD display
 Push-to-Push consumption, Daily, Weekly, Monthly consumption.
 Terminal covers to avoid direct contact of the supply terminals along with sealing provision.
 Data transfer through optical communication*.
 Easy mounting on DIN rail with locking.
 Energy recording at current as low as 0.02A.

* Note:
1) Additional “Wi-Fi Module” is available to get data over Wi-Fi (to be purchased separately).
2) Mobile Application is also available for Energy Monitoring for iOS, Android, Windows & Symbian
Operating systems.
3) RS485 Module is available.

TECHNICAL SPECIFICATIONS

Meter Type 1P2W Direct Whole current Operated, Direct


Connected, Unidirectional
Voltage Rating 240 V (Phase to Neutral)
Current Rating 5A (Ibasic), 40A (Imax)
Starting Current 0.4% Ibasic
Accuracy Class 1.0 (5% to 800% Ibasic)
Operating Voltage 168V to 288V
Current Display Range 0.05A onwards
Operating Frequency 50Hz ±5%
Meter Constant 3200 Imp/kWh
Measurement Category Category III
Standard Compliance IEC 62052-11, IEC 62053-21, IP20
Enclosure Polycarbonate
Dimension 36mm x 83mm x 66.5mm (Tolerances Apply)
Weight 132 grams(Approximate)
Communication Compatible with Wi-Fi & RS485 communication
Page 2 of 8
WIRING DIAGRAM, OPERATING INSTRUCTIONS & DISPLAY
WIRING DIAGRAM

Neutral

Phase
M1 M0

1 Phase Load

L1

OPERATING INSTRUCTIONS

Parameter scrolling: The default display mode is Auto Scroll Mode in which the parameters scroll
automatically. On pressing key, the meter display goes to manual mode. If key press doesn’t happen
for approximately 30 seconds, meter display returns to default mode i.e. Auto Scroll mode.

Push-to-push consumption: The push button is also used for measuring Push-to-Push kWh
consumption. Follow the below steps to measure the Push-to-Push kWh consumption:

a) Scroll through the parameters until Display No.11 (Refer Display Parameters Table 2) is displayed.
b) When Display No.11 is displayed; press and hold the push button, it resets to zero.
c) Energy recording starts in Display No.11.
d) Check Display No.12 to get the energy consumed value between the previous start-&-stop
operations.

DISPLAY
1

3 2

Page 3 of 8
DISPLAY PARAMETERS

Table 1.
DISPLAY EXPLANATION
Sl. No. Parameter Display Legend
1 Quantities measured
2 Energy, Voltage, Amps, Power kWh, V, A, kW
Different consumptions
Present day D (Flashing)
Present week W (Flashing)
Present month M (Flashing)
3
Previous day D
Previous week W
Previous month M
Push-to-Push kWh consumption(present) T (Flashing)
Push-to-Push kWh consumption(previous) T

DISPLAY PARAMETERS

Table 2.
No
Parameter LCD Pattern No. Parameter LCD Pattern
.

Cumulative Forward
1 2 Present kW
kWh

3 Current 4 Voltage

Current Month
consumption Last month
5 6
'M' will be flashing consumption
at the rate of 0.5sec

Current Week
consumption Last Week
7 8
'W' will be flashing consumption
at the rate of 0.5sec

Current DAY
consumption
9 10 Last DAY consumption
'D' will be flashing at
the rate of 0.5sec

Current Push-to-
Push consumption Last Push-to-Push
11 12
'T' will be flashing at consumption
the rate of 0.5sec

Page 4 of 8
DISPLAY PARAMETERS & METER SETTING
No. Parameter LCD Pattern No. Parameter LCD Pattern

Meter Mode of
communication 1st Byte of IP Address of
13 14
Configuration Wi-Fi Module *
display

2nd Byte of IP
3rd Byte of IP Address of
15 Address of Wi-Fi 16
Wi-Fi Module *
Module *

4th Byte of IP
Meter Modbus
17 Address of Wi-Fi 18
Communication Slave ID **
Module *

Meter Modbus
20 Meter Modbus
19 Communication
Communication Parity **
Baud rate **

Note:

* Parameters available only in WiFi mode of Communication.


** Parameters available only in MODBUS mode of Communication.

CONFIGURING COMMUNICATION:

Following settings need to be done to configure the DIN meter to WiFi or MODBUS mode:

• Connect the meter to the power supply and manually scroll till parameter "Config" is displayed.

• Press and hold the push button for approximately 5 sec, meter will display “Yi-Fi”, “ndbus”,”IEC”and
“ESC”on each scroll.

• Press and hold the push button for approximately 5 sec after the required mode of communication. Select
“Yi-Fi” for Wi-Fi mode to use with Wi-Fi module and “ndbus” for MODBUS mode to use with RS-485 module.

• Meter will restart in selected mode of communication.

• Escape is to exit from the configuration mode.

• 30 Second timeout is given from configuration mode to the Auto scroll mode.

Page 5 of 8
METER SETTING & MEMORY MAP
Memory Map
g Table 3.
Address Parameters Words MF
Read only Parameters ( Function Code 4)
Instantaneous Parameters
30001 R Phase Voltage 2 0.01
30007 R Phase Current 2 0.001
30013 Average Voltage 2 0.01
30015 Average Current 2 0.001
30017 Total Active Power 2 0.0001
30023 Total Power Factor 2 0.001
NOTE: Format for above addresses 7 to 11, 15 to 23
1st word – (MSW) 0x0000 if value positive 0xFFFF if value negative
2nd word – value itself, if positive as indicated by 1st word
2’s complement of value, if negative as indicated by 1st word
30025 Line Frequency 2 0.01
30027 Cumulative energy – forward kWh 2 0.01
30029 Previous Day Consumption-kWh 2 0.01
30031 PresentDay Consumption-kWh 2 0.01
30033 Previous Week Consumption-kWh 2 0.01
30035 Present Week Consumption-kWh 2 0.01
30037 Previous Month Consumption-kWh 2 0.01
30039 Present Month Consumption-kWh 2 0.01
30041 Current Push-to-Push Consumption-kWh 2 0.01
30043 Backup Push-to-Push Consumption-kWh 2 0.01
LS DATA -Last 4 IP kWh
30049 IMPKWH Previous Integration 2 0.01
30051 IMPKWH Previous to Previous Integration 2 0.01
30053 IMPKWH Previous to Previous to Previous Integration 2 0.01
IMPKWH Previous to Previous to Previous to Previous
30055 2 0.01
Integration
Meter Serial Number
30057 6 1
Format For Above :ASCII Value
Read Write Parameters(Read supported by function
code 3)(Supported by function code 6 and 16)
Communication Parameters
42385 Meter Address 1 1
Baud Rate
42386 Format : 3 -> 1200 4 -> 2400 5 -> 4800 6 -> 9600 1 1
baud rate
Parity
42387 Format of Address 2387: 1 1
0 -> None Parity 1 -> Odd Parity 2 -> Even Parity
42388 Push-to-Push Consumption Reset Command 1 1

Page 6 of 8
DIMENSIONS

All dimensions are in mm

INSTALLATION PROCEDURE

STEP 1 STEP 2 STEP 3 STEP 4

PULL** PRESS
* For terminal cover sealing, wire used should be of maximum 0.8mm diameter.

UN-INSTALLATION PROCEDURE

Note:
1) Before installing & uninstalling the meter make sure that the
Power supply to meter is switched off.
2) Remove all the connections to the meter before uninstalling.
3) ** PULL the locking clips with the help of a screwdriver by
inserting it in slot provided in the clip.

PULL **

Page 7 of 8
WARRANTY & DISCLAIMER

WARRANTY

Larsen & Toubro warrants that 1 PHASE DIN RAIL ENERGY METER is free from defects in workmanship and
material. Larsen & Toubro’s obligation under this warranty shall be for a period of 18 months from the date of
sale subject to the following terms and conditions provided the notice of defects and satisfactory proof thereof
is given to Larsen & Toubro by its Customer within the warranty period.

1. Larsen & Toubro shall provide only repairs for the sold item.
2. Defective parts shall be serviced or replaced by Larsen & Toubro.

This warranty does not cover any defect in the product caused by accident, misuse, mishandling (includes
improper electrical, mechanical installation), tamper, neglect, alteration/modification or substitution of any of
the components or parts, or any attempt of internal adjustment by unauthorized service personnel. For
applicability of warranty Larsen & Toubro shall be the sole judge.

Under no circumstance shall Larsen & Toubro be liable for any consequential or resulting injury or for loss,
damage or expense directly or indirectly from the use of this product.

The foregoing warranty is in lieu of all other warranties, expressed or implied, and is the sole and exclusive
remedy for any claim arising from any defect in the product.

DISCLAIMER

Sufficient care is taken to provide all information regarding the product but Larsen & Toubro Electrical and
Automation does not claim any responsibility for the damage caused by using the product directly or indirectly.

In case of customer complaint please contact


Customer Interaction Centre (CIC)
Toll Free: 1800 233 5858, 1800 200 5858
Telephone: 022 6774 5858
Email: cic@LNTEBG.com

L&T Electrical & Automation

Electrical Standard Products


L&T Business Park, Tower ‘B’ / 3rd Floor
Saki Vihar Road, Powai, Mumbai 400 072
Website: www.Lntebg.com

WD4000DR06A – 1P

Page 8 of 8

Das könnte Ihnen auch gefallen