Sie sind auf Seite 1von 2

Instruction Leaflet IL032010EN Effective December 2015 Version 2.

105U-G-5W wireless gateway


installation guide
Figure 1. Antenna Installation

Antenna* 1 Wavelength
(minimum)

Wavelengths:
360 MHz = 32.7" (83 cm)
512 MHz = 22.8" (58 cm)

Stress
Relief
Loop
Weatherproof
Connections
(recommended:
3M™ 23 self-
NOTE bonding tape)

Refer to the user manual for


important regulatory and safety
information before installing and
using this product. 105U-G-5W Coaxial Cable
Mast

CAUTION ELPRO
Wireless Gateway
105U-G-5W
Ethernet

For continued protection against risk


RX
Serial
TX

RX
Radio

of fire, replace the module fuse only


TX

ACT OK

with the same type and rating.


Earth Conductor
BAT+
DIO 1
DIO 2
DIO 3
DIO 4
DIO 5
DIO 6

DIO 7
DIO 8

SUP1
SUP2
GND

GND

GND

Surge Arrestor at least 5 AWG


(recommended) (16 mm2)

Statutory requirements *For maximum


range, install
GND above local
EC: Unlicensed operation limits the at least 11 AWG (4 mm2) obstructions
radio power. High gain aerials may
Earth Stake
only be used to compensate for
cable losses. Provide good ground
connection to mast,
module, and surge
arrestor.
Antenna installation
If ground conditions
Use Figure 1 as a guide for are poor, use more
than one stake.
installing an antenna and attaching
it to the module.
Instruction Leaflet IL032010EN 105U-G-5W wireless gateway installation guide
Effective December 2015 EATON_105U-G-5W Install Guide
Version 2.0 
Installation Figure 2. Wiring Diagram
Choose a power supply option:
Host Protocol
• 12–24 Vac, 1.5A CSA certified Connection
Class 2 *
• 15–30 Vdc, 1.5A CSA certified
Class 2 *
• 11–15 Vdc, 2.0A
• Solar panel with battery

After choosing a power supply


option, wire the module as
shown in Figure 2.
NNote: All I/O must be SELV. ELPRO
DIO channels can be wired as inputs Wireless Gateway
or outputs.
105U-G-ET1
*Backup battery must be used Ethernet
if radio power is set to 2W or
higher.

When the wiring is completed, RX


connect the module to a Serial

computer (PC) and configure TX


it using the configuration
software. For details, refer to RX
the user manual. Radio
TX
Before operating the module,
read the sections on operation
and configuration in the user
manual to take advantage of all ACT OK
product features.

WARNING
EXPLOSION HAZARD
Do not disconnect while circuit
is live unless area is known to be
non-hazardous.

BAT+
DIO 1
DIO 2
DIO 3
DIO 4
DIO 5
DIO 6
DIO 7
DIO 8

SUP1
SUP2
SUP1
SUP1

SUP2

GND

GND

GND
GND

2A

– + – +
– +
DC Supply AC Supply 12–24 Vac
9–30 Vdc, 16 Vac 12V Backup Battery
Do not earth (optional; up to 100 Ah)
SUP1 or SUP2 Digital Input
connection.
Voltage-Free
Contact or To Earth
Transistor Connection
To Earth Device
Connection
+ –
Digital Output
Max. 30 Vdc, 500 mA
DC Relay Supply

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com © 2014 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Eaton’s wireless business Publication No. IL032010EN All other trademarks are property
www.eaton.com/wireless December 2015 of their respective owners.