Sie sind auf Seite 1von 9

Proceedings of

2000 International Joint Power Generation Conference


Proceedings of IJPG:
InternationalMiami
JointBeach,
Power Florida, JulyConference
Generation 23-26, 2000
July 23 - July 26, 2000 - Miami, Florida

IJPGC2000-15034

Paper Number ###


FOSTER WHEELER ENERGY INTERNATIONAL
FOSTER WHEELER LIMITED, SPECIAL PRODUCTS DIVISION

HOW EXPERIENCE AND DESIGN CAN IMPROVE THE RELIABILITY OF


CONDENSER STEAM DUMPS
Christopher P. Barszcz
John R. Presley P.Eng.
Foster Wheeler Limited
509 Glendale Ave. E.
Niagara-on-the-Lake, Ontario
LOS 1J0

ABSTRACT steam bypass system be discussed. It should be noted that the


Not too long ago, condenser "steam dumps", or more design of a proper steam dump system is not solely the
correctly "turbine by-pass systems", were non-standard items, responsibility of the condenser designer but includes proper
only occasionally supplied Today, steam dumps are required external system design as well as proper operation and
for most new condenser projects. Due to the potential for maintenance of several systems affecting the condenser.
serious damage to the condenser and other equipment by a Although it is understood that proper location and
poor quality steam dump, it is essential that good design distribution of all types of flows including flashing drains and
principles be incorporated at the earliest stage of the project. make-up is also very important, we are only addressing the
The following information, based on specific feedback from test Steam By-pass flows here. Flows, which enter the condenser as
work and operating units, ensures the highest possible flashing liquid or cold liquid, require a different set of
reliability and performance. guidelines. Discussion of industry experience and previous
study on these types of flows is left for future works.
1.0 INTRODUCTION
Early in their history condensers were identified as an ideal 2.0 INDUSTRY EXPERIENCE
location to return steam, drains and vents back into the overall 2.1 First Experience
cycle. As plants designers were asked to become more space FWL experience with steam dump systems started in 1957
conscious to improve cost effectiveness condenser designers with a condenser supplied for US marine service. A sketch of
were forced to include internal provisions for equipment such the condenser, steam dump and the steam dump cross section is
as feedwater heaters and bled steam piping. In conjunction with shown in Figure 1.
this the condenser was determined to be the best location to This condenser had a surface of 3,200 sq.ft, and was
dump Emergency and By-pass system flows. Other literature ( capable of accepting 120,000 lb/hr of dumped steam (365
[1] Surface Allotment for Surface Condensers- W. Bow) has psig/437 F) through a single 5" connection located in the
tried to promote the need to maintain proper space within the exhaust neck. It is noted that the steam dump flow is 101% of
condenser so that steam can be effectively distributed and the normal turbine flow, and the space into which the steam is
condensed while maintaining acceptable velocities around tube discharged is quite small, due to the restricted space available
bundles. Velocity limits are important in preventing erosion on a marine vessel.
and excessive tube vibration. Unfortunately the pressure for Due to the need for the highest possible reliability, full
reducing space requirements has not lessened and this scale testing was undertaken. These tests included the steam
combined with changes in technology like the introduction of velocity profile, temperature profile and tube vibration
Combined Cycle Power systems has resulted in greater characteristics. The results of these tests, which are shown in
challenges for the condenser designer. With space becoming Figure 2, demonstrated the adequacy of the design,
more of a premium outside and inside the condenser it is subsequently verified by satisfactory performance.
important that guidelines for the design, and operation of the

Copyright © #### by ASME


1 Copyright (C) 2000 by ASME
CONDENSER WITH
100 % S T E A M D U M P
MARINE VESSEL PROGRAM ... 1 9 5 9

TURBINE EXHAUST
TURBINE

DISCHARGEHEADER TUBE BANK

FIGURE 1 - Steam Dump First Experience in a Marine Condenser

Copyright © #### by ASME


2 Copyright (C) 2000 by ASME
FULL-SCALE STEAM DUMP
T E S T RESULTS ... 1959

V E L O C I T Y PROFILE
DISCHARGE
HEADER
~368.8-435.8 M/S) (292.6 M/S) (60.9-228.6 M/S)
\ t210-1430 FT/S 960 FTIS 200-750 FT/S
• ..... " *

41" DUMP
- -. ' ~,,,.
,b/--." (355.6 rnm) (584.2 mm) (584.2 mm)

~ I N -~14"MAX. (91.4-164.5 M/S)


(127 mm MIN.- 355.6mm MAX,) NEG. NEG. 300-540 FTIS
!
! i
I
I l

T E M P E R A T U R E PROFILE TUBEBANK

345~-365 ° F
.8~-184.9° C) , ~ 330" F
425 ° F (165.5 ° C)
(218"3°
STEAM C)"'~, MAXIMUM

(OISC,HARGEHEADE. )
,,,, ~1 --1550-175OF
~""~ (68.30-79.4" C)

330 ° F
-,-
(105.5 ° C)
MAXIMUM
TUBE BANK (165.5 ° C)
MAXIMUM

FIGURE 2 - Model and Test Results of First Experience Steam Dump Arrangement

Copyright © #### by ASME


3 Copyright (C) 2000 by ASME
2.2 Expanded Service Requirements operation occurred in 1971 and not long after it was noted that
This first generation steam dump was developed for one severe general erosion in the hotwell area was evident.
specific service requirement, which was to allow the steam This steam dump discharges 3,410,000 lb/hr of steam at
turbine to be by-passed on a short term, emergency basis (until 390 F (1200 btu/lb) and 200 psig. The steam quantity
the source could be stopped). In the following years, other diminishes from the initial 3,410,000 lb/hr (194% of normal
reasons for using a condenser steam dump became apparent. turbine discharge) to 1,550,000 lb/hr (88% of normal turbine
The following is a list of the "Expanded Service discharge) in 4 minutes. See Figure 3 for the general
Requirements": arrangement of the steam dump.
Emergency only: Characterised by a short duration for each The 24" diameter steam dump connection is located at one
occurrence and a short cumulative operating time. end of the shell, slightly above the hotwell elevation. Inside the
Hot Start Service: For this application, the steam dump would condenser, the steam dump consists of a 24" diameter x 3/8"
be used to allow matching of the turbine temperature and the thick carbon steel pipe with nine integral 42" o/d x 3/8" thick
superheater outlet steam temperature. For a unit in "peaking" stainless steel shrouds evenly spaced over the full length of the
service, this could occur daily. hotwell.
Extended Operation: The erosion, due to the entrainment of the water dripping
1) For some nuclear reactor units, the steam dump may into the hotwell, was evident on the stainless steel tubes at the
experience extended operation as the reactor may be held in bottom of the tube bundles as well as on the carbon steel
operation at relatively high load (to prevent reactor structural members and plates. The pattern of erosion showed
"poisoning") while the steam turbine is being by-passed. that the maximum damage occurred on surfaces at right angles
2) For co-generation plants, the gas turbine may continue to the steam flow whereas those surfaces parallel to the steam
operation while the steam turbine is not in service. In this case, flow were not eroded at all. Also, the erosion pattern very close
the steam output from the HRSG may be directed to the to the distribution header discharge showed that the steam
condenser via the steam dump and the steam quantity and expands at a very wide angle (i.e. 90 degrees included angle)
duration may be very high. after release from the discharge header. See Figure 4 for
details.
2.3 S u b s e q u e n t Industry Experience Changes were made to the condenser to protect vulnerable
As the number of condensers with steam dumps increased, the components from erosion (i.e. installation of impingement
industry began to see occasional problems. These problems fell plates and "dummy" pipes under the tubes).
into one of the following categories: The recommendation from this example were:
• Mechanical failure of the internal dump pipes due to high • High volume steam release in the hotweU area should be
stresses caused by improper design of the perforations in avoided.
the dump pipe, the thermal expansion provisions or the • Avoid steam discharge at right angles to the tube length to
mechanical supports, eliminate the potential for erosion and tube vibration.
• Erosion of the condenser internals, including tubes and
structural components, due to poor selection of the 2.3.2 Case 2
discharge location and/or inadequate internal provisions, This 533,646 sq ft, triple shell condenser serves a 680 MW
• Tube damage through impingement from the discharged nuclear station. The steam dump consists of 4 x 18" diameter
steam due to improperly directed or located dump lines, connections in each shell located in the hotwell.
• Overheating of the condenser internals due to improperly The steam dump was designed for a total steam quantity of
conditioned steam and/or improper condenser operation 7,138,000 lb/hr at 1,204 btu/lb (422 F)/315 psia. This steam
during steam bypass, flow represents 143% of the 100% maximum continuous rating
• Mechanical damage to the condenser and dump pipes due (MCR) flow from the steam turbine.
to "water hammer" from improperly drained upstream The 18" diameter pipes enter on each side of the hotwell
pipes, (two each side), pass below the tubes and then make a 90
• Damage to the steam turbine caused by impingement from degree turn upward into the centre steam lane, terminating
improperly directed steam. approximately 5ft above the tube nest. The steam discharges
into the centre steam lane between the two tube banks via two
The following are three typical cases, together with the rows of 1 1/8" diameter holes at 2" pitch. There is a single row
associated design recommendations arising from the situation. of holes on each side of the pipe and the steam discharges
parallel to the tube length. See Figure 5 for the general
2.3.1 C a s e 1 arrangement.
Unit 1 of this 250 MW nuclear station has a 200,000 sq ft Above the tube bank, the steam discharges through four
surface condenser with a hotwell discharge steam dump. First rows of 3/4" diameter holes. Each row has 27 holes spaced
equally around the circumference of the pipe.

Copyright © #### by ASME


4 Copyright (C) 2000 by ASME
During the commissioning phase, the steam dump pipes degree than the rest of the bundle imposing abnormal bending
inside the condenser, as well as the condenser itself, were badly stresses on the empty tubes. This combined with the greatly
damaged due to a "water hammer" effect following the opening reduced structural properties at extreme temperatures resulted
of the by-pass valves. Subsequent inspection revealed that the in failure with the same fluid forces.
hotwell bottom plate had been split for a length of
approximately 18" at one of the steam dump pipe support The emphasis or recommendation from this example being:
points. The upward movement of the pipe had also damaged • Proper monitoring of water level in condenser waterboxes
some of the tubes and internal bracing. The steam dump pipe is critical to avoid overheating during steam by-pass
itself did not fail. operation.
The water in the pipe was believed to be either due to
inadequate drainage upstream of the steam by-pass valve or 3.0 DEVELOPMENT OF GUIDELINES
ingress from the hotwell via a drain hole in the steam dump The design concepts developed for the marine program,
pipe due to abnormally high hotweli level. Although never together with subsequent experience with other applications,
confirmed, the plant personnel believed that the latter became the framework for Foster Wheeler's steam dump
explanation was the most likely as abnormally high hotweli design guidelines. The discussion of the development of these
levels had been observed and the distance between the high guidelines begins with Detailed Analyses, and is followed by
water level HWL and the bottom of the pipe was only 4". General Guidelines and Operational Guidelines.

The recommendations concluded from this example are: 3.1 Detailed Analyses
• Avoid hotwell entry points whenever possible, thereby It is important for two reasons to discuss the detailed
eliminating a pipe loop which can trap water. analyses that are available to the by-pass system designer.
• If the steam dump connection must be located in the Firstly, many of the general guidelines listed in the next section
hotwell, ensure that there is adequate clearance between were supported by detailed analysis and secondly a detailed
the bottom of the steam dump pipe and the hotwell water analysis may be necessary when given design parameters for
level. This is particularly important for multi-shell the by-pass system fall outside of the general guidelines.
condensers where drains into one shell may have to flow The following is a brief overview of three aspects of
into the other shell via a cross-over pipe. detailed analyses, which are available.

2.3.3 Case 3 3.1.1 Vibration Analysis. Much work has been done over the
This condenser was a 125,000 sq.ft, two-pass Titanium years regarding vibration of tubes in heat exchangers. The Heat
Tube unit which received 540,000 lb/hr of steam at 215 psi(a) Exchange Institute (HEI) Standards for Steam Surface
and 426 F (1225 Btu/lb). The steam was distributed through Condensers [2] provides a simplified method which is based on
two 16" Steam dump pipes each with three 30 .... cans" similar forces due to turbine exhaust flows at sonic velocities. This
to the design shown in case 1 (figure 4). The lines were located only examines an allowable deflection in the tube due to the
in the upper exhaust neck with lines running parallel to the flow force imposed on it. Other more detailed analyses are available
and discharging perpendicular to the bundle axis. It was noticed (Pettigrew [3], (Eisinger[4], Connors, H.J.[5]) which examines
after some initial period of operation that a few of the top tubes tube natural frequency with respect to vortex shedding, fluid
of the bundle sheared mid-span between supports near below elastic instability, and random turbulent forces. The computer
the first can. At some point in the investigation two items of analyses have become extremely effective in predicting
operational significance were noted. It was suggested that the damaging vibration however the one key to all these analyses is
possibility existed that steam may have been introduced into the initial velocity distribution model. Steam distribution has to
the condenser without desuperheating. In addition it was noted be modeled and input into these programs. In the design of
that tubes in the top of the condenser bundle were running dry condensers, steam distribution is extremely complex and
at certain times during operation. At this point a tube section typically requires a number of conservative assumptions to
analysis and a vibration analysis examining the possibility of simplify the model.
damage due to flow induced fluid elastic instability were
performed. The conclusion of the tube analysis was that the
tube sheared due to some type of overload with evidence of
high temperatures involved. Although evidence of fatigue was
not present, it was not ruled out. The follow up tube vibration
analysis determined that under normal Steam Dump operation
the calculated tube vibration was well within safe limits. It was
proposed that due to lack of water in the tubes during steam
dump operation the empty tubes expanded to a much greater

Copyright © #### by ASME


5 Copyright (C) 2000 by ASME
F I E L D E X P E R I E N C E ... 1971 FIELD E X P E R I E N C E ,.. 1982
HOTWELL ENTRY WITH HOTWELL ENTRY WITH
HOTWELL DISCHARGE EXHAUST NECK & CENTER LANE DISCHARGE

STEAM DISCHARGESAT 50 % DISCHARGEDINTO


RIGHT ANGLES TO TUBES EXHAUSTNECK &
50 % DISCHARGEDINTO
CENTER LANE

FADER

JNDLE

STEAM DUMP ARGES


100 % DISCHARGE HEADER TUBES
INTO L. . . . . . . .
FLEXIBLE SUPPORT DRAIN HOLES

F I G U R E 3 - First C a s e S t e a m Discharge in Hotwell FIGURE 5 - Second Case Center Steam Lane Discharge

F I E L D E X P E R I E N C E ... 1971
HOTWELL ENTRY WITH TYPICAL EXHAUST NECK
HOTWELL DISCHARGE PROTECTION SPRAY

DUMP
HEADER

HOTVVEL~

(3/8" (10 f ~E

CONDENSATE PUMP
DISCHARGE

~ ~ ~ ........... / STEAMDUMP
42" 4
(3/8" (10 r

FIGURE 4 - First C a s e Showing Erosion Pattern F I G U R E 6 - E x h a u s t N e c k Fog Spray S y s t e m

Copyright © #### by ASME


6 Copyright (C) 2000 by ASME
3.1.2 Stress Analysis. Two applications where a detailed needs to be careful not to provide wet steam to the condenser
stress analysis can be utilised is for the design of by-pass piping which can result in deleterious erosion to condenser internals.
runs and checking bending stresses in condenser shell plate, In addition to limits on flow enthalpies and pressures the
where the by-pass lines enter the condenser. amount of flow in each line should also be limited. When flows
A computer generated piping analysis would be one type quantities are too large header diameters become
of detailed analysis which is used to generate a table of forces unmanageable.
and loads imposed by thermal and pressure related forces Located down stream of the conditioning valve and within
through piping and onto supports as well as onto the condenser the condenser is a second stage of desuperheating which
shell. This type of analysis should always be performed by the reduces the steam to saturated levels. This is a curtain or fog
designer of the piping outside of the condenser. The results are spray that is located between the internal distribution header in
compared with forces and moments tables provided by the the condenser and the turbine connection. The fog spray
condenser manufacturer that list the maximum X, Y and Z provides protection from overheating to condenser internals
forces and moments allowed on the condenser shell. such as expansion joints, as well as inhibiting high temperature
Typically the classical structural analysis (Roark's from detrimentally effecting turbine internals. (See figure 6.0)
Formulas for Stress and Strain [6] for example) would be When designing fog sprays adequate distance from the spray to
performed to check the adequacy of added stiffening required the header is required to allow even mixing and avoid water
around connections where the forces and moment guidelines droplet erosion.
provided by the condenser manufacturer are exceeded. Some of the other considerations mentioned below are
protection for thermal and mechanical stresses on the
3.1.3 Jet Stream Analysis Effectively when the bypass flow connection point to the condenser. Limits on stress and
exits the distribution header orifices into the condenser the temperature should be followed, avoiding cracking of
resulting flow is a sonic jet expanding into a vacuum. components due to excessive stress levels.
Dissipation of the velocity and momentum of this flow was Orifice design in the condenser distribution header is also
described earlier in the "First Experience" test where the first critical The condenser manufacturer, through years of
general guidelines for safe distances and velocities away from experience has developed orifice sizing criteria that will keep
the discharge header were established. the back-pressure in the by-pass line at the required levels. One
Further analytical models have been established on the aspect of the design that is sometimes lost in overall system
properties of jet flow in a vacuum. Based on this research design is the fact that the design of the final distribution header
Fowler [7] suggested safe distance for critical internal within the condenser is based on a single condition point.
components from the source of this bypass jet flow. These Therefore the plant designer must work with the bypass-
formulations along with almost half a century of practical designer and provide the one case for design that will work
experience have been used to develop the general guidelines over the range of conditions the bypass line will see. Another
discussed below. aspect of orifice design is the type of discharge. Based on the
pressure the designer can provide either a single or multi-
3.2 General Desi.qn Guidelines and Considerations pressure reduction design. The single pressure reduction would
The general design guidelines and considerations provided in be a perforated pipe. A multi-pressure reduction design would
the following discussion are based on the operational be a perforated pipe with an external shroud. A final aspect of
experience and detailed analyses completed on a number of the orifice design encompasses structural considerations. Based
previous installations. Although these items cover the on experience the designer has developed limits on hole size
significant major items they do not cover all aspects of steam and ligament spacing to prevent structural damage due to stress
dump design. intensity caused by the holes or slots in the pipe which must be
followed.
Undoubtedly, the most important design consideration in a by- When laying out the piping both inside and outside of the
pass system design are the limits imposed on the flow condenser consideration must be made of low points where
conditions at the connection to the condenser (listed below). condensate can collect. A frequent cause of damage to the
Flow energy must be reduced through steam conditioning condenser internals has been the result of slugs of water being
valves to safe levels before entering the condenser Admitting picked up from low points in the pipe design bending
flows with excessive temperatures and pressures runs the risk condenser shell plates, and tearing condenser piping supports.
of overheating and damaging both condenser and LP turbine The f'mal aspect of the internal header design is the
internals. (Some of these guidelines are also be found listed in distribution of the steam within the condenser and how it
HEI for Steam Surface condensers). It should be noted however interacts with the critical condenser internals. The items listed
that more is not always better as in the case of conditioning. below provide guidelines and design considerations to avoid
When reducing the steam pressure and enthalpy the designer damaging vibration as well as damage do to the momentum of
the steam impinging on structural components.

7 Copyright © #### by ASME


7 Copyright (C) 2000 by ASME
• Level gauges should be present at the top of the
The following is a list of the guidelines discussed above: waterboxes and should be maintained and monitored.
Waterboxes should be kept full so that overheating of top
• The service condition of the stream dump should be tubes does not occur during Steam Bypass Operation. A
defined by the purchaser, i.e. emergency only; quick start continuous priming system and/or air release valve may be
only (temperature matching); extended operation required to prevent air build up in the top of the waterbox.
(cogeneration plants.). • Cooling water should always be flowing through bundles
• Limit the steam inlet conditions 1200 btu/lb, 250 psia. adjacent to steam dump to avoid overheating of the tube
• The inlet steam condition should be dry saturated or bundle.
slightly superheated (approximately 50 F) to reduce wet • A note on HEI Standards for Steam Surface Condensers
steam erosion. [2]: HEI has a section on connection guidelines which is a
• Provide a thermal sleeve on piping with temperatures good initial reference for customers and AE's who design
greater than 450 F. bypass systems and other fluid systems that are routed to
• If flow quantities exceed 500,000 lb/hr add a second the. condenser. These basic guidelines are based largely on
connection. manufacturer's experiences with steam dump design as are
• Include a fog spray within the condenser. described in this paper.
• For pressure up to 175 psia use holes in a single discharge
header and for higher pressure use a discharge header with 4.0 SUMMARY
integral external shrouds (baffles). As was shown in the above cases and discussions the
• Check orifice sizing and hole diameter and layout are successful bypass design involves the examination of a number
within manufacturers established guidelines. of parameters from flow conditions to steam distribution as
• Check forces and moments provided by the piping design well as structural considerations. It also points out that the
are within allowable limits for the condenser plate around design requires co-ordination at various phases in the project
the connection. between plant designers, system designers and condenser
• Keep pipe routing simple. Preferred routing is in the designers.
condenser neck followed by the centre steam lane. (See The general guidelines and operational guidelines provided
figures 7 & 8) here are based on years of valuable experience form the basis
• Preferred flow discharge is parallel to the tubes. for most turbine steam turbine bypass distribution system
• The location of the distribution pipe and arrangement of design. Detailed analysis is available for cases that cannot meet
discharge must be adequate to allow the steam velocity to the standard guidelines as well as checking and developing
reduce from sonic at the discharge orifice to approximately general guidelines.
500 ft/s (@ 2 in Hg) 4 ft from the discharge point. Critical As plants become more complex and designers are forced
structural internals should be a minimum of 6-8 ft from the to provide cost effective arrangements additional pressure is
discharge orifice. placed on condenser manufacturers to accept higher and more
• Check that steam velocities in the main steam lanes and aggressive flows into their equipment. The experiences and
bundle periphery are below the critical values, so that design philosophies discussed in this paper provide the
damaging vibrations are avoided. condenser designer, the plant designer and operators guidelines
• The location of the inlet connection, and the internal and which result in a safe and reliable Steam turbine system for
external pipe routing, must be arranged to prevent any low today's plant requirements.
points, to ensure full drainage of the internal pipes and
headers.
• Check that manufacturers provided limits of forces and
moments on the condenser shell plate are not exceeded.

3.3 Operational Guidelines

Design of the desuperheat system is the first line of


defence against damage to condenser internals.
Desuperheat devises must be operating properly, flow
injection systems must be functional. Operation of the
system should be monitored and maintained. Proper design
includes providing adequate mixing distance from the
condenser.

Copyright © #### by ASME


8 Copyright (C) 2000 by ASME
REFERENCES:
TYPICALSTEAM DUMP
EXHAUST NECK ENTRY WITH 1. Bow, W.J. (Foster Wheeler), "Space Allotment for Surface
EXHAUST NECK DISCHARGE
Condensers" Presented at EPRI Condenser Symposium,
Orlando Florida June 7-9, 1983 10 pgs.
2. Heat Exchange Institute, Inc. "Standards for Steam Surface
100 % DISCHARGED Condensers" Ninth Edition, by Heat Exchange Institute
INTO EXHAUST NECK
STEAM DUMP /
1995.
3. Pettigrew, M. (AECL), "Fluid Elastic Instability of Heat
|[ ~ ~ ~ STEAM DISCHARGES
Exchanger Tube Bundles: Review and Design
Recommendations" Journal of Pressure Vessel
Technology Transactions of ASME, May 1991, Vol. 113
p.242-256
4. Eisinger, F. (Foster Wheeler), Prevention and Cure of Flow
induced Vibration Problems in Tubular Heat Exchnagers"
Journal of Pressure Vessel Technology Transactions of
ASME, May 1980, Vol. 102 p.138-145
I ~ ~ ; _ 2 N - ~ ..-a~ ! 5. Connors, H. J., "Fluid Elastic Vibration of Tube Arrays
Excited by Crossflow," Flow-Induced Vibrations in Heat
Excchangers, ASME-WAM New York, 1970 p.42-56
TUBE BUNDLE ~" %DRAIN HOLE
6. Young, Warren C. "Roark's Formulas for Stress and
Strain" Sixth Edition, McGraw-Hill, Inc. 1989.
FLEXIBLE SUPPORT 7. Fowler, J.E. (General Electric) "Factors Affecting the
Design of Turbine - Condenser Connections", Journal of
Engineering for Power, July 1977 p.429-436.
FIGURE 7 - Exhaust Neck Entry

TYPICAL STEAM DUMP


EXHAUST NECK & CENTER LANE DISCHARGE

50 oV~DISCHARGED INTO EXHAUST NECK &


50 oVo DISCHARGED INTO CENTER LANE

STEAM DISCHARGES
TO TUBES

STEAM DUMP /
DISCHARGE HEADER

N I ARD HOLE DEMAT


OTTO
B END
OF DISCHARGE HEADER
(not shown)

FIGURE 8 -Exhaust Neck and Center Lane Discharge

Copyright © #### by ASME


9 Copyright (C) 2000 by ASME

Das könnte Ihnen auch gefallen