Relion ® 615 series

Motor protection and control


REM615
Compact and versatile solution for utility
and industrial power distribution systems
Compact protection and control for
asynchronous motors

REM615 is a dedicated motor protection and control relay Standardized communication and redundancy
for protection, control, measurement and supervision of REM615 fully supports the IEC 61850 standard for
asynchronous motors in the manufacturing and process communication and interoperability of substation automation
industry. devices, including fast GOOSE messaging and IEC 61850-
9-2 LE, and can now also benefit from the extended
Application interoperability provided by Edition 2. The motor relay
REM615 has been designed to be the main protection for further supports both the parallel redundancy protocol
asynchronous motors and their drives in manufacturing and (PRP) and the high-availability seamless redundancy (HSR)
process industry. Typically, the motor relay is used with protocol, together with the DNP3, IEC 60870-5-103 and
circuit-breaker and contactor-controlled MV motors and Modbus® protocols. With the protocol adapter SPA-ZC 302,
medium-sized and large contactor-controlled LV motors Profibus DVP1 can also be used. REM615 is able to use two
in a variety of drives. The drives include both continuously communication protocols simultaneously.
and intermittently operated asynchronous motor drives with
varying load, such as pumps and conveyors, crushers and For redundant Ethernet communication, REM615 offers either
choppers, mixers and agitators, fans and aerators. two optical or two galvanic Ethernet network interfaces. A
third port with a galvanic Ethernet network interface provides
REM615 is available in four standard configurations, one connectivity of any other Ethernet device to an IEC 61850
of which includes support for three combi-sensor inputs station bus inside a switchgear bay. The redundant Ethernet
for phase currents (Rogowski coil) and voltages (voltage solution can be built on the Ethernet-based IEC 61850,
divider) and the other for conventional current and voltage Modbus ® and DNP3 protocols.
instrument transformers. The standard configurations can be
tailored to meet application-specific requirements using the The implementation of the IEC 61850 standard in REM615
IEC 61850-compliant Protection and Control IED Manager covers both vertical and horizontal communication, including
PCM600. GOOSE messaging with both binary and analog signals as
well as parameter setting according to IEC 61850-8-1. Also
To minimize the effects of an arc fault, REM615 can be IEC 61850-9-2 LE process bus with sending sampled values
equipped with high-speed outputs decreasing the operate of not only analog voltages but now also currents, in addition
time by four to six milliseconds compared to conventional to receiving sampled values of voltages, is supported. For
binary outputs. process bus applications, which require high-accuracy time
synchronization, IEEE 1588 V2 is used, with a time stamp
Human-machine interface resolution of not more than four microseconds. IEEE 1588
As a member of the Relion® product family, REM615 shares V2 is supported in all variants with a redundant Ethernet
the same human -machine-interface (HMI) look and feel as the communication module. In addition, REM615 supports
other Relion protection and control relays and IEDs. The same synchronization over Ethernet using SNTP or over a separate
look and feel includes the location of a push button with a bus using IRIG-B.
certain function and the menu structure.

REM615 is equipped with a large graphical display which


can show customizable single-line diagrams (SLD) with
position indication for the circuit breaker, disconnectors and
the earthing switch. Also measured values provided by the
chosen standard configuration can be displayed. The SLDs
are customized using PCM600 and can have multiple pages
for easy access to selected information. The SLDs can be
accessed not only locally but also via the web browser-based
HMI that has now been enriched with a number of usability
enhancing features.

2 Motor protection and control | REM615


UL1UL2UL3 REM615 MOTOR PROTECTION AND CONTROL RELAY STANDARD
B
CONFIGURATION

PROTECTION LOCAL HMI ALSO AVAILABLE

- Disturbance and fault recorders


2× 3× - Event log and recorded data
Master Trip Master Trip
- High-Speed Output module (optional)
Configuration A
System
HMI

Lockout relay Lockout relay


Time
Authorization

- Local/Remote push button on LHMI


94/86 94/86 I ESC Clear
- Self-supervision
- Time synchronization: IEEE 1588 v2,
A
O R
L
U12 0. 0 kV
P 0.00 kW
SNTP, IRIG-B
3I
Q 0.00 kVAr

2× - User management
IL2 0 A

3I< I2>M I2>> - Web HMI


37 46M 46R I
AND
ESC Clear

O R
L
OR

Is2t n< 3Ith>M


49, 66, 48, 51LR 49M

CONDITION MONITORING COMMUNICATION


3× 3× AND SUPERVISION
ARC 3I>>> Protocols:
50L/50NL 50P/51P 3I Io
IEC 61850-8-1/-9-2LE
Modbus®
IEC 60870-5-103
3I>/Io>BF Ist> FUSEF CBCM MCS 3I DNP3
51BF/51NBF 51LR 60 CBCM MCS 3I Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial: Serial glass fiber (ST),
2× RS-485, RS-232
3I> 3I>> OPTS TCS Redundant protocols:
51P-1 51P-2 OPTM TCM HSR
PRP
RSTP
Io Io

Io>>
CONTROL AND INDICATION 1) MEASUREMENT
51N-2
Io - I, U, Io, P, Q, E, pf, f
Object Ctrl 2)
Ind 3)
- Limit value supervision
CB 1 - - Load profile record
- RTD/mA measurement (optional)
DC 2 3 - Symmetrical components
Io>→
67N-1 ES 1 2
1)
Check availability of binary inputs/outputs Analog interface types 1)

from technical documentation Current transformer 4


Uo 2)
Control and indication function for
primary object Voltage transformer 3
UL1UL2UL3

3)
Status indication function for
primary object
1)
Conventional transformer inputs

UL1UL2UL3 2×
3U< U2> U1< f>/f<, ESTART
df/dt
27 47O- 47U+ ESTART
81

REMARKS
18× Optional 3× No. of Calculated OR Alternative
MAP function instances value function to be
MAP Io/Uo defined when
6xRTD ordering
2xmA

Protection function overview of REM615 standard configuration B

Main benefits 615 series


− − Withdrawable plug-in unit design for swift installation and REM615 is a member of ABB’s Relion product family and
testing part of its 615 protection and control series of relays,
− − Motor protection both during motor start-up and normal characterized by compactness and withdrawable plug-in unit
run, with protection and fault clearance also in abnormal design. In addition to REM615, the 615 series includes the
situations following relays:
− − Ready-made standard configurations for fast and easy −− REF615 Feeder protection and control
setup with tailoring capabilities − − RED615 Line differential protection and control
− − Motor protection with motor start-up and loss of load − − RET615 Transformer protection and control
supervision as well as thermal overload, motor load jam −− REU615 Voltage protection and control
and phase-reversal protection, either with sensors or − − REV615 Capacitor bank protection and control
conventional instrument transformers −− REG615 Generator and interconnection protection
− − IEC 61850 Edition 2 and Edition 1 support, including HSR
and PRP, GOOSE messaging and IEC 61850-9-2 LE for Life cycle services
less wiring and supervised communication ABB offers full support for all protection and control relays
−− IEEE 1588 V2 for high-accuracy time synchronization throughout their entire lifecycle. Our extensive life cycle
and maximum benefit of substation-level Ethernet services include training, customer support, maintenance and
communication modernization.
− − Large graphical display for showing customizable SLDs,
accessible either locally or through a web browser-based
HMI

REM615 | Motor protection and control 3


Standard configurations

Standard configurations
Standard
Description
configuration
Basic motor protection (RTD option) A
Motor protection with voltage and frequency based protection and measurements (RTD option) B
Motor protection with voltage and frequency based protection and measurements C
Motor protection with voltage and frequency based protection and measurements (sensor inputs) D

Supported functions, codes and symbols


Functionality
Protection
Three-phase non-directional overcurrent protection, low stage
Three-phase non-directional overcurrent protection, high stage
Three-phase non-directional overcurrent protection, instantaneous stage
Non-directional earth-fault protection, low stage
Non-directional earth-fault protection, high stage
Directional earth-fault protection, low stage
Three-phase undervoltage protection
Positive-sequence undervoltage protection
Negative-sequence overvoltage protection
Frequency protection
Negative-sequence overcurrent protection for motors
Loss of load supervision
Motor load jam protection
Motor start-up supervision
Phase reversal protection
Thermal overload protection for motors
Circuit breaker failure protection
Master trip
Arc protection
Multi-purpose protection
Control
Circuit-breaker control
Disconnector control
Earthing switch control
Disconnector position indication
Earthing switch indication
Emergergency startup

4 Motor protection and control | REM615


1, 2,.. = number of included instances / I/Os
( ) = optional

IEC 61850 IEC 60617 IEC-ANSI A B C D

PHLPTOC 3I> 51P-1 1 1 1 1


PHHPTOC 3I>> 51P-2 1 1 1 1
PHIPTOC 3I>>> 50P/51P 1 1 1 1
EFLPTOC Io> 51N-1 1 - -   -
EFHPTOC Io>> 51N-2 1 1 1 1
DEFLPDEF Io> → 67N-1 -  1 1)
1 1 1)

PHPTUV 3U< 27 -  1 1 1
PSPTUV U1< 47U + -  1 1 1
NSPTOV U2> 47O - -  1 1 1
FRPFRQ f>/f<, df/dt 81 -  2 2 2
MNSPTOC I2>M 46M 2 2 2 2
LOFLPTUC 3I< 37 1 1 1 1
JAMPTOC Ist> 51LR 1 1 1 1
STTPMSU Is2t n< 49, 66, 48, 51LR 1 1 1 1
PREVPTOC I2>> 46R 1 1 1 1
MPTTR 3Ith>M 49M 1 1 1 1
CCBRBRF 3I>/Io>BF 51BF/51NBF 1 1 1 1
TRPPTRC Master Trip 94/86 2(5) 2)
2(5) 2)
2(5) 2)
2(5) 2)

ARCSARC ARC 50L/50NL (3) (3) (3) (3)


MAPGAPC MAP MAP 18 18 18 18

CBXCBR I ↔ O CB I ↔ O CB 1 1 1 1
DCXSWI I ↔ O DCC I ↔ O DCC 2 2 2 2
ESXSWI I ↔ O ESC I ↔ O ESC 1 1 1 1
DCSXSWI I ↔ O DC I ↔ O DC 3 3 3 3
ESSXSWI I ↔ O ES I ↔ O ES 2 2 2 2
ESMGAPC ESTART ESTART 1 1 1 1

REM615 | Motor protection and control 5


Supported functions, codes and symbols
Functionality
Condition Monitoring
Circuit-breaker condition monitoring
Trip circuit supervision
Current circuit supervision
Fuse failure supervision
Runtime counter for machines and devices
Measurement
Disturbance recorder
Load profile record
Fault record
Three-phase current measurement
Sequence current measurement
Residual current measurement
Three-phase voltage measurement
Residual voltage measurement
Sequence voltage measurement
Three-phase power and energy measurement, including power factor
RTD/mA measurement
Frequency measurement
IEC 61580-9-2 LE sampled value sending 3)4)

IEC 61580-9-2 LE sampled value receiving (voltage sharing) 3)4)

6 Motor protection and control | REM615


1, 2,... = number of included instances / I/Os
( ) = optional

IEC 61850 IEC 60617 IEC-ANSI A B C D

SSCBR CBCM CBCM 1 1 1 1


TCSSCBR TCS TCM 2 2 2 2
CCRDIF MCS 3I MCS 3I 1 1 1 1
SEQRFUF FUSEF 60  - 1 1 1
MDSOPT OPTS OPTM 1 1 1 1

RDRE DR DFR 1 1 1 1
LPDMSTA LOADPROF LOADPROF 1 1 1 1
FLTRFRC FAULTREC FAULTREC 1 1 1 1
CMMXU 3I 3I 1 1 1 1
CSMSQI I1, I2, I0 I1, I2, I0 1 1 1 1
RESCMMXU Io In 1 1 1 1
VMMXU 3U 3V -  1 1 1
RESVMMXU Uo Vn -  -  1 - 
VSMSQI U1, U2, U0 V1, V2, V0 -  1 1 1
PEMMXU P, E P, E -  1 1 1
XRGGIO130 X130 (RTD) X130 (RTD) (1) (1) -  (1)
FMMXU f f -  1 1 -
SMVSENDER SMVSENDER SMVSENDER -  (1) (1) (1)
SMVRCV SMVRCV SMVRCV - (1) (1) (1)

1) “Uo calculated” is always used.


2) Master trip is included and connected to the corresponding HSO in the configuration only when the BIO0007 module is used. If additionally the
ARC option is selected, ARCSARC is connected in the configuration to the corresponding master trip input.
3) Available only with IEC 61850-9-2
4) Available only with COM0031-0037

REM615 | Motor protection and control 7


Contact us

For more information, please refer to

© Copyright 2016 ABB. All rights reserved.


REM615 Product Guide, or contact us:

ABB Oy, Medium Voltage Products


Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone: +358 10 22 11
Fax: +358 10 22 41094

ABB India Limited, Distribution Automation

1MRS 756902 H, 5.0 FP1


Maneja Works
Vadodara – 390013, India
Phone: +91 265 272 4402
Fax: +91 265 263 8922

www.abb.com/mediumvoltage
www.abb.com/substationautomation

Das könnte Ihnen auch gefallen