Example 1
A 220 kV, 60 Hz, three phase transmission line is 40 km long. The resistance per phase is
0.15 Ω/km and the inductance per phase is 1.3263 mH/km. The shunt capacitance is
negligible. Use the short line model to find the voltage and power at the sending end and
the voltage regulation and efficiency when the line is supplying a three phase load of
Solution
Semester 1, 2012/2013
EET301 Power System Engineering
Voltage regulation is
(b) The current for 381 MVA with 0.8 leading power factor is
Voltage regulation is
Semester 1, 2012/2013
EET301 Power System Engineering
Example 2
A 345 kV, 60 Hz, three phase transmission line is 130 km long. The resistance per phase is
0.036 Ω per km and the inductance per km is 0.8 mH/km. The shunt capacitance is 0.0112
μF per km. The receiving end load is 270 MVA with 0.8 power factor lagging at 325 kV. Use
the medium line model to find the voltage and power at the sending end and the voltage
regulation.
Solution:
Semester 1, 2012/2013
EET301 Power System Engineering
Voltage regulation is
Semester 1, 2012/2013
EET301 Power System Engineering
Example 3
A 765 kV, 60 Hz, three phase transmission line is 300 km long. The series impedance is z =
0.0165 + j0.3306 Ω per phase/km and the shunt admittance is y = j4.674 x 10-6 S per
phase/km. Evaluate the ABCD parameter and the equivalent π model.
Solution
Semester 1, 2012/2013
EET301 Power System Engineering
Exercise
A 345 kV, three phase transmission line is 130 km long. The series impedance is z = 0.036 +
j0.3 Ω per phase/km and the shunt admittance is y = j4.22 x 10-6 S per phase/km. The
sending end voltage is 345 kV and the sending end current is 400 A at 0.95 power factor
lagging. Find the voltage, current and power at the receiving end and the voltage regulation.
(Answer: IR = 441.832 A; VR (L-L) = 330.68 kV; SR = 224.592 MW + 116.612 Mvar; %VR = 5.46%)