Beruflich Dokumente
Kultur Dokumente
uniport
On
07/07/2015
SITE GUIDE
site Basement
guide
waterproofing
Foreword
This publication is one of a series related to basements for housing. It has been produced under the direction of the
Basement Development Group, which was initiated and is co-sponsored by the British Cement Association.
Acknowledgements
The British Cement Association (BCA) is grateful to the British Structural Waterproofing Association (BSWA) for co-
sponsoring this publication. It is also grateful for the assistance and comments provide by members of the Basement
Development Group and to the considerable work of its Waterproofing Task Group in drafting and progressing this
publication. Thanks are also extended to all others who provided input to and comments on the preparatory drafts.
Many construction activities are potentially dangerous, so care is needed at all times. Current legislation requires all
persons to consider the effects of their actions or lack of action on the health and safety of themselves and others. Advice
on safety legislation may be obtained from any of the area offices of the Health and Safety Executive.
48.059 Published by
First published 1994 British Cement Association
ISBN 0 7210 1476 3 Century House, Telford Avenue
Price group D Crowthorne, Berks RG11 6YS
© British Cement Association 1994 Telephone (0344) 762676
Fax (0344) 761214
From April 1995 the code will be (01344)
All advice or information from the British Cement Association is intended for those who will evaluate the significance and limitations of its contents and take responsibility for its use and
application. No liability (including that for negligence) for any loss resulting from such advice or information is accepted. Readers should note that all BCA publications are subject to revision
from time to time and should therefore ensure that they are in possession of the latest version.
Contents Introduction 2
Scope
Glossary 21
References 21
1
adequately protects the structure - and is practicable to
Introduction
install.
The benefits of basements, and their viability and costs
Unless otherwise agreed with the designer, the materials
were examined in a previous report (1) . This indicated that
and installation should be in accordance with the
they can be economically introduced onto most sites. In
specified details, and all work should be carried out to
particular, it showed they have clear advantages where
the same high standards irrespective of the Grade of
the ground is poor and might otherwise be difficult and
internal environment. All junctions, service penetrations,
possibly uneconomic to build on. However, to ensure
dpc/cavity tray junctions and laps in materials should be
success, particular attention must be given to the design
formed according to the designer’s or manufacturer’s
and construction of the basement and any necessary
details.
waterproofing. This publication provides specific
guidance on the site application or installation of the The specialist waterproofing contractor should not use
various waterproofing systems and comments on other alternative waterproofing systems or membranes since
Licensed copy from CIS: uniport, UNIVERSITY OF PORTSMOUTH, 07/07/2015, Uncontrolled Copy.
associated construction matters. they may not be appropriate for the conditions. For
example, the system may have been selected to resist not
A companion publication, Basement waterproofing:
just water but a specific ground chemical. Similarly, any
Design guide (2), gives design information to help the
protection boards or screeds should comply with the
builder or building designer decide which construction
specifications and be positioned as on the drawings.
technique and waterproofing method offer the best
solution, and to help them avoid unsuitable construction. In essence, no alterations should be made to the
specified materials, their relative position and installation
Scope sequence, without clearance from the designer or the
The details and comments in this publication relate to manufacturer of the waterproofing system.
the categories of structural waterproofing which provide
Grade 2 or 3 internal environments, as defined in Site information
BS 8102, which are appropriate for residential basements. Before the form of construction and the necessary
waterproofing system can be chosen, information must
A Grade 2 environment is for use as workshops, plant
be gathered on soil type, water tables and other relevant
rooms and other areas where the performance level
factors. This is the designer’s responsibility.
permits no water penetration but where higher levels of
water vapour would be tolerable and surface The main contractor should find out from the designer
condensation may occur. what the site conditions are - particularly the likely
severity of ground water conditions, and pass this
A Grade 3 environment is for ventilated residential and
information to the specialist waterproofing contractor.
working areas which require a drier environment.
Sometimes, the main contractor may need to lower the
water table temporarily or permanently to enable
construction and waterproofing to go ahead.
Principles of design and
Any lowering of the water table will need to be
installation maintained until the loads acting on the basement, from
either itself or in combination with the superstructure,
General
are greater than the forces that would be generated by
Applying or installing a waterproofing system are
the water pressures as the water table returns to its
specialist tasks that are just as important as choosing and
original level.
specifying the system. The manufacturer should have
been consulted early in the design stage to ensure that Although a site survey will have determined the general
the most appropriate system has been selected. The nature of the site, there may be local variations. Any
manufacturer will also be able to carry out the significant differences should be brought to the attention
installation or to recommend specialist waterproofing of the designer as they may create an additional hazard
contractors familiar with the system to be used. not previously taken into account. Changes from
Installation or application should not be left to impervious to permeable soils may produce unexpected
inexperienced workers. water channels. Similarly, interception of previous land
drains or other elements could increase the amount of
The British Structural Waterproofing Association can
water present. Any unexpected chemicals or suspect
provide details of manufacturers of various waterproofing
materials should also be brought to the designer’s
systems and of appropriate specialist waterproofing
attention.
contractors.
Construction category
Contract details
The structural walls will usually fall into one of the
The specialist waterproofing contractor should examine
following three construction categories.
the contract drawings and waterproofing specifications to
ensure the design requirements are completely Type A (tanked protection) structures will often be of
understood. Since the designer should have consulted masonry construction, although plain or reinforced
with the manufacturer of the waterproofing system concrete may be used. The latter may be in-situ or
during the design, there should be no obvious errors in precast. The structure is regarded as having no integral
the contract details. However, the important thing is that protection against water ingress and so relies on the
the final construction should perform satisfactorily. The applied waterproofing system to provide the necessary
specialist waterproofing contractor should therefore control. Masonry walls may need a cement rendering or
establish that the waterproofing concept does enable a flush pointing to product an acceptable surface for
continuous barrier to be created - or otherwise subsequent application of the waterproofing system.
2
The waterproofing system will, depending on its type, Chemical barriers
tolerate certain construction cracks or minor defects. Fine An externally applied membrane may have been
hair-line cracks up to 0.3 mm wide in reinforced specified to resist the effects of aggressive chemicals in
construction will generally be acceptable. Any larger or the soil. It must not be replaced by any other membrane
unusual cracks should be brought to the designer’s or system without the designer’s approval.
attention to allow for possible remedial action before the
waterproofing system is installed or applied. Movement joints
Type B (structurally integral protection) structures will The designer is advised to eliminate movement joints in
generally be of reinforced or prestressed concrete. Since the basement substructure wherever possible. Where
they are specifically designed to be water-resistant, they are incorporated, details should have been included
further waterproofing will be required only where in the contract drawings and must be followed exactly. If
additional control against free water or water vapour is the specialist waterproofing contractor finds movement
Licensed copy from CIS: uniport, UNIVERSITY OF PORTSMOUTH, 07/07/2015, Uncontrolled Copy.
considered necessary. In some instances, the additional joints with no specific waterproofing details, the designer
protection may be used to safeguard the structure from must be asked to provide appropriate details. On no
aggressive chemicals. Again, any noticeable cracking or account should a waterproofing system be continued
defect should be brought to the attention of the designer. directly across movement joints.
3
General
A: Health & Safety
DOs
OBTAIN Health & Safety product and equipment data, and have available on site
DO NOT ignore Health & Safety advice Accidents - personal injury, prosecution
DO NOT transfer materials into unlabelled containers Improper handling and disposal of unidentifiable
materials and risk of injury
DO NOT expose materials to heat or flame Fire, explosion (primers) and severe personal injury
B: Information
DOs
ENSURE that detail drawings, manufacturers’ literature and site instructions are available to operatives on site
CHECK that all information and details are in accordance with the waterproofing manufacturer’s instructions
DO NOT apply membrane without consulting the Incorrect application leading to potential failure and
manufacturer’s literature. financial loss
4
C: Associated works
DOs
ENSURE that associated works are co-ordinated and do not impede or damage waterproofing
CHECK that other products and methods are compatible
TAKE CARE not to damage system, but repair simple defects according to manufacturer’s instructions
ALWAYS refer to manual
PROVIDE for attendance of other trades where specified
Licensed copy from CIS: uniport, UNIVERSITY OF PORTSMOUTH, 07/07/2015, Uncontrolled Copy.
ARRANGE for hoisting facilities and any necessary scaffolding or other plant
PROVIDE suitable surface for application
ENSURE that measures taken will not interfere with the watertightness of the system
DO NOT proceed if unsure of next stage or of its effect Damage, leakage, or longer-term adverse reactions
on work in hand between materials
DO NOT drag steelwork across unprotected work Damage or leakage
DO NOT expect installers to provide services normally Poor workmanship
provided by other trades
DO NOT pierce or breach waterproofing system Leakage
DO NOT introduce non-specified chemicals, etc. Harm to waterproofing system
DO NOT introduce any necessary vibration, heat, cold Damage to membrane by imposed loads
or pressure until the system will accept this
DO NOT change drainage details without considering Development of water pressures incompatible with
the waterproofing system forms of construction
DO NOT mix waterproofing systems, even if specified - Failure through incompatibility of hybrid systems
refer to client, designer or manufacturer
DO NOT continue if the continuity of the membrane has Damp/water penetration
been broken
5
1 Bonded sheet membranes
1A: Storage and handling
DOs
STORE upright
FOLLOW manufacturer’s instructions and check that all ancillary items, tools and protective clothing are present on site
DO NOT leave out on site or allow rolls to become cold Difficulty in stripping release paper and probably poor
or wet adhesion
DO NOT store rolls horizontally Edges of sheet become damaged and rolls become
difficult to strip and lay
DO NOT allow material to get too cold Material could lose its adhesion
DO NOT allow material to get too hot May become too sticky and prove difficult to lay
DO NOT mix products and ancillary items from different Incompatibility or unsuitability, with no redress in case
manufacturers of failure
DOs
INSPECT surface to be waterproofed. Does it meet manufacturer’s requirements for finish, imperfections and other
criteria?
CHECK whether in accordance with drawings, especially provision of chamfers at corners/edges and chases for
terminations
ENSURE that surface is free from all contaminants (mud, wet, release agents, curing compounds, etc.) and in
accordance with manufacturer’s requirements
PLAN works to prevent membrane being left exposed for long period of time
DO NOT accept just any degree of finish Membrane puncture under load
DO NOT waterproof over blow holes, poorly Membrane not sandwiched correctly
compacted concrete or where brickwork or blockwork
has not been flush pointed
DO NOT take on the contract unless you are happy the Your company will get the blame for foreseen leaks
membrane will be protected and that a suitable lap will
be left to connect to
6
1 C : Application
DOs
MAKE SURE the correct primer is applied, following the instructions for number of coats and coverage rate
ALLOW primer to dry for the required length of time before applying membrane
ENSURE that reinforcing strips, angle fillets, etc. are used at changes in direction and are as required by manufacturer
ENSURE that all specified laps are provided and are rolled down
ALWAYS check what is required as a minimum loading coat, since the membrane is designed to be sandwiched
DO NOT omit primer on horizontal surfaces unless Subsequent defects in unbonded sheets provide a path
agreed by manufacturer for water ingress
DO NOT prime more than can be waterproofed in the Contamination with site dust/condensation/rain resulting
same day in lack of adhesion
DO NOT just unroll and drop down a vertical surface Air pockets behind the membrane
DOs
ALWAYS USE a suitable protection board, of the correct thickness to avoid damage, spot-bonded to the membrane
DISCUSS the backfilling procedure with the site manager or design team. If this work is to be done by others,
arrange to be present to check for site damage
ENSURE that the backfilling does not impede a lap joint that you may have to work from later
DO NOT store materials on unprotected membrane Leakage from punctured or damaged membrane
DO NOT tip waste material as backfill Settlement and downward displacement of protection
board and membrane
DO NOT leave a sheet membrane unprotected Subsequent problems, since damage - whether
intentional or not - often goes unrecorded
DO NOT drill or puncture surface without checking with Loss of waterproofing integrity of the membrane and
the installer potential for leakage
7
2 Cavity drain membranes
2A: Storage and handling
DO
DO NOT allow ancillary sealing tapes to become cold Difficulty stripping release paper and probably poor
or wet adhesion
DOs
CHECK and remedy unacceptable leaks in concrete or masonry substrate before the system is installed
CHECK there are no depressions in floor slab which may cause ponding
DO NOT lay cavity former over uneven floor surface Damage and ponding, leading to leakage
DOs
CHECK total integrity of cavity drainage system and inspect membrane for damage before placing screeds or
blockwork finishes
ENSURE that mesh reinforcement (if required) for floor screeds is supported
DO NOT allow fixing through finished floor screeds, or Cavity membrane will not be loaded correctly
unauthorised channels in the finished loading screed
DO NOT allow membrane and finishes over membrane A meaningful guarantee could not be issued by the
to be carried out by two different parties membrane installer
8
2 D : Protection and backfilling
DOs
ENSURE that reinforcement mesh is supported and has not damaged cavity drainage system while being positioned
Licensed copy from CIS: uniport, UNIVERSITY OF PORTSMOUTH, 07/07/2015, Uncontrolled Copy.
DO NOT proceed until everything has been inspected Water penetration at damaged areas
and any damage repaired
DO NOT drag reinforcing mesh across cavity drainage Damage and perhaps water penetration
system
9
3 Bentonite clay active membranes
3A: Storage and handling
DOs
DO NOT place materials in standing water Prehydration and need for replacement
D O
DOs
DO NOT place panels on unrendered masonry surfaces Loss of bentonite into voids. Loss of efficiency
DO NOT leave exposed for more than 48 hours Prehydration and need for replacement
DO NOT lay large areas and leave uncovered Prehydration and need for replacement
10
3 D : Protection and backfilling
DOs
USE sand if possible, but nothing larger than 50 mm (MOT Type II is acceptable)
DO NOT use plastic sheeting or prevent water System takes longer to react
reaching the system
11
4 Liquid-applied membranes
4A: Storage and handling
DOs
ROTATE stock
Licensed copy from CIS: uniport, UNIVERSITY OF PORTSMOUTH, 07/07/2015, Uncontrolled Copy.
DO NOT STORE longer than 12 months Some loss of solvents, causing increase in viscosity
DOs
FOLLOW manufacturer’s recommendations for surface flatness, keeping it generally within 3-4 mm
PLAN works to prevent membrane being left exposed for long periods
DO NOT apply to a dusty or flaking surface Membrane will not bond to substrate or may not leave
the brush
12
4C: Application and finishing
DOs
DO NOT apply when temperature is below 5°C Surface may frosty, i.e. wet
DO NOT pour onto substrate or apply thickly Trapped solvent and failure to cure
DO NOT leave exposed to UV light for more than Membrane will weather, become thin and brittle
28 days
DO NOT apply the material too thinly Membrane will not function as designed but instead
will leak
DO NOT apply a second coat before the first is fully Will damage continuity of first coat and cause solvent
cured entrapment
DOs
External protection
Internally
ADD masonry skin with 20 mm cavity filled with sand/cement mortar as work proceeds
In all cases
ALWAYS allow for suitable protection which should be provided by the company laying the membrane
DO NOT leave membrane unsupported internally Membrane will ‘blow’, leading to failure
13
5 Mastic asphalt membranes
5A: Storage and handling
DOs
DO NOT increase the distance that molten material is Material could cool down and become difficult to lay
carried
DOS
ENSURE all oils, greases and contaminates are removed from all surfaces
DO NOT penetrate horizontal or vertical surfaces with Leakage failure around pipes
services
5C: Application
DOs
PIERCE and make good any ‘blows’ while mastic asphalt is still warm
ENSURE all succeeding coats follow the preceding coats without delay
DO NOT allow temperature of remelt to exceed 230°C Adverse effect on viscosity of bitumen
for sustained periods
DO NOT lay successive coats on cold or contaminated Lack of bond and contamination between coats
preceding coats
14
5 D : Protection and backfilling
DOs
PROVIDE protective screed to horizontal asphalt work as soon as practicable after laying
PROVIDE vertical brickwork protection and concrete loading coat designed to withstand the expected water pressure
on internally applied tanking,
MAINTAIN sump with pump facility until all loading is complete - if water pressure present
Licensed copy from CIS: uniport, UNIVERSITY OF PORTSMOUTH, 07/07/2015, Uncontrolled Copy.
DO NOT backfill externally without protection to the Damage to asphalt by other trades, before and during
vertical asphalt backfilling
15
6 Cementitious crystallization active systems
6A: Storage and handling
DOs
WEAR suitable protective clothing to prevent contact with skin, eyes, nose, throat, etc.
DO NOT use materials once they have become wet or Materials will not hydrate fully
hardened
DOs
CONTROL suction
DO NOT ignore defects in the substrate Cracking and debonding of the system
6 C : Application
DOs
16
6 D : Protection and backfilling
DOs
17
7 Proprietary cementitious multi-coat renders, toppings, and
coatings
7A: Storage and handling
DOs
WEAR protective clothing, and keep a copy of the manufacturer’s safety sheet handy
Licensed copy from CIS: uniport, UNIVERSITY OF PORTSMOUTH, 07/07/2015, Uncontrolled Copy.
KEEP out of reach of children, and dispose of waste and surplus correctly
DO NOT allow materials to freeze or be subject to Material may become unusable and system ineffective
extreme heat, or store in an unsuitable environment
DOs
ROUGHEN or hack all the surface to produce mechanical key or use surface retarders when placing concrete
IDENTIFY likely problems or defective areas and agree what will be done as regards repair
DO NOT apply materials to a frosted surface, or when Slow rate of cure and poor surface bond
temperature is below 5°C
DO NOT use beyond shelf life Mix will be incorrect and the system will not function
DO NOT proceed until water infiltration is stopped Unable to apply system correctly to surface
DO NOT apply to substrate of inferior structural quality Cracking and failure of system
and soundness
DO NOT apply to thoroughly dry surface Rapid drying out of material, causing poor surface bond
18
7 C : Application
DOs
USE correct grading of sand, and seive sand and cement before use, where appropriate
Licensed copy from CIS: uniport, UNIVERSITY OF PORTSMOUTH, 07/07/2015, Uncontrolled Copy.
FOLLOW manufacturer’s application procedures, and have a copy available for reference
CURE correctly
MONITOR their progress to ensure backgrounds are prepared correctly and that each coat is applied properly
DO NOT ‘scratch’ the previous coat to form a key. System failure and inability to apply materials correctly
Use a ‘splatter coat’
DO NOT butt-joint coats System failure and inability to apply materials correctly.
Damp/water penetration
DO NOT use soft sand or old cement System failure and inability to apply materials correctly.
If wrong mix is used, the system will leak
DO NOT add unspecified materials to the mix If wrong mix is used, the system will leak
DO NOT use inexperienced staff System failure and inability to apply materials correctly
AVOID fittings fixed mechanically through the system Continuity of waterproofing may be compromised,
leading to water/damp penetration
DO NOT mix materials incorrectly Poor quality render, system will leak
DO NOT exceed waiting times between coats Poor bond between coats
DO NOT use unsieved sand or cement Oversize grains and foreign bodies can cause problems
DO NOT forget to cure correctly May cause cracking and water penetration
DOs
BOND fixings
DO NOT use unsuitable decorative coatings/finishes Visual deterioration of coating/finish may occur
19
Geocomposite drainage systems
A: S t o r a g e a n d h a n d l i n g
DO
DO NOT leave exposed to ultraviolet light for long Decomposition of geotextile fabric
periods
B: Preparation of substrate
D O
C: A p p l i c a t i o n a n d f i n i s h i n g
DOs
ENSURE that geocomposite filter membrane extends to wrap drainage pipe or links to a fin or other drain
ENSURE drainage outlet is to lower side of structure and drains away from building
DO NOT allow bonding tapes to become cold or wet Difficulty in stripping release paper or poor adhesion
D O
2 0
Loading coat A material applied to the
Glossary waterproofing membrane to enable
it to resist hydrostatic pressure
Air dry When the surface humidity of a
material is equal to that of the Low-permeability Resistant to water penetration
ambient surrounding air
Low water table Where the water table is
C o m b i n e d s y s t e m Two or more waterproofing permanently below the underside
systems used together of the lowest floor level
Expansion joint Joint that permits relative Vapour resistance The ability of a material to resist
movement caused by expansion vapour penetration
and contraction due to changes of
temperature or moisture Vapour-resistant Excludes water and has a high
resistance to vapour penetration
External Where the waterproofing system is
waterproofing positioned and placed against the Variable water Where the water is occasionally
outside face of the main structure table above the underside of the lowest
floor level
External (reverse) Where the waterproofing is
Water Water in its liquid form
waterproofing positioned outside the main
structure but placed against the
Waterstop A product or system, placed in-situ,
enabling works
to prevent the passage of water
through a discontinuity or joint in
Free-draining Ground through which free water
site-placed concrete
rapidly drains away
Waterproof Impervious to water, not permitting
High water table Where the water table is above the water to penetrate
underside of the lowest floor level
Waterproofing The total method or combination of
Hydrostatic head Water pressure, expressed as an system materials used to create a
equivalent depth of water waterproof protection
Hydrostatic The water pressure exerted as a Water-resistant Having a high resistance to water
pressure result of a hydrostatic head penetration
21
BASEMENT WATERPROOFING: SITE GUIDE
British
Structural
Waterproofing
Association