Agenda
OVERVIEW OF REGULATIONS
NSPS, 40 CFR Part 60, Subpart Ja
Refinery Sector Rule 63.670
GE RSR SOLUTION
2
Confidential. Not to be copied, distributed, or reproduced without prior approval.
Refinery Sector Rule (RSR)
63.670
IMPLEMENTATION TIMELINE
OVERVIEW OF REGULATION
• Includes ALL sources, not just new sources
• Flares must control, maintain and demonstrate a 96.5% combustion efficiency or a 98% destruction efficiency
• Flares must maintain a minimum combustion zone Net Heating Value of 270 BTU/scf and report values every 15 minutes
• Flares must operate with no visible emissions, except for periods not to exceed a total of 5 minutes during any 2 consecutive
hours
• Flare tip pilot flame must be maintained and velocities may not exceed 400 ft/s
• Operators must measure and control all assist flows to assure that the combustion zone stays above the minimum Net
Heating value
3
Confidential. Not to be copied, distributed, or reproduced without prior approval.
RSR (continued)
TABLE 13 - CALIBRATION AND QUALITY CONTROL REQUIREMENTS FOR CPMS
Parameter Minimum accuracy requirements
Temperature ±1% over normal measured range or 2.8 ˚C, whichever is greater
±5% over normal measured range or 0.5 GPM, whichever is greater for liquid flow
Flow rate for all flows other than
±5% over normal measured range or 10 CFM, whichever is greater for gas flow
flare vent gas
±5% over normal measured range for mass flow
±20% of flow rate at velocities raging from 0.1 to 1 ft/s
Flare vent gas flow rate
±5% of flow rate at velocities greater than 1 ft/s
Pressure ±5% over normal operating range or 0.12 kilopascals, whichever is greater
Hydrogen analyzer ±2% over the concentration measured or 0.1 volume percent, whichever is greater
4
Confidential. Not to be copied, distributed, or reproduced without prior approval.
Challenges for Flare Control
5
Confidential. Not to be copied, distributed, or reproduced without prior approval.
GE RSR Solution
Generalized schematic of flare control
flare.IQ
DCS
ETHERNET
Control Valve
Meter
STEAM/AIR
CONTROL VALVE FLOW Fuel
Meter
6
Confidential. Not to be copied, distributed, or reproduced without prior approval.
flare.IQ Field Validation Testing
DEMONSTRATED ACCURACY: 3-5% against Mass Spectrometer Reference
1500
1400
1100
1000
900
BTU/SCFH
800
700
600
500
400
300
200
100
0
0 500 1000 Time (min) 1500 2000 2500 3000
7
Confidential. Not to be copied, distributed, or reproduced without prior approval.
Nitrogen Purge flare.IQ Performance
DEMONSTRATED ACCURACY: 6% against Mass Spectrometer Reference
1000 50
800 40
N2 CONCENTRATION
NHV
600 30
400 20
200 10
0 0
8
Confidential. Not to be copied, distributed, or reproduced without prior approval.
flare.IQ Field Validation Testing
DEMONSTRATED ACCURACY: 3-5% against GC with time corrected data
1400
NHV_Flare.IQ NHV_GC
1300
1200
1100
1000
900
800
700
600
500
400
1110 1120 1130 1140 1150 1160 1170 1180
9
Confidential. Not to be copied, distributed, or reproduced without prior approval.
BHGE flare.IQ Technology
Overview
OUTPUT:
USER INPUTS: Qsteam_req CALCULATE:
Qsteam (min,max)
Qfuel (min, max)
Qfuel_req
MW
NHVcz
Cmeasured to MWm to NHVm
H2 Compensated NHVvg =
Vtip
= = =
11
Confidential. Not to be copied, distributed, or reproduced without prior approval.
NHVvg from flare.IQ and GC in Customer Site
(GC output update rate ~ 10min)
1300
1280 GC FlareIQ
1260
NHV (BTU)
1240
1220
1180
12:00 PM 6:00 PM 12:00 AM 6:00 AM 12:00 PM
Time
2500 35
30
2000 NHV from Gas Chromatograph NHV from FlareIQ
25
Iso-Butane (%)
iso-Butane
NHV (BTU)
1500
20
15
1000
10
500
5
0 0
9:36:00 AM 2:24:00 PM 7:12:00 PM 12:00:00 AM 4:48:00 AM 9:36:00 AM 2:24:00 PM
Time
2300
2100
NHV from Gas Chromatograph NHV from FlareIQ
1900
1700
NHV (BTU)
1500
1300
1100
900
700
500
6:57:36 PM 7:12:00 PM 7:26:24 PM 7:40:48 PM 7:55:12 PM 8:09:36 PM 8:24:00 PM
Time
340
330
320
310
NHVcz
300
290
280
NHVcz NHVcz lower limit
270
12:00 PM 6:00 PM 12:00 AM 6:00 AM 12:00 PM
Time
70
60
50
Vtip (ft/s)
40
30
10
0
12:00 PM 6:00 PM 12:00 AM 6:00 AM 12:00 PM
Time
Questions?