Sie sind auf Seite 1von 2

Test device Date/Time 4/4/2019 10:38

Test device CT-Analyzer Device serial no KH183G


File name D:\CT Test Data\3rd floor 3\3F-3_KM02\B-1.xml

Overall assessement OK

Asset
Ipn 150.0 A Object Location
Isn 5.0 A Manufacturer SIPIE Company ABB
Rated burden 5.0 VA /0.80 Type TF59D Country KSA
Operating burden 5.0 VA /0.80 Serial number Station 3F-3
Standard IEC 60044-1 Core 1 Feeder KM02
Application Metering Tap Phase B
Class 0.5 Optional IEC-ID
Frequency 60.0 Hz Comment
Rct max 0.073 Ω ?
FS 5.0
Ts

Secondary winding resistance Primary winding resistance


R-meas (20.0 °C) 0.065 Ω R-meas (20.0 °C)+Rlead 0.065 Ω R-meas
R-ref (50.0 °C) 0.073 Ω R-ref (50.0 °C)+Rlead 0.073 Ω R-ref

Burden
Burden cos φ: Z
V-meas I-meas

Excitation
Ls 0.000043 H Lm 0.176799 H Results at rated burden (5.00 VA) Results at operating burden (5.00 VA)
Kr 63.34 % FS > 2.24 FSi > 2.20 FS > 2.24 FSi > 2.20
Standard IEC 60044-1 εci (@ FS=5) εci (@ FS=5)
V-kn 2.24 V I-kn 0.0412 A Ts 0.760 s Ts 0.760 s

Ratio
Turns ratio 29.8729 Results at rated burden (5.00 VA) Results at operating burden (5.00 VA)
εt -0.4236 % Ratio 150.0 : 5.0014 Ratio 150.0 : 5.0014
Polarity OK ε 0.0290 % ∆φ -1.61 min ε 0.0290 % ∆φ -1.61 min
εc 0.0447 % εc 0.0447 %

Residual magnetism
Residual flux
Residual magnetism

Excitation curve
10.00

1.00
0.00 0.001 0.01 0.10 1.00 10.00
Voltage [V]

X1-X2
0.10

0.01

0.001
Ie [A]

1/2
Current ratio error in % at % of rated current at rated burden (5.00 VA)
VA/cos φ 1.00 % 5.00 % 10.00 % 20.00 % 50.00 % 100.00 % 120.00 % 200.00 %
5 / 0.8 -0.4065 -0.3411 -0.2351 -0.1226 -0.0107 0.0290 0.0306 -0.1541
2.5 / 1 0.2590 0.1134 0.0860 0.1001 0.1422 0.1719 0.1788 0.1913
1.25 / 1 0.3175 0.2363 0.1948 0.1877 0.2161 0.2382 0.2436 0.2557
1/1 0.3282 0.2593 0.2186 0.2083 0.2316 0.2520 0.2570 0.2692

Phase in min at % of rated current at rated burden (5.00 VA)


VA/cos φ 1.00 % 5.00 % 10.00 % 20.00 % 50.00 % 100.00 % 120.00 % 200.00 %
5 / 0.8 32.3511 11.4480 4.7583 0.8827 -1.6486 -1.6101 -1.1870 14.0828
2.5 / 1 28.6395 18.5988 12.6175 8.1859 4.6177 3.2548 2.9875 3.5501
1.25 / 1 20.4632 15.2380 10.8289 7.0961 4.0069 2.6118 2.4425 2.1681
1/1 18.7839 14.4134 10.4321 6.8959 3.8886 2.5293 2.3081 1.9230

Current ratio error in % at % of rated current at rated burden (5.00 VA)


2.0000 5.00 VA
1.5000
1.0000 2.50 VA
Current ratio error [%]

0.5000
1.25 VA
0.0000
-0.5000 1.00 VA

-1.0000
Limits
-1.5000
-2.0000
0.00 50.00 100.00 150.00 200.00 250.00
I/Ipn [%]

Phase in min at % of rated current at rated burden (5.00 VA)


100.0000
5.00 VA
80.0000
60.0000
2.50 VA
40.0000
Phase [min]

20.0000
1.25 VA
0.0000
-20.0000
1.00 VA
-40.0000
-60.0000 Limits
-80.0000
-100.0000
0.00 50.00 100.00 150.00 200.00 250.00
I/Ipn [%]

2/2