Sie sind auf Seite 1von 2

DC Power Supply

Type DCPS-S
TYPE LIST
Type DCPS-S 24-x DCPS-S 48-x DCPS-S 110/125- x

Nominal voltage 24V DC 48V DC 110/125V DC

Category DC Power Supply

AC INPUT GENERAL DATA


Nominal voltage 230 V AC +15/-20%

Input frequency 47-63 Hz

Power factor λ > 0.95 vid Pn o m < 25% ; > 0.97 vid 50% > Pnom > 25% ; > 0.99 vid 100% > Pnom > 50%

Efficiency ≥ 90% ≥ 91% ≥ 91%

Internal Fusing For each module

AC INPUT GENERAL DATA / MAX MODULES


• Flexible 19” systems with “Hot Nominal voltage 24 V DC 48 V DC 110/125 V DC

Plug-in” Ability Rectifiers 20A; 40A; 10A; 30A; 4,5A; 13,4A:


modules Max: 120A Max: 90A Max: 40,2A

• Compact design with switch DC/DC


Converters
- 240W/modul 480; 1400W/modul

mode modules Inverter modules - 1,2kVA 1,2kVA

• Extensive microprocessor Distribution panels 2xLUC-9


2xLUC-10SA
2xLUC-9
2xLUC-10SA
1xLUC-9
1xLUC-10SA

controlled monitoring facilities Monitoring units MU500 MU500 MU500


MU1000C MU1000C MU1000C
MU2000C MU2000C MU2000C
• Wide range of modules to fit in Batteries 25Ah; 50Ah; 80Ah; 100Ah 25Ah; 50Ah; 80Ah; 100Ah 25Ah; 50Ah; 80Ah;
most applications 160Ah; 200Ah 160Ah; 200Ah

Voltage ripple ≤ 20 mVpp

Psophometric ≤ 1.0 mVeff


ripple acc. to
CCITT
A combination of modern switching power conversion technol-
ogy and a flexible 19“ compatible mechanic in the DCPS Dynamic < 3% Unom for load jumps between 10% - 90% - 10% Inom
systems gives many advantages and is suitable for a wide behaviour Reaction time t ≤ 1 ms
range of applications.
Short circuit protec- Continuous short circuit proof, 1x In o m
These power supplies are designed for the following tion
applications:
Option
− Power supply for all small to high power DC loads
Options Intersection switches, Temperature compensation, Battery test socket, Mains switch, Door,
− Rectifiers in DC systems with battery backup Alarm panel 16 channels, Cell voltage equalizers, Separate batteries Open vented/NiCd

− Telecommunication

− Railroad signalling systems

− Industrial control systems


STANDARD FEATURES
− Low– and high voltage switchgear back-up supplies
LED indications Operation and alarms
− Charging and buffering of stationary batteries in electri-
Digital displays Output voltage, output current
cal power plants
Relay contacts A-alarm; B-alarm
The combination of an active power factor correction unit and
a soft-switching DC / DC - converter provides a wide input
Monitoring Output voltage high / low, mains fault, module fault, earth fault; fuse tripped; battery fault
voltage range, high efficiency, small dimensions, and low
weight.

The parallel operation mode as integrated standard of each KLIMAT


single module results in high grade flexibility of the power
supply solutions in the n+1 configuration even for higher Ambient Operation: -10°C to +40°C
power demands. temperature Storage: - 30°C to +50°C

Customized power solutions with different voltage levels can Climatic IEC 721-3-3 class 3K3 / 3Z1 / 3B1 / 3C2 / 3S2 / 3M2
be realized in a compact designed system configuration. conditions

Humidity class F
A CAN-bus interface allows monitoring, control and signalling
of all connected modules by the central supervisory unit Dust < 1 mg / m³
(MU1000C).
Altitude ≤ 1000 m a.s.l.; extension possible

Audible noise < 30 dB (A) in 1 m distance

D24-1000.DB101S,Aiab DC Systems AB © 2002


DC Power Supply
Type DCPS-S

MECHANICAL CONSTRUCTION
Construction Steel cabinets with 19” mounting

Dimensions [mm] W/H/D


DCPS-S 600 / 2100 / 400

Cooling Air cooling natural convection

Protection class IP20 (mech.); 1 (electr.) acc. To EN 60950

Surface Powder coating RAL 7032 or RAL 7035, constructive parts: anodised

COMPLIANCES
Conducted and EN 55011 / EN 55022 class B
radiated emissions
EN 50081-1

Safety EN 60950 ; VDE 0100 part 410; VDE 0110, EN 50178, EN 60146

Interference Case:
Immunity Electrostatic discharge: EN 61000-4-2 (6 kV contact, 8 kV air discharge)
EN 50082-2 Radiated radio frequency: EN 61000- 4-3 (10V/m, 30 MHz - 1 GHz)

Power line: At higher power demands there is also Power


EN 61000-4-4 ( 2 kV, other 2 kV) supplies type DCPS-M and DCPS-L available (see
EN 61000-4-5 (4 kV unsymmetrical, 2 kV symmetrical, others: 2 kV unsymmetrical) separate brochure).
Aiab DC Systems AB Also construct and builds
Control line customer specified systems. Please contact Aiab
EN 61000-4-4 ( 2 kV ) DC Systems for consultation.
EN 61000-4-5 (2 kV unsymmetrical)

GENERAL MECHANICAL DIMENSIONS

DCPS-S

PSS18

- + - + - +

Oerlikon Oerlikon Oerlikon


batterie batterie batterie

12CP100/1912V-100Ah 12CP100/1912V-100Ah 12CP100/19 12V-100Ah

- + - + - +

Oerlikon Oerlikon Oerlikon


batterie batterie batterie
12CP100/1912V-100Ah 12CP100/1912V-100Ah 12CP100/19 12V-100Ah

- + - + - +

Oerlikon Oerlikon Oerlikon


batterie batterie batterie

12CP100/1912V-100Ah 12CP100/1912V-100Ah 12CP100/19 12V-100Ah

W/H/D
600/2100/400

Additional Information Contact:


Full information, drawings, manuals and application notes and
advice to any of the wide range of Aiab DC Systems products Aiab DC Systems AB
are available on request. Box 1031
Aiab DC Systems reserve the right to change the specifica- S651 15 Karlstad, Sweden
tion, product design and parameters at any time, without Tel: +46 (0)54 56 77 14
notice.
Aiab DC Systems AB Fax: +46 (0)54 56 77 15
No part of this publication may be copied, transmitted, sold Email: info@aiabdc.se
etc. and used in a commercial way without notice and
agreement of Aiab DC Systems . Web: www.aiabdc.se

Vi reserverar oss från eventuella tryckfel D24-1000.DB101S, Aiab DC Systems AB © 2002