Sie sind auf Seite 1von 1

TECHNICAL SPECIFICATION

DETAILED MATERIAL LIST MAIN SWITCHBOARD


24kV, 630A(Busbar), 16kA/1s --- BUS 20kV
Cubicle Name INCOMING OUTGOING

Product SM6R SM6R

Cubicle Type IM QM
Quantity 1 1
Ith 16kA/1s 16kA/1s
Depth / mm 1030 1030
Height / mm 1600 1600
Width / mm 500 500
Colour RAL9003 RAL9003

Safety Internal Arc Protection (3 sided / 4 sided) YES / 3 sided YES / 3 sided
Internal Arc Protection 12,5kA 12,5kA
Gas Exhaust Direction Downwards Downwards
IP Protection Degree IP3X IP3X
Antiseismic Protection --- ---

Busbar Busbar Current (A) 630A 630A


Busbar (Horizontal main busbars) Sleeved Sleeved

Switching Compartment Withdrawable or Fixed Fixed - Manual Fixed - Manual


Type of Breaker/Switch LBS - CIT LBS - CI1
Rated Current at 40°C 630A 200A
Short Time Withstand 16kA/1s 16kA/1s

Circuit Breaker Frequency --- ---


Opening Coil (qty:1) --- ---
Closing Coil (qty:1) --- ---
Motor (qty:1) --- ---
Undervoltage Coil --- ---

Fuse Rating of Fuse --- Fusarc 16A

Earthing Switch Earthing Switch YES YES


Signalling Contact --- ---

Voltage Transformer Type --- ---


Connection --- ---
Reference Number --- ---
Primary Voltage --- ---
1. Secondary --- ---
2. Secondary --- ---
Blown Fuse Contact --- ---
MV Fuse --- ---

1st Current Transfomer Q'ty / Manufacturer --- ---


Conventional Type Reference Number --- ---
Primary Current --- ---
1. Secondary, Burden and Class --- ---
2. Secondary, Burden and Class --- ---
3. Secondary, Burden and Class --- ---
Ith --- ---

Ring CT Q'ty / Manufacturer --- ---


Type --- ---
Primary Current --- ---
1st CT, Burden and Class --- ---
2nd CT, Burden and Class --- ---
Ith --- ---

MV Cable Connection/ Max. Quantity of cables per phase BOTTOM entry BOTTOM entry
Cable Type XLPE / STANDARD XLPE / STANDARD
Cable section 3x1c maxi 240mm² 3x1c maxi 240mm²
Cable Box --- ---
Voltage Presence Indicators YES YES
Surge Arrester --- ---

LV Equipment Thermostat Heater --- ---


Door Lock --- ---
Internal Lighting --- ---
Heater YES - 220VAC YES - 220VAC
Test Terminal --- ---
Protection Relay --- ---
Metering and Other Equipment --- ---
Push Button --- ---
Pilot Lamp --- ---
Selector Switch --- ---

Mimic Diagram Type YES YES

Packing Seaworthy / Land packing Seaworthy Seaworthy


Fumigation --- ---

Switchboard Accessories
End Cover Plates (for complete switchboard)

Das könnte Ihnen auch gefallen