Sie sind auf Seite 1von 1

ELASTOMERIC WATERPROOFING

EL.(+)3.75m COATING & GEOTEXTILE LAYER


75 mm HIGH, 115 THK. BRICK WALL
M25 SCREED CONCRETE 50mm THK.
EL.(+)3.50m
SLOPE
SLOPE
0 ( 1 :1 00 ) (1:100)
END LOCK

690 1000 1200 820


R.C.C. SLAB(150mm THK.)
1950
TYP. DETAIL OF ROOF WATER
PROOFING/FINISHING
1200

1200

1200
W1 W1
RS1 W1

2100
75 mm HIGH, 115 THK. BRICK
D-1A WALL

15THK. CEMENT
900

900

900
SAND PLASTER

EL.(±)0.20m
FFL WATER FILTER NET
EL.(±)0.00m EL.(+)0.15m
FGL FGL ROOF FINISH
DRAIN
AS PER DETAIL
75mm THK. PCC
COMPACTED EARTH FILLING
(1:4:8) EL.(±)0.00m GENERAL NOTES:
FGL
1. ALL DIMENSIONS ARE IN MM & LEVEL ARE IN METER.
A B C 100mm THK.
GRAVEL D ROOF SLAB 2. ALL RCC WORKS SHALL BE DONE WITH MIN. CONCRETE DESIGN MIX OF
CONC. FILLET GRADE M-25, AS PER RELEVANT IS.456-2000.
400 1175 2775 2300 3245 1175 110Ø PVC PIPE 3. ALL BRICK WORK SHALL BE USING AT LEAST CLASS DESIGNATION 5 OF
115 OUTER FACE APPROVED QUALITY CONFORMING TO IS: 2212 & IS:1077.
GRID-5 ELEVATION OF WALL 4. DOORS AND WINDOWS SHALL HAVE ELECTRO COLOR DYED ALUMINUM
FRAMEWORK ANODIZED WITH 15 MICRON COATING THICKNESS AS PER
ROOF WITH RAIN WATER STANDARD SPECIFICATION.
5. ROOF OF THE MCR BUILDING SHALL CONSIST OF CAST IN SITU RCC SLAB
DOWN TAKE PIPE TREATED WITH A WATER PROOFING SYSTEM. AS PER STANDARD
SPECIFICATION. CLAUSE NO:- 2.4.10.7.
1000 LITERS. WATER 6. THE PAINT SHALL BE ANTI-FUNGAL QUALITY OF REPUTED BRAND SUITABLE
TANK (SINTEX HDPE) FOR MASONRY SURFACES FOR HIGH RAINFALL ZONE. FOR DETAIL OF PAINT
CONFIRMING AS PER FGL +0.400L
IS:12701
OF WALLS & CEILING OF STANDARD SPECS. SHALL BE FOLLOWS 2.4.10.10.
7. THE SCADA/ OFFICE & AC STORE SHALL BE PROVIDED WITH FALSE CEILING
ALUMINIUM FRAME WORK USING 25mm SIZE ALUMINUM 'T' & 'L' ANGLE
PATTERNED COLOR COATED FORMED ALUMINUM SLATS WITH INSULATION
BACKING AS PER CI.2.4.10.9 OF STANDARD SPECIFICATION.
CONCRETE M20 8. ALL FINISHING ITEMS SHALL BE AS PER STANDARD SPECIFICATION
EL.(+)3.75m THK.=75MM 9. NECESSARY ANTI TERMITE TREATMENT SHALL BE PROVIDED FOR MCR
1 BUILDING AS PER STANDARD SPEC.
EL.(+)3.50m NGL ±0.000L 10. ALL WINDOW & VENTILATORS OF BUILDING SHALL BE PROVIDED WITH
3 SUITABLE MS GRILLS.
-0.200L 11. COLUMN SHALL BE EXTENDED ABOVE FLOOR SLAB BY 1250 MM
300

25NB PVC PIPE


TOILET INLET
2000 715 1800 405 GRAVEL STONE 20x30
1500 FILL THE GRAVEL AND SIDE FOR APPROVAL
PLY BOARD
COVER IN BRICK WALL 00 27.03.19
PARTITION
5 REV. DATE REVISION HISTORY
PARTITION
TYP. DETAIL OF RAMP
PROJECT TITLE :
1200

1200

1200
W2 D3 W1 100 MW SOLAR PLANT IN THENAMPATTI, TAMIL
W1 NADU

CLIENT :
TIRUNVELI SOLAR PROJECT PVT. LTD.
E-5,GROUND FLOOR,DEFENCE COLONY,
900

900

900

NEW DELHI-110024
230 THK.
BRICK WALL OWNERS ENGINEER:
115
EL.(+)0.00m
FGL DRAIN FICHTNER CONSULTING ENGINEERS (INDIA) PVT.
1000 400 LTD. , CHENNAI, BENGALURU
75mm THK. PCC (1:4:8) 100mm THK. GRAVEL COMPACTED EARTH FILLING
2775 2300 3245 INTERNAL
25NB PVC PIPE A B C D PLINTH PLASTER
50 THK. PCC EPC CONTRACTOR: RAYS POWER INFRA PVT. LTD. 3RD
WATER TANK INLET COPING 1:3:6
12mmTHK.1:4 FLOOR LANDMARK HOUSE
BEAM FFL
PLOT-65,SECTOR-44 GURUGRAM 122003
GRID-1 ELEVATION FGL FGL

VARIES
DRAWING TITLE :
50 MCR ARCHITECTURAL PLAN &
ELEVATION DETAIL
FFL 50 THK. 75 THK.
CM 1:4 75 THK.
FGL PLASTER PCC 1:3:6 PCC 1:2:4 DRAWING NO. : RPIPL-TN-CE-DWG-MCR-002
12mm THK. 75 THK. BRICK BALLAST PCC 1:3:6
50MM PCC
40mm NOMINAL SIZE SITE CO-ORDINATE. : 8.96925833N, 77.90166667E
BRICK BASE (1:3:6)
MASONRY
75 THK. TYP.DETAIL OF PLINTH PROTECTION SHEET NO. 2 OF 2 SCALE N.T.S.
50 THK.
PCC 1:3:6
PCC 1:3:6 STEP DETAIL DRAWN VSH PAPER SIZE A0
CHECKED PAYAL REV NO. R0
APPROVED NSG DATE 27.03.2019

Das könnte Ihnen auch gefallen