Sie sind auf Seite 1von 84

Close

Close

2
Close
Grooved Piping Products
Tyco Fire Products is ISO 9001 Certified with products
manufactured in our newly constructed state of the art
domestic ductile iron foundry and manufacturing facilities. We
are committed to maintaining our leadership role in the
grooved piping industry through aggressive research and
development. The products that will improve our industry
tomorrow are being designed today. With this level of
investment and commitment, Tyco Fire Products is prepared to
become the industry standard.
Tyco Fire Products is a world leader in the manufacture and
distribution of piping products. Years of development,
engineering, pattern and tooling manufacturing, and the
acquisition of the necessary resources has provided the finest
grooved products available on the market today. Grooved Piping
Products are domestically manufactured to scrutinizing quality
standards as set forth by independent testing laboratories.
Our Technical and Engineering Services, located in Bethlehem,
PA, direct product development from concept through design,
testing and manufacturing, then forwards all aspects of
application engineering and quality assurance. Owners,
architects, consulting engineers, contractors, and tenants
demand the most dependable, quality grooved products for their
piping systems - the Bethlehem Engineering facility ensures their
demands are met each and every time.

General Notes: It is the Designer’s responsibility to


select products suitable for the intended service and
to ensure that pressure ratings and performance
data is not exceeded. Always read and understand
the installation instructions. Never remove any
piping component nor correct or modify any piping
deficiencies without first depressurizing and
draining the system. Material and gasket selection
should be verified to be compatible for the specific
application.

3
Close
Table of Contents
General Information .......................................... 3 - 11

System Design ............................................... 12 - 13

Groove Specifications ...................................... 14 - 17


Roll Groove ............................................................................. 14 - 15
Cut Groove .............................................................................. 16 - 17

Gaskets ........................................................ 18 -19

Installation Instructions .................................... 20 - 74


General Notes; Care and Maintenence ...................... 20
Grooved Couplings ........................................ 21 - 36
Figures 572 and 772 Rigid Couplings ........................... 21 - 25
Figure 575, 705 and 707 Flexible Couplings .............. 26 - 32
Figure 716 Reducing Coupling ....................................... 33 - 36

Mechanical Outlets ....................................... 37 - 45


Figure 730 Mechanical Tee and Cross .......................... 37 - 42
Figure 40-5 Strap .................................................................. 43 - 45

Flange Adapter
Figure 71 Flange Adapter ................................................. 46 - 48

Butterfly Valves ............................................ 49 - 52


Figures 570 and 580 ............................................................ 49 - 50
Supervisory Switch Replacement .................................. 51 - 52

Check Valves ............................................... 53 - 58


Figures 590F and 590FR..................................................... 53 - 56
Maintenance Kit .................................................................... 56 - 58

4 Table of Contents
Close
Table of Contents
Grooved Fittings ........................................... 58 - 68
ADACAP® ............................................................................................................................................................. 59
Figure 201 ............................................................................... 62 - 63
Figure 210 ............................................................................... 62 - 63
Figure 219 ............................................................................... 62 - 63
Figure 260 ........................................................................................ 64
Figure 301 ........................................................................................ 66
Figure 302 ........................................................................................ 66
Figure 303 ........................................................................................ 66
Figure 312 ........................................................................................ 64
Figure 313 ........................................................................................ 64
Figure 321 ........................................................................................ 67
Figure 326 ........................................................................................ 65
Figure 327 ........................................................................................ 65
Figure 341 ........................................................................................ 66
Figure 350 ........................................................................................ 68
Figure 501 ............................................................................... 60 - 61
Figure 510 ............................................................................... 60 - 61
Figure 519 ............................................................................... 60 - 61
Figure 513 ............................................................................... 69 - 74

Unit Conversions and Sprinkler Formulae .............. 75 - 77


Terms and Conditions of Sale ............................. 78 - 80
Product Index ................................................ 82 - 83

Table of Contents 5
Close
METALLURGICAL SPECIFICATIONS
Grooved Piping Products are domestically manufactured in our
state of the art ductile iron foundry. The applicable material
specifications for ductile iron, galvanizing and rubber-injection
apply.
HOUSING / FITTING SPECIFICATIONS
ASTM A-536 - (Cast Products)
Standard Specification for Ductile Iron Castings
Grade 65-45-12, Tensile Strength, minimum psi: 65,000
Yield Strength, minimum psi: 45,000
Elongated in 2" or 50mm, minimum 12%
ASTM A53 -
Schedule 40 Steel Pipe - Series 300 fittings
ASTM A-153 -
Standard Specification for Hot Dip Galvanizing
GASKET SPECIFICATIONS
(Refer to Gasket Recommendation Tables - No. 18-9.0 and 18-9.2)
Gaskets: Grade “E” EPDM with green color code identification
conforms to ASTM D-2000 for service temperature from -30°F
(-34°C) to 230°F (110°C). They are recommended for hot
water not to exceed 230°F (110°C), plus a variety of dilute
acids, oil free air and many chemical services. They are not
recommended for petroleum services.
Gaskets (fire protection): Grade “A” EPDMA with violet color
code identification conforms to ASTM D2000 for fire protection
services. For dry pipe and freezer systems use Tri-Seal Grade
“E” Gaskets with rigid couplings.
Gaskets: Grade “T” Nitrile with orange color code identification
conforms to ASTM D2000 for petroleum products. Not
recommended for hot water systems.
BOLT / NUT SPECIFICATIONS
Bolts and Nuts: Coupling bolts and nuts are heat treated carbon
steel, oval-neck track head bolts and heavy hex nuts, conforming
to ASTM A-183 minimum tensile strength of 110,000 psi. Bolts
and nuts are Zinc electroplated.
PAINT SPECIFICATIONS
Orange - non lead (standard)
Fire Brigade Red - non lead (optional)

6 General Information
Close
ISO 9001 CERTIFIED
Tyco Fire Products is ISO 9001 Certified confirming
conformance to quality standards of our products.

Factory Mutual Research Corporation


CERTIFICATE OF REGISTRATION
FMRC certifies herewith that

TYCO FIRE PRODUCTS


1550 Valley Center Parkway, Suite 135
Bethlehem, PA 18017
has demonstrated a Quality Assurance System
that complies with the requirements of

ISO 9001
Scope:

DESIGN AND MANUFACTURE OF CASTINGS, PIPE


COUPLINGS, FITTINGS, VALVES, AND RELATED PIPING
SYSTEM PRODUCTS

Registration No. Expiration Date

990604.1 June 30, 2002

This registration is subject to ongoing audits by FMRC.


Any change to the basis of this registration requires
acceptance in writing by FMRC.

August 31, 2000


Date
R.L. Martell, Asst. Vice President

TY SYS
LI
TE
A
QU

FMRC
RE

GI
S T R AT I O
®
RvA
The Dutch Council for Accreditation

General Information 7
Close
GOVERNMENT AGENCIES
Coast Guard - Approved each vessel individually
Corps of Engineers (COE) - GEGS 15000
Federal Aviation Administration (FAA) -
HVAC, Plumbing and Fire Protection
Federal Housing Administration (FHA)
General Services Administration (GSA) - 15000 Series
Military Specifications (MIL) - MILP - 10388 Fittings;
MIL - C - 10387 Couplings;
MIL - P - 11087A (CE) Steel Pipe,
Grooved MIL - I - 45208 Inspection Procedure
National Aeronautics and Space Administration (NASA)
Naval Facilities Engineering Command (NAVFAC)- NFGS 15000 Series
National Institute of Health (NIH) - Dept. of Health - 15000 Series
Veterans Affairs (VA) - 15000 Series
GENERAL CODE GROUPS, ASSOCIATIONS,
LABORATORIES AND APPROVAL BODIES
American Bureau of Shipping (ABS)
American National Standards Institute / American
Water Works Association (ANSI / AWWA)
American Petroleum Institute (API) - API Std. 5L, Sect. 7.5
American Society of Heating, Refrigerating and
Air Conditioning Engineers (ASHRAE)
American Society of Mechanical Engineers (ASME)
Power Piping, B-31.1; Chemical Plant and Petroleum
Refinery Piping, B-31.3; Refrigeration Piping, B-31.5;
Building Services Piping, B-31.9.
Building Officials and Code Administrators (BOCA)
Factory Mutual Engineering Corp. (FM) -
Approved for Fire Protection Services
Material Equipment and Acceptance (MEA)
National Fire Protection Association (NFPA)
New York Board of Standards and Appeals (NY-BSA)
Southern Building Code Congress International
(SBCCI) - Standard Plumbing
Underwriter’s Laboratories, Inc. (UL) - FM
Listed for Fire Protection Services See Fire Protection Submittal Sheet
Underwriters Laboratories of Canada (ULC) - for pressure rating and Listing and
Approval information.
Listed for Fire Protection Services

8 General Information
Close
Grooved Piping Products provide several design and economic
advantages when compared to welded or flanged systems.
Field modifications are easily accommodated with the Grooved
System as couplings and fittings can be easily rotated,
eliminated and/or added to facilitate the necessary
modification.

ECONOMICAL RETROFIT
Grooved couplings are the The Grooved System method
fastest method to join steel allows for quick economical
pipe. There is no need for changes as necessary for field
two holing with flanges, and retrofit, with the ability to isolate
the potential of fire hazards is equipment and piping systems
eliminated when compared to for tenant changes and system
welding or brazing. repair.

Rigidity ALIGNMENT
Figure 572 and 772 Rigid Every grooved coupling is a
Grooved Couplings are ideally union which provides easy
suited for valve and fitting access for maintenance or
connections, long runs, and piping system modification.
risers where pipe movement is Field modification can be
undesirable. Rigid couplings handled easily with minimal
provide for joints which are effort due to the
comparable to pipe jointing interchangeability of the
such as welding and flanging. grooved method.

DEPENDABILITY FLEXIBILITY
The coupling housing are Figure 575 and 705 Flexible
designed to engage into the Grooved Couplings allow for
grooves and provide a secure deflection of the piping system.
joint. The pipe ends are
sealed by a pressure
responsive gaskets which is
encapsulated by the ductile
iron housing.

General Information 9
Close
Decimal Equivalents of Fractions (inches)

1/64 0.015625 33/64 0.515625


1/32 0.03125 17/32 0.53125
3/64 0.046875 35/64 0.546875
1/16 0.0625 9/16 0.5625
5/64 0.078125 37/64 0.578125
3/32 0.09375 19/32 0.59375
7/64 0.109375 39/64 0.609375
1/8 0.125 5/8 0.625
9/64 0.140625 41/64 0.640625
5/32 0.15625 21/32 0.65625
11/64 0.171875 43/64 0.671875
3/16 0.1875 11/16 0.6875
13/64 0.203125 45/64 0.703125
7/32 0.21875 23/32 0.71875
15/64 0.234375 47/64 0.734375
1/4 0.25 3/4 0.75
17/64 0.265625 49/64 0.765625
9/32 0.28125 25/32 0.78125
19/64 0.296875 51/64 0.796875
5/16 0.3125 13/16 0.8125
21/64 0.328125 53/64 0.828125
11/32 0.34375 27/32 0.84375
23/64 0.359375 55/64 0.859375
3/8 0.375 7/8 0.875
25/64 0.390625 57/64 0.890625
13/32 0.40625 29/32 0.90625
27/64 0.421875 59/64 0.921875
7/16 0.4375 15/16 0.9375
29/64 0.453125 61/64 0.953125
15/32 0.46875 31/32 0.96875
31/64 0.484375 63/64 0.984375
1/2 0.5 1 1.

10 General Information
Close
Bolt / Socket Sizes
772 705 707 71
Size Bolt Socket Bolt Socket Bolt Socket Bolt Socket
Size Size Size Size Size Size Size Size
1 1⁄ 4" 3
⁄ 8" 11
⁄16" 3
⁄ 8" 11
⁄16"
1 1⁄ 2" 3
⁄ 8" 11
⁄16" 3
⁄ 8" 11
⁄16" 1
⁄ 2" 7
⁄ 8"
3 11 3 11 1 7 5
2" ⁄ 8" ⁄16" ⁄ 8" ⁄16" ⁄ 2" ⁄ 8" ⁄ 8" 11⁄16"
2 1⁄ 2" 3
⁄ 8" 11
⁄16" 3
⁄ 8" 11
⁄16" 1
⁄ 2" 7
⁄ 8" 5
⁄ 8" 11⁄16"
76.1mm M10 16mm M12 18mm M12 18mm
3 11 1 7 1 7 5
3" ⁄ 8" ⁄16" ⁄ 2" ⁄ 8" ⁄ 2" ⁄ 8" ⁄ 8" 11⁄16"
3 11 1 7 5 1 5
4" ⁄ 8" ⁄16" ⁄ 2" ⁄ 8" ⁄ 8" 1 ⁄16" ⁄ 8" 11⁄16"
5 1 5 1 3
5" ⁄ 8" 1 ⁄16" ⁄ 8" 1 ⁄16" ⁄ 4" 1 1⁄ 4" 3
⁄ 4" 1 1⁄ 4"
165.1mm M16 24mm M16 24mm M20 30mm
5
6" ⁄ 8" 11⁄16" 5
⁄ 8" 11⁄16" 3
⁄ 4" 1 1⁄ 4" 3
⁄ 4" 1 1⁄ 4"
3
8" ⁄ 4" 1 1⁄ 4" 3
⁄ 4" 1 1⁄ 4" 7
⁄ 8" 17⁄16" 3
⁄ 4" 1 1⁄ 4"
10" 1" 1 5⁄ 8" 1" 1 5⁄ 8" 1" 1 5⁄ 8" 7
⁄ 8" 17⁄16"
12" 1" 1 5⁄ 8" 1" 1 5⁄ 8" 1" 1 5⁄ 8" 7
⁄ 8" 17⁄16"

40-5 572 & 575 730


Size Bolt Socket Bolt Socket Bolt Socket
Size Size Size Size Size Size
1 1⁄ 4" 3
⁄ 8" 9
⁄16" 3
⁄ 8" 11
⁄16"
1 1⁄ 2" 3
⁄ 8" 9
⁄16" 3
⁄ 8" 11
⁄16"
3 9 3 11 3 11
2" ⁄ 8" ⁄16" ⁄ 8" ⁄16" ⁄ 8" ⁄16"
2 1⁄ 2" 3
⁄ 8" 9
⁄16" 3
⁄ 8" 11
⁄16" 3
⁄ 8" 11
⁄16"
3 11 1 7
3" ⁄ 8" ⁄16" ⁄ 2" ⁄ 8"
3 11 1 7
4" ⁄ 8" ⁄16" ⁄ 2" ⁄ 8"
5 1
5" ⁄ 8" 1 ⁄16"
1 7 5
6" ⁄ 2" ⁄ 8" ⁄ 8" 11⁄16"
5
8" ⁄ 8" 11⁄16" 3⁄4" 1 1⁄ 4"

716
Size Bolt Socket
Size Size
2" x 11⁄2" 3
⁄ 8" 11
⁄16"
21⁄2" x 2" 3
⁄ 8" 11
⁄16"
1 7
3" x 2" ⁄ 2" ⁄ 8"
3" x 21⁄2" 1
⁄ 2" 7
⁄ 8"
5 1
4" x 2" ⁄ 8" 1 ⁄16"
4" x 21⁄2" 5
⁄ 8" 11⁄16"
5
4" x 3" ⁄ 8" 11⁄16"
5" x 4" 3
⁄ 4" 1 1⁄ 4" Note: See Installation
3
6" x 4" ⁄ 4" 1 1⁄ 4" Instructions Section
3
6" x 5" ⁄ 4" 1 1⁄ 4" for bolt torques.
7
8" x 6" ⁄ 8" 17⁄16"

General Information 11
Close
System Design
Grooved Piping Products provide the versatility required in
piping systems through the use of rigid and flexible piping
products. Figure 572 and 575 Couplings incorporate rotation
resistant gripping teeth which provide the installer and
designer with increased benefits.

Rigid Joints

Rigid Couplings provide rigid gripping of the pipe. They are


designed to bring the pipe ends closely together and the
coupling clamps firmly onto the pipe OD and also into the
bottom of the grooves. Because Rigid Couplings clamp
around the entire pipe surface, they provide resistance to
flexural loads and therefore permit longer spacing to ASME/
ANSI B31.1 (Power Piping) and ASME/ANSI B39.1 (Building
Services) requirements as well as NFPA 13 (Sprinkler
Systems).

Flexible Joints

Flexible Couplings act as an "expansion joint", allowing linear


and angular movement of the pipe. They are designed with
the coupling keys engaging the pipe without gripping on the
bottom of the grooves, while still providing for a restrained
mechanical joint. This is particularly useful to allow for pipe
expansion or contraction and piping misalignment.

12 System Design
Close
Pipe Hanger Spacing
All piping systems require that the support system
accommodate the weight of the pipe, joint connections, fluid
and other system components.
In general, the requirements of NFPA 13 govern sprinkler
system design.

Nominal Suggested Max. Span Nominal Suggested Max. Span


Size Between Supports Size Between Supports
Inches Feet Inches Feet
mm Meters mm Meters
1 12 4 15
33.4 3.7 114.3 4.6
1
1 /4 12 5 15
42.2 3.7 141.3 4.6
11/2 15 15
165.1mm
48.3 4.6 4.6
2 15 6 15
60.3 4.6 168.3 4.6
1
2 /2 15 8 15
73.0 4.6 219.1 4.6
15 10 15
76.1mm
4.6 273.0 4.6
3 15 12 15
88.9 4.6 323.9 4.6
Spacing by NFPA 13 Sprinkler Systems
(Steel Pipe except Threaded Lightwall)

System Design 13
Close
Standard Specifications – Roll Groove

A T
B

OD C

1. The maximum allowable Pipe O.D.


tolerances for IPS pipe from Nom Inches
Pipe mm
square cut ends is 0.030" (0.76mm) Size Tolerance
for sizes 11⁄4" thru 3"; 0.045" O.D.
+ -
(1.14mm) for sizes 4" thru 6"; and 11/4"
1.660 0.016 0.016
0.060" (1.52mm) for sizes 8" and 42.2 0.41 0.41
1.900 0.019 0.019
above. 11/2"
48.3 0.48 0.48
2. Gasket Seating Surface "A" must 2"
2.375 0.024 0.024
be free from score marks, ridges, 60.3 0.61 0.61
2.875 0.029 0.029
indentations, projections, loose 21/2"
73.0 0.74 0.74
paint, scale, dirt chips, grease, 3.000 0.030 0.030
76.1mm
rust, etc. that would prevent a 76.1 0.76 0.76
positive seal. 3.500 0.035 0.031
3"
88.9 0.89 0.79
3. Groove diameter "C" must be of 4.500 0.045 0.031
4"
uniform depth around the 114.3 1.14 0.79
circumference of the pipe. 5.563 0.056 0.031
5"
141.3 1.42 0.79
4. Groove Depth "D" is a reference 165.1mm
6.500 0.063 0.031
dimension only. The Groove 165.1 1.60 0.79
6.625 0.063 0.031
Diameter "C" must be maintained. 6"
168.3 1.60 0.79
5. Minimum Wall Thickness "T" is the 8"
8.625 0.063 0.031
minimum wall thickness that 219.1 1.60 0.79
10.750 0.063 0.031
should be roll grooved. 10"
273.1 1.60 0.79
6. Maximum allowable pipe end flare 12"
12.750 0.063 0.031
diameter is measured at the pipe 323.9 1.60 0.79
end diameter.

14 Groove Specifications
Close
Standard Specifications – Roll Groove (cont.)

A T
B

OD C

A B C D T Maximum
Nom ± 0.030" ± 0.030" Groove Dia. Groove Minimum Allow. Flare
Pipe ± 0.76mm ± 0.76mm Inches Depth Wall Diameter
Size Inches Inches mm Inches Inches Inches
mm mm Actual Tol.+ 0 mm mm mm
0.625 0.281 1.535 -0.015 0.063 0.065 1.77
11/4"
15.88 7.14 38.99 -0.38 1.60 1.65 44.96
0.625 0.281 1.775 -0.015 0.063 0.065 2.01
11/2"
15.88 7.14 45.09 -0.38 1.60 1.65 51.05
0.625 0.344 2.250 -0.015 0.063 0.065 2.48
2"
15.88 8.74 57.15 -0.38 1.60 1.65 62.99
0.625 0.344 2.720 -0.018 0.078 0.083 2.98
21/2"
15.88 8.74 69.09 -0.46 1.98 2.11 75.69
0.625 0.344 2.845 -0.018 0.076 0.083 3.10
76.1mm
15.88 8.74 72.26 -0.46 1.93 2.11 78.74
0.625 0.344 3.344 -0.018 0.078 0.083 3.60
3"
15.88 8.74 84.94 -0.46 1.98 2.11 91.44
0.625 0.344 4.334 -0.020 0.083 0.083 4.60
4"
15.88 8.74 110.08 -0.51 2.11 2.11 116.84
0.625 0.344 5.395 -0.022 0.084 0.109 5.66
5"
15.88 8.74 137.03 -0.56 2.13 2.77 143.76
0.625 0.344 6.330 -0.022 0.085 0.109 6.60
165.1mm
15.88 8.74 160.78 -0.56 2.16 2.77 167.64
0.625 0.344 6.455 -0.022 0.085 0.109 6.73
6"
15.88 8.74 163.96 -0.56 2.16 2.77 170.94
0.750 0.469 8.441 -0.025 0.092 0.109 8.80
8"
19.05 11.91 214.40 -0.64 2.34 2.77 223.52
0.750 0.469 10.562 -0.027 0.094 0.134 10.92
10"
19.05 11.91 268.27 -0.69 2.39 3.40 277.37
0.750 0.469 12.531 -0.030 0.109 0.156 12.92
12"
19.05 11.91 318.29 -0.76 2.77 3.96 328.17

Groove Specifications 15
Close
Standard Specifications – Cut Groove

A T
B

OD C

1. The maximum allowable Pipe O.D.


tolerances for IPS pipe from Nom Inches
square cut ends is 0.030" (0.76mm) Pipe mm
Size Tolerance
for sizes 11⁄4" thru 3"; 0.045" O.D.
+ -
(1.14mm) for sizes 4" through 6"; 1.660 0.016 0.016
11/4"
and 0.060 in. (1.52mm) for sizes 8" 42.2 0.41 0.41
and above. 1.900 0.019 0.019
11/2"
48.3 0.48 0.48
2. Gasket Seating Surface "A" must 2"
2.375 0.024 0.024
be free from score marks, ridges, 60.3 0.61 0.61
indentations, projections, loose 2.875 0.029 0.029
21/2"
73.0 0.74 0.74
paint, scale, dirt chips, grease, 3.000 0.030 0.030
76.1mm
rust, etc. that would prevent a 76.1 0.76 0.76
positive seal. 3"
3.500 0.035 0.031
88.9 0.89 0.79
3. Groove diameter "C" must be of 4.500 0.045 0.031
4"
uniform depth around the 114.3 1.14 0.79
circumference of the pipe. 5"
5.563 0.056 0.031
141.3 1.42 0.79
4. Groove Depth "D" is a reference 6.500 0.063 0.031
165.1mm
dimension only. The Groove 165.1 1.60 0.79
Diameter "C" must be maintained. 6.625 0.063 0.031
6"
168.3 1.60 0.79
5. Minimum Wall Thickness "T" is the 8.625 0.063 0.031
8"
minimum wall thickness that 219.1 1.60 0.79
should be cut grooved. 10.750 0.063 0.031
10"
273.1 1.60 0.79
12.750 0.063 0.031
12"
323.9 1.60 0.79

16 Groove Specifications
Close
Standard Specifications – Cut Groove (cont.)

A T
B

OD C

A B C D T
Nom ± 0.030" ± 0.030" Groove Dia. Groove Minimum
Pipe ± 0.76mm ± 0.76mm Inches Depth Wall
Size Inches Inches mm Inches Inches
mm mm Actual Tol.+ 0 mm mm
11/4" 0.625 0.313 1.535 -0.015 0.062 0.140
15.88 7.95 38.99 -0.38 1.57 3.56
11/2" 0.625 0.313 1.775 -0.015 0.062 0.145
15.88 7.95 45.09 -0.38 1.57 3.68
2" 0.625 0.313 2.250 -0.015 0.062 0.154
15.88 7.95 57.15 -0.38 1.57 3.91
21/2" 0.625 0.313 2.720 -0.018 0.078 0.188
15.88 7.95 69.09 -0.46 1.98 4.78
76.1mm 0.625 0.313 2.845 -0.018 0.076 0.188
15.88 7.95 72.26 -0.46 1.93 4.78
3" 0.625 0.313 3.344 -0.018 0.078 0.188
15.88 7.95 84.94 -0.46 1.98 4.78
4" 0.625 0.375 4.334 -0.020 0.083 0.203
15.88 9.53 110.08 -0.51 2.11 5.16
5" 0.625 0.375 5.395 -0.022 0.084 0.203
15.88 9.53 137.03 -0.56 2.13 5.16
165.1mm 0.625 0.375 6.330 -0.022 0.085 0.219
15.88 9.53 160.78 -0.56 2.16 5.56
6" 0.625 0.375 6.455 -0.022 0.085 0.219
15.88 9.53 163.96 -0.56 2.16 5.56
8" 0.750 0.438 8.441 -0.025 0.092 0.238
19.05 11.13 214.40 -0.64 2.34 6.05
10" 0.750 0.500 10.562 -0.027 0.094 0.250
19.05 12.70 268.27 -0.69 2.39 6.35
12" 0.750 0.500 12.531 -0.030 0.109 0.279
19.05 12.70 318.29 -0.76 2.77 7.09

Groove Specifications 17
Close
Gaskets
(Refer to Gasket Recommendations No. 18-9.0 and 18-9.2
for specific application recommendations)

Temp. Color
Grade Compound General Service Application
Range Code
Ambient Fire Protection Systems. Not
to Recommended for Hot Water Systems
A EPDMA Violet
+150°F For dry pipe or freezer systems,
(+66°C) use Tri-Seal Grade E Gasket.
-30°F Hot Water, dilute acids, alkalies, and
(-34°C) many chemical services not involving
E to EPDM Green petroleum products. Excellent
+230°F oxidation resistance. NOT FOR USE
(+110°C) WITH HYDROCARBONS.
-20°F Petroleum products, vegetable oils,
(-29°C) and air with oils. Not recommended
T to Nitrile Orange for Hot Water Systems. Not
+180°F recommended for Hot Dry Air over
(+82°C) +140°F (+60°C)

Note: Dry pipe and freezer systems are unique


applications which benefit from proper pipe
preparation and the use of rigid couplings, such as
our Figures 572 and 772 couplings and our Tri-Seal
gaskets. Reducing couplings are not recommended
for these applications. Standard lube is not
recommended for this application as it freezes and
can cause leakage.
Proper pipe end preparation and grooving is
mandatory to prevent leakage (See specifications for
cut and roll grooving). The gasket seat surface must
be free from score marks, ridges, indentations,
projections, loose paint, flaking galvanizing, scale,
dirt chips, grease, rust, etc. that would prevent a
positive seal.
The best choice for a trouble free system is to use
our rigid couplings with our Tri-Seal gaskets and a
petroleum free silicone base lubricant. Pre-
lubricated gaskets do not require the use of silicone
lubricant.

18 Gaskets
Close
Tri-Seal Freezer Gasket

The Tri-Seal Grade E freezer gasket is used primarily for dry


pipe fire protection systems, vacuum service, and freezer
applications. The Tri-Seal freezer gasket differs from standard
gaskets by closing off the gap or gasket cavity. This is
accomplished by positioning the center “rib” of the gasket over
the gap between the pipes. The Tri-Seal freezer gasket has
two tapered sealing edges in addition to the center rib for
additional strength and sealing.
The Tri-Seal freezer gasket is available in sizes 11/4" to 12"
and is designed for use with Figure 575, 572, 705, 707 and
772 Couplings. A petroleum-free silicone based lubricant is
recommended for dry pipe systems. For low temperature
services or dry systems in cold storage or freezer applications,
use Tri-Seal freezer gaskets. For vacuum services greater
than 10" Hg, Tri-Seal gaskets should be used.
Note: Rigid couplings are preferred for vacuum, dry pipe and
freezer applications.

Pre-Lubricated Gasket
Pre-lubricated gaskets are provided with a propritary coating
which eliminates the need for the installer to apply a lubricant
during the assembly process. They are available in both the
Grade A EPDM or Tri-Seal Grade E EPDM styles.

TM

Lube

Gaskets 19
Close
Installation Instructions

General Notes: It is the Designer’s responsibility to


select products suitable for the intended service and
to ensure that pressure ratings and performance
data is not exceeded. Always read and understand
the installation instructions. Never remove any
piping component nor correct or modify any piping
deficiencies without first depressurizing and
draining the system. Material and gasket selection
should be verified to be compatible for the specific
application.

Care and Maintenance


The owner is responsible for the inspection, testing,
and maintenance of their fire protection system and
devices in accordance with the applicable standards
of the National Fire Protection Association (e.g.,
NFPA 25), in addition to the standards of any
authority having jurisdiction. The installing
contractor or product manufacturer should be
contacted relative to any questions. Any impairment
must be immediately corrected.
It is recommended that automatic sprinkler systems
be inspected, tested, and maintained by a qualified
Inspection Service.

20 Installation Instructions
Close
Figure 572 - Patented

B C

Pipe Max. * Max.† Max.†


O.D. End Gap Pressure End Load
Size Inches Inches psi Lbs.
mm mm kPa N FM
1.660 0.06 300 649
11⁄4" See Fire Protection Submittal Sheet
42.2 1.5 2,068 2,887
for pressure rating and Listing and
1.900 0.06 300 850
11⁄2" Approval information.
48.3 1.5 2,068 3,781
2.375 0.06 300 1,328
2"
60.3 1.5 2,068 5,907 * Maximum available gap
2.875 0.06 300 1,947 between pipe ends. Minimum
21⁄2" gap = 0
73.0 1.5 2,068 8,660
† Maximum pressure and end
3.500 0.06 300 2,885
3" load are based on standard
88.9 1.5 2,068 12,832 weight steel pipe. Pressure
4.500 0.19 300 4,769 ratings and end loads may
4"
114.3 4.8 2,068 21,213 differ on other pipe materials
6.625 0.19 300 10,336 and/or wall thickness. Contact
6" Tyco Fire Protection for details.
168.3 4.8 2,068 45,975 See Fire Protection Submittal
8.625 0.19 300 17,519 Sheet for Listing and Approval
8"
219.1 4.8 2,068 77,925 pressure ratings.

Dimensions Bolt Net


Pipe A B C Bolt Torque Wt.
Size Inches Inches Inches Size Lbs.-Ft. Lbs.
mm mm mm Dia. x Lg. Nm Kg.
2.56 4.09 1.69 30 0.9
11⁄4" 3
⁄8" x 21⁄4"
65.0 103.9 42.9 41 0.4
2.81 4.38 1.69 30 1.0
11⁄2" 3
⁄8" x 21⁄4"
71.4 111.3 42.9 41 0.5
3.31 4.82 1.69 30 1.2
2" 3
⁄8" x 21⁄4"
84.1 122.4 42.9 41 0.5
3.81 5.38 1.69 30 1.3
21⁄2" 3
⁄8" x 21⁄4"
96.8 136.7 42.9 41 0.6
4.50 6.06 1.69 30 1.7
3" 3
⁄8" x 21⁄4"
114.3 153.9 42.9 41 0.8
5.69 7.38 1.81 30 2.7
4" 3
⁄8" x 21⁄4"
144.5 187.5 46.0 41 1.2
7.94 9.88 1.88 50 5.3
6" 1
⁄2" x 3"
201.7 251.0 47.8 68 2.4
10.13 12.69 2.25 50 7.2
8" 1
⁄2" x 3"
257.3 322.3 57.2 68 3.3

Installation Instructions – Figure 572 and 772 Couplings 21


Close
Figure 772 patented

B C

Pipe Max. * Max.† Max.†


O.D. End Gap Pressure End Load
Size Inches Inches psi Lbs.
mm mm kPa N
1.660 0.06 300 649
11⁄4"
42.2 1.5 2,068 2,887
1.900 0.08 500 1,417
11⁄2"
48.3 2.0 3,447 6,303
2.375 0.13 500 2,214
2"
60.3 3.3 3,447 9,848
2.875 0.13 500 3,244
21⁄2"
73.0 3.3 3,447 14,430
3.000 0.13 300 2,120
76.1mm
76.1 3.3 2,068 9,430
3.500 0.13 500 4,808
3"
88.9 3.3 3,447 21,387
4.500 0.19 500 7,948
4"
114.3 4.8 3,447 35,353
5.563 0.19 300 7,288
5"
141.3 4.8 2,068 32,417
6.500 0.19 300 9,950
165.1mm
165.1 4.8 2,068 44,258
6.625 0.19 400 13,782
6"
168.3 4.8 2,758 61,302
8.625 0.19 450 26,278
8"
219.1 4.8 3,103 116,885
10.750 0.13 250 22,679
10"
273.1 3.3 1,724 100,876
12.750 0.13 250 31,903
12"
323.4 3.3 1,724 141,905
* Maximum available gap between pipe ends.
Minimum gap = 0
† Maximum pressure and end load are based on
standard weight steel pipe. Pressure ratings and end
loads may differ on other pipe materials and/or wall
thickness. Contact Tyco Fire Protection for details.
See Fire Protection Submittal Sheet for Listing and
Approval pressure ratings.

22 Installation Instructions – Figure 572 and 772 Couplings


Close
Figure 772 (Continued) patented

FM

See Fire Protection Submittal Sheet


for pressure rating and Listing and
Approval information.

Dimensions Bolt Net


Bolt
Pipe A B C Torque Wt.
Size**
Size Inches Inches Inches Lbs.-Ft. Lbs.
Dia. x Lg.
mm mm mm Nm Kg.
2.75 4.38 1.81 30 1.0
11⁄4" 3
⁄8" x 21⁄4"
69.9 111.3 46.0 41 0.5
3.00 4.62 1.81 30 1.0
11⁄2" 3
⁄8" x 21⁄4"
6.2 117.3 46.0 41 0.5
3.41 5.12 1.88 30 1.5
2" 3
⁄8" x 21⁄4"
6.6 130.0 47.8 41 0.7
3.91 5.63 1.88 30 2.5
21⁄2" 3
⁄8" x 21⁄4"
99.3 143.0 47.8 41 1.1
4.19 5.72 2.00 30 2.6
76.1mm M10 x 57
106.4 145.3 50.8 41 1.2
4.63 6.25 1.88 30 2.6
3" 3
⁄8" x 21⁄4"
117.6 158.8 47.8 41 1.2
5.81 7.50 1.97 30 3.5
4" 3
⁄8" x 21⁄4"
147.6 190.5 50.0 41 1.6
7.09 9.72 2.06 90 7.5
5" 5
⁄8" x 31⁄4"
180.1 246.9 52.3 122 3.4
8.09 10.53 2.13 90 7.6
165.1mm M16 x 83
205.5 267.5 54.1 122 3.4
8.09 10.53 2.13 90 7.6
6" 5
⁄8" x 31⁄4"
205.5 267.5 54.1 122 3.4
10.56 13.56 2.62 150 18.0
8" 3
⁄4" x 43⁄4"
268.2 344.4 66.5 203 8.2
12.84 16.41 2.62 200 24.6
10" 1" x 61⁄2"
326.1 416.8 66.5 271 11.2
15.41 18.84 2.62 200 42.0
12" 1" x 61⁄2"
391.4 478.5 66.5 271 19.1

** - Metric bolt size used on 76.1mm and 165.1mm couplings.

Installation Instructions – Figure 572 and 772 Couplings 23


Close
Figure 572 and 772 Rigid Coupling patented
Always read and understand the instructions. Never remove any
piping component without verifying that the system is depressurized
and drained.
Rigid Couplings with Tri-Seal gaskets are preferred for dry pipe
and freezer applications.
Installation / Assembly Instructions
The following instructions apply to Figure 572 and 772 Rigid
Couplings. The installation is based on pipe grooved in accordance
with Standard Cut Groove or Roll Groove Specifications.
Step 1. Inspect exterior groove and ends of the
pipe to verify all loose debris, dirt, chips, paint
and any other foreign material such as grease
are removed. Pipe ends sealing surfaces must
be free from projections, indentations, or other
markings.
Step 2. Verify that the coupling and gasket grade
are correct for the application intended. Plese
refer to “Gasket Grades and Gasket
Recommendations” Literature for additional
information.
The edges and outer surfaces of the gasket
should be covered with a fine layer of petroleum-
free silicone lubricant or equivalent. Petroleum lubricant should not
be used on Grade “E” “EPDM” or Grade A “EPDMA” gaskets to
prevent deterioration of the gasket material. Tri-seal gaskets are
recommended for freezer applications.
Note: Silicone lubricant must be used in Dry Pipe and Freezer
Applications. (Pre-lubricated gaskets do not require silicone libricant.)
Step 3. Install the gasket by placing the gasket over
the pipe, which is to be fastened by the rigid
coupling and ensure that the gasket lip does not
extend beyond the end of the pipe.

Step 4. Bring both pipe ends together, ensure proper


alignment and slide the gasket into position,
properly centering it between the grooved
portions of each pipe.
Note: the gasket should not protrude into the grooves on either pipe
segments or extend between the pipe ends.

24 Installation Instructions – Figure 572 and 772 Couplings


Close
Figure 572 and 772 Rigid Coupling (Cont.) patented

Step 5. With one nut and bolt removed, “swing


around” as shown. Verify that the housings are
over the gasket and that the housing keys are
fully engaged into the grooves.

Note: Sizes 11⁄4" - 12" Figure 772 and


Figure 572 utilize a tongue and recess
arrangement, which must be mated
properly for the coupling to function
according to design.
These pictures show the patented “Universal
Tongue and Recess” arrangement. These
coupling housings have identical tongue/
recess pairs at each end, which allow an
engagement fit no matter which end of the
housing is brought together.

Step 6. Insert the other bolt into the coupling and


rotate the nuts until finger tight. Verify that the
bolt heads are fully recessed in the housing.

Step 7. Alternate between bolts when tightening


nuts until properly torqued as shown in the
table. Note: uneven tightening can cause the
gasket to pinch or bind.

Note that on the 11⁄4" - 8" Figure 572 and 11⁄4" -


12" 772 couplings there is an intended gap of up
to 1/16 of an inch at each pad to allow for
positive rigid gripping onto the pipe.

Installation Instructions – Figure 572 and 772 Couplings 25


Close
Figure 575 - Patent Pending
B C

FM
A
See Fire Protection Submittal Sheet
for pressure rating and Listing and
Approval information.

Pipe Max. * Max.† Max.† Deflection


O.D. End Gap Pressure End Load
Size Inches Inches psi Lbs. °Per Inches/Foot
mm mm kPa N Coupling mm/m
1.660 0.09 3.00 649 3° - 13' 0.67
11⁄4"
42.2 2.3 2,068 2,887 55.8
1.900 0.09 3.00 850 2° - 48' 0.59
11⁄2"
48.3 2.3 2,068 3,781 49.2
2.375 0.09 3.00 1,328 2° - 15' 0.47
2"
60.3 2.3 2,068 5,907 39.2
2.875 0.09 3.00 1,947 1° - 51' 0.39
21⁄2"
73.0 2.3 2,068 8,660 32.5
3.500 0.09 3.00 2,885 1° - 31' 0.32
3"
88.9 2.3 2,068 12,832 26.7
4.500 0.19 3.00 4,769 2° - 24' 0.50
4"
114.3 4.8 2,068 21,213 41.7
6.625 0.19 3.00 10,336 1° - 38' 0.34
6"
168.3 4.8 2,068 45,975 28.3
8.625 0.19 3.00 17,519 1° - 16' 0.26
8"
219.1 4.8 2,068 77,925 21.7
* Maximum available gap between pipe ends. Minimum gap = 0
† Maximum pressure and end load are based on standard weight steel pipe. Pressure
ratings and end loads may differ on other pipe materials and/or wall thickness. Contact
Tyco Fire Protection for details.

Dimensions Bolt Net


Pipe A B C Bolt Torque Wt.
Size Inches Inches Inches Size Lbs.-Ft. Lbs.
mm mm mm Dia. x Lg. Nm Kg.
11⁄4" 2.50 4.09 1.69 3 30 0.9
⁄8" x 21⁄4"
63.5 103.9 42.9 41 0.4
2.75 4.34 1.69 30 1.0
11⁄2" 3
⁄8" x 21⁄4"
69.9 110.2 42.9 41 0.5
3.25 4.82 1.69 30 1.2
2" 3
⁄8" x 21⁄4"
82.6 122.4 42.9 41 0.5
3.75 5.38 1.72 30 1.3
21⁄2" 3
⁄8" x 21⁄4"
95.3 136.7 43.7 41 0.6
3" 4.38 6.06 1.75 3 30 1.7
⁄8" x 21⁄4"
111.3 153.9 44.5 41 0.8
5.63 7.38 1.81 30 2.7
4" 3
⁄8" x 21⁄4"
143.0 187.5 46.0 41 1.2
7.88 9.88 1.88 50 5.3
6" 1
⁄2" x 3"
200.0 251.0 47.8 68 2.4
10.06 12.68 2.25 50 7.2
8" 1
⁄2" x 3"
255.5 322.1 57.2 68 3.3

26 Installation Instructions – Figure 575, 705 and 707 Couplings


Close
Figure 705

B C

Pipe Max. * Max.† Max.† Deflection


O.D. End Gap Pressure End Load Inches/
Size Inches Inches psi Lbs. °Per Foot
mm mm kPa N Coupling mm/m
1.660 0.13 300 649 0.90
11⁄4" 4° - 19'
42.2 3.3 2,068 2,887 75.0
1.900 0.13 300 850 0.79
11⁄2" 3° - 46'
48.3 3.3 2,068 3,781 65.8
2.375 0.13 300 1,328 0.63
2" 3° - 1'
60.3 3.3 2,068 5,907 52.5
2.875 0.13 300 1,947 0.52
21⁄2" 2° - 29'
73.0 3.3 2,068 8,660 43.3
3.000 0.13 300 2,120 0.50
76.1mm 2° - 23'
76.1 3.3 2,068 9,430 41.7
3.500 0.13 300 2,885 0.43
3" 2° - 3'
88.9 3.3 2,068 12,832 35.8
4.500 0.25 300 4,769 0.67
4" 3° - 11'
114.3 6.4 2,068 21,213 55.8
5.563 0.25 300 7,288 0.54
5" 2° - 35'
141.3 6.4 2,068 32,417 45.0
6.500 0.25 300 9,950 0.46
165.1mm 2° - 12'
165.1 6.4 2,068 44,258 38.3
6.625 0.25 300 10,336 0.45
6" 2° - 10'
168.3 6.4 2,068 45,975 37.5
8.625 0.25 300 17,519 0.35
8" 1° - 40'
219.1 6.4 2,068 77,925 29.2
10.750 0.25 250 22,679 0.28
10" 1° - 20'
273.1 6.4 1,724 100,876 23.3
12.750 0.25 250 31,903 0.23
12" 1° - 7'
323.9 6.4 1,724 141,905 19.2
* Maximum available gap between pipe ends. Minimum gap = 0
† Maximum pressure and end load are based on standard weight steel pipe.
Pressure ratings and end loads may differ on other pipe materials and/or wall
thickness. Contact Tyco Fire Protection for details. See Fire Protection Submittal
Sheet for Listing and Approval pressure ratings.

Installation Instructions – Figure 575, 705 and 707 Couplings 27


Close
Figure 705 (cont.)

FM

See Fire Protection Submittal Sheet


for pressure rating and Listing and
Approval information.

Dimensions Bolt Net


Bolt
Pipe A B C Torque Wt.
Size**
Size Inches Inches Inches Lbs.-Ft. Lbs.
Dia. x Lg.
mm mm mm Nm Kg.
2.53 4.19 1.81 3 30 1.5
11⁄4" ⁄8" x 21⁄4"
64.3 106.4 46.0 41 0.7
2.75 4.43 1.81 3 30 1.6
11⁄2" ⁄8" x 21⁄4"
69.9 112.5 46.0 41 0.7
3.25 4.84 1.88 3 30 1.7
2" ⁄8" x 21⁄4"
82.6 122.9 47.8 41 0.8
3.69 5.50 1.88 3 30 2.0
21⁄2" ⁄8" x 21⁄4"
93.7 139.7 47.8 41 0.9
3.97 5.75 1.88 50 3.1
76.1mm M10 x 57
100.8 146.1 47.8 68 1.4
4.38 6.50 1.88 1 50 3.0
3" ⁄2" x 3"
111.3 165.1 47.8 68 1.4
5.68 7.75 2.06 1 50 4.0
4" ⁄2" x 3"
144.3 196.9 52.3 68 1.8
6.88 9.72 2.06 5 90 7.0
5" ⁄8" x 31⁄4"
174.8 246.9 52.3 122 3.2
7.75 10.68 2.06 90 7.1
165.1mm M16 x 83
196.9 271.3 52.3 122 3.2
7.91 10.68 2.06 5 90 7.1
6" ⁄8" x 31⁄4"
200.9 271.3 52.3 122 3.2
10.19 13.56 2.47 3 150 14.5
8" ⁄4" x 43⁄4"
258.8 344.4 62.7 203 6.6
12.69 16.38 2.63 200 28.0
10" 1" x 61⁄2"
322.3 416.1 66.8 271 12.7
14.91 18.84 2.63 200 36.5
12" 1" x 61⁄2"
378.7 478.5 66.8 271 16.6
** Metric Bolts used for 76.1mm and 165.1mm couplings.

28 Installation Instructions – Figure 575, 705 and 707 Couplings


Close
Figure 707

B C

Pipe Max. * Max.† Max.† Deflection


O.D. End Gap Pressure End Load
Size Inches Inches psi Lbs. °Per Inches/Foot
mm mm kPa N Coupling mm/m
1.900 0.13 500 1,418 0.79
11⁄2" 3° - 46'
48.3 3.3 3,447 6,308 65.8
2.375 0.13 500 2,215 0.63
2" 3° - 1'
60.3 3.3 3,447 9,853 52.5
2.875 0.13 500 3,246 0.52
21⁄2" 2° - 29'
73.0 3.3 3,447 14,439 43.3
3.000 0.13 300 2,121 0.50
76.1mm 2° - 23'
76.2 3.3 2,068 9,435 41.7
3.500 0.13 500 4,811 0.43
3" 2° - 3'
88.9 3.3 3,447 21,400 35.8
4.500 0.25 500 7,952 0.67
4" 3° - 11'
114.3 6.4 3,447 35,372 55.8
5.563 0.25 500 12,153 0.54
5" 2° - 35'
141.3 6.4 3,447 54,059 45.0
6.500 0.25 300 9,955 0.46
165.1mm 2° - 12'
165.1 6.4 2,068 44,282 38.3
6.625 0.25 500 17,236 0.45
6" 2° - 10'
168.3 6.4 3,447 76,670 37.5
8.625 0.25 500 29,213 0.35
8" 1° - 40'
219.1 6.4 3,447 129,946 29.2
10.750 0.25 500 45,381 0.28
10" 1° - 20'
273.1 6.4 3,447 201,864 23.3
12.750 0.25 500 63,838 0.23
12" 1° - 7'
323.9 6.4 3,447 283,966 19.2
* Maximum available gap between pipe ends. Minimum gap = 0
† Maximum pressure and end load are based on standard weight steel pipe.
Pressure ratings and end loads may differ on other pipe materials and/or wall
thickness. Contact Tyco Fire Protection for details. See Fire Protection Submittal
Sheet for Listing and Approval pressure ratings.

Installation Instructions – Figure 575, 705 and 707 Couplings 29


Close
Figure 707 (cont.)

FM

See Fire Protection Submittal Sheet


for pressure rating and Listing and
Approval information.

Dimensions Bolt Bolt Net


Pipe A B C Size** Torque Wt.
Size Inches Inches Inches Dia x Lg. Lbs.-Ft. Lbs.
mm mm mm Nm Kg.
2.97 4.63 1.81 1
50 2.5
11⁄2" /2" x 3"
75.4 117.6 46.0 68 1.1
3.54 5.25 1.88 1 50 3.0
2" /2" x 3"
89.9 133.4 47.8 68 1.4
4.06 5.75 1.88 1 50 3.5
21⁄2" /2" x 3"
103.1 146.1 47.8 68 1.6
4.19 5.75 1.88 50 3.7
76.1mm M12 x 76
106.4 146.1 47.8 68 1.7
4.69 6.38 1.88 1
50 4.0
3" /2" x 3"
119.1 162.1 47.8 68 1.8
5.95 8.25 2.06 5 90 7.0
4" /8" x 31/4"
151.1 209.6 52.3 122 3.2
7.08 10.00 2.06 3 150 10.5
5" /4" x 43/4"
179.8 254.0 52.3 203 4.8
8.19 11.25 2.06 150 12.5
165.1mm M20 x 121
208.0 285.8 52.3 203 5.7
8.30 11.25 2.06 3
150 12.5
6" /4" x 43/4"
210.8 285.8 52.3 203 5.7
10.68 14.00 2.47 7 200 23.5
8" /8" x 61/2"
271.3 355.6 62.7 271 10.7
13.06 16.44 2.63 200 33.0
10" 1" x 61/2"
331.7 417.6 66.8 271 15.0
15.39 18.84 2.63 200 37.0
12" 1" x 61/2"
390.9 478.5 66.8 271 16.8

** Metric Bolts used for 76.1mm and 165.1mm couplings.

30 Installation Instructions – Figure 575, 705 and 707 Couplings


Close
Figure 575, 705 & 707 Flexible Couplings
Always read and understand the instructions. Never
remove any piping component without verifying that
the system is depressurized and drained.

Rigid Couplings with Tri-Seal gaskets are preferred for dry pipe
and freezer applications.
Installation / Assembly Instructions
The following instructions apply to Figures 575, 705 and 707
Flexible Couplings. The installation is based on pipe grooved
in accordance with Standard Cut Groove or Roll Groove
Specifications.
Step 1. Inspect exterior groove and ends of the
pipe to verify all loose debris, dirt, chips, paint
and any other foreign material such as grease
are removed. Pipe ends sealing surfaces must
be free from projections, indentations, and/or
other markings.

Step 2. Verify that the coupling and gasket grade


are correct for the application intended. Please
refer to “ Gasket Grades and Gasket
Recommendations” literature for additional
information.

The edges and outer surfaces of the gasket


should be covered with a fine layer of
petroleum-free silicone lubricant or equivalent. Petroleum lubricant
should not be used on Grade “E” “EPDM” or Grade A “EPDMA”
gaskets to prevent deterioration of the gasket material. Rigid
Couplings and Tri-seal gaskets are recommended for freezer
applications. Prelubricated gaskets do not require added lubrication.

Step 3. Install the gasket by placing the gasket


over the pipe, which is to be fastened by the
flexible coupling and ensure that the gasket
lip does not extend beyond the end of the
pipe.

Installation Instructions – Figure 575, 705 and 707 Couplings 31


Close
Figure 575, 705 & 707 Flexible Couplings (cont.)

Step 4. Bring both pipe ends together, ensure


proper alignment and slide the gasket into
position, properly centering it between the
grooved portions of each pipe. Note: the gasket
should not protrude into the grooves on either
pipe segments or extend between the pipe
ends.

Step 5. With one nut and bolt removed, “swing


around” as shown. Verify that the housings are
over the gasket and that the housing keys are
fully engaged into the grooves.

Step 6. Insert the other bolt into the coupling and


rotate the nuts until finger tight. Verify that the
bolt heads are fully recessed in the housing.

Step 7. Alternate between bolts when tightening


nuts until properly torqued to bring housing in
contact with the bolt pads. Note: uneven
tightening can cause the gasket to pinch or
bind. For proper bolt torques please refer to
the table listed on the previous pages.

Note: Figures 575, 705 and 707 Coupling Housing


bolt pads must be in contact metal to metal.

32 Installation Instructions – Figure 575, 705 and 707 Couplings


Close
Figure 716

C
B

Pipe Max. * Max.† Max.† Deflection


O.D. End Gap Pressure End Load Inches
°Per
Size Inches Inches psi Lbs. /Foot
Coupling
mm mm kPa N mm/m
2.375 x 1.900 0.13 350 992 0.39
2" x 11⁄2" 1° - 53'
60.3 x 48.8 3.3 2,413 4,412 32.9
2.875 x 2.375 0.13 350 1,550 0.32
21⁄2" x 2" 1° - 33'
73.0 x 60.3 3.3 2,413 6,894 27.0
3.500 x 2.375 0.13 350 1,550 0.27
3" x 2" 1° - 17'
88.9 x 60.3 3.3 2,413 6,894 22.4
3.500 x 2.875 0.13 350 2,271 0.27
3" x 21⁄2" 1° - 17'
88.9 x 73.0 3.3 2,413 10,101 22.4
4.500 x 2.375 0.19 350 1,550 0.55
4" x 2" 2° - 38'
114.3 x 60.3 4.8 2,413 6,894 45.9
4.500 x 2.875 0.19 350 2,271 0.55
4" x 21⁄2" 2° - 38'
114.3 x 73.0 4.8 2,413 10,101 45.9
4.500 x 3.500 0.19 350 3,366 0.55
4" x 3" 2° - 38'
114.3 x 88.9 4.8 2,413 14,972 45.9
5.563 x 4.500 0.25 350 5,564 0.44
5" x 4" 2° - 5'
141.3 x 114.3 6.4 2,413 24,749 36.4
6.625 x 4.500 0.25 300 4,769 0.36
6" x 4" 1° - 44'
168.3 x 114.3 6.4 2,068 21,213 30.2
6.625 x 5.563 0.25 300 7,288 0.36
6" x 5" 1° - 44'
168.3 x 141.3 6.4 2,068 32,417 30.2
8.625 x 6.625 0.25 300 10,336 0.26
8" x 6" 1° - 15'
219.1 x 168.3 6.4 2,068 45,975 21.8

* Maximum available gap between pipe ends. Minimum gap = .06" with metal insert.
† Maximum pressure and end load are based on standard weight steel pipe. Pressure
ratings and end loads may differ on other pipe materials and/or wall thickness.
Contact Tyco Fire Protection for details. See Fire Protection Submittal Sheet for
Listing and Approval pressure ratings.

Installation Instructions – Figure 716 Flexible Reducing Couplings 33


Close
Figure 716 (cont.)

FM

See Fire Protection Submittal Sheet


for pressure rating and Listing and
Approval information.

Dimensions Bolt Net


Bolt
Pipe A B C Torque Wt.
Size
Size Inches Inches Inches Lbs.-Ft. Lbs.
Dia. x Lg.
mm mm mm Nm Kg.
3.50 5.06 1.88 3 30 2.0
2" x 11⁄2" ⁄8" x 21⁄4"
88.9 128.5 47.8 41 0.9
4.00 5.50 1.88 3 30 2.5
21⁄2" x 2" ⁄8" x 21⁄4"
101.6 139.7 47.8 41 1.1
4.69 6.50 1.88 1 50 4.5
3" x 2" ⁄2" x 3"
119.1 165.1 47.8 68 2.0
4.69 6.50 1.88 1 50 4.6
3" x 21⁄2" ⁄2" x 3"
119.1 165.1 47.8 68 2.1
6.00 8.13 2.00 5 90 6.0
4" x 2" ⁄8" x 31⁄4"
152.4 206.5 50.8 122 2.6
6.00 8.13 2.00 5 90 6.1
4" x 21⁄2" ⁄8" x 31⁄4"
152.4 206.5 50.8 122 2.8
6.00 8.13 2.00 5 90 6.2
4" x 3" ⁄8" x 31⁄4"
152.4 206.5 50.8 122 2.8
7.13 9.56 2.06 3 150 10.1
5" x 4" ⁄4" x 43⁄4"
181.1 242.8 52.3 203 4.6
8.38 10.88 2.06 3 150 11.6
6" x 4" ⁄4" x 43⁄4"
212.9 276.4 52.3 203 5.3
8.38 10.88 2.06 3 150 11.7
6" x 5" ⁄4" x 43⁄4"
212.9 276.4 52.3 203 5.3
10.69 13.75 2.25 7 200 21.6
8" x 6" ⁄8" x 61⁄2"
271.5 349.3 57.2 271 9.8

34 Installation Instructions – Figure 716 Flexible Reducing Couplings


Close
Figure 716 Flexible Reducing Couplings
Always read and understand the instructions.
Never remove any piping component without
verifying that the system is depressurized and
drained.
Note: Reducing Couplings are not recommended
for freezer applications.
Installation / Assembly Instructions
The following instructions apply to Figure 716 Flexible
Reducing Couplings. The installation is based on pipe
grooved in accordance with Standard Cut Groove or Roll
Groove Specifications.

Step 1. Inspect exterior groove and ends of the


pipe to verify all loose debris, dirt, chips, paint
and any other foreign material such as grease
are removed. Pipe ends sealing surfaces must
be free from projections, indentations, and/or
other markings.

Step 2. Verify that the coupling and gasket grade


are correct for the application intended. Please
refer to “ Gasket Grades and Gasket
Recommendations” literature for additional
information.
The edges and outer surfaces of the gasket
should be covered with a fine layer of petroleum-
free silicone lubricant or equivalent. Petroleum lubricant should not
be used on Grade “E” “EPDM” or Grade A “EPDMA” gaskets to
prevent deterioration of the gasket material. Prelubricated gaskets
do not require added lubrication.

Step 3. Install the gasket by placing the gasket


over the pipe which has the larger diameter.
Bring the smaller pipe end into alignment and
slide the pipe into position, properly centering
it between the grooved portions of each pipe.
Note: the gasket should not protrude into the grooves on either pipe
segment.

Installation Instructions – Figure 716 Flexible Reducing Couplings 35


Close
Figure 716 Flexible Reducing Couplings (cont.)

Step 4. With both bolts removed place the


coupling housings over the gasket. Verify that
the housings are over the gasket and that the
housing keys are fully engaged into the
grooves.

Step 5. Insert the bolts into the coupling and


rotate the nuts until finger tight. Verify that the
bolt heads are fully recessed in the housing.

Step 6. Alternate between bolts when tightening


nuts until properly torqued to bring housing in
contact with the bolt pads. Note: uneven
tightening can cause the gasket to pinch or
bind. For proper bolt torques please refer to
the table listed on the previous pages.

Note: Figure 716 Coupling Housings bolt pads must


be in contact metal to metal.

An optional Type 304 stainless steel metal insert is available.


Pipe telescoping can be a concern when installed in the
vertical position. If you are using a metal insert, place the
insert inside the gasket, align the insert slots with the ribs on
the gasket.

36 Installation Instructions – Figure 716 Flexible Reducing Couplings


Close
Figure 730 Grooved

B C B C

A A

E A

Figure 730 Mechanical Tee Figure 730 Mechanical Cross


Grooved Outlet Grooved Outlet

Nominal Max.† Max.† Dimensions Net


Size Pressure End Load A B C E Wt.
Run x psi (Branch) Inches Inches Inches Inches Lbs.
Branch kPa Lbs. / N mm mm mm mm Kg.
300 649 2.78 4.88 3.32 1.59 2.5
2" x 11/4"
2,068 2,887 70.6 124.0 84.3 40.4 1.1
300 850 2.62 4.88 3.32 1.59 2.5
2" x 11/2"
2,068 3,781 66.5 124.0 84.3 40.4 1.1
300 649 3.00 5.25 3.56 1.81 3.1
21/2" x 11/4"
2,068 2,887 76.2 133.4 90.4 46.0 1.4
300 850 3.07 5.25 3.59 1.81 3.3
21/2" x 11/2"
2,068 3,781 78.0 133.4 91.2 46.0 1.5
300 649 3.34 6.13 3.32 2.21 3.9
3" x 11/4"
2,068 2,887 84.8 155.7 84.3 56.1 1.8
300 850 3.38 6.13 3.56 2.21 4.2
3" x 11/2"
2,068 3,781 85.9 155.7 90.4 56.1 1.9
300 1,328 3.50 6.13 4.09 2.21 4.7
3" x 2"
2,068 5,907 88.9 155.7 103.9 56.1 2.1
300 649 3.92 7.13 3.32 2.78 5.5
4" x 11/4" 2,068 2,887 99.6 181.1 84.3 70.6 2.5
300 850 4.00 7.13 3.56 2.78 5.5
4" x 11/2" 2,068 3,781 101.6 181.1 90.4 70.6 2.5
300 1,328 4.00 7.13 4.06 2.78 6.0
4" x 2" 2,068 5,907 101.6 181.1 103.1 70.6 2.7
300 1,947 4.00 7.13 4.38 2.78 6.0
4" x 21/2" 2,068 8,660 101.6 181.1 111.3 70.6 2.7
300 2,120 4.00 7.13 4.38 2.78 6.0
4" x 76.1mm 2,068 9,430 101.6 181.1 111.3 70.6 2.7
300 2,885 4.13 7.13 5.13 2.78 7.0
4" x 3" 2,068 12,832 104.9 181.1 130.3 70.6 3.2
† Maximum pressure and end load are based on standard weight steel pipe. Pressure
ratings and end loads may differ on other pipe materials and/or wall thickness.
Contact Tyco Fire Protection for details. See Fire Protection Submittal Sheet for
Listing and Approval pressure ratings.

Installation Instructions – Figure 730 Mechanical Outlet 37


Close
Figure 730 Grooved (cont.)

FM

See Fire Protection Submittal Sheet


for pressure rating and Listing and
Approval information.

Nominal Max.† Max.† Dimensions Net


Size Pressure End Load A B C E Wt.
Run x psi (Branch) Inches Inches Inches Inches Lbs.
Branch kPa Lbs. / N mm mm mm mm Kg.
300 850 4.63 8.13 3.56 3.37 6.5
5" x 11/2"
2,068 3,781 117.6 206.5 90.4 85.6 2.9
300 1,328 4.63 8.13 4.06 3.37 7.1
5" x 2"
2,068 5,907 117.6 206.5 103.1 85.6 3.2
300 1,947 4.75 8.13 4.38 3.37 7.3
5" x 21/2"
2,068 8,660 120.7 206.5 111.3 85.6 3.3
300 2,885 5.00 8.13 5.13 3.37 7.6
5" x 3"
2,068 12,832 127.0 206.5 130.3 85.6 3.4
300 850 5.13 9.25 3.56 3.90 7.4
6" x 11/2"
2,068 3,781 130.3 235.0 90.4 99.1 3.4
300 1,328 5.13 9.25 4.06 3.90 7.5
6" x 2"
2,068 5,907 130.3 235.0 103.1 99.1 3.4
300 1,947 5.13 9.25 4.38 3.90 7.5
6" x 21/2"
2,068 8,660 130.3 235.0 111.3 99.1 3.4
300 2,885 5.50 9.25 5.13 3.90 9.5
6" x 3"
2,068 12,832 139.7 235.0 130.3 99.1 4.3
300 4,769 5.38 9.25 6.13 3.90 10.0
6" x 4" 2,068 21,213 136.7 235.0 155.7 99.1 4.5
300 1,947 6.25 12.50 4.38 4.90 10.2
8" x 21/2" 2,068 8,660 158.8 317.5 111.3 124.5 4.6
300 2,885 6.50 12.50 5.13 4.90 12.5
8" x 3" 2,068 12,832 165.1 317.5 130.3 124.5 5.7
300 4,769 6.38 12.50 6.13 4.90 12.5
8" x 4" 2,068 21,213 162.1 317.5 155.7 124.5 5.7
† Maximum pressure and end load are based on standard weight steel pipe. Pressure
ratings and end loads may differ on other pipe materials and/or wall thickness.
Contact Tyco Fire Protection for details. See Fire Protection Submittal Sheet for
Listing and Approval pressure ratings.

38 Installation Instructions – Figure 730 Mechanical Outlet


Close
Figure 730 Threaded

B C B C

D A A
D
TAKEOUT TAKEOUT

E D
TAKEOUT A

Figure 730 Mechanical Tee Figure 730 Mechanical Cross


Threaded Outlet Threaded Outlet

Nominal Max.† Max.† Dimensions Net


Size Pressure End Load A B C D E Wt.
Run x psi (Branch) Inches Inches Inches Inches Inches Lbs.
Branch kPa Lbs. / N mm mm mm mm mm Kg.
300 166 2.62 4.88 3.07 2.12 1.59 2.2
2" x 1/2"
2,068 738 66.5 124.0 78.0 53.8 40.4 1.0
300 260 2.62 4.88 3.07 2.12 1.59 2.2
2" x 3/4"
2,068 1,156 66.5 124.0 78.0 53.8 40.4 1.0
300 407 2.62 4.88 3.07 2.12 1.59 2.2
2" x 1"
2,068 1,810 66.5 124.0 78.0 53.8 40.4 1.0
300 649 2.78 4.88 3.32 1.93 1.59 2.5
2" x 11/4"
2,068 2,887 70.6 124.0 84.3 49.0 40.4 1.1
300 850 2.62 4.88 3.32 1.93 1.59 2.5
2" x 11/2" 2,068 3,781 66.5 124.0 84.3 49.0 40.4 1.1
300 166 2.88 5.25 3.07 2.38 1.81 2.7
21/2" x 1/2" 2,068 738 73.2 133.4 78.0 60.5 46.0 1.2
300 260 2.88 5.25 3.07 2.38 1.81 2.7
21/2" x 3/4" 2,068 1,156 73.2 133.4 78.0 60.5 46.0 1.2
300 407 2.88 5.25 3.07 2.38 1.81 2.7
21/2" x 1" 2,068 1,810 73.2 133.4 78.0 60.5 46.0 1.2
300 649 3.00 5.25 3.56 2.19 1.81 3.1
21/2" x 11/4" 2,068 2,887 76.2 133.4 90.4 55.6 46.0 1.4
300 850 3.07 5.25 3.59 2.17 1.81 3.3
21/2" x 11/2" 2,068 3,781 78.0 133.4 91.2 55.1 46.0 1.5
300 166 3.19 6.13 3.07 2.56 2.21 3.7
3" x 1/2" 2,068 738 81.0 155.7 78.0 65.0 56.1 1.7
300 260 3.19 6.13 3.07 2.56 2.21 3.7
3" x 3/4" 2,068 1,156 81.0 155.7 78.0 65.0 56.1 1.7
300 407 3.19 6.13 3.07 2.56 2.21 3.7
3" x 1" 2,068 1,810 81.0 155.7 78.0 65.0 56.1 1.7
300 649 3.34 6.13 3.32 2.50 2.21 3.9
3" x 11/4" 2,068 2,887 84.8 155.7 84.3 63.5 56.1 1.8
300 850 3.38 6.13 3.56 2.48 2.21 4.2
3" x 11/2" 2,068 3,781 85.9 155.7 90.4 63.0 56.1 1.9
300 1,328 3.50 6.13 4.09 2.75 2.21 4.7
3" x 2" 2,068 5,907 88.9 155.7 103.9 69.9 56.1 2.1
300 166 3.69 7.13 3.07 3.06 2.78 5.5
4" x 1/2" 2,068 738 93.7 181.1 78.0 77.7 70.6 2.5
300 260 3.69 7.13 3.07 3.06 2.78 5.5
4" x 3/4" 2,068 1,156 93.7 181.1 78.0 77.7 70.6 2.5
300 407 3.69 7.13 3.07 3.06 2.78 5.5
4" x 1" 2,068 1,810 93.7 181.1 78.0 77.7 70.6 2.5
Please see notes on previous page

Installation Instructions – Figure 730 Mechanical Outlet 39


Close
Figure 730 Threaded (cont.)

FM

See Fire Protection Submittal Sheet


for pressure rating and Listing and
Approval information.

Nominal Max.† Max.† Dimensions Net


Size Pressure End Load A B C D E Wt.
Run x psi (Branch) Inches Inches Inches Inches Inches Lbs.
Branch kPa Lbs. / N mm mm mm mm mm Kg.
300 649 3.92 7.13 3.32 3.00 2.78 5.5
4" x 11/4" 2,068 2,887 99.6 181.1 84.3 76.2 70.6 2.5
300 850 4.00 7.13 3.56 2.98 2.78 5.5
4" x 11/2" 2,068 3,781 101.6 181.1 90.4 75.7 70.6 2.5
300 1,328 4.00 7.13 4.06 3.25 2.78 6.0
4" x 2" 2,068 5,907 101.6 181.1 103.1 82.6 70.6 2.7
300 1,947 4.00 7.13 4.38 3.12 2.78 6.0
4" x 21/2" 2,068 8,660 101.6 181.1 111.3 79.2 70.6 2.7
300 2,120 4.00 7.13 4.38 3.12 2.78 6.0
4" x 76.1mm 2,068 9,430 101.6 181.1 111.3 79.2 70.6 2.7
300 2,885 4.13 7.13 5.13 3.31 2.78 7.0
4" x 3" 2,068 12,832 104.9 181.1 130.3 84.1 70.6 3.2
300 850 4.63 8.13 3.56 4.00 3.37 6.5
5" x 11/2" 2,068 3,781 117.6 206.5 90.4 101.6 85.6 2.9
300 1,328 4.63 8.13 4.06 3.88 3.37 7.1
5" x 2" 2,068 5,907 117.6 206.5 103.1 98.6 85.6 3.2
300 1,947 4.75 8.13 4.38 3.88 3.37 7.3
5" x 21/2" 2,068 8,660 120.7 206.5 111.3 98.6 85.6 3.3
300 2,120 4.75 8.13 4.38 3.88 3.37 7.3
5" x 76.1mm 2,068 9,430 120.7 206.5 111.3 98.6 85.6 3.3
300 2,885 5.00 8.13 5.13 4.06 3.37 7.6
5" x 3" 2,068 12,832 127.0 206.5 130.3 103.1 85.6 3.4
300 850 5.13 9.25 3.56 4.04 3.90 7.4
6" x 11/2" 2,068 3,781 130.3 235.0 90.4 102.6 99.1 3.4
300 1,328 5.13 9.25 4.06 4.31 3.90 7.5
6" x 2" 2,068 5,907 130.3 235.0 103.1 109.5 99.1 3.4
300 1,947 5.13 9.25 4.38 4.18 3.90 7.5
6" x 21/2" 2,068 8,660 130.3 235.0 111.3 106.2 99.1 3.4
300 2,120 5.13 9.25 4.38 4.18 3.90 7.5
6" x 76.1mm 2,068 9,430 130.3 235.0 111.3 106.2 99.1 3.4
300 2,885 5.50 9.25 5.13 4.37 3.90 9.5
6" x 3" 2,068 12,832 139.7 235.0 130.3 111.0 99.1 4.3
300 4,769 5.38 9.25 6.13 4.56 3.90 10.0
6" x 4" 2,068 21,213 136.7 235.0 155.7 115.8 99.1 4.5
300 1,947 6.25 12.50 4.38 5.12 4.90 10.2
8" x 21/2" 2,068 8,660 158.8 317.5 111.3 130.0 124.5 4.6
300 2,120 6.25 12.50 4.38 5.12 4.90 10.2
8" x 76.1mm 2,068 9,430 158.8 317.5 111.3 130.0 124.5 4.6
300 2,885 6.50 12.50 5.13 5.37 4.90 12.5
8" x 3" 2,068 12,832 165.1 317.5 130.3 136.4 124.5 5.7
300 4,769 6.38 12.50 6.13 5.56 4.90 12.5
8" x 4" 2,068 21,213 162.1 317.5 155.7 141.2 124.5 5.7
Please see notes on previous page

40 Installation Instructions – Figure 730 Mechanical Outlet


Close
Figure 730 Mechanical Outlet
Always read and understand the instructions. Never
remove any piping component without verifying that
the system is depressurized and drained.

Pipe Preparation

Hole Dia.‡ Step 1. The hole size should be


Nominal Size Hole Max. verified in the table on the left.
Run x Inches Inches
Branch mm mm ‡ Proper hole preparation is required for effective
sealing and performance. Check the pipe seal
2", 21/2", 3", 4" x 1
1 /2 15/8
1
surface within 5/8” of the hole to be certain it is
/2", 3/4", 1" 38.1 41.3 free from conditions which would affect proper
13/4 17/8 gasket sealing. Remove any sharp or rough
2" x 11/4", 11/2"
44.5 47.6 edges from the hole or upper housing contact
2 21/8 area, which might affect assembly, proper
1 1 1
2 /2" x 1 /4", 1 /2" seating of the locating collar or flow from the
50.8 54.0
3 7
outlet. Check gasket grade to be certain it is
1
1 /4* 1 /8 suitable for the service. For crosses, ensure
3", 4" x 1 /4"
44.5 47.6 double outlet holes are aligned on opposite
1 2 21/8 sides of the pipe. The use of threaded products
3", 4", 5", 6" x 1 /2" other than steel pipe, such as dry pendents,
50.8 54.0
etc. may not be compatible with the female
21/2 25/8
3", 4", 5", 6" x 2" threaded outlet on the Mechanical Tee. Always
63.5 66.7 confirm compatibility by contacting Tyco Fire
4", 5", 6", 8" x 23/4 27/8 Products.
21/2", 76.1mm 69.9 73.0
31/2 35/8 * Changed from 2" previously used on the
4", 5", 6", 8" x 3" Figure 720.
88.9 92.1
1 5
4 /2 4 /8
6", 8" x 4"
114.3 117.5

Step 2. Hole must be drilled on the pipe


centerline. For crosses, ensure double outlet
holes are aligned.

Step 3. Holes should be de-burred. The gasket-


seating surface on the pipe should be
examined to verify all loose debris, dirt, chips,
paint and any other foreign material such as
grease are removed.

Installation Instructions – Figure 730 Mechanical Outlet 41


Close
Installation / Assembly Instructions
The following instructions apply to Figure 730 Mechanical
Outlet Tee and Cross with threaded and grooved outlets. If a
cross configuration is desired the lower housing is replaced
with an upper outlet housing.
Verify that the gasket grade is correct for the application
intended. Please refer to “Gasket Grades and Gasket
Recommendations” literature for additional information.
Step 1. Check for proper gasket positioning in
housing. The alignment tabs on the gasket
should fit into the recesses of the housing.
Gasket lubrication is not required on this
product.

Step 2. With one nut and bolt removed, “swing


around” as shown.

Step 3. Verify that the housing outlet spike is


positioned in the hole. Insert the other bolt
into the housing and rotate the nuts
clockwise until finger tight. Verify that the
bolt heads are fully recessed in the housing.

Step 4. Alternate between bolts when tightening


nuts until properly torqued with even gaps
between the bolt pads. Note: uneven
tightening can cause the gasket to pinch or
bind. For proper bolt torques please refer to
the table listed below.

Pipe Size (Run)


Bolt Bolt Torque
Inches Size Lbs. - Ft.
2" - 21⁄2" 3
⁄ 8" 30
1
3" - 4" ⁄ 2" 50
5
5" ⁄ 8" 50
5
6" ⁄ 8" 70
3
8" ⁄ 4" 70

42 Installation Instructions – Figure 730 Mechanical Outlet


Close
Figure 40-5 Strap

C
FM
1
2 See Fire Protection Submittal Sheet
for pressure rating and Listing and
Approval information.
3
A
B Item Description
1 Housing
2 Gasket
4 D 3 Flanged Nut
4 U-Bolt

Nominal Size Dimensions Net


A B C D Wt.
Run x Branch Inches Inches Inches Inches Lbs.
mm mm mm mm Kg.
2.00 1.50 3.50 1.20 0.84
11/4" x 1/2"
50.8 38.1 88.9 30.5 0.4
2.00 1.50 3.50 1.20 0.88
11/4" x 3/4"
50.8 38.1 88.9 30.5 0.4
2.31 1.68 3.50 1.20 1.13
11/4" x 1"
58.7 42.7 88.9 30.5 0.5
2.12 1.62 3.50 1.32 0.84
11/2" x 1/2"
53.8 41.1 88.9 33.5 0.4
2.12 1.62 3.50 1.32 0.88
11/2" x 3/4" 53.8 41.1 88.9 33.5 0.4
2.43 1.80 3.50 1.32 1.13
11/2" x 1" 61.7 45.7 88.9 33.5 0.5
2.36 1.86 3.74 1.55 0.88
2" x 1/2" 59.9 47.2 95.0 39.4 0.4
2.36 1.86 3.74 1.55 0.95
2" x 3/4" 59.9 47.2 95.0 39.4 0.4
2.67 2.04 3.74 1.55 1.16
2" x 1" 67.8 51.8 95.0 39.4 0.5
2.61 2.11 4.25 1.80 0.90
21/2" x 1/2" 66.3 53.6 108.0 45.7 0.4
2.61 2.11 4.25 1.80 0.99
21/2" x 3/4" 66.3 53.6 108.0 45.7 0.4
2.92 2.29 4.25 1.80 1.21
21/2" x 1" 74.2 58.2 108.0 45.7 0.5

Pressure Rating = 175 psi (1207 kPa)

Installation Instructions – Figure 40-5 Strap 43


Close
Figure 40-5 Strap
Always read and understand the instructions. Never
remove any piping component without verifying that
the system is depressurized and drained.
Pipe Preparation
The Pipe should be examined for the following:
Hole Size Step 1. The hole size should be verified in
Nominal Size Inches
mm
the table on the left.
13/16
11/4" x 1/2"
30.2
13/16
11/4" x 3/4"
30.2
13/16
11/4" x 1"
30.2
13/16
11/2" x 1/2"
30.2
13/16
11/2" x 3/4"
30.2
13/16
11/2" x 1"
30.2
13/16
2" x 1/2"
30.2
13/16
2" x 3/4"
30.2
13/16
2" x 1"
30.2
13/16
21/2" x 1/2"
30.2
13/16
21/2" x 3/4"
30.2
13/16
21/2" x 1" 30.2

Step 2. Hole must be drilled on the pipe


centerline.

Step 3. Holes should be de-burred. The gasket-


seating surface on the pipe should be
examined to verify all loose debris, dirt, chips,
paint and any other foreign material such as
grease are removed.

44 Installation Instructions – Figure 40-5 Strap


Close
Installation / Assembly Instructions
The following instructions apply to Figure 40-5 Strap.
Verify that the gasket grade is correct for the application
intended. Please refer to “Gasket Grades and Gasket
Recommendations” literature for additional information.

Step 1.
Check for proper gasket positioning in
housing. Gasket lubrication is not required
on this product.

Step 2.
To assemble the strap on the pipe, remove the
“U” bolt. Place the outlet housing over the
hole in the pipe. Verify that the housing spike
is positioned in the hole.

Step 3.
Insert the “U” bolt into the housing and rotate
the nuts clockwise until finger tight.

Step 4.
Alternate between tightening nuts until
properly torqued. The torque should not
exceed 15 lbs.-ft. (20 Nm) on pipe with a wall
thickness less than Schedule 10, or 25 lbs.-ft.
(34 Nm) for Schedule 10 and above.
Overtorqueing can damage thin wall pipe and
will not increase sealing efficiency.

Installation Instructions – Figure 40-5 Strap 45


Close
Figure 71

A C

FM

F B E D See Fire Protection Submittal Sheet


for pressure rating and Listing and
Approval information.

Dimensions
Pipe A B C D* E* F
Size Inches Inches Inches Inches Inches Inches
mm mm mm mm mm mm
6.38 4.75 0.75 2.38 3.41 7.25
2"
162.1 120.7 19.1 60.5 86.6 184.2
7.00 5.50 0.88 2.88 3.91 7.88
21⁄2"
178.0 140.0 22.0 73.0 99.0 200.0
7.50 6.00 0.94 3.50 4.53 9.88
3"
190.5 152.4 23.9 88.9 115.1 251.0
9.00 7.50 0.94 4.50 5.53 9.90
4"
228.6 190.5 23.9 114.3 140.5 251.5
10.00 8.50 1.00 5.56 6.72 11.38
5"
254.0 215.9 25.4 141.2 170.7 289.1
11.00 9.50 1.00 6.62 7.78 11.88
6"
279.4 241.3 25.4 168.1 197.6 301.8
13.50 11.75 1.13 8.62 9.94 14.38
8"
342.9 298.5 28.7 218.9 252.5 365.3
16.00 14.25 1.19 10.75 12.31 16.88
10"
406.4 362.0 30.2 273.1 312.7 428.8
19.00 17.00 1.25 12.75 14.31 20.00
12"
482.6 431.8 31.8 323.9 363.5 508.0
* Dimensions D and E represent minimum and maximum sealing surfaces.

46 Installation Instructions – Figure 71 Flange Adapter


Close
Figure 71 (cont.)

Pipe Max.† Max.† Bolt Net


O.D. Pressure End Load Torque Wt.
Size
Size Inches psi Lbs. Qty. Lbs.-Ft. Lbs.
Dia. x Lg.
mm kPa N Nm Kg.
2.375 250 1,107 5 90 3.0
2" ⁄8" x 3" 4
60.3 1,724 4,924 122 1.4
2.875 250 1,622 5 90 5.0
21⁄2" ⁄8" x 3" 4
73.0 1,724 7,215 122 2.3
3.500 250 2,404 5 90 5.6
3" ⁄8" x 3" 4
88.9 1,724 10,693 122 2.5
4.500 250 3,974 5 90 7.0
4" ⁄8" x 3" 8
114.3 1,724 17,676 122 3.2
5.563 250 6,073 3 150 9.2
5" ⁄4" x 31⁄2" 8
141.3 1,724 27,013 203 4.2
6.625 250 8,614 3 150 10.0
6" ⁄4" x 31⁄2" 8
168.3 1,724 38,315 203 4.5
8.625 250 14,599 3 150 16.6
8" ⁄4" x 31⁄2" 8
219.1 1,724 64,936 203 7.5
10.750 250 22,679 7 200 21.8
10" ⁄8" x 4" 12
273.1 1,724 100,876 271 9.9
12.750 250 31,903 7 200 24.2
12" ⁄8" x 4" 12
323.9 1,724 141,905 271 11.0
† Maximum pressure and end load are based on standard weight steel pipe. Pressure
ratings and end loads may differ on other pipe materials and/or wall thickness.
Contact Tyco Fire Protection for details. See Fire Protection Submittal Sheet for
Listing and Approval pressure ratings.

* Note: Bolts and nuts are not supplied. Bolt lengths shown are standard; it is the
responsibility of the purchaser to verify correct length for the intended application.

Figure 71 Flange Adapter


Always read and understand the instructions. Never
remove any piping component without verifying that
the system is depressurized and drained.-
Installation / Assembly Instructions
The following instructions apply to Figure 71 Flange Adapter.
The installation is based on pipe grooved in accordance with
Standard Cut Groove or Roll Groove Specifications.

Step 1. Inspect exterior groove and ends of the


pipe to verify all loose debris, dirt, chips, paint
and any other foreign material such as grease
are removed. Pipe ends sealing surfaces must
be free from projections, indentations, and/or
other markings.

Installation Instructions – Figure 71 Flange Adapter 47


Close
Figure 71 Installation / Assembly Instructions (cont.)

Step 2. Verify that the gasket selection is correct


for the application intended. Please refer to
“Gasket Grades and Gasket Recommendations”
literature for additional information.
Insert one flange bolt (not supplied) in hinge
section of Figure 71 Flange Adapter. Place the
hinged assembly into the groove on the pipe.
Step 3. Close the flange with another bolt. To
ease in the closure of the flange, two tabs are
provided. Take an adjustable wrench and
place it over the two tabs as shown. Move the
wrench parallel to the pipe until the holes
align. Once the holes align insert a bolt.
Verify that the housing keys are fully engaged
into the groove.
Step 5. The edges and outer surface of the gasket
should be covered with a fine layer of
petroleum-free silicone lubricant or equivalent.
Petroleum lubricant should not be used on
Grade “E” EPDM or Grade “A” EPDMA gaskets
to prevent deterioration of the gasket material.
Step 6. Place the gasket into the gasket pocket
with the gasket marking side in first.

Step 7. Bring both the Figure 71 Flange and the


opposite Flange together. Ensure proper
alignment and slide each of the remaining
flange bolts (not supplied) in each of the
remaining bolt holes. Tighten all nuts
uniformly to bring the flange faces firmly together and ensure that
the nuts are sufficiently torqued. (see torque values on previous page)
Note: Metal flange washer adapters are required when the Figure 71
Flange Adapter is used against surfaces such as:
1. Rubber surfaces 2. Adapting to AWWA cast flanges
3. Rubber faced wafer valves 4. Serrated flange surfaces
Figure 71 Flange Adapters are not recommended for applications
which incorporate tie rods for anchoring or on a standard fitting
within 90° of each other. Contact Tyco Fire Products for
recommendations prior to using with plastic pipe.

48 Installation Instructions – Figure 71 Flange Adapter


Close
Figure 570 and 580

POSITION
F INDICATOR

FM

See Fire Protection Submittal Sheet


C for pressure rating and Listing and
Approval information.
A
B

G G
E
D
Front view with valve open Side view with valve open

A B C D E F G Net Wt.
Size Inches Inches Inches Inches Inches Inches Inches lbs.
mm mm mm mm mm mm mm Kg.
5.34 10.41 7.22 2.88 3.81 5.72 12.0
21⁄2" 135.6 N/A*
264.4 183.4 73.0 96.8 145.3 5.4
5.67 11.38 8.75 3.50 3.81 5.72 14.0
3" N/A*
144.0 289.1 222.3 88.9 96.8 145.3 6.4
6.76 12.70 9.65 4.75 4.56 5.72 22.0
4" N/A*
171.7 322.6 245.1 120.7 115.8 145.3 10.0
7.15 14.56 10.23 6.25 5.81 6.18 31.0
5" N/A*
181.6 369.8 259.8 158.8 147.6 157.0 14.1
7.88 15.23 10.96 6.75 5.81 6.18 36.0
6" N/A*
200.2 386.8 278.4 171.5 147.6 157.0 16.3
9.24 17.50 13.37 10.00 5.25 6.43 1.22 52.0
8" 234.7 444.5 339.6 254.0 133.4 163.3 31.0 23.6
11.81 21.78 16.93 12.00 6.25 7.96 1.75 75.0
10"** 299.9 553.2 430.0 304.3 158.8 202.2 44.5 34.1
12.97 24.11 19.10 14.27 6.50 8.83 2.60 90.0
12"** 329.4 612.4 485.1 362.5 165.1 224.3 66.0 40.9
* - end of disc does not extend beyond valve body
** - Contact Tyco Fire Products for availability

Fire Alarm
Supervisory Tamper Control Panel
Switch Circuits Supervisory
(Valve Fully Open) Circuit
Pressure Ratings:
NC BLK
S1 NO RED End of Line Figure 570 = 175 psi
COM Resistance
Or, Next Device (1207 kPa)
WHT
NC BLK/ORN Voltage
Figure 580 = 300 psi
S2 NO Source (2068 kPa)
CHASSIS COM RED/ORN

WHT/ORN
Auxiliary Switch Rating:
Signal
Device 10A 125,250 VAC
Utilization and Connection of Auxiliary Switch 0.25A 250 VDC
to be Reviewed and Approved by the Local
Authority Having Jurisdiction 0.50A 125 VDC

Installation Instructions – Control Valves 49


Close
Butterfly Valves
Always read and understand the instructions.
Never remove any piping component without
verifying that the system is depressurized and
drained.
These valves are furnished with grooved ends and can be
installed using Grooved Flexible or Rigid Couplings. To
prevent rotation of the valves it is recommended that the
Butterfly Valve be installed with rigid type couplings, such as
the Figure 572 or 772. If flexible couplings are used,
additional support may be needed to prevent rotation.
Butterfly Valves should be located where they will by readily
accessible for operation inspection and maintenance.
All replacement parts must be obtained from Tyco Fire
Products to assure proper operation of the valve. When
ordering parts please specify model number and size.
Butterfly Valves in sizes 8, 10, and 12 inches must be closed
prior to installation as the disc extends beyond the valve
body. If the valve is installed with the disc extended
mechanical damage to the disc can occur.

Supervisory Switch Replacement


For ease of replacement, the kit consists of a new gear
operator with internal switches.

Note:
Before replacing the gear operator with switches, verify
that the wiring is per the wiring diagram found in step 7.
IMPORTANT:
All replacement parts must be obtained from the
manufacturer to assure proper operation of the valve.
Warning:
Any system maintenance or inspection that involves
placing a valve "out-of-service" will eliminate the fire
protection normally provided by the fire protection
system. Prior to proceeding, be certain to secure
permission from all Authorities Having Jurisdiction and
notify all personnel who may be affected during system
shutdown. A fire watch during maintenance periods is a
recommended precaution.

50 Installation Instructions – Control Valves


Close
Butterfly Valves

Warning (cont.): C

The owner is responsible for A B

the proper operating condition


of all fire protection devices
and accessories. The NFPA
Standard 25 entitled, "Care
and Maintenance of Sprinkler E D
Systems" contains guidelines
and minimum maintenance
requirements. Futhermore, the
Authority Having Jurisdiction
may have additional
regulations and requirements
for maintenance, testing and
inspection that must be
obeyed.

DANGER:
To reduce the risk of electric shock disconnect
the electrical power to the switches.

Important:
Marking the lead wires will aid in reconnecting
the replacement wiring in Step 7.

Step 1. Disconnect electrical power and all lead wires to the switch
circuit.

Step 2. Remove the indicator (A) by using a pin punch and a hammer
to drive out the roll pin (B) (Save these parts).

Step 3. Remove the hand wheel (C) by using a pin punch and a
hammer to drive out the pin (D) (Save these parts). Important: pin
(D) is a special UL Section of Weakness pin. Use only this part. If
it is damaged, order a replacement part from Tyco Fire Products.

Installation Instructions – Control Valves 51


Close
Butterfly Valves

Step 4. Remove the mounting bolts (E)


(Save these parts) and carefully remove
the gear operator off the upper stem
ensuring that the key is not lost (see
photo).

Inspect the key and if it appears to be


damaged, order a replacement part
from Tyco Fire Products.

Important: this key is a special FM requirement; do


not substitute another component. Should the key
fall out, apply a little grease to the key to help it
“stick” in place.

Step 5 Install the new gear operator with bolts (E) from step 4.

Step 6 Replace the handwheel (C) with pin (D) and replace the
indicator (A) with pin (B).

Step 7 Connect all of the lead wires to the switch circuit


(see wiring diagram below).
Fire Alarm
Supervisory Tamper Control Panel
Switch Circuits Supervisory
(Valve Fully Open) Circuit

NC BLK
S1 NO End of Line
RED
COM Resistance
Or, Next Device
WHT
NC BLK/ORN Voltage
S2 NO Source
CHASSIS COM RED/ORN

WHT/ORN
Auxiliary
Signal
Device

Utilization and Connection of Auxiliary Switch


to be Reviewed and Approved by the Local
Authority Having Jurisdiction

Step 8 Conduct testing to verify operation.

52 Installation Instructions – Control Valves


Close
Figure 590F

B A

C
CHECK
VALVE

D
1/2"
J NPT
1/2" NPT E
F

A B C D E F G Net Wt.
Size Inches Inches Inches Inches Inches Inches Inches lbs.
mm mm mm mm mm mm mm Kg.
8.00 5.80 3.41 3.40 3.88 6.00 1.70 10.0
21⁄2"
203.2 147.3 86.6 86.4 98.6 152.4 43.2 4.5
8.37 5.76 3.60 3.40 3.88 6.00 1.70 11.0
3"
212.6 146.3 91.4 86.4 98.6 152.4 43.2 5.0
9.63 6.74 4.61 3.63 4.53 7.13 1.84 25.0
4"
244.6 171.2 117.1 92.2 115.1 181.1 46.7 11.3
10.50 7.50 5.29 4.20 4.90 7.60 1.90 29.0
5"
266.7 190.5 134.4 106.7 124.5 193.0 48.3 13.2
11.50 8.05 5.75 4.50 5.00 7.60 1.48 47.0
6"
292.1 204.5 146.1 114.3 127.0 193.0 37.6 21.3
14.00 10.25 7.75 5.62 5.45 8.40 2.20 66.0
8"
355.6 260.4 196.9 142.7 138.4 213.4 55.9 29.9

Pressure Rating for Figures 590F


and 590FR = 300 psi (2068 kPa)

FM

See Fire Protection Submittal Sheet


for pressure rating and Listing and
Approval information.

Installation Instructions – Figure 590 Check Valve 53


Close
Figure 590FR

K
Central System Side Gauge

H A Supply Central

CENTRAL
CHECK VALVE
• FIG. 590 J Side
USA

SIZE
YR OF MFG
300 PSI Gauge

Main Drain
C Main Drain

B
F G D

A B C D E F G H J K Net Wt.
Size Inches Inches Inches Inches Inches Inches Inches Inches Inches Inches Lbs.
mm mm mm mm mm mm mm mm mm mm Kg.
1 8.00 12.53 3.88 13.20 3.41 2.69 8.13 10.35 3.40 7.68 10.00
2 ⁄2"
203.2 318.3 98.6 335.3 86.6 68.3 206.5 262.9 86.4 195.1 4.5
8.37 13.02 3.88 13.65 3.60 2.86 8.35 10.35 3.40 7.90 11.0
3"
212.6 330.7 98.6 346.7 91.4 72.6 212.3 262.9 86.4 200.7 5.0
9.63 14.38 4.96 15.38 4.61 3.33 8.95 11.01 3.67 8.49 25.0
4"
244.6 365.3 126.0 390.7 117.1 84.6 227.1 279.7 93.2 215.6 11.3
10.50 14.95 4.96 15.95 5.29 3.70 9.47 12.23 4.92 9.03 29.0
5"
266.7 379.7 126.0 405.1 134.4 94.0 240.5 310.6 125.0 229.4 13.2
11.50 15.25 4.98 16.25 5.75 4.00 10.00 12.48 5.25 9.56 47.0
6"
292.1 387.4 126.5 412.8 146.1 101.6 254.0 317.0 133.4 242.8 21.3
14.00 16.37 5.48 17.37 7.94 5.07 10.72 15.73 8.07 10.27 66.0
8"
355.6 415.8 139.2 441.2 201.7 128.8 272.2 399.5 205.0 260.9 30.0

Trim Kit 21/2" & 3" Trim Kit 4", 5", 6" & 8"
Riser Check Valve Riser Check Valve
Main Drain Main Drain
11/4" X 21/2" Nipple 2" X 21/2" Nipple
11/4" M X F Ball Valve 2" M X F Ball Valve
11/4" 90° Elbow 2" 90° Elbow
Gauge (system side) Gauge (system side)
0-300 psi Gauge 0-300 psi Gauge
1 1
/4" X 2" Nipple /4" X 2" Nipple
1 1
/4" Three-Way Globe Valve /4" Three-Way Globe Valve
1 1
/4" Plug /4" Plug
FM
Gauge (supply side) Gauge (supply side)
0-300 psi Gauge 0-300 psi Gauge See Fire Protection Submittal Sheet
1 1
/4" X 5" Nipple /4" X 5" Nipple for pressure rating and Listing and
1
/4" Three-Way Globe Valve 1
/4" Three-Way Globe Valve Approval information.
1 1
/4" Plug /4" Plug

54 Installation Instructions – Figure 590 Check Valve


Close
Figure 590 Check Valve

Always read and understand the instructions. Never


remove any piping component without verifying that
the system is depressurized and drained.
These valves are furnished with grooved ends and can be in
installed using Grooved flexible or rigid couplings. Please refer
to the installation instruction for the particular coupling.
These valves may be installed in either horizontal or vertical
piping systems. The arrow cast into the valve body must point
in the direction of the flow.
Repair Instruction (Figure 590F and 590FR)
All replacement parts must be obtained from Tyco Fire
Products to assure proper operation of the valve. When
ordering parts please specify model number and size.
Step 1. Remove the bolts from the cap.

Step 2. Inspect the nickel seating surface to verify the there is no


evidence of mechanical damage. The seat also needs to be free of
all loose debris. If the seat is damaged the entire valve will need to
be replaced.
Step 3. Inspect the elastomer seal facing the
spring loaded clapper to verify that there is no
evidence of mechanical damage. If there is
damage to the elastomer seal and you have a
clapper repair kit then proceed to Step 4.

Step 4. Inspect new replacement clapper sub-


assembly.

Step 5. Remove the old bonnet gasket material


and clean. Place a new gasket on the cleaned
surface.

Installation Instructions – Figure 590 Check Valve 55


Close
Figure 590 Check Valve

Step 6. Insert replacement clapper sub assembly


into check valve body.

Step 7. Apply Loctite #242 to bolts. Tighten all


nuts uniformly bring the cap and gasket faces
firmly together and ensure that the nuts are
torqued properly as listed in the table below.

Check Valve Bolt Torque


Size Lbs. - Ft.
21⁄2", 3" 30
4", 5" 32
6" 54
8" 58

Maintenance Kit for Figure 590F Check Valve


The Maintenance Check Valve Kit is specially designed to
allow the maintenance procedure of backflushing through the
fire department connection. The maintenance kit is intended
to ease the task of backflushing without removing the Figure
590F Check Valve from the pipe line. This is accomplished by
replacing the cap / clapper assembly with the maintenance kit
(see Installation section for full procedure).
IMPORTANT:
All replacement parts must be obtained from the
manufacturer to assure proper operation of the valve.
Never remove any piping component without verifying
that the system is depressurized and drained.
The owner is responsible for the proper operating condition of
all fire protection devices and accessories. The NFPA
Standard 25 entitled, "Care and Maintenance of Sprinkler
Systems" contains guidelines and minimum maintenance
requirements. Futhermore, the Authority Having Jurisdiction
may have additional regulations and requirements for
maintenance, testing and inspection that must be obeyed.

56 Installation Instructions – Figure 590 Check Valve


Close
Figure 590 Check Valve
Warning:
The Maintenance Cap is provided with warning
labels and tags to indicate that the check valve is
out of service. Any system maintenance or
inspection that involves placing a valve "out-of-
service" will eliminate the fire protection
normally provided by the fire protection system.
Prior to proceeding, be certain to secure
permission from all Authorities Having
Jurisdiction and notify all personnel who may be
affected during system shutdown. A fire watch
during maintenance periods is a recommended
precaution.

Step 1. Verify that the system is depressurized and drained on both


sides of the Check Valve.
Step 2. Remove the bolts from the cap and remove cap with clapper
assembly and cap gasket from the check valve. Inspect the
elastomer seal facing on the spring loaded clapper to verify that
there is no damage. If there is damage to the elastomer seal, a
clapper repair kit will be required (Contact Tyco Fire Products for
details).

CAP
GASKET
CAP
CAP WITH BOLTS
CLAPPER
ASSEMBLY

Step 3. Inspect the nickel seat surface to verify it is free of all loose
debris and dirt which could affect proper sealing.
Step 4. Clean the surface for the cap gasket and place the new gasket
(supplied) on the cleaned surface.

Installation Instructions – Figure 590 Check Valve 57


Close
Figure 590 Check Valve

Step 5. Insert the Maintenance Cap (supplied). Tighten all bolts


(supplied) uniformly to bring the cap and gasket firmly together
and ensure that the bolts are sufficiently torqued to the proper
values.

OUT OF DANGER MAINTENANCE


SERVICE
OUT OF
SERVICE
CAP, GASKET
TAG AND BOLTS

Torque Values

Check Valve Bolt Torque


Size Lbs. - Ft.
21⁄2", 3" 30
4", 5" 32
6" 54
8" 58

Step 6. Backflush the system. When done backflushing, verify that the
system is depressurized and drained.

Step 7. Remove the bolts from the maintenance cap, and remove the
cap.

Step 8. Replace the cap with clapper assembly (removed in Step 2)


into the Check Valve body. Apply Loctite® #242 to bolts. Torque all
bolts (per torque values in Step 5), uniformly bringing the cap and
gasket firmly together.

Step 9. Restore system into service.

58 Installation Instructions – Figure 590 Check Valve


Close
®
Figure ADA CAP - Patented
These grooved fittings are installed with Tyco Fire Produts
Grooved Couplings. The installation instructions for the
respected grooved coupling must be followed as if the fittings
was a piece of grooved piping.

C
B

FM
A
See Fire Protection Submittal Sheet
for pressure rating and Listing and
Approval information.

Pipe Dimensions
O.D. Takeout Center to End Net
Size Outlet A B C D Wt.
NPT* Inches Inches Inches Inches Lbs.
mm mm mm mm Kg.
1
⁄2" 1.25 1.75 1.89 0.77
31.8 44.5 48.0 0.3
11⁄2" 3
⁄4" 1.900 1.25 1.75 1.89 0.77
48.3 31.8 44.5 48.0 0.3
1" 1.37 2.00 2.02 0.88
34.8 50.8 51.3 0.4
1
⁄2" 1.25 1.75 1.89 0.92
31.8 44.5 48.0 0.4
2" 3
⁄4" 2.375 1.25 1.75 1.89 0.92
60.3 31.8 44.5 48.0 0.4
1" 1.37 2.00 2.02 1.06
34.8 50.8 51.3 0.5
1
⁄2" 1.47 1.97 1.89 1.28
37.3 50.0 48.0 0.6
21⁄2" 3
⁄4" 2.875 1.47 1.97 1.89 1.28
73.0 37.3 50.0 48.0 0.6
1" 1.37 2.00 2.02 1.50
34.8 50.8 51.3 0.7
* BSP threaded outlets are available upon request.

Pressure Rating = 300 psi (2068 kPa)

Grooved Fittings 59
Close

This page intentionally blank

60 Grooved Fittings
Close
Figure 501, 510 and 519 – Patent Pending

C to E
C to E

C to E C to E

Figure 501 Figure 519

FM

See Fire Protection Submittal Sheet


for pressure rating and Listing and
C to E Approval information.

Series 200, 300, 500:


Maximum Pressure Rating =
C to E 300 psi (2068 kPa)
Figure 510 Pressure rating is depending
on pipe and coupling rating.
Figure 501 Figure 510 Figure 519
45° Elbow 90° Elbow Tee
Nominal C to E Appx. Wt. C to E Appx. Wt. C to E Appx. Wt.
Size Inches Lbs. Inches Lbs. Inches Lbs.
Inches mm Kg. mm Kg. mm Kg.
1 1.75 0.8 2.75 1.0 2.75 1.4
1 ⁄4"
44.5 0.4 69.9 0.5 69.9 0.6
1.75 1.0 2.75 1.4 2.75 1.8
11⁄2"
44.5 0.5 69.9 0.6 69.9 0.8
2.00 1.3 3.25 1.8 3.25 2.6
2"
50.8 0.6 82.6 0.8 82.6 1.2
2.25 1.9 3.75 2.7 3.75 3.9
21⁄2"
57.2 0.9 95.3 1.2 95.3 1.8
2.50 2.6 4.25 3.7 4.25 5.4
3"
63.5 1.2 108.0 1.7 108.0 2.4
3.00 5.0 5.00 7.0 5.00 10.1
4"
76.2 2.3 127.0 3.2 127.0 4.6
3.50 8.6 6.50 13.4 6.50 18.8
6"
88.9 3.9 165.1 6.1 165.1 8.5
4.25 17.2 7.75 26.3 7.75 36.3
8"
108.0 7.8 196.9 11.9 196.9 16.5

Grooved Fittings 61
Close
Friction Resistance for the 200 Series Fittings

Friction Resistance
(Expressed as Equivalent Straight Pipe)
Figure 210 Figure 201 Figure 219 Tee
Size 90° Elbow 45° Elbow Branch Run
Inches Feet Feet Feet Feet
mm Meters Meters Meters Meters
11⁄4 1.9 1.0 4.8 1.9
42.2 0.6 0.3 1.5 0.6
11⁄2 2.3 1.2 5.8 2.3
42.2 0.7 0.4 1.8 0.7
2 3.2 1.6 8.0 3.2
60.3 1.0 0.5 2.5 1.0
21⁄2 3.9 2.0 9.8 3.9
73.0 1.2 0.6 3.0 1.2
76.1mm 4.1 2.1 10.3 4.1
1.2 0.6 3.1 1.2
3 4.9 2.4 12.2 4.9
88.9 1.5 0.7 3.7 1.5
4 6.5 3.3 16.3 6.5
114.3 2.0 1.0 5.0 2.0
5 8.2 4.1 20.5 8.2
141.3 2.5 1.3 6.3 2.5
165.1mm 9.5 4.8 23.8 9.5
2.9 1.4 7.2 2.9
6 9.9 5.0 24.8 9.9
168.3 3.0 1.5 7.6 3.0
8 13.1 6.6 32.8 13.1
219.1 4.0 2.0 10.0 4.0
10 16.5 8.3 41.3 16.5
273.0 5.0 2.5 12.6 5.0
12 19.9 9.9 49.7 19.9
323.4 6.1 3.0 15.1 6.1

62 Grooved Fittings
Close
Figure 201, 210 and 219
C to E
C to E

C to E C to E

Figure 201 Figure 219

FM

C to E See Fire Protection Submittal Sheet


for pressure rating and Listing and
Approval information.
C to E
Figure 210
Figure 201 Figure 210 Figure 219
45° Elbow 90° Elbow Tee
Nominal C to E Appx. Wt. C to E Appx. Wt. C toE Appx. Wt.
Size Inches Lbs. Inches Lbs. Inches Lbs.
Inches mm Kg. mm Kg. mm Kg.
d d d
11/4 1.75 0.9 2.75 1.0 2.75 1.4
44.5 0.4 69.9 0.5 69.9 0.6
11/2 1.75d 1.1 2.75d 1.2 2.75d 1.8
44.5 0.5 69.9 0.5 69.9 0.8
2 2.00d 1.8 3.25d 2.0 3.25d 2.7
50.8 0.8 82.6 0.9 82.6 1.2
21/2 2.25d 2.2 3.75d 3.0 3.75d 5.8
57.2 1.0 95.3 1.4 95.3 2.6
d
76.1mm 2.25 2.2 3.75d 3.0 3.75d 5.8
57.2 1.0 95.3 1.4 95.3 2.6
3 2.50d 3.5 4.25d 4.5 4.25d 7.0
63.5 1.6 108.0 2.0 108.0 3.2
4 3.00d 5.2 5.00d 8.5 5.00d 11.8
76.2 2.4 127.0 3.9 127.0 5.4
d d d
5 3.25 8.5 5.50 13.5 5.50 17.0
82.6 3.9 139.7 6.1 139.7 7.7
d d d
165.1mm 3.50 12.0 6.50 18.5 6.50 26.0
88.9 5.4 165.1 8.4 165.1 11.8
d d d
6 3.50 12.0 6.50 18.5 6.50 26.0
88.9 5.4 165.1 8.4 165.1 11.8
d d d
8 4.25 23.0 7.75 36.5 7.75 45.0
108.0 10.4 196.9 16.6 196.9 20.4
10 4.75d/† 31.0 9.00d/* 60.0 9.00d/** 72.1
120.7 14.1 228.6 27.2 228.6 32.7
12 5.25d/† 40.0 10.00d/* 67.0 10.00d/** 92.5
133.4 18.1 254.0 30.4 254.0 42.0
d - These fittings are only available in domestic ductile iron. All other sizes are fabricated steel.
† - These sizes can also be ordered in the Figure 111 which is cast ductile iron purchased from a foreign supplier.
* - These sizes can also be ordered in the Figure 110 which is cast ductile iron purchased from a foreign supplier.
** - These sizes can also be ordered in the Figure 120 which is cast ductile iron purchased from a foreign supplier.

Grooved Fittings 63
Close
Figure 260, 312 and 313

E to E C to E

C to E

C to E
C to E

Figure 260 Figure 312 Figure 313

FM FM
FM See Fire Protection See Fire Protection
Submittal Sheet for Submittal Sheet for
See Fire Protection Submittal Sheet pressure rating and Listing pressure rating and Listing
for pressure rating and Listing and and Approval information. and Approval information.
Approval information.

Figure 260‡ Figure 312 Figure 313


End Cap 221/2° Elbow 111/2° Elbow
Nominal E to E Appx. Wt. C to E Appx. Wt. C to E Appx. Wt.
Size Inches Lbs. Inches Lbs. Inches Lbs.
Inches mm Kg. mm Kg. mm Kg.
0.88 0.4 1.75 0.4 1.38 0.4
11/4
22.4 0.2 44.5 0.2 35.1 0.2
1 0.88 0.6 1.75 0.5 1.38 0.5
1 /2
22.4 0.3 44.5 0.2 35.1 0.2
0.88 0.9 1.88 0.6 1.38 0.6
2
22.4 0.4 47.8 0.3 35.1 0.3
0.88 0.9 2.00 0.7 1.50 1.1
21/2
22.4 0.4 50.8 0.3 38.1 0.5
0.94 1.1
76.1mm — — — —
23.9 0.5
0.88 1.1 2.25 1.4 1.50 1.2
3
22.4 0.5 57.2 0.6 38.1 0.5
1.00 2.6 2.63 2.4 1.75 2.2
4
25.4 1.2 66.8 1.1 44.5 1.0
1.00 5.0 2.88 4.1 2.00 3.3
5
25.4 2.3 73.2 1.9 50.8 1.5
1.00 7.5
165.1mm — — — —
25.4 3.4
1.00 7.5 3.13 5.6 2.00 4.6
6
25.4 3.4 79.5 2.5 50.8 2.1
1.19 12.8 3.88 11.1 2.00 8.7
8
30.2 5.8 98.6 5.0 50.8 3.9
1.25 20.0 4.38 14.0 2.13 9.1
10
31.8 9.1 111.3 6.4 54.1 4.1
1.25 36.0 4.88 22.0 2.25 16.7
12
31.8 16.3 124.0 10.0 57.2 7.6
‡ - Sizes 11⁄4" - 12" are available with 1⁄2" and 1" tap plugs.

64 Grooved Fittings
Close
Figure 326 and 327
C to E
C to E

C to E

C to E

Figure 326

Figure 327

FM FM
See Fire Protection See Fire Protection
Submittal Sheet for Submittal Sheet for
pressure rating and Listing pressure rating and Listing
and Approval information. and Approval information.

Figure 326* Figure 327


90° Drain Elbow Cross
Nominal C to E Appx. Wt. C to E Appx. Wt.
Size Inches Lbs. Inches Lbs.
Inches mm Kg. mm Kg.
11/4 2.75 2.0
— —
69.9 0.9
11/2 2.75 2.2
— —
69.9 1.0
3.25 2.7
2 — —
82.6 1.2
1 3.75 3.00 3.75 5.0
2 /2
95.3 1.4 95.3 2.3
3 4.25 3.60 4.25 7.1
108.0 1.6 108.0 3.2
4 5.00 3.75 5.00 11.9
127.0 1.7 127.0 5.4
5.50 4.25 5.50 17.1
5
139.7 1.9 139.7 7.8
6.50 10.70 6.50 27.5
6
165.1 4.9 165.1 12.5
8 7.75 20.78 7.75 47.0
196.9 9.4 196.9 21.3
10 9.00 68.0
— —
228.6 30.8
12 — — — —

* - Figure 326 90° Elbows have a standard 1" female


threaded outlet.

Grooved Fittings 65
Close
Figure 301, 302, 303 and 341

E to E E to E
FM
See Fire Protection
Submittal Sheet for
pressure rating and Listing
and Approval information.

Figure 301 Figure 302

E to E

E to E

Figure 303 Figure 341

Figure 301, 302 and 303 Figure 341


Adapter Nipples 150 Lbs.
Flange Adapter
Nominal E to E Appx. Wt. Nominal E to E Appx. Wt.
Size Inches Lbs. Size Inches Lbs.
Inches mm Kg. Inches mm Kg.
4.00 0.8 4.00 3.2
11/4 1
1 /2
101.6 0.4 101.6 1.5
4.00 0.9 4.00 5.2
11/2 2
101.6 0.4 101.6 2.4
4.00 1.2 4.00 8.0
2 1
2 /2
101.6 0.5 101.6 3.6
4.00 1.9 4.00 10.2
21/2 3
101.6 0.9 101.6 4.6
4.00 2.5 6.00 17.2
3 4
101.6 1.1 152.4 7.8
6.00 5.5 6.00 21.4
4 5
152.4 2.5 152.4 9.7
6.00 7.4 6.00 26.0
5 6
152.4 3.4 152.4 11.8
6.00 9.5 6.00 38.4
6 8
152.4 4.3 152.4 17.4
6.00 14.2 8.00 65.0
8 10
152.4 6.4 203.2 29.5
8.00 27.0 8.00 91.0
10 12
203.2 12.2 203.2 41.3
8.00 33.0
12
203.2 15.0

66 Grooved Fittings
Close
Figure 321
C to E

FM
See Fire Protection
Submittal Sheet for Figure 321
pressure rating and Listing Reducing Tee
and Approval information.
C to E

Nominal C to E Appx. Wt. Nominal C to E Appx. Wt.


Size Inches Lbs. Size Inches Lbs.
Inches mm Kg. Inches mm Kg.
3.25 2.0 6.50 26.6
11/2 x 11/2 x 11/4 6 x 6 x 4*
82.6 0.9 165.1 12.1
3.25 2.7 6.50 27.0
2 x 2 x 11/2* 6x6x5
82.6 1.2 165.1 12.2
3.75 4.2 7.75 36.2
21/2 x 21/2 x 11/4 8x8x2
95.3 1.9 196.9 16.4
3.75 4.2 7.75 36.5
21/2 x 21/2 x 11/2 8x8x3
95.3 1.9 196.9 16.6
3.75 4.3 7.75 36.6
21/2 x 21/2 x 2* 8x8x4
95.3 2.0 196.9 16.6
4.25 5.3 7.75 36.8
3 x 3 x 11/2 8x8x5
108.0 2.4 196.9 16.7
4.25 5.5 7.75 37.0
3 x 3 x 2* 8x8x6
108.0 2.5 196.9 16.8
4.25 5.8 9.00 57.1
3 x 3 x 21/2 10 x 10 x 2
108.0 2.6 228.6 25.9
5.00 9.8 9.00 57.4
4 x 4 x 11/4 10 x 10 x 3
127.0 4.4 228.6 26.0
5.00 9.9 9.00 57.6
4 x 4 x 11/2 10 x 10 x 4
127.0 4.5 228.6 26.1
5.00 10.1 9.00 57.8
4 x 4 x 2* 10 x 10 x 5
127.0 4.6 228.6 26.2
5.00 10.3 9.00 58.0
4 x 4 x 21/2* 10 x 10 x 6
127.0 4.7 228.6 26.3
5.00 10.5 9.00 58.4
4 x 4 x 3* 10 x 10 x 8
127.0 4.8 228.6 26.5
5.50 14.5 10.00 80.2
5x5x2 12 x 12 x 3
139.7 6.6 254.0 36.4
5.50 14.8 10.00 80.5
5 x 5 x 21/2 12 x 12 x 4
139.7 6.7 254.0 36.5
5.50 15.2 10.00 80.7
5x5x3 12 x 12 x 5
139.7 6.9 254.0 36.6
5.50 15.8 10.00 80.9
5x5x4 12 x 12 x 6
139.7 7.2 254.0 36.7
6.50 26.5 10.00 91.4
6x6x2 12 x 12 x 8
165.1 11.9 254.0 41.5
6.50 26.5 10.00 91.8
6 x 6 x 21/2 12 x 12 x 10
165.1 12.0 254.0 41.6
6.50 26.5 * - These sizes can be ordered in the Figure 121
6 x 6 x 3*
165.1 12.0 which is cast ductile iron pruchased from a
foreign supplier.

Grooved Fittings 67
Close
Figure 350

E to E E to E

FM
See Fire Protection
Submittal Sheet for
pressure rating and Listing
and Approval information.
Figure 350 Figure 350
Concentric Reducer Concentric Reducer
(Up to 6") (8" to 12")

Nominal E to E Appx. Wt. Nominal E to E Appx. Wt.


Size Inches Lbs. Size Inches Lbs.
Inches mm Kg. Inches mm Kg.
2.50 0.6 4.00 6.0
11/2 x 11/4 6 x 2*
63.5 0.3 101.6 2.7
2.50 0.8 4.00 6.0
2 x 11/4 6 x 21/2
63.5 0.4 101.6 2.7
2.50 0.8 4.00 6.0
2 x 11/2 6 x 3*
63.5 0.4 101.6 2.7
2.50 1.0 4.00 5.9
21/2 x 11/4 6 x 4*
63.5 0.5 101.6 2.7
2.50 1.3 4.00 5.8
21/2 x 11/2 6 x 5*
63.5 0.6 101.6 2.6
2.50 1.2 5.00 12.2
21/2 x 2* 8x2
63.5 0.5 127.0 5.5
2.50 1.3 5.00 12.1
3 x 11/4 8 x 21/2
63.5 0.6 127.0 5.5
2.50 1.3 5.00 12.0
3 x 11/2 8x3
63.5 0.6 127.0 5.5
2.50 1.3 5.00 11.9
3 x 2* 8 x 4*
63.5 0.6 127.0 5.4
2.50 1.5 5.00 11.3
3 x 21/2* 8x5
63.5 0.7 127.0 5.1
3.00 2.2 5.00 10.8
4 x 11/4 8 x 6*
76.2 1.0 127.0 4.9
3.00 2.3 6.00 21.9
4 x 11/2 10 x 4
76.2 1.0 152.4 10.0
3.00 2.3 6.00 21.6
4 x 2* 10 x 5
76.2 1.0 152.4 9.8
3.00 2.3 6.00 21.1
4 x 21/2* 10 x 6*
76.2 1.0 152.4 9.6
3.00 2.6 6.00 19.5
4 x 3* 10 x 8*
76.2 1.2 152.4 8.9
3.50 4.6 7.00 28.0
5 x 11/2 12 x 4
88.9 2.1 177.8 12.7
3.50 4.6 7.00 30.0
5x2 12 x 6
88.9 2.1 177.8 13.6
3.50 4.5 7.00 28.0
5 x 21/2 12 x 8*
88.9 2.0 177.8 12.7
3.50 4.4 7.00 33.0
5x3 12 x 10*
88.9 2.0 177.8 15.0
3.50 4.5 * - These sizes can also be ordered in the Figure 150
5 x 4*
88.9 2.0 Grooved Concentric Reducer whicdh is cast ductile
iron purchased from a foreign supplier.

68 Grooved Fittings
Close
1" Threaded Residential Riser Manifold – Figure 513D
All sizes rated at 175 PSI
Approximate Trimmed Weight - 3.63
Note: [values] are [92.2]
7.5 lbs. (3.4Kg.)
in millimeters 1 * .63 [16]
The width of the Riser Manifold BOTH ENDS
is approximately 31⁄2". 4 TEST
AND
DRAIN

GAUGE
Note: Items 7 & 8 are used on 10.00 5

1"/33.4MM
CENTRAL
* .38 3
Manifolds for use in [254]
[9.7] 6
Canada Only
7
2
FLOW
4.50
[114.3]

175 PSI
FM 8
See Fire Protection Submittal Sheet 2.88
for pressure rating and Listing and * Approx. thread
engagement. [73.2]
Approval information. 9.75
[247.7]

Bill of Material – 1" Threaded Residential Riser Manifold


Detail No. Description No. Req’d P/N
1 Manifold Body F x F 1 976-363-01
2 Potter Waterflow Switch # VSR-SF w/Paddle 1 H-416-01
1
3 ⁄4" Water Pressure Gauge 1 971-118-02
3
4 ⁄4" 90° Street Elbow 1 H-463-075
3
5 ⁄4" Close Nipple 1 H-474-12
3
6 ⁄4" Ball Valve 1 971-116-02
7 Tamper Switch (ULC only) 1 H-419-01
8 Label (ULC only) 1 976-343-01

11⁄2" Threaded Residential Riser Manifold – Figure 513D/513R


Reference Bill of Materials (on following page)

Approximate Trimmed Weight - Note: [values] are in millimeters


8.7 lbs. (3.9Kg.) 5.38
[136.7]
* .63 [16]
The width of the Riser Manifold 1
is approximately 31⁄2". 12
Note: Items 16 & 17 are used
GAUGE
175 PSI

11 7
on Manifolds for use in AL
TEST
AND
TR DRAIN
Canada Only
CEN

16
1 1/2"/48.3MM
CENTRAL

10.00 13
[254] 2
15 * .63
[16]
FLOW
17
11.25 1 3
[285.8] * .63
2.13 4.50
[114.3] [16]
[54.1]
Male x Male 11.38 [289.1]
Body Option * Approx. thread engagement.

Figure 513 69
Close
11⁄2" Threaded Commercial Riser Manifold – Figure 513

Approximate Trimmed Weight -


11.2 lbs. (5.1Kg.) Note: [values] are in millimeters
The width of the Riser Manifold 12.50 [317.5]
is approximately 31⁄2". 6.25 [158.8]
7A
* .63 [16] 1
Note: Items 16 & 17 are used
on Manifolds for use in 12 8
Canada Only.

175 PSI
GAUGE
14.38
[365.3] 4 9
TEST
AND 10
10.00 DRAIN
16

1 1/2"/48.3MM
CENTRAL
[254] 2
15 5 14
FIG 513
USA

FLOW
6 17
11.25 1
[285.8] *.63
1.13 * .63 [16] * Approx. thread
[28.7] [16] 5.50 engagement.
Male x Male [139.7]
Body Option

Bill of Material: 11⁄2" Threaded Residential and Commercial Riser Manifold


Detail No. Req’d
No. Description Com. Res. Part Number
1 Manifold Body M x F 1 1 976-339-01
2 Potter Waterflow Switch
# VSR-SF w/ 11⁄4" Paddle 1 1 H-416-02
3 1" Ball Valve F101 0 1971-116-03
1
4 1" x ⁄2" x 1" Reducing Tee 1 0 H-469-100-050-100
5 1" Insp. Test & Drain Valve F202
w/ 1⁄2" Test Orifice 1 0 971-122-04
6 Sight Glass M x F 1 0 H-418-100
1
7 ⁄4" Water Pressure Gauge 0 1 971-118-02
1
7a ⁄4" Water Pressure Gauge 1 0 971-118-01
1
8 ⁄4" Pipe Plug 1 0 H450-025-000
1
9 ⁄4" 3-Way Globe Valve 1 0 971-119-01
1
10 ⁄4" x 3" Nipple 1 0 H-459-025-30
1
11 1" x ⁄2" x 1" California Tee 0 1 976-385-01
1
12 ⁄2" Pipe Plug 1 1 H450-050-000
13 1" Close Nipple 0 1 H-474-16
14 1" Ball Valve 1 0 971-121-01
15 11⁄2" Close Nipple 1 1 H-474-24
16 Tamper Switch (ULC only) 1 1 H-419-01
17 Label (ULC only) 1 1 976-343-01

70 Figure 513
Close
11⁄2" Grooved Commercial Riser Manifold – Figure 513
Note: [values] are in millimeters
Approximate Trimmed Weight - 12.50 [317.5]
11.2 lbs. (5.1Kg.) 6.25 [158.8]
1 6
The width of the Riser Manifold
is approximately 31⁄2". 11 7
14.38

GAUGE
175 PSI
Note: Items 12 & 13 are used [365.3] 8
10 TEST 9
on Manifolds for use in 10.00
AND
DRAIN
12

1 1/2"/48.3MM
CENTRAL
Canada Only. [254] 2
4 3

FLOW
5 13
FIG 513
USA

1.13 *.63 * Approx. thread


[28.7] [16] 5.50 engagement.
[139.7]
Bill of Material: 11⁄2" Grooved Commercial Riser Manifold
Detail
No. Description No Req’d P/N
1 Manifold Body G x G 1 976-399-02
2 Potter Waterflow Switch # VSR-SF w/ 11⁄4" Paddle 1 H-416-02
3 1" Ball Valve F101 1 971-121-01
4 1" Insp. Test & Drain Valve F202 w/ 1⁄2" Test Orifice 1 971-122-04
5 Sight Glass M x F 1 H-418-100
1
6 ⁄4" Water Pressure Gauge 1 971-118-01
1
7 ⁄4" Pipe Plug 1 H-450-025-000
1
8 ⁄4" 3-Way Globe Valve 1 971-119-01
1
9 ⁄4" x 3" Nipple 1 H-459-025-30
1
10 1" x ⁄2" x 1" Reducing Tee 1 H-469-100-050-100
1
11 ⁄2" Pipe Plug 1 H-450-050-000
12 Tamper Switch (ULC only) 1 H-419-01
13 Label (ULC only) 1 976-343-01

2" Grooved Residential Riser Manifold – Figure 513D/513R


Reference Bill of Materials (on following page)
Approximate Trimmed Weight - Note: [values] are in millimeters
11.0 lbs. (5.0Kg.) 12.00 [304.8]
5.44 [138.2]
The width of the Riser Manifold is
CENTRAL USA AND
GAUGE

10
approximately 31⁄2".
2"/60.3MM
FIG. 513

13.00
[330.2] 12 6
Note: Items 16 & 17 are used on 1
Manifolds for use in Canada Only. 13
DRAIN
TEST

TRA
L 16
CEN

14 2
FLOW
*.63
13.00 [16]
[330.2]
175 PSI

17
15
1a
2.25 4.50 * Approx. thread
2" Male x Groove Body Option [57.2] [114.3] engagement.

Figure 513 71
Close
Grooved Commercial Riser Manifold – Figure 513
Approximate Weights and Dimensions of Trimmed Note: [values] are in millimeters
Grooved Commercial Riser Manifolds C
6
Appx.
5.50 [139.7]
Size A B C D Width Wt.
In. In./mm In./mm In./mm In./mm In./mm Lbs./Kg. 10

GAUGE
CENTRAL USA AND
2" 17.13 0.88 12.88 5.25 3.50 13.5

XXX/XXXMM DRAIN
12

FIG. 513
135.0 22.2 327.0 139.7 88.9 6.1 11 9 7
A 8
21/2" 18.13 1.88 13.75 6.38 3.50 16.8 1

TEST
460.4 47.6 349.3 155.6 88.9 7.6 **13.00 16
[330.2] 2
3" 18.13 1.88 14.38 6.25 3.50 18.7 FLOW
4 3
460.4 47.6 365.1 158.8 88.9 8.5

175 PSI
4" 20.00 3.75 17.38 8.38 4.50 32.7 5 17
508.0 95.3 441.3 212.7 114.3 14.8
6" 20.00 3.75 19.25 9.25 6.63 41.6
B * Approx. thread
* .63 [16] engagement.
508.0 95.3 489.0 235.0 182.3 18.9 D ** 13" is take-out
for all sizes 2" to 6"
Bill of Material: 2" Gr, 2" Thd x Gr and 2", 21/2", 3", 4", and 6" Commercial Riser Manifold
Detail
No. Description No. Req’d P/N
2" Manifold Body Groove x Groove 1 976-254-01
21⁄2" Manifold Body Groove x Groove 1 976-254-02
1 3" Manifold Body Groove x Groove 1 976-254-03
4" Manifold Body Groove x Groove 1 976-254-04
6" Manifold Body Groove x Groove 1 976-254-05
1a 2" Manifold Body Male x Groove 1 976-411-01
Potter Waterflow Switch # VSR-SF w/ 2" Paddle 1 976-357-01
Potter Waterflow Switch # VSR-SF w/ 21⁄2" Paddle 1 976-357-02
2 Potter Waterflow Switch # VSR-SF w/ 3" Paddle 1 976-357-03
Potter Waterflow Switch # VSR-SF w/ 4" Paddle 1 976-357-04
Potter Waterflow Switch # VSR-SF w/ 6" Paddle 1 976-357-05
1" Ball Valve F101 (2") 1 971-121-01
3 11⁄4" Ball Valve F101 (21⁄2" and 3") 1 971-121-02
2" Ball Valve F101 (4" and 6") 1 971-121-03
1" Insp. Test & Drain Valve F202 (2") w/1⁄2" Test Orifice 1 971-122-04
4 11⁄4" Insp. Test & Drain Valve F202 (21⁄2" and 3")
w/1⁄2" Test Orifice 1 971-122-05
2" Insp. Test & Drain Valve F202 (4" & 6")
w/ 1⁄2" Test Orifice 1 971-122-06
1" Sight Glass (2") 1 H-418-100
1 1
5 1 ⁄4" Sight Glass (2 ⁄2" and 3") 1 H-418-125
2" Sight Glass (4" and 6") 1 H-418-200
6 1⁄4" Water Pressure Gauge 1 971-118-01
7 1⁄4" Pipe Plug 1 H-450-025-000
1
8 ⁄4" 3-Way Globe Valve 1 971-119-01
9 1⁄4" x 3" Nipple 1 H-459-025-30
10 1" Pipe Plug 1 H-450-100-000
1" x 1⁄2" x 1" Reducing Tee (2") 1 H-469-100-050-100
11 11⁄4" x 1⁄2" x 11⁄4" Reducing Tee (21⁄2" and 3") 1 H-469-125-050-125
1
2" x ⁄2" x 2" Reducing Tee (4" and 6") 1 H-469-200-050-200
12 1⁄2" Pipe Plug 1 H-450-050-000
13 1" x 1⁄2" x 1" California Tee 1 976-385-01
14 1" Close Nipple 1 H-474-16
15 1" Ball Valve F101 1 971-116-03
16 Tamper Switch (ULC only) 1 H-419-01
17 Label (ULC only) 1 976-343-01
Note: Items 16 & 17 are used on Manifolds for use in Canada Only

72 Figure 513
Close
Potter Waterflow Switch Terminal Connections

Caution: An uninsulated section of a


INCOMING
single conductor is not permitted to be
looped around the terminal and serve
as two separate connections. The wire
must be severed to serve as two
separate connections, thereby
OUTGOING
providing supervision of the
connection in the event that the wire becomes dislodged from the
terminal.
Potter Waterflow Switch Typical Electrical Connections

Local Bell Transformer Style B / Class B


or Battery Powered End of Line Resistor CKT. (see note)
Open on Close on
Alarm Alarm End of Line
Open on Close on Resistor
Alarm Alarm
Signaling Device

Typical Switch Action Supervised Loop (see note)

Open on From To Additional


Close on Close on
Alarm Alarm Control Open on Alarm
Devices or
Panel Alarm Return to
Control

Note: For supervised circuits, see "Switch Terminal Connections" and caution
note (above). The Model VSC and Model VSR-SF have two switches, one
can be used to operate a central station, proprietary or remove signaling
unit, while the other contact is used to operate a local audible or visual
annunciator.
Testing: The frequency of testing for the Model VSC and Model VSR-SF and
their associated protective monitoring system should be in accordance with
applicable NFPA Standards and/or the Authority Having Jurisdiction, but
under no circumstances less than bimonthly.

Potter Tamper Switch Typical Electrical Connection

NC
Contacts S.P.D.T. (form C)
Contact Rating: 5A@125V AC Contacts shown with
COM Cover in Place
2.5A@30V DC
NO

Installation for Models VSC and VSR-SF


Remove the one retard assembly mounting screw.
Place the switch assembly over the retard mounting tab.
Replace the screw.

Figure 513 73
Close
Optional Pressure Relief Valve Grooved Commercial Trim

Relief Valve is factory set at 175psi


(nonadjustable).
3 1 4

Note: If the optional pressure relief kit

CENTRAL USA AND


GAUGE
2

XXX/XXXMM DRAIN
FIG. 513
is desired for Figures 3 and 4, an
outlet on the riser must be
1
provided, and the connection and

TEST
material between the riser and the
FLOW
manifold will need to be supplied
NORMALLY NORMALLY
and fabricated by the installer.

175 PSI
IN DRAIN CLOSED
POSITION

Bill of Material – Optional Pressure Relief Valve Kit


Detail
No. Description No Req’d Number
1 90° Compression Fitting 2 H-475-050-038
1
2 ⁄2" Watts Pressure Relief Valve Model FP53L (UL, FM) 1 H-476-01
Tubing (2") 1 976-419-01
3 Tubing (21⁄2" and 3") 1 976-419-02
Tubing (4" and 6") 1 976-419-03
1
4 1" x ⁄2" Reducing Bushing 1 H-477-01

M = Male N.P.T. Optional Figure 513


Pressure Relief Valve Kit
F = Female N.P.T. Size Part Number
G = Grooved Connection 2" 4063
21⁄2" and 3" 4072
4" and 6" 4073

Size Figure P/N Size Figure P/N


1" 513D, F x F (UL, FM) 4067 2" 513D/513R, M x G (ULC) 4094
1" 513D, F x F (ULC) 4085 2" 513D/513R, G x G (UL, FM) 4059
11⁄2" 513D/513R, F x M(UL, FM) 4057 2" 513D/513R, G x G (ULC) 4093
11⁄2" 513D/513R, M x M(UL, FM) 4058 2" 513, G x G, 1⁄2" Test Orifice (UL, FM) 4060
11⁄2" 513D/513R, F x M(ULC) 4088 2" 513, G x G, 1⁄2" Test Orifice (ULC) 4090
11⁄2" 513D/513R, M x M(ULC) 4089 21⁄2" 513, G x G, 1⁄2" Test Orifice (UL, FM) 4061
11⁄2" 513, F x M 1⁄2" Test Orifice (UL, FM) 4055 21⁄2" 513, G x G, 1⁄2" Test Orifice (ULC) 4091
11⁄2" 513, M x M 1⁄2" Test Orifice (UL, FM) 4056 3" 513, G x G, 1⁄2" Test Orifice (UL, FM) 4062
11⁄2" 513, F x M 1⁄2" Test Orifice (ULC) 4086 3" 513, G x G, 1⁄2" Test Orifice (ULC) 4092
11⁄2" 513, M x M 1⁄2" Test Orifice (ULC) 4087 4" 513, G x G, 1⁄2" Test Orifice (UL, FM) 4065
11⁄2" 513, G x G 1⁄2" Test Orifice (UL, FM) 4056G 4" 513, G x G, 1⁄2" Test Orifice (ULC) 4095
11⁄2" 513, G x G 1⁄2" Test Orifice (ULC) 4087G 6" 513, G x G, 1⁄2" Test Orifice (UL, FM) 4066
2" 513D/513R, M x G (UL, FM) 4064 6" 513, G x G, 1⁄2" Test Orifice (ULC) 4096

74 Figure 513
Close
Standard Conversions
TO CHANGE TO MULTIPLY BY
Inches .............................................. Feet ................................................ 0.0833
Inches .............................................. Millimeters .......................................... 25.4
Feet .................................................. Inches .................................................... 12
Feet .................................................. Yards .............................................. 0.3333
Yards ................................................ Feet .......................................................... 3
Square Inches .................................. Square feet ................................... 0.00694
Square feet ...................................... Square inches ...................................... 144
Square feet ...................................... Square yards ................................ 0.11111
Square yards ................................... Square feet ............................................... 9
Cubic Inches .................................... Cubic feet ..................................... 0.00058
Cubic feet ......................................... Cubic inches ...................................... 1728
Cubic feet ......................................... Cubic yards .................................. 0.03703
Cubic yards ...................................... Cubic feet ............................................... 27
Cubic Inches .................................... Gallons ......................................... 0.00433
Cubic feet ......................................... Gallons ................................................ 7.48
Gallons ............................................. Cubic inches ........................................ 231
Gallons ............................................. Cubic feet ....................................... 0.1337
Gallons ............................................. Pounds of water ................................. 8.33
Pounds of water .............................. Gallons ......................................... 0.12004
Ounces ............................................. Pounds ........................................... 0.0625
Pounds ............................................ Ounces ................................................... 16
Inches of water ................................ Pounds per square inch ................ 0.0361
Inches of water ................................ Inches of mercury .......................... 0.0735
Inches of water ................................ Ounces per square inch .................... 0.578
Inches of water ................................ Pounds per square foot ........................ 5.2
Inches of mercury ........................... Inches of water ................................... 13.6
Inches of mercury ........................... Feet of water .................................. 1.1333
Inches of mercury ........................... Pounds per square inch ................ 0.4914
Ounces per square inch .................. Inches of mercury ............................. 0.127
Ounces per square inch .................. Inches of water ................................. 1.733
Pounds per square inch .................. Inches of water ................................. 27.72
Pounds per square inch .................. Feet of water ....................................... 2.31
Pounds per square inch .................. Inches of mercury ............................... 2.04
Pounds per square inch .................. Atmospheres .................................. 0.0681
Feet of water .................................... Pounds per square inch ................... 0.434
Feet of water .................................... Pounds per square foot ...................... 62.5
Feet of water .................................... Inches of mercury .......................... 0.8824
Atmospheres ................................... Pounds per square inch ................ 14.696
Atmospheres ................................... Inches of mercury ............................. 29.92
Atmospheres ................................... Feet of water .......................................... 34
Long tons ........................................ Pounds ............................................... 2240
Short tons ........................................ Pounds ............................................... 2000
Short tons ........................................ Long tons ..................................... 0.89285

Reference 75
Close
Sprinkler System Formulas
SIMPLE FLOW RATE
Q = K x P 0.5 , where
Q = flow rate (GPM)
K = discharge coefficient of pipe
P = pressure (PSI)

GENERAL VOLUMETRIC FLOW RATE


Q = 29.8 x D 2 x Cd x P 0.5 , where:
Q = flow rate (GPM)
D = outlet diameter (Inches)
Cd = discharge coefficient based on outlet geometry
P = pressure (PSI)

PRESSURE TANK SIZING (TANK ABOVE SPRINKLERS)


P = (30/A) - 15, where
P = air pressure in tank (PSI)
A = proportion of air in the tank

PRESSURE TANK SIZING (TANK BELOW SPRINKLERS)


P = [(30/A) - 15] + (0.43 x H/A), where
P = air pressure carried in tank (PSI)
A = proportion of air in the tank
H = height of highest sprinkler above tank bottom (Ft)

PRESSURE TANK SIZING (HYDRAULICALLY CALCULATED)


Pi = [(Pf + 15)/A] - 15, where
Pi = tank air pressure to use (PSI)
A = proportion of air in the tank
Pf = system pressure req'd per hydraulic calc. (PSI)

DARCY-WEISBACH FORMULA FOR FRICTION LOSS:


hl = f x v 2 /(2 x g x D), where
hL = friction loss (Ft)
Re = Reynolds number
f = friction factor (f=64/Re)
v = water velocity (Ft/Sec)
g = gravitational constant (Ft/Sec^2)
D = pipe diameter (Ft)

76 Reference
Close
Sprinkler System Formulas
HAZEN-WILLIAMS FORMULA FOR PRESSURE LOSS
p = (4.52 x Q 1.85)/(C1.85 x D4.87), where:
P = pressure loss (PSI) per lineal ft.
Q = flow rate (GPM)
C = friction factor of pipe (constant)
D = internal diameter of pipe (Inches)

Typical “C” values:


Unlined cast or ductile iron .................... 100
Black steel (dry sys.incl.preaction) ........ 100
Black steel (wet sys.incl.deluge) ............ 120
Galvanized (all) ...................................... 120
Plastic (listed)– all ................................. 150
Cement lined cast or ductile iron ........... 140
Copper tube or stainless steel ............... 150

HAZEN-WILLIAMS FORMULA FOR PRESSURE LOSS (IN SI UNITS):

p = (10 5 x 6.05 x Q 1.85)/(C1.85 x D4.87), where:


P = pressure loss (Bars) per lineal meter
Q = flow rate (Liter/Min)
C = friction factor of pipe (constant)
D = internal diameter of pipe (mm)

PRESSURE VELOCITY:
Pv = (0.001123 x Q 2) /(D 4 ), where
Pv = pressure velocity (PSI)
Q = upstream flow rate (GPM)
D = internal dia. of pipe (Inches)

ESTIMATE – DRY PIPE TRIP TIME:


t= 0.0352 x (Vt/(An x To 0.5 )) x log(pao/pa),
t = time (seconds)
Vt = dry volume of sprinkler system(Cu. Ft)
An = flow area of open sprinklers (Sq. Ft)
TO = air temperature (Degrees Rankine)
pao = initial air pressure (absolute)
pa = trip pressure (absolute)

Reference 77
Close
Terms of Sale
General
All sales by Tyco Fire Products shall be subject to the following terms
and conditions which, together with product specifications and
designs, shall be subject to change without prior notice. The
placement of orders with Tyco Fire Products shall constitute
acceptance of the terms, conditions, specifications and designs then
in effect and being offered. Terms and conditions in effect are not
subject to modification or waiver by a purchase order or any other
document unless agreed to in writing by and authorized representative
of Tyco Fire Products.

Prices
All selling prices are F.O.B. Lansdale or Regional Tyco Fire Products
Distribution Warehouse. Prices are subject to change without prior
notice.

Late Charges
Domestic, including Canada - unless otherwise agreed by Tyco Fire
Products, terms shall be net 30 days. A charge of 11⁄2% per month
(18% per annum) will be added to all past due amounts.
Overseas - Irrevocable Letter of Credit or other form of payment
acceptable to Tyco Fire Products, paid prior to shipment.

Minimum Charge
$50.00 per order, domestic shipment only.

Export Packing
An extra charge will be made for special packaging in the amount of
1% of the cost of the goods being shipped of air and ocean
shipments. If it is required that we fully crate a shipment at
customer’s request, the charge for the crating will be 3% of the cost of
the goods being shipped.

Special Handling
An extra charge may be made for special handling and packaging.

78 Terms of Sale
Close
Terms of Sale (cont.)
Special Terms
Special material orders and make-to-order products may not be
cancelled unless agreed to by Tyco Fire Products in writing, and upon
agreement to compensation for work already performed. Any special
material, Tyco Fire Products non-manufactured items deemed to be
nonstandard may not be cancelled.

Method of Shipment
Unless shipment method or routing is designated by the Buyer, Tyco
Fire Products will make this selection in its sole discretion at Buyer’s
risk. Tyco Fire Products shall bear no risk of loss, damage or delay by
a carrier while in transit.

Return Shipments
There shall be no credit given for material returned without written
authorization. Requests for returns must be made within 14 days of
receipt of materials and shall include the date and invoice number of
the original purchase. Returns will be credited for the amount of the
purchase price less 20% for handling, inspection, and retesting
provided the goods are in resalable condition. Returns must be
shipped freight prepaid to Tyco Fire Products Distribution Center (our
option). Materials purchased for you from other manufacturers are
subject to their return policy terms and may not be returnable.

Specify gasket grade when ordering and confirm receipt of grade


ordered, to insure suitability for intended use; Tyco Fire Products
shall not be liable for selection of improper gasket grades, or the
return of gaskets under such circumstances.

Liability
Shipping or delivery dates are approximate only and subject to
reasonable delay. Tyco Fire Products will not be liable for any
damages (incidental, consequential, liquidated or otherwise) which
may be incurred or arise, directly or indirectly, from any failure by
Tyco Fire Products to meet shipping or delivery dates.

Terms of Sale 79
Close
Terms of Sale (cont.)
Limited Warranty
Products manufactured by Tyco Fire Products are warranted solely to
the original Buyer for ten (10) years against defects in material and
workmanship when paid for and properly installed and maintained
under normal use and service. This warranty will expire ten (10) years
from date of shipment by Tyco Fire Products. No warranty is given for
products or components manufactured by companies not affiliated by
ownership with Tyco Fire Products or for products and components
which have been subject to misuse, improper installation, corrosion,
or which have not been installed, maintained, modified or repaired in
accordance with applicable Standards of the National Fire Protection
Association (NFPA), and/or the standards of any other Authorities
Having Jurisdiction. Materials found by Tyco Fire Products to be
defective shall be either repaired or replaced, at Tyco Fire Products’
sole option. Tyco Fire Products neither assumes, nor authorizes any
person to assume for it, any other obligation in connection with the
sale of products or parts of products. Tyco Fire Products shall not be
responsible for sprinkler system design errors or inaccurate or
incomplete information supplied by Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE, IN
CONTRACT, TORT, STRICT LIABILITY OR UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL, INDIRECT, SPECIAL OR
CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO
LABOR CHARGES, REGARDLESS OF WHETHER TYCO FIRE
PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT SHALL TYCO FIRE PRODUCTS’
LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER
WARRANTIES EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
Governing Law
These terms and conditions of sale shall be construed under and in
accordance with the laws of the Commonwealth of Pennsylvania.
Buyer consents and agrees to the jurisdiction and venue of the Court
of Common Pleas of Montgomery County, Pennsylvania and the U.S.
District Court for the Eastern District of Pennsylvania with respect to
any proceeding arising out of or in connection with any transaction
entered into between Tyco Fire Products and Buyer. Buyer further
agrees that mailing to either party by certified registered mail shall
constitute lawful and valid services of process.

80 Terms of Sale
Close
Notes

Notes 81
Close
Index

ADACAP® ........................................................................................................................................................................... 59
Figure 201 45° Elbow .................................................................. 62 - 63
Figure 210 90° Elbow .................................................................. 62 - 63
Figure 219 Tee ............................................................................... 62 - 63
Figure 260 Cap ....................................................................................... 64
Figure 301 Adapter Nipple (Gr. x Thd.) ......................................... 66
Figure 302 Adapter Nipple (Gr. x Gr.) ............................................ 66
Figure 303 Adapter Nipple (Gr. x Bev.) ......................................... 66
Figure 312 221⁄2° Elbow ...................................................................... 64
Figure 313 111⁄4° Elbow ...................................................................... 64
Figure 321 Reducing Tee (Gr. x Gr.) ................................................ 67
Figure 326 90° Drain Elbow ............................................................... 65
Figure 327 Cross .................................................................................... 65
Figure 341 150 Lbs. Flange Adapter .............................................. 66
Figure 350 Concentric Reducer (Gr. x Gr.) ................................... 68
Figure 40-5 Strap .......................................................................... 43 - 45
Figure 501 45° Elbow .................................................................. 60 - 61
Figure 510 90° Elbow .................................................................. 60 - 61
Figure 513 Riser Manifold ......................................................... 69 - 74
Figure 519 Tee ............................................................................... 60 - 61

82 Index
Close
Index

Figure 570 Butterfly Valve ......................................................... 49 - 50


Figure 572 Rigid Coupling ........................................................ 20 - 25
Figure 575 Flexible Coupling ................................................... 26 - 32
Figure 580 Butterfly Valve ......................................................... 49 - 50
Figure 590F Check Valve ........................................................... 53 - 56
Figure 590FR Check Valve ......................................................... 53 - 56
Figure 705 Flexible Coupling ................................................... 26 - 32
Figure 707 Flexible Coupling ................................................... 26 - 32
Figure 71 Flange Adapter ......................................................... 46 - 48
Figure 716 Reducing Coupling ............................................... 33 - 36
Figure 730 Mechanical Tee and Cross .................................. 37 - 42
Figure 772 Rigid Coupling ........................................................ 20 - 25
General Data ..................................................................................... 3 - 11
Gaskets ............................................................................................. 18 - 19
Groove Specifications ................................................................. 14 - 17
Maintenance Kit ............................................................................ 56 - 58
Supervisory Switch Replacement .......................................... 51 - 52
System Design ............................................................................... 12 - 13

Index 83
Close

Certified Company

Tyco Fire Products


www.tyco-grooved.com
451 North Cannon Avenue
Lansdale, Pennsylvania 19446 USA

Customer Service/Sales
Tel: (215) 362-0700 / Fax: (215) 362-5385

Technical Services
Tel: (800) 381-9312 / Fax: (800) 791-5500

Flow Control Tyco Fire


P r o d u c t s

Printed in USA, ©2000 Tyco Fire Products IH-1000 09-00

Das könnte Ihnen auch gefallen