ANALYSIS OF SUPPORTING Z BRACKET

DESIGN LOADS TO BE CONSIDERED FOR THE STRUCTURAL


ANALYSIS OF THE SS Z BRACKET SYSTEM
DESIGN FOR 600MM DIAMETER PIPE (VALID FOR PIPE DIAMETER OF
RANGE 300-600 MM)

PIPE LOAD = 117.32 KG/M


WATER LOAD = 282.7 KG/M
TOTAL LOAD = 400.02 KG/M X 1M = 400 KGS

Material : SS Z Bracket of 60mm wide x 75mm depth x 6mm thick of 60mm long

Of 304 Grade

 Factored Design Load = 400 x 1.5 = 600 kgs

 Bending Moment in the SS C Bracket = 600 x 0.06 = 36 kgm

 Section Modulus (Z) Required = 36 x 100/1500 = 2.4cm3

Section Modulus provided in the SS Z Bracket


of 40 x 75 x 6mm thick of 60mm long

Section Modulus Z = Ix/y

Z = 32 cm3 >2.4 cm3

Shear stress 𝝈 = 𝑷/𝑨

= 600÷(6 x0.6 )

= 166.7 kg/sq cm < 1000𝑘𝑔/𝑠𝑞𝑐𝑚

Tensile stress 𝝈 = 𝑷/𝑨

= 600÷(6 x0.6 )

= 166.7 kg/sq cm < 1200𝑘𝑔/𝑠𝑞𝑐𝑚

Deflection 𝜹 = PL3/3EI

=(600x63)÷(3x2.1x106x 96)

= 0.0002 cm

=0.002mm< 1𝑚𝑚

Permissible Deflection not to exceed 1mm

Therefore a SS Z of 60 X 75 X 6mm thick 60 mm long of 304 grade is


found to be stable which be fixed to the RCC Slab as SS bracket.
CHECK FOR THE SHEAR STRESS IN THE SS U BOLTS FOR
THE SS Z BRACKET

 Factored Design Load = 400 x 1.5 = 600 kgs

Considering 1 no's of SS U Bolts of M16 X 1000mm and it varies


Long of 304 grade in each SS Z Bracket

 Shear Stress in the S S U Bolts = (600)/3.14 /4 X1.6 X 1.6 X 0.75

= 398 kg/sq cm <1125 kg /sq cm

 Bearing stress = 600/0.6 x 1.6

= 625kg/sq cm < 3000 kg/sq cm

 Tensile stress in the SS U Bolt = (600)/3.14/4 x 1.6 x 1.6 x 0.75

= 398Kg/sq cm < 1200kg/sq cm

Therefore SS U Bolts Per Bracket of 304 Grade of M16x 1000L is safe in


Tensile , Bearing & Shear stress criteria.
CHECK FOR THE SS M10 ANCHOR BOLTS FOR THE SS Z
BRACKETS.

RECOMMENDED DESIGN RESISTANCE FOR THE H S A -R HILTI MAKE


M10 x 100L.

 ALLOWABLE LOAD IN TENSION --- 6.7KN

 ALLOWABLE LOAD IN SHEAR --- 10.3KN

 Factored Design Load = 400 x 1.5 = 600 kgs

 Tension Per SS Bolt = 6/2 = 3KN < 6.7KN

 Shear Per SS Bolt = 6/2 = 3KN < 10.3KN

Therefore SS Anchor Bolts of H S A – R M10 x 110L Hilti Make M10 x 110

Is safe in Tension and shear Load per Bracket.


DESIGN LOADS TO BE CONSIDERED FOR THE STRUCTURAL
ANALYSIS OF THE SS Z BRACKET SYSTEM

DESIGN FOR 500MM DIAMETER PIPE (VALID FOR PIPE DIAMETER OF


RANGE 100-250 MM)
PIPE LOAD = 88.87 KG/M
WATER LOAD = 196.35 KG/M
TOTAL LOAD = 285.22 KG/M X 1M = 285.22 KGS

Material : SS Z Bracket of 40mm wide x 75mm depth x 6mm thick of 60mm long

Of 304 Grade

 Factored Design Load = 285.22 x 1.5 = 428 kgs

 Bending Moment in the SS C Bracket = 428 x 0.06 = 26 kgm

 Section Modulus (Z) Required = 26 x 100/1500 = 1.73cm3

Section Modulus provided in the SS Z Bracket


of 40 x 75 x 6mm thick of 60mm long

Section Modulus Z = Ix/y

Z = 46 cm3 >1.73 cm3

Shear stress 𝝈 = 𝑷/𝑨

= 428÷(4 x0.6 )

= 178 kg/sq cm < 1000𝑘𝑔/𝑠𝑞𝑐𝑚

Tensile stress 𝝈 = 𝑷/𝑨

= 428÷(4 x0.6 )

= 178 kg/sq cm < 1200𝑘𝑔/𝑠𝑞𝑐𝑚

Deflection 𝜹 = PL3/3EI

=(428x63)÷(3x2.1x106x 96)

= 0.0001 cm

=0.001mm< 1𝑚𝑚

Permissible Deflection not to exceed 1mm

Therefore a SS Z of 40 X 75 X 6mm thick 60 mm long of 304 grade is


found to be stable which be fixed to the RCC Slab as SS bracket.
CHECK FOR THE SHEAR STRESS IN THE SS U BOLTS FOR
THE SS Z BRACKET

 Factored Design Load = 285.22 x 1.5 = 428 kgs

Considering 1 no's of SS U Bolts of M12 X 1000mm and it varies


Long of 304 grade in each SS Z Bracket

 Shear Stress in the S S U Bolts = (428)/3.14 /4 X1.2 X 1.2 X 0.75

= 505 kg/sq cm <1125 kg /sq cm

 Bearing stress = 428/0.6 x 1.2

= 594kg/sq cm < 3000 kg/sq cm

 Tensile stress in the SS U Bolt = (428)/3.14/4 x 1.2 x 1.2 x 0.75

= 505Kg/sq cm < 1200kg/sq cm

Therefore SS U Bolts Per Bracket of 304 Grade of M12x 1000L is safe in


Tensile , Bearing & Shear stress criteria.