Sie sind auf Seite 1von 48

DAYSIMps

User Manual
Marth 2014

Manual authored by Richard Mistrick, Ph.D.


Penn State University

This version of DAYSIM is a revision/expansion to the DAYSIM software


developed and distributed by the National Research Council of Canada and
the Fraunhofer Institute for Solar Energy Systems © 2012. These revisions
were performed at the Pennsylvania State University, University Park, PA,
USA under the direction of Richard Mistrick, and were funded by Samsung
C&T of Seoul, Korea and by the Department of Energy under the DOE Energy
Efficient Buildings HUB.
This software package makes use of Radiance, Copyright © 1990 – 2011 by
The Regents of the University of California, through Lawrence Berkeley
National Laboratory. All rights reserved.

[Program Setup: Install the downloadable version 4.0 version of DAYSIM, then copy the
DAYSIMps files into the Daysim\bin_windows folder, replacing any existing files.] 1
1

Start DAYSIM but executing the shortcut to the DAYSIMps.jar file in the 
Daysim\bin_windows folder.

[1] To begin creating a new file, select FILE then NEW. 
[2] Enter the path and name of the project header file you would like to use, 
then click OK. The .hea extension is required. 
TIP ‐ In most cases, it is best to create a new folder on your hard drive in which 
the header file and all associated files for this project will be located.  
Otherwise, you will have files from multiple projects in the same folder.
Make sure there are no “space” keys in the folder name, header file name 
and any project related file names. (Only letters and numbers are allowed.)

2
1

[1] Select SITE then  LOAD CLIMATE FILE.
[2] Select the type of weather file, .EPW or .WEA, that you have downloaded 
and have available for your site, then click next and browse for your file.  
A good source for .EPW files is: 
http://apps1.eere.energy.gov/buildings/energyplus/cfm/weather_data.cfm

3
1

[1] Select an appropriate time step. For a faster analysis, select 60 minutes.  If 
you select a shorter time period, sky conditions will be permitted to fluctuate 
about the values provided in the weather file.

4
1

[1] Under the BUILDING tab, select IMPORT OCCUPANCY FILE to load a DAYSIM 
.occ file that lists the hours of operation for the space.  More details on the 
structure of this file are provided on the following page.

5
Occupancy File Format
1
An occupancy file (.occ) is an ASCII text file 
indicating when the space is occupied with 
the lights in operation and lists these 
2
operating conditions over the entire year. 
The days of the week are entered into this 
file as Mo, Tu, We, Th, Fr, Sa, Su. The first 
line of the file [1] initializes the year based 
on the day of the week that should be 
assigned to January 1. 

[2] Enter different spans of dates to specify 
occupancy based on the days of the week, 
with the hours of the day ranging from 0‐24 
as shown.  Occupancy can range from 0 to 1, 
with 1 indicating occupancy 100% of the  3
time during this time interval.  Fractions of 
full occupancy are applied to the annual 
energy calculations that DAYSIM performs.  
Daylight autonomy and threshold 
illuminance calculations will be performed 
for times that have occupancy of 50% or 
greater.

[3] Schedules for individual dates, such as 
holidays, may also be entered.

Daylight savings time is likely to be a future 
addition, but must be entered as a change to 
the schedule at the present time.

6
1
3

[1] Select BUILDING, then IMPORT 3D BUILDING MODEL, then select one of the 
available formats.
[2] If you are using the .rad format, you can build your model in AutoCAD, then 
use DXF2RAD (http://www.schorsch.com/download/dxf2rad/) to convert the 
polygons in your.dxf file to the .rad format.  It is best to build models as 3dfaces. 
You will then need to add Radiance material descriptions at the beginning of the 
.rad file, or in a separate .rad file.  With dxf2rad, layer names are converted to 
material names by placing an “l_” in front of the AutoCAD layer name.  For 
example, polygons in a layer named “floor” will be assigned a material name that 
is “l_floor”. Material descriptions and formats can be found at the Radiance 
website: http://radsite.lbl.gov/radiance/refer/ray.html#Materials.  Most models 
can be constructed using the plastic, glass, and trans materials.  A Microsoft Excel 
file, trans_input.xls, is located in the Daysim\bin_windows folder to assist you in 
the creation of trans material input values.
7
2

[1] To import a building model, browse to add the .RAD files for the base room 
model (adjustable interior blinds or shades will be added later).  You can select 
more than one file at a time using the CTRL key. [2] Click on ADD FILE once you 
have the files selected. [3] After all files have been added, click on IMPORT 
BUILDING DATA INTO EXISTING PROJECT.  

8
3

5 4

[1] After a few seconds, your building/room model should appear on the 
screen.  You can change the VIEW POINT and UPDATE VIEW to view the 
model from a different angle.  If your building is rotated under the 
BUILDING tab, it will be rotated within this view.
[2] Select the appropriate IMPORT UNITS, then select CONFIRM.  Next, 
select the DISPLAY UNITS you would like DAYSIM to display.  [3]
[4] Click on CREATE ANALYSIS POINTS to create an analysis grid across the 
space, or enter the name of an existing point file under LOAD ANALYSIS 
POINTS [5].

9
2

When creating a new Sensor Point File, you first need to select the layers that 
contain the floor materials to define the shape of the area over which the 
analysis points should be placed by listing them under the FLOOR MATERIALS 
pull down menu [1]. DAYSIM will include layers containing polygons that lie on 
the ground plane as a starting point, in which case exterior ground polygons may 
also be listed.  You must transfer exterior ground material or other layers from 
the FLOOR MATERIALS list (left side) to the ROOM MATERIALS list (right side) 
using the arrow keys [2] and the pull down menu. 

[3] Next, complete the x, y and z entries for GRID SPACING, GRID OFFSET (x and 
y position relative to the lower left starting point on the drawn image, and the 
appropriate z position/height within your model – z is not relative), and the 
SENSOR ORIENTATION.  Note that the Z grid spacing is generally 0, otherwise 
points in different columns of analysis points will be placed at different heights. 
10
2
1

[1] When you click on CREATE GRID, the point locations will appear in the 
graphic image.

[2] If the layout is acceptable, click on SAVE and enter a name for the .PTS 
file.  To revise the points, enter new grid data and click on CREATE GRID 
again, then SAVE the resulting analysis point locations to a file.

11
1

[1] To include operable shading devices in your room model, you can click on 
ADD GROUP Æ ADD SETTING, browse to add the .RAD files for the first group 
shading settings, click on SAVE once you have files appropriately selected as 
you want. [2]
Repeat ADD GROUP Æ ADD SETTING to add the second group if necessary. 
These .rad files should describe the blinds, shades, etc. that are to be added to 
the window apertures and include their material descriptions, unless these 
materials have already been defined in the main room model.  Avoid including 
polygons in the shade files that will intersect polygons in your base room 
model. 12
1

[1] The building model you entered can be rotated under the BUILDING 
menu.  Building rotation will only appear in the 3D view on this screen.  All 
other plan views of the space will display the room in an unrotated position, 
with a North arrow indicating the direction of polar North.

13
1

After entering the room and analysis points, you will need to describe the 
electric lighting system.  First, select LUMINAIRES, then CREATE NEW 
SCHEDULE [1].

14
2 3 4 5

1 6 7

Click on ADD LUMINAIRE TYPE [1] , then complete the cells on the entry line.
TYPE [2] refers to a schedule label for this luminaire.  BF MIN [3] is the 
minimum dimming level for the ballast or lamp and POWER MIN [4] is the 
input power at the minimum dimming level.  If a standard non‐dimming 
ballast is being used, BF MIN should remain blank.  Include all light loss 
factors (except the ballast factor) in the OTHER LLF’s column [5].  You may 
enter as many luminaire types as you wish. When finished, click on SAVE 
TABLE [6], then click on LAYOUT TABLE [7].

15
2 3 4

In the layout table screen, luminaire locations are specified through arrays 
(columns and rows) of luminaires.  Click on ADD LUMINAIRE TYPE [1] to get a 
new entry line.  Enter the luminaire type [2], then enter the X,Y, and Z 
coordinates for the lower left luminaire in an array, then the number of 
columns and rows followed by the spacing to use [3] .  Z‐spacing can be used 
to increase or decrease luminaire height from row to row (moving in the Y 
direction). Avoid placing luminaires outside the room, particularly in the z‐
dimension.  Note that Z‐spacing for a luminaire array will typically be zero.  

IMPORTANT – Luminaire locations are entered in the model coordinate system 
that is present in the model .rad files.  If luminaires are inadvertently placed 
outside the room, they will appear outside the shaded floor area.

Luminaires can be rotated within the grid or the entire grid can be rotated 
about the lower left luminaire [4] .  Positive tilt raises the luminaire nadir in  16
the zero‐degree horizontal photometric plane.  Spin rotates the luminaire 
about its axis after it has been tilted.
1

Control zones are groups of lighting equipment that will be controlled together.  
Select the control zones from the pull‐down menu in the ZONE column [1].  Up 
to four possible lighting control zones are permitted in a single DAYSIM run.  
You will be able to turn individual zones on and off later after they have been 
analyzed.  Different luminaire layout lines in the table may refer to the same 
control zone.  The graphic image illustrates the luminaire locations within the 
room and differentiates control zones by the color of the luminaire.  

Currently, only one zone may be dimmed at a time.

17
1
3

After the luminaires have been entered, you are now ready to run a 
simulation.  Double‐click on SIMULATION [1] to view the Radiance parameter 
settings [2], which may be changed to fine tune the analysis.  The default 
conditions should be satisfactory for most runs.  Select RUN SIMULATION [3]
to start the calculation process.  

For a relatively fast calculation to validate that a model appears to be working 
and for general tutorial purposes, ambient bounces may be reduced to 3 or 4, 
ambient divisions may be reduced to 300 and ambient resolution reduced to 
150 to speed up the run.  

18
1

3 3

DAYSIM will ask you to confirm which calculations are to be performed [1], 
and whether you want to start the calculations immediately or run them 
later in batch mode [2].  Once the daylight calculations begin, a DOS 
window will appear [3] that shows the Radiance operations in progress.
This process will likely take a few minutes, and longer when multiple blind 
conditions or large, complex models are being considered.

19
1

When the calculations are complete, the program will return to the calculation 
parameters screen.  Select ANALYSIS, then CONTOURS, then ILLUMINANCE  [1] to 
view the system’s performance.

20
1 2
3
4
5

When the calculations are complete, the program will return to the calculation 
parameters screen.  Select ANALYSIS, then CONTOURS  [1] to view the system’s 
performance in terms of either Illuminance contours [2], Daylight Factor [3],  
Daylighting Autonomy (DA), Continuous Daylight Autonomy (DAcon), or Useful 
Daylight Illuminance (UDI) (these final three are all available under the Continuous 
Daylight Autonomy tab [4]).

Threshold Illumination [5] permits a full annual analysis of the entire work plane 
sensor grid to evaluate the fraction of time that total illuminance from daylight and 
electric lighting is either above or below a selected target point.  All times with an 
occupancy value of 0.5 or higher are included in this analysis.  This analysis can only 
be performed following control algorithm selection, calibration and processing.

21
1

After selecting illuminance contours and most of the other types of analysis, you 
will be asked to indicate the daylight condition to display.  Select the desired date 
and time [1]. You can also select between the weather file and a standard clear 
and overcast day [2] (clear & overcast skies are not yet operational).  

If you have only entered a single shade or shades on a single window group (the 
window groups are designated above by Shade 1 and Shade 2), only those data 
entry cells will used.

22
3 4 3 4 5
2

1 6

If shading devices have been entered, use the pull down menu on the left side [1] to 


set the shades on a window group to one of the three possible blind models (OFF, 
ON1, ON2) for all times of the year, or apply one of three available automatic control 
strategies to select the appropriate shading device: SIGNAL, ANGLE OR BOTH. 

The SIGNAL is that of an open‐loop photosensor which considers the daylight 
received by that device under the base case. A photosensor file, location and 
orientation [2] must be entered, along with the photosenor signal that will activate 
the first and second shade setting [3].  When using SIGNAL mode, the first signal must 
be the smaller of the two signals. When facing downward, the 0 degree angle azimuth 
angle on the photosensor is facing to the East in the plan view of the room.

For solar ANGLE control [4], the solar profile angles below which the first and second 
shade conditions are to be applied must be entered.  The first angle (Ang 1) must 
have a higher solar altitude angle than the second (Ang 2).

To consider both signals and angles in determining which shade setting to apply, a 
setting will be applied when the sun is below the profile angle and the listed signal is 
exceeded.  Ang 1 must be larger than Ang 2, with no restrictions on the signals.

ELAZ [5] is the orientation of the façade (its elevation azimuth). South = 0°, with


positive angles to the West and negative angles to the East.

After entering the shade control information, click on CALCULATE [6] to  apply this 23
control algorithm to the daylight conditions.  
2

1
3

Daylight Autonomy consists of an annual analysis to determine the fraction of the 
occupied time when daylight levels exceed a specified target illuminance [1].  Press 
the CAL button [2] to process the data and revise the contour graph for a new 
target illuminance entry. Spatial daylight autonomy is displayed above the room 
graphic. [3] The times considered are all times with an occupancy of 0.5 (50%) or 
greater. 

24
1
2

Continuous Daylight Autonomy consists of an annual analysis to determine the 
fraction of the occupied time when daylight levels exceed a specified target 
illuminance, with partial credit assigned for times when a portion of this value is 
met by daylight [1]. Press the CAL button [2] to process the data and revise the 
contour graph for a new target illuminance entry. The times considered are all 
times with an occupancy of 0.5 (50%) or greater. 

25
1 2

Useful Daylight Illuminance (UDI) determines the fraction of the year that daylight 
falls between a given range of values. [1]. Press the CAL button [2] to process the 
data and revise the contour graph for a new target illuminance entry. The times 
considered are all times with an occupancy of 0.5 (50%) or greater. 

26
1

If you have selected to view illuminance contours, the next window to appear is 
for the Electric Light Settings.  If this is the first appearance of this window, you 
will need to ADD a new control setting [1].  You will then see a table listing the 
electric lighting zones. Initially, control zones should be set to ON in the second 
column  [2].  After selected a critical task location, which will be described on 
the following pages, you can add a photosensor to the lighting zone being 
controlled.  
When you are ready to view the contours, click on CONTINUE [3].

27
2 1 3

This screen displays illuminance contours for daylight across the space at a 
specified date and time.  You may view daylight or electric light alone, or in 
combination, by clicking on the appropriate boxes [1].  The contours and pseudo 
color shading may be toggled on and off separately [2] along with a color bar scale
[3].  Each colored box In the image represents the value at one analysis point.  
Finer point spacing will provide higher resolution and smoother shading, but will 
take longer to calculate. In the upper left corner, you can advance the time 
condition one step at a time [4], or you may change the date and time manually 
using the SET DAYLIGHT button [5].

Note that a small arrow appears in the upper left corner of the room indicating the 
location of the polar north direction [6].  As the room model is rotated under the 
BUILDING tab, this arrow will rotate to show the polar north location. Data on the 
shading devices and luminaire zone settings are also provided [7].  
28
3

This screen shows illuminance contours for the electric light distribution across 
the analysis grid (i.e., only electric light is turned on) [1].  

If you wish to change the values assigned to the contours, click on CUSTOMIZE 
DISPLAY [2].

Currently, if you remove both electric light and daylight from the display you will 
need to click the COLOR and CONTOURS button after requesting one or the other 
to be redisplayed [3].

29
In the Customize Display screen, settings such as the contour font size and values 
may be changed.  Dimming level settings for the analysis of the critical task point 
may also be modified.

30
1
2
3
5
6

In order to calibrate a photosensor that will control an electric lighting zone, 
you must first indicate the critical task point to be used for calibrating the 
system.  Turn on daylight and all electric lighting zones, then click on the 
CRITICAL POINT checkbox [1] to begin this process.

Next, select the lighting zone that will be dimmed or switched [2].  Input the 
target illuminance you would like to maintain at the critical work plane point, 
then click the CAL button [3]. Contours of the dimming level required from 
the selected lighting zone to achieve the target illuminance at each analysis 
point within the room will appear, A small black square [4] indicates the 
point requiring the highest light output from the controlled zone.  If the 
selected time provides too much daylight, no contours may be displayed.

You may enter an illuminance threshold [5] to have DAYSIM consider only 
points that receive an illuminance greater than this value from the controlled 
lighting zone in selecting the critical point. Open the CP Tool [6] for further 
refinement and to locate the critical point.  Move the X to the desired  31
location and click on the SET CP button to finalize the point location, which 
will turn the X black.
3 4

1
2

The gray area on this screen [1] represents the area that receives less than 
100 lux from zone 1 since an illuminance threshold has been entered (the 
critical point will not be located at positions where the controlled lighting 
zone provides illuminance below this value).  The square [2] is the point 
requiring the highest output from zone 1.  When you open the CP Tool, you 
will see a white X on your screen, typically at the location of the square.  
Move this X to the work plane location at which you wish to place the critical 
point using the arrow buttons [3].  Click SET CP [4] and the X will turn black, 
indicating the location of the critical point. You can eliminate additional 
points, columns, or rows of data from consideration for this critical point 
using the masking tool [5].  Points or areas that have been masked will 
appear gray.
32
1 2
3

4
After locating the critical work plane point to use for calibration, select the SET 
ELECTRIC button on the contour screen to display the window shown here.  
Change the control for the desired zone to either DIMMED or SWITCHED [1].  
Note that only one zone can currently be controlled via a photosensor.  For the 
controlled zone, enter the location and orientation of the photosensor [2], then 
import a photosensor distribution file [3]. When facing downward, the 0 degree 
angle azimuth angle on the photosensor is facing to the East in the plan view of 
the room.

After entering this information, click on CALCULATE SIGNALS [4] to compute the 


sensor signals across the entire year.

When in DIMMED or SWITCHED mode, the CONTINUE button will be inactive 
until signals are calculated, a control algorithm is selected, and the system is 
calibrated.

33
1 2

After the sensor signals have been calculated, you are ready to select and 
calibrate a control algorithm.  Select one of the standard control algorithms from 
the pull‐down menu [1], then click on the CALIBRATION button [2] to set up the 
control algorithm. The daylight condition applied in calibrating the photosensor 
is important and will be the one that last appeared in the contour window. For 
dimming systems, the daylight condition must require a dimming level for the 
dimmed lighting zone that is above the minimum setting (BFmin).  It is best if it 
is close to the minimum value (below 50% light output).
The calibration windows for the different control algorithms are shown on the 
following pages.

34
2
3

1
5

This is the input window for an OPEN LOOP DIMMING control algorithm.  
This algorithm assumes the photosensor receives no signal from the 
electric lighting system at night and provides full light output at this signal.  
Enter the target illuminance [1] for the daytime calibration condition, 
then select UPDATE [2] and SAVE [3].  You may change the daylight 
condition using the RESET button [4] on the right.  If the control algorithm 
is to also turn the controlled zone off after it reaches the minimum 
dimming level, click the OFF CONDITION box [5].

35
3
1 4

5
2

Here is the input window for a CLOSED‐LOOP PROPORTIONAL DIMMING control 
algorithm.  This algorithm requires a nighttime target illuminance [1] as well as a 
target illuminance at the critical point under the selected daylight condition [2]. 
Enter these two values, then select UPDATE [3] and SAVE [4].  You may change 
the daylight condition using the RESET DAYLIGHT CONDITION[5] button on the 
right. If the system will turn the controlled zone off after reaching the minimum 
dimming level, click the OFF CONDITION box [6].

36
2

1
4

This is the input window for a CLOSED‐LOOP CONSTANT SETPOINT 
DIMMING control algorithm.  The algorithm requires entry of a 
photosensor signal [1] that the control system will attempt to maintain by 
dimming the electric lighting zone. Enter a target illuminance at either a 
nighttime or daytime condition to establish this signal, then select UPDATE 
[2] and SAVE [3]. If you want the system to turn off the controlled zone 
after reaching the minimum dimming level, click the OFF CONDITION box 
[4]. 

37
2
3

1
4

This is the input window for an OPEN‐LOOP SWITCHING control algorithm.  
Open‐loop control should have no electric light contribution to the 
photosensor signal.  The difference between the OFF and ON signal, known 
as the dead band, can therefore be relatively small.  Enter values for the 
OFF and ON signal [1], and the desired TARGET ILLUMINANCE [2] to apply 
for comparison to an optimal control condition, then select UPDATE [3] and  
SAVE [4]. 

38
2
3

1
4

This is the input window for the CLOSED‐LOOP SWITCHING control 
algorithm. The difference between the ON and OFF signal (the dead 
band) must be greater than the signal from the switched zone to avoid 
oscillations in switching control.  Enter the ON signal and OFF signal [1], 
then select UPDATE [2] and SAVE [3]. The target illuminance [4] is used 
to establish an “optimum” control condition that exactly meets the target 
value at all times for comparison to the system’s actual performance.

39
2 1

Threshold illumination, which can be accessed from the ANALYSIS pull down menu, 
addresses the performance of the control system over the entire year relative to a 
single target illuminance value is applied at each point [1].  The fraction of time that 
the combination of daylight and electric light is either above or below a specified 
target value, indicated by either < or > [2], is computed and graphed for all work 
plane analysis points.  Since this analysis is for an operating control system, it can only 
be applied following calibration and processing of a lighting control photosensor and 
algorithm. Only those times of the year with an occupancy value of 0.5 (50%) or 
higher are included in this analysis.  

40
1

The general performance and the energy savings provided by the photosensor 
control system can be analyzed by selecting ANALYSIS, then GRAPHS, then 
either TIME PLOT, HISTOGRAM, or PHOTOSENSOR SIGNAL VS DIMMING LEVEL 
[1].   For the time plot and histogram, you will be asked to select a date and 
start time for these graphs.

41
3
1
4 2

The TIME PLOT graphs show the total illuminance provided by the photosensor 
system compared to the illuminance under optimum control (the dimming level 
that meets the target illuminance whenever possible). You can change the 
length of the plot from a single day to a week under the LENGTH pull‐down 
menu [1]. Any longer time period is generally not useful due to the limited size 
of the graph.  Note that the time interval between points on the graph can be 
changed using the INTERVAL pull‐down menu [2].  In addition, the data graphed 
can be changed from the critical point to the average illuminance across the 
entire calculation grid [3].  To display a single day of data, move the TIME to 
1:00:00 AM [4], otherwise the graph will start in the middle of a day. Note that 
above the target Illuminance, if both the optimum and algorithm set the electric 
light to minimum or off, the illuminance provided by the algorithm will exactly 
coincide with the optimum.  Differences will appear when the dimming level is 
between the maximum and minimum output. 42
5
1
2
3

The HISTOGRAM output contains bins of data for the total light provided at 
the critical point from the control algorithm (blue) compared to a system 
that provides optimal control (green) in maintaining the target illuminance 
at the critical point.  In addition to illuminance, the data plotted may be 
shown as dimming level or lighting power values [1].  When illuminance is 
plotted, the illuminance at the critical point or the average of all points may 
be plotted [2].  The length of this study may be selected by the user to 
include either a day, week, month or year [3] with the start point being the 
date and time entered at the top of the screen [4].  Click on the UPDATE 
button [5] to refresh the results after changing the settings. In spaces with 
high daylight conditions that set the dimming level to minimum a large 
fraction of the time, the two conditions will show very similar performance.
43
1

This graph shows data for the DIMMING LEVEL plotted over an entire week. You can 
change the data that are plotted from ILLUMINANCE to DIMMING LEVEL or POWER 
INPUT under the DATA menu [1]. Poor performance is likely to occur at daylight 
conditions that require a level of dimming above the minimum.

44
1

If the Energy Table button is selected [1], DAYSIM will compute the energy savings 
over the entire year, month by month.  Energy consumption is listed separately for 
the controlled zone and the entire room (see tabs [2]). The base case incorporates no 
lighting control.  The optimal case dims or switches to maintain the target illuminance 
at the critical point with minimal energy consumption, while the algorithm case 
applies the photosensor signal processed through the calibrated control algorithm at 
every time period.  The percent occupancy is used to weight the energy values at 
every hour of the year in computing total energy in al of these cases.

46
2
3
4
5 1

The ECONOMIC ANALYSIS button [1] permits the user to compute the simple payback
period and rate of return for the control system.  This analysis is based on the first 
cost of the control system [2], energy costs [3], and a demand charge [4], if 
applicable.  The peak demand reduction is assumed to be the average of the largest 
five demand load reductions at the peak demand hour [5] for each month of the year.

47
General Tips and known problems:

1) Do not import any files from the DAYSIM folders that are stored within your 
project folder (occ, rad, res, etc.).  This may cause the system to attempt to copy a 
file onto itself, which will destroy the file.
2) Close DAYSIM and restart DAYSIM before moving to another input file.
3) If errors occur in the building input files, you will likely see an error message.  
Errors in the shade files, however, may cause a simulation to halt with no error 
message.  It may be possible to catch an error message by running the simulation 
batch file from a command prompt.
4) To recalculate the electric lighting, it may be necessary to first re‐enter one of the 
luminaire locations in the luminaire layout table, then resave the layout, prior to 
rerunning the simulation.
5) Calibration must be performed at a daylight condition that requires a level of 
dimming above the minimum.
6) It is best to place each project (.hea file) within a unique folder, but not required.
7) If the program appears to get stuck, check the Windows Task Manager to see if a 
Radiance program or Java program is still consuming significant resources.  Some 
simulations take significant time to run to completion.
8) It should be possible to copy an entire folder to a folder of another name to 
duplicate a project that you wish to modify.  Spaces are not permitted in folder 
and file names.

48

Das könnte Ihnen auch gefallen