MODE OPERATOIRE
MODE OPERATOIRE
Modification de structure Niveau 7
Date: 17/02/2019
Revisions
Rev. Date Revision description Prepared
0 18/02/2019 Issued to Client for information H.I
Approved by:
1
Travaux de Montage Mécanique concernant
l’extension de la cimenterie de chlef
MODE OPERATOIRE
The ease the use tower crane for installing the mechanical installations inside the above
mentioned structure above level 7 a proposal for FCB to modify the columns with a splice in
the same level of the existing splice for column on axis 42.b in the 5 columns
BRI propose to add the splice connection at site
The typical splice plate designed in each corresponding column to be copied at the proposed
level to ensure
The material and bolts will be provided by BRI if not aviable in FCB store
The overall work will be done at worksite using the site regulation procedures for applying any
modifications
Cutting will be the use of manual grinding discs while drilling will be with the magnetic drills
To ensure correct drilling all splice plates will be drilled in place with columns before spliting
the columns
The as buit drawings and a parts list are provided by BRI as copies of FCB drawing with a
higher revision no. Stam for FCB APPROVAL
Upon FCB technical acceptance of the modification procedure to star tat site
2. prefabrication:
2.1 fabrication of splice plate
the splice plate to be cut in the workshop as defined on materiial list and detail drawings
but not drilled as per detail drawing
2.2. cutting and drilling splice plates with columns
The splice plates to be tack welded to each corresponding column in the position
defined on arrongement drawing CHL 1S2036H04-H05 revised by BRI and approved
By FCB
Marking the positionof splitting and and its corresponding holes at each splice plate as
per detailed draxwings
2
Travaux de Montage Mécanique concernant
l’extension de la cimenterie de chlef
MODE OPERATOIRE
By the use of magnetic drill the holes on splice plate and columns to be drilled together
to confirm correctpositionning of holes on splice plates and columns to be drilled
together to confirm correct positionning of holes and splice plates relative to coumns
After drilling the tack welds to be removed to separate the splice plates from colmns
The splitting position defined on columns in now clear and columns are redy for
spliting
Spliting to be carried out by use ofv the manual grider discs and no use of gas cutting is
permitted
FCB supervisor to monitor all the operation and instruct operator as nessessary
3. installation :
Columns to be lfted and installed as per submitted erection procedure