Type of studies:
• Switching frequency over voltage studies
• Temporary over voltage studies
1.00
0.50
0.00
2.00
E_A2_Open_End
Modelling Aspects:
• System represented at least up to two buses away from point
of study
• Frequency dependent transmission line models
• Detailed transformer model including saturation data
• Shunt devices
• Surge arrester non- linear characteristics
• Equivalent voltage source models to represent network
boundaries
30743 31243
Equivalent
Voltage
SUDAIR 19011
132 kV
Side 19008 19015
19030 19013
Model data
• Bus voltage & angle
• Real power & reactive
power
RRL
• Positive sequence
impedance
Zero sequence
RL
•
impedance
Modelling type
• PI-section Model
COUPLED
• Provide the correct fundamental frequency
impedance, but do not provide an accurate PI
SECTION
full-frequency transient response.
• Suitable for steady-state studies (such as a
load flow).
Bergeron Model Options
Modelling type
• Frequency-Dependent Model
• Represent the transmission line’s travelling wave
characteristics.
• It is accurate for all range of frequencies.
G1 G2
Tower cross section
• Geometrical arrangement of C3 12 [m] C6
30 [m]
conductors
C2 C5
• Ground clearance 9 [m]
• Line sag C1 C4
Tower: H-Frame-3H4
32 [m] Conductors: chukar
Ground_Wires: 1/2_HighStrengthSteel
0 [m]
1 1 1 1 1 1 1 1
#2
Model data #1 #2 #1 #3
• General Data
• Ratings, impedance
• Saturation Data
Transformer Saturation Characteristics
1.5
1
Flux linkage (pu)
0.5
0
‐100 ‐50 0 50 100
‐0.5
‐1
‐1.5
Current (%)
Model
• Shunt reactor – with equivalent inductance
• Shunt capacitor – with equivalent capacitance
• Series compensation – with equivalent capacitance
2.20 [uF]
3.19 H
Model data
• Bus voltage & angle
• Real power & reactive
power
RRL
• Positive sequence
impedance (Xd”)
Zero sequence
RL
•
impedance (if available)
Model data
• Arrester rating i.e. 360 kV
• V-I characteristic
• Energy absorption capability i.e. 13 kJ/kV
2.6
2.2
Voltage (pu)
1.8
1.4
1.0
0 5 10 15 20
Current (kA) 25 30 35 40 45
Cable model
• Bergeron model
• R,X,B (or Surge impedance and Bergeron Model Options
1 1 1
Cable model
• Pipe type
• Three cables flat or trefoil configuration
A
Inner Coax Cable
Conductor B
Conductor
Insulator 1 Insulator 1
Sheath Sheath
Insulator 2 Insulator 2
0.022 0.022
0.0395 0.0395 0.041 [m]
0.044 0.044 0.042 [m]
0.0475 0.0475 0.043 [m]
0.0 [m]
• Fault levels
• Field results
Simulation setup
• Point on wave impact - 100 points over a cycle
• Trapped charge on lines
• Statistical breaker
• Network topology (credible scenarios)
1.5
0.5
Voltage (pu)
0
0 t1 t2 tx 0.01 0.02
‐0.5
‐1
‐1.5
Time (seconds)
Meas-Enab
. Meas-Enab
Ch. 1 . V1
.
.
Ch. 2
Multiple
Run
Ch. 3 Multiple Addtional
Run Recording
Ch. 4
Trapped Charge
Main : Graphs
2.00
E_GV_Line End
Simulation of trapped charge
on transmission line
1.50
1.00
0.00
-0.50
-1.00
-1.50
-2.00
x 0.480 0.500 0.520 0.540 0.560 0.580 0.600 0.620
Main : Graphs
E_GV_Line End
2.00
0.00
Credible Scenarios
• 10 -20 different scenarios for each line
- 100 point on wave simulations for each scenario
Voltage in kV
Closing Time E_19011 E_31227 E_A1 E_A2 E_B1 E_B2