Beruflich Dokumente
Kultur Dokumente
Maragondon Branch
Maragondon, Cavite
Submitted by:
Gonzales, John Robert S.
Nolasco, Maverick John C.
BSME – IV
Submitted to:
Engr. Jhay Ahr C. Flores
March 2019
TABLE OF CONTENTS
Page
4.0 Overall Heat Transfer Coefficient (U Factor) for First Floor ................................. 9
ii
5.1 Heat Transfer through Opaque Surfaces ................................................... 14
iii
CONFERENCE ROOM (2ND FLOOR) COOLING LOAD CAPACITY ............................ 29
9.0 Overall Heat Transfer Coefficient (U Factor) for Conference Room .................. 33
iv
11.0 Estimation of Internal Loads (Conference Room) ........................................... 41
13.0 Wall Surface Area for Office of the Punong Barangay .................................... 47
13.1 Sun Effect for the Office of the Punong Barangay .................................... 47
14.3 U-Factors for Office of the Punong Barangay (Opaque Surfaces) ............ 51
v
15.1.3 For Ceiling/Roof ............................................................................. 52
17.0 Required Cooling Load Capacity (Office of the Punong Barangay) ................. 62
References ................................................................................................................... 64
Appendices .................................................................................................................. 65
vi
1
Definition of Terms
Used terms relative to heat transmission and load calculations are defined below
rooms.
British thermal unit (Btu) – is the approximate heat required to raise 1 lb. of water 1 deg
Fahrenheit, from 59°F to 60°F. Air conditioners are rated by the number of British Thermal
Units (Btu) of heat they can remove per hour. Another common rating term for air
conditioning size is the “ton,” which is 12,000 Btu per hour and Watts. Some countries
utilize one unit, more than the others and therefore it is good if you can remember the
used for calculating the instantaneous external cooling load across a wall or roof.
Sensible Heat Gain – is the energy added to the space by conduction, convection and/or
radiation.
Latent Heat Gain – is the energy added to the space when moisture is added to the space
flow through a unit area of building envelope material or assembly, including boundary
2
films, per unit of temperature difference between the inside and outside air. The U-factor
Thermal Resistance (R) – is the reciprocal of a heat transfer coefficient and is expressed
in ((hr °F ft2)/Btu. For example, a wall with a U-value of 0.25 would have a resistance value
Cooling Load – is the rate at which sensible and latent heat must be removed from the
space to maintain a constant space dry-bulb, air temperature and humidity. Sensible heat
into the space causes its temperature to rise while latent heat is associated with the rise
of the moisture constant in the space. The building design, internal equipment, occupants
and outdoor weather conditions may affect cooling load in a building using different heat
transfer mechanisms.
Wall Gain Load – sometimes called the wall leakage load, is a measure of the heat which
leaks through the walls of the air-conditioned space from the outside to the inside. Since
there is no perfect insulation there is always a certain amount of heat passing from the
outside to the inside whenever the inside temperature is below of that on the outside.
Air Change Load – when the door of an air-conditioned space is opened, warm outside
air enters the space to replace the more dense cold air which is lost from the air-
conditioned space through the open door. This part of the cooling load is the air change
load.
all miscellaneous sources of heat. Chief among these are people working in or otherwise
occupying the air-conditioned space along with lights and other electrical equipment
the table below represents the peak temperature for the span of 10 years:
Maximum Maximum
Year Temperature Relative
Humidity
o
C o
F (%)
2009 30 86 88
2010 31 87.8 84
2011 31 87.8 83
2012 32 89.6 84
2013 33 91.4 83
2014 33 91.4 83
2015 33 91.4 80
2016 33 91.4 84
2017 33 91.4 80
2018 33 91.4 84
Considering the peak temperature 91.4 oF (33 oC) for the surrounding temperature
where the room is exposed to. The desired temperature from the range of 67 oF – 82 oF
from ASHRAE Standard 55-2013, using 72.5 oF (22.5 oC) which is ideal room temperature.
4
the solar radiation. A cooling factor or allowance for solar radiation (ASR) is considered to
be added to the difference of the outdoor maximum temperature (OMT) and indoor desired
form:
Materials
Walls (North, East, West, and South) 4.33” concrete block, sand aggregate with 0.835”
cement plaster
Floor (1st floor & 2nd floor) 6” concrete lightweight aggregate with ¼” linoleum
tile
Windows (1st floor & 2nd floor) 0.25” single glaze clear glass with operable
aluminum frame
Door (1st floor & 2nd floor) 2” oak wood
0.385” Gypsum wall, 2”x4” wood rafter, 26 gauge
Ceiling/Roof
metal panel
2
1𝑓𝑡 2
𝐴𝑛𝑜𝑟𝑡ℎ 𝑤𝑎𝑙𝑙 = 14500.60𝑖𝑛 × ( )
12𝑖𝑛
𝐴𝑠𝑜𝑢𝑡ℎ 𝑤𝑎𝑙𝑙 = (𝐿 × ℎ)
𝐴𝑠𝑜𝑢𝑡ℎ 𝑤𝑎𝑙𝑙 = (188.928𝑖𝑛 × 106.272𝑖𝑛)
1𝑓𝑡 2
𝐴𝑠𝑜𝑢𝑡ℎ 𝑤𝑎𝑙𝑙 = 20077.76𝑖𝑛2 × ( )
12𝑖𝑛
𝑨𝒔𝒐𝒖𝒕𝒉 𝒘𝒂𝒍𝒍 = 𝟏𝟑𝟗. 𝟒𝟑𝒇𝒕𝟐
7
𝐴𝑒𝑎𝑠𝑡 𝑤𝑎𝑙𝑙 = (𝐿 × ℎ)
𝐴𝑒𝑎𝑠𝑡 𝑤𝑎𝑙𝑙 = (118.08𝑖𝑛 × 106.272𝑖𝑛)
2
1𝑓𝑡 2
𝐴𝑒𝑎𝑠𝑡 𝑤𝑎𝑙𝑙 = 19987.64𝑖𝑛 × ( )
12𝑖𝑛
𝑨𝒆𝒂𝒔𝒕 𝒘𝒂𝒍𝒍 = 𝟏𝟑𝟖. 𝟖𝟎𝒇𝒕𝟐
𝐴𝑤𝑖𝑛𝑑𝑜𝑤 = (𝑊𝑤 × ℎ𝑤 )
𝐴𝑤𝑖𝑛𝑑𝑜𝑤 = (39.36𝑖𝑛 × 39.36𝑖𝑛)
2
1𝑓𝑡 2
𝐴𝑤𝑖𝑛𝑑𝑜𝑤 = 1549.21𝑖𝑛 × ( )
12𝑖𝑛
𝑨𝒘𝒊𝒏𝒅𝒐𝒘 = 𝟏𝟎. 𝟕𝟔𝒇𝒕𝟐
8
𝐴𝑑𝑜𝑜𝑟 = (𝑊𝑑 × ℎ𝑑 )
𝐴𝑑𝑜𝑜𝑟 = (31.488𝑖𝑛 × 78.72𝑖𝑛)
2
1𝑓𝑡 2
𝐴𝑑𝑜𝑜𝑟 = 2478.74𝑖𝑛 × ( )
12𝑖𝑛
𝑨𝒅𝒐𝒐𝒓 = 𝟏𝟕. 𝟐𝟏𝒇𝒕𝟐
1𝑓𝑡 2
𝐴𝑓𝑙𝑜𝑜𝑟𝑖𝑛𝑔 = 22308.62𝑖𝑛2 × ( )
12𝑖𝑛
𝑨𝒇𝒍𝒐𝒐𝒓𝒊𝒏𝒈 = 𝟏𝟓𝟒. 𝟗𝟐𝒇𝒕𝟐
9
Where:
Windows 10.76
Door 17.21
Flooring 154.92
1
𝑈=
𝑅𝑇
1
𝑈=
1 𝑥1 𝑥2 1
+ + +
ℎ𝑖 𝑘1 𝑘2 ℎ𝑜
10
2009)
𝐵𝑡𝑢 − 𝑖𝑛
𝑘𝑐𝑒𝑚𝑒𝑛𝑡 𝑝𝑙𝑎𝑠𝑡𝑒𝑟 = 5.0
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢 − 𝑖𝑛
𝑘𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 = 10 𝑡𝑜 20
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢 − 𝑖𝑛
𝑊𝑒 𝑐𝑜𝑛𝑠𝑖𝑑𝑒𝑟, 𝑘𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 = 15
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
Fundamentals, 2009)
11
𝐵𝑡𝑢
ℎ𝑖 = 1.46
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
ℎ𝑜 = 4.0
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
For 4.33” concrete block, sand aggregate, with 0.835” cement plaster substitute
the values we get from above tables, to solve for the 𝑈𝑤𝑎𝑙𝑙 .
1
𝑈𝑤𝑎𝑙𝑙 =
1 𝑥𝑐𝑒𝑚𝑒𝑛𝑡 𝑝𝑙𝑎𝑠𝑡𝑒𝑟 𝑥𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 1
+ + +
ℎ𝑖 𝑘𝑐𝑒𝑚𝑒𝑛𝑡 𝑝𝑙𝑎𝑠𝑡𝑒𝑟 𝑘𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 ℎ𝑜
1
𝑈𝑤𝑎𝑙𝑙 =
1 0.835𝑖𝑛 4.33𝑖𝑛 1
𝐵𝑡𝑢 + 𝐵𝑡𝑢 − 𝑖𝑛 + 𝐵𝑡𝑢 − 𝑖𝑛 + 𝐵𝑡𝑢
1.46 5.0 15 4.0
ℎ𝑟 − 𝑓𝑡2 − 𝐹 ℎ𝑟 − 𝑓𝑡2 − 𝐹 ℎ𝑟 − 𝑓𝑡2 − 𝐹 ℎ𝑟 − 𝑓𝑡2 − 𝐹
𝑩𝒕𝒖
𝑼𝒘𝒂𝒍𝒍 = 𝟎. 𝟕𝟏𝟗
𝒉𝒓 − 𝒇𝒕𝟐 − 𝑭
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝑅𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 = 1.79
𝐵𝑡𝑢
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝑅𝑙𝑖𝑛𝑜𝑙𝑒𝑢𝑚 𝑡𝑖𝑙𝑒 = 0.51
𝐵𝑡𝑢
𝐵𝑡𝑢 − 𝑖𝑛
𝑘𝑐𝑒𝑚𝑒𝑛𝑡 𝑝𝑙𝑎𝑠𝑡𝑒𝑟 = 5.0
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
For 6” concrete lightweight aggregate substitute the values from above to solve for
𝑈𝑓𝑙𝑜𝑜𝑟𝑖𝑛𝑔 .
1
𝑈𝑓𝑙𝑜𝑜𝑟𝑖𝑛𝑔 = 𝑥𝑐𝑒𝑚𝑒𝑛𝑡 𝑝𝑙𝑎𝑠𝑡𝑒𝑟
𝑅𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 + 𝑅𝑙𝑖𝑛𝑜𝑙𝑒𝑢𝑚 𝑡𝑖𝑙𝑒 +
𝑘𝑐𝑒𝑚𝑒𝑛𝑡 𝑝𝑙𝑎𝑠𝑡𝑒𝑟
1
𝑈𝑓𝑙𝑜𝑜𝑟𝑖𝑛𝑔 =
ℎ𝑟 − 𝑓𝑡 2
−𝐹 ℎ𝑟 − 𝑓𝑡 2 − 𝐹 0.5𝑖𝑛
1.79 𝐵𝑡𝑢 + 0.51 𝐵𝑡𝑢 + 𝐵𝑡𝑢 − 𝑖𝑛
5.0
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝑩𝒕𝒖
𝑼𝒇𝒍𝒐𝒐𝒓𝒊𝒏𝒈 = 𝟎. 𝟒𝟐
𝒉𝒓 − 𝒇𝒕𝟐 − 𝑭
For values of ℎ𝑖 and ℎ𝑜 see Table 6. Surface Conductance for Walls (ASHRAE
Handbook-Fundamentals, 2009).
𝐵𝑡𝑢
ℎ𝑖 = 1.46
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
ℎ𝑜 = 4.0
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
13
𝐵𝑡𝑢. 𝑖𝑛
𝑘𝑑𝑜𝑜𝑟 = 1.185
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
For 3” oak wood substitute the values from above to solve for 𝑈𝑑𝑜𝑜𝑟 .
1
𝑈𝑑𝑜𝑜𝑟 =
1 𝑥𝑜𝑎𝑘 𝑑𝑜𝑜𝑟 1
+ +
ℎ𝑖 𝑘𝑜𝑎𝑘 𝑑𝑜𝑜𝑟 ℎ𝑜
1
𝑈𝑑𝑜𝑜𝑟 =
1 3𝑖𝑛 1
𝐵𝑡𝑢 + 𝐵𝑡𝑢. 𝑖𝑛 + 𝐵𝑡𝑢
1.46 2 1.185 2 4.0
ℎ𝑟 − 𝑓𝑡 − 𝐹 ℎ𝑟 − 𝑓𝑡 − 𝐹 ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝑩𝒕𝒖
𝑼𝒅𝒐𝒐𝒓 = 𝟎. 𝟐𝟗
𝒉𝒓 − 𝒇𝒕𝟐 − 𝑭
𝐵𝑡𝑢
U-Factor (ℎ𝑟−𝑓𝑡 2 −𝐹)
Walls 0.719
Flooring 0.42
Door 0.29
This is a sensible heat transfer process. The heat transfer rate through opaque
𝑄𝑜𝑝𝑎𝑞𝑢𝑒 = 𝑈. 𝐴. 𝐶𝐿𝑇𝐷
Where
𝐴 = ℎ𝑒𝑎𝑡 𝑡𝑟𝑎𝑛𝑠𝑓𝑒𝑟 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑡ℎ𝑒 𝑠𝑢𝑟𝑓𝑎𝑐𝑒 𝑜𝑛 𝑡ℎ𝑒 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑡ℎ𝑒 𝑐𝑜𝑛𝑑𝑖𝑡𝑖𝑜𝑛𝑒𝑑 𝑠𝑝𝑎𝑐𝑒 (see Table 4)
𝐵𝑡𝑢
𝑄𝑛𝑜𝑟𝑡ℎ 𝑤𝑎𝑙𝑙 = (0.719 ) . (100.7𝑓𝑡 2 ). (20.9℉)
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
𝑄𝑛𝑜𝑟𝑡ℎ 𝑤𝑎𝑙𝑙 = 1502.71
ℎ𝑟
𝐵𝑡𝑢
𝑄𝑤𝑒𝑠𝑡 𝑤𝑎𝑙𝑙 = (0.719 ) . (76.385𝑓𝑡 2 ). (22.9℉)
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
𝑄𝑤𝑒𝑠𝑡 𝑤𝑎𝑙𝑙 = 1257.69
ℎ𝑟
15
𝐵𝑡𝑢
𝑄𝑠𝑜𝑢𝑡ℎ 𝑤𝑎𝑙𝑙 = (0.719 ) . (139.43𝑓𝑡 2 ). (20.9℉)
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
𝑄𝑠𝑜𝑢𝑡ℎ 𝑤𝑎𝑙𝑙 = 2095.23
ℎ𝑟
𝐵𝑡𝑢
𝑄𝑒𝑎𝑠𝑡 𝑤𝑎𝑙𝑙 = (0.719 ) . (138.80𝑓𝑡 2 ). (22.9℉)
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
𝑄𝑒𝑎𝑠𝑡 𝑤𝑎𝑙𝑙 = 2285.36
ℎ𝑟
𝐵𝑡𝑢
𝑄𝑑𝑜𝑜𝑟 = (0.29 ) . (17.21𝑓𝑡 2 ). (20.9℉)
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
𝑄𝑑𝑜𝑜𝑟 = 104.31 ℎ𝑟
𝐵𝑡𝑢
𝑄𝑓𝑙𝑜𝑜𝑟𝑖𝑛𝑔 = (0.42 ) . (154.92𝑓𝑡 2 ). (18.9℉)
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
𝑄𝑓𝑙𝑜𝑜𝑟𝑖𝑛𝑔 = 1229.75 ℎ𝑟
16
Heat transfer through transparent surface such as window, includes heat transfer
by conduction due to temperature difference across the window and heat transfer due to
Where
𝑆𝐶 = 𝑆ℎ𝑎𝑑𝑖𝑛𝑔 𝐶𝑜𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑡
The material for windows are single glaze clear glass with operable aluminum
frame. For approximate value of SC we need to use the formula 𝑆𝐻𝐺𝐶 = 𝑆𝐶 × 0.87; 0.75 =
Table 13. Cooling Load Factor (CLF) for glass with interior shading and located in north
𝐵𝑡𝑢 1𝑑𝑎𝑦
𝑄𝑡𝑟𝑎𝑛𝑠 = (10.76𝑓𝑡 2 )(712 𝑓𝑡 2 −𝑑𝑎𝑦 × 24ℎ𝑟𝑠)(0.86)(0.82)(2)
𝐵𝑡𝑢
𝑄𝑡𝑟𝑎𝑛𝑠 = 450.22 ℎ𝑟
𝐵𝑡𝑢 1𝑑𝑎𝑦
𝑄𝑡𝑟𝑎𝑛𝑠 = (10.76𝑓𝑡 2 )(1048 × )(0.86)(0.76)
𝑓𝑡 2 −𝑑𝑎𝑦 24ℎ𝑟𝑠
𝐵𝑡𝑢
𝑄𝑡𝑟𝑎𝑛𝑠 = 307.09 ℎ𝑟
19
components.
𝑄𝑠,𝑖𝑛𝑓 = 𝐶𝑠 𝑄𝑠 (𝑇𝑜 − 𝑇𝑖 )
Where
𝐵𝑡𝑢
𝐶𝑠 = 𝑎𝑖𝑟 𝑠𝑒𝑛𝑠𝑖𝑏𝑙𝑒 ℎ𝑒𝑎𝑡 𝑓𝑎𝑐𝑡𝑜𝑟 = 1.1
ℎ𝑟. 𝑓𝑡 3 . ℉
𝑄𝑆 = 𝑐𝑜𝑚𝑏𝑖𝑛𝑒𝑑 𝑖𝑛𝑓𝑖𝑙𝑡𝑟𝑎𝑡𝑖𝑜𝑛 𝑎𝑛𝑑 𝑣𝑒𝑛𝑡𝑖𝑙𝑎𝑡𝑖𝑜𝑛 𝑟𝑎𝑡𝑒 (𝑐𝑓𝑚)
𝑇𝑜 = 𝑜𝑢𝑡𝑑𝑜𝑜𝑟 𝑑𝑟𝑦 𝑏𝑢𝑙𝑏 𝑡𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 = 91.4℉
𝑉
𝑄𝑆 = (𝐴𝐶𝐻). (𝑐𝑓𝑚)
3600
Where
Table 15. Air Change per Hour (Flow Tech Inc., 2019)
1𝑓𝑡 3
𝑉 = 2370781.478𝑖𝑛3 × ( )
12𝑖𝑛
𝑉 = 1371.98𝑓𝑡 3
Substitute the values of ACH and volume to get the infiltration rate:
𝑉
𝑄𝑠 = (𝐴𝐶𝐻). 3600
1371.98𝑓𝑡 3
𝑄𝑠 = (6 𝑎𝑖𝑟 𝑐ℎ𝑎𝑛𝑔𝑒𝑠 𝑝𝑒𝑟 ℎ𝑜𝑢𝑟).
3600
𝑓𝑡 3 60𝑠
𝑄𝑠 = 2.286 × = 137 𝑐𝑓𝑚
𝑠 1𝑚𝑖𝑛
21
𝑄𝑠,𝑖𝑛𝑓 = 𝐶𝑠 𝑄𝑠 (𝑇𝑜 − 𝑇𝑖 )
𝐵𝑡𝑢
𝑄𝑠,𝑖𝑛𝑓 = (1.1 ) (137𝑐𝑓𝑚)(91.4 − 72.5)℉
ℎ𝑟. 𝑐𝑓𝑚. ℉
𝐵𝑡𝑢
𝑄𝑠,𝑖𝑛𝑓 = 2848.23
ℎ𝑟
𝑄𝑙,𝑖𝑛𝑓 = 𝐶𝑙 𝑄𝑠 (𝑊𝑜 − 𝑊𝑖 )
Where
𝐵𝑡𝑢
𝐶𝑙 = 𝑎𝑖𝑟 𝑙𝑎𝑡𝑒𝑛𝑡 ℎ𝑒𝑎𝑡 𝑓𝑎𝑐𝑡𝑜𝑟 = 4840
ℎ𝑟. 𝑐𝑓𝑚
Through interpolation we can get the outdoor and indoor humidity ratio from Table 13.
𝑊𝑜 = 0.0326814
𝑊𝑖 = 0.0172785
𝑄𝑙,𝑖𝑛𝑓 = 𝐶𝑙 𝑄𝑠 (𝑊𝑜 − 𝑊𝑖 )
𝐵𝑡𝑢
𝑄𝑙,𝑖𝑛𝑓 = (4840 ) (137𝑐𝑓𝑚)(0.0326814 − 0.0172785)
ℎ𝑟. 𝑐𝑓𝑚
𝐵𝑡𝑢
𝑄𝑙,𝑖𝑛𝑓 = 10213.35
ℎ𝑟
𝐵𝑡𝑢 𝐵𝑡𝑢
𝑄𝑖𝑛𝑓/𝑣𝑒𝑛 = 2848.23 + 10213.35
ℎ𝑟 ℎ𝑟
𝐵𝑡𝑢
𝑄𝑖𝑛𝑓/𝑣𝑒𝑛 = 13061.58 ℎ𝑟
The internal cooling load due to occupants consists of both sensible and latent
heat components. The full design capacity of the first floor is 12 persons. 10 are assumed
seated with very light work and the other 2 are moderately active in office work.
23
CLF for people is a function of the time people spending in the conditioned space,
and the time elapsed since first entering. CLF is equal to 1 if the space temperature is not
The full design capacity of the first floor is 12 persons. 10 are assumed seated with
very light work and the other 2 are moderately active in office work. The average sensible
Since the latent heat gain from the occupants is instantaneous the CLF for latent
Lighting adds sensible heat to the conditioned space. Since the heat transferred
Where
𝑆𝐹 = 𝑠𝑝𝑎𝑐𝑒 𝑓𝑟𝑎𝑐𝑡𝑖𝑜𝑛
The lighting usage factor is the ratio of wattage in use, for conditions under which
the load estimate is being made, to total installed wattage. For commercial applications
such as stores, the use factor is generally 1.0 (ASHRAE Handbook-Fundamentals, 2009).
The special allowance factor takes into account the heat from ballasts. This factor
is typically 1.2 for fluorescent lights and 1.0 for incandescent lights due to the lack of
Space Fraction
The first floor has one recessed fluorescent luminaire and has 40𝑊 wattage. Now
𝐵𝑡𝑢
𝑄𝑙𝑖𝑔ℎ𝑡𝑖𝑛𝑔 = 3.41 ℎ𝑟 . (40𝑤𝑎𝑡𝑡𝑠)(1)(1.2)(0.69)
𝑤𝑎𝑡𝑡𝑠
𝐵𝑡𝑢
𝑄𝑙𝑖𝑔ℎ𝑡𝑖𝑛𝑔 = 112.94
ℎ𝑟
Instantaneous sensible heat gain from equipment operated by electric motors such
𝑃
𝑄𝑒𝑚 = 2545. ( ) . (𝐹𝑈 ). (𝐹𝐿 )
𝐸𝑀
Where
𝐵𝑡𝑢/ℎ 0.054ℎ𝑝
𝑄𝑒𝑚 = 2545 .( ) . (1). (1)
ℎ𝑝 0.45
𝑄𝑒𝑚 = 305.4𝐵𝑡𝑢/ℎ𝑟
27
For appliances and equipment such as televisions, computers, printers etc., the
load is in the form of sensible heat transfer and is estimated based on the rated power
consumption.
1 LED Television 40
𝐵𝑡𝑢
𝑄𝑎𝑝𝑝𝑙𝑖𝑎𝑛𝑐𝑒𝑠 = 498𝑤𝑎𝑡𝑡𝑠 × 3.41 ℎ𝑟
𝑤𝑎𝑡𝑡𝑠
𝐵𝑡𝑢
𝑄𝑎𝑝𝑝𝑙𝑖𝑎𝑛𝑐𝑒𝑠 = 1698.18
ℎ𝑟
The total building load consists of heat transferred through the envelope (walls,
roof, floor, windows, doors etc.) and heat generated by occupants, equipment, and lights.
The total heat load is needed to be cooled by the air-conditioner. It is needed to be able
to choose the proper size of an air-conditioner for the first floor of Barangay Hall of
The selection of air-conditioner for the first floor of Barangay Hall varies from the
required cooling load. The total heat load needs to convert to horsepower in order to select
operation.
𝐵𝑡𝑢 8 ℎ𝑜𝑢𝑟𝑠
𝑅𝑒𝑞𝑢𝑖𝑟𝑒𝑑 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐿𝑜𝑎𝑑 = 29444.46 ×
ℎ𝑟 24 ℎ𝑜𝑢𝑟𝑠
𝐵𝑡𝑢 1𝑇𝑅
𝑅𝑒𝑞𝑢𝑖𝑟𝑒𝑑 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐿𝑜𝑎𝑑 = 9814.82 ×
ℎ𝑟 12000 𝐵𝑡𝑢
ℎ𝑟
An 1 𝑇𝑅 Air conditioner can remove the heat per hour from the 1st floor of the
Barangay Hall of Brgy. Poblacion 2-B because the capacity of the air conditioner must be
We consider the room is not affected on sunlight at all directions because of the
partitions, see the figure below for the sun effect directions.
2
1𝑓𝑡 2
𝐴𝑤𝑒𝑠𝑡 𝑤𝑎𝑙𝑙 = 14350.144𝑖𝑛 × ( )
12𝑖𝑛
1𝑓𝑡 2
𝐴𝑠𝑜𝑢𝑡ℎ 𝑤𝑎𝑙𝑙 = 20077.76𝑖𝑛2 × ( )
12𝑖𝑛
𝐴𝑒𝑎𝑠𝑡 𝑤𝑎𝑙𝑙 = (𝐿 × ℎ)
2
1𝑓𝑡 2
𝐴𝑒𝑎𝑠𝑡 𝑤𝑎𝑙𝑙 = 15899.35𝑖𝑛 × ( )
12𝑖𝑛
𝐴𝑤𝑖𝑛𝑑𝑜𝑤 = (𝑊𝑤 × ℎ𝑤 )
1𝑓𝑡 2
𝐴𝑤𝑖𝑛𝑑𝑜𝑤 = 1549.21𝑖𝑛2 × ( )
12𝑖𝑛
𝐴𝑤𝑖𝑛𝑑𝑜𝑤 = 10.76𝑓𝑡 2
32
𝐴𝑐𝑒𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 = (𝐿 × 𝑊)
1𝑓𝑡 2
𝐴𝑐𝑒𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 = 28265.52𝑖𝑛2 × ( )
12𝑖𝑛
𝐴𝑐𝑒𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 = 196.29𝑓𝑡 2
Where:
𝑊𝑤 = 𝑤𝑖𝑑𝑡ℎ 𝑜𝑓 𝑤𝑖𝑛𝑑𝑜𝑤
Windows 10.76
Ceiling/Roof 196.29
𝑈 = 1/𝑅
1
𝑈=
1 𝑥1 𝑥2 1
+ + +
ℎ𝑖 𝑘1 𝑘2 ℎ𝑜
The materials, thickness, and surface conductance for the 1st floor walls are the
same with the conference room at 2nd floor. So the 𝑈𝑤𝑎𝑙𝑙 of 1st floor is the same as the
conference room.
𝐵𝑡𝑢
𝑈𝑤𝑎𝑙𝑙 = 0.719
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
34
1
𝑈𝑐𝑒𝑖𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 =
ℎ𝑟 − 𝑓𝑡 2 − ℉
3.48 𝐵𝑡𝑢
𝐵𝑡𝑢
𝑈𝑐𝑒𝑖𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 = 0.287
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
U-Factor ( )
ℎ𝑟−𝑓𝑡 2 −𝐹
Walls 0.719
Ceiling/Roof 0.287
This is a sensible heat transfer process. The heat transfer rate through opaque
𝑄𝑜𝑝𝑎𝑞𝑢𝑒 = 𝑈. 𝐴. 𝐶𝐿𝑇𝐷
35
Where
𝐴 = ℎ𝑒𝑎𝑡 𝑡𝑟𝑎𝑛𝑠𝑓𝑒𝑟 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑡ℎ𝑒 𝑠𝑢𝑟𝑓𝑎𝑐𝑒 𝑜𝑛 𝑡ℎ𝑒 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑡ℎ𝑒 𝑐𝑜𝑛𝑑𝑖𝑡𝑖𝑜𝑛𝑒𝑑 𝑠𝑝𝑎𝑐𝑒 (see Table 20)
𝐵𝑡𝑢
𝑄𝑤𝑒𝑠𝑡 𝑤𝑎𝑙𝑙 = (0.719 ) . (76.385𝑓𝑡 2 ). (22.9℉)
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
𝑄𝑤𝑒𝑠𝑡 𝑤𝑎𝑙𝑙 = 1257.69
ℎ𝑟
𝐵𝑡𝑢
𝑄𝑠𝑜𝑢𝑡ℎ 𝑤𝑎𝑙𝑙 = (0.719 ) . (99.65𝑓𝑡 2 ). (20.9℉)
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
𝑄𝑠𝑜𝑢𝑡ℎ 𝑤𝑎𝑙𝑙 = 1497.45
ℎ𝑟
𝐵𝑡𝑢
𝑄𝑒𝑎𝑠𝑡 𝑤𝑎𝑙𝑙 = (0.719 ) . (110.41𝑓𝑡 2 ). (22.9℉)
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
𝑄𝑒𝑎𝑠𝑡 𝑤𝑎𝑙𝑙 = 2285.36
ℎ𝑟
36
𝐵𝑡𝑢
𝑄𝑐𝑒𝑖𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 = (0.287 ) . (196.29𝑓𝑡 2 ). (27.9℉)
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
𝑄𝑐𝑒𝑖𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 = 1571.75
ℎ𝑟
Opaque Surfaces
𝐵𝑡𝑢
Heat Gain ( )
ℎ𝑟
Heat transfer through transparent surface such as window, includes heat transfer
by conduction due to temperature difference across the window and heat transfer due to
Where
𝑆𝐶 = 𝑆ℎ𝑎𝑑𝑖𝑛𝑔 𝐶𝑜𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑡
See Table 11 for the value of Solar Heat Gain Factor (SHGF) at windows facing
towards west.
𝐵𝑡𝑢
SHGF for West Windows = 1048
𝑓𝑡 2 −𝑑𝑎𝑦
The materials, thickness and type of glass windows used in the conference room
are the same as the windows in the first floor. So 𝑺𝒉𝒂𝒅𝒊𝒏𝒈 𝑪𝒐𝒆𝒇𝒇𝒊𝒄𝒊𝒆𝒏𝒕 = 𝟎. 𝟖𝟔.
See Table 13 for the value of Cooling Load Factor (CLF) when the direction the
sunlit window is facing is west at 15 h solar time. So CLF for West Wall = 𝟎. 𝟕𝟐
Now we can get the heat gain through fenestration on the window
𝐵𝑡𝑢 1𝑑𝑎𝑦
𝑄𝑡𝑟𝑎𝑛𝑠 = 10.76𝑓𝑡 2 . (1048 × ) . (0.86). (0.72)
𝑓𝑡 2− 𝑑𝑎𝑦 24ℎ𝑟𝑠
𝐵𝑡𝑢
𝑄𝑡𝑟𝑎𝑛𝑠 = 290.93 ℎ𝑟
components.
38
𝑄𝑠,𝑖𝑛𝑓 = 𝐶𝑠 𝑄𝑠 (𝑇𝑜 − 𝑇𝑖 )
Where
𝐵𝑡𝑢
𝐶𝑠 = 𝑎𝑖𝑟 𝑠𝑒𝑛𝑠𝑖𝑏𝑙𝑒 ℎ𝑒𝑎𝑡 𝑓𝑎𝑐𝑡𝑜𝑟 = 1.1
ℎ𝑟. 𝑓𝑡 3 . ℉
𝑉
𝑄𝑆 = (𝐴𝐶𝐻). (𝑐𝑓𝑚)
3600
Where
Table 24. Air Change per Hour (Flow Tech Inc., 2019)
𝑉 = 𝐿×𝑊×ℎ
1𝑓𝑡 3
3
𝑉 = 3003883.137𝑖𝑛 × ( )
12𝑖𝑛
𝑉 = 1738.329𝑓𝑡 3
Substitute the values of ACH and volume to get the infiltration rate:
𝑉
𝑄𝑠 = (𝐴𝐶𝐻). 3600
1738.329𝑓𝑡 3
𝑄𝑠 = (8 𝑎𝑖𝑟 𝑐ℎ𝑎𝑛𝑔𝑒𝑠 𝑝𝑒𝑟 ℎ𝑜𝑢𝑟).
3600
𝑓𝑡 3 60𝑠
𝑄𝑠 = 3.86 × = 231.7 𝑐𝑓𝑚
𝑠 1𝑚𝑖𝑛
𝑄𝑠,𝑖𝑛𝑓 = 𝐶𝑠 𝑄𝑠 (𝑇𝑜 − 𝑇𝑖 )
𝐵𝑡𝑢
𝑄𝑠,𝑖𝑛𝑓 = (1.1 ) (231.7𝑐𝑓𝑚)(91.4 − 72.5)℉
ℎ𝑟. 𝑐𝑓𝑚. ℉
𝐵𝑡𝑢
𝑄𝑠,𝑖𝑛𝑓 = 4817.043
ℎ𝑟
40
𝑄𝑙,𝑖𝑛𝑓 = 𝐶𝑙 𝑄𝑠 (𝑊𝑜 − 𝑊𝑖 )
Where
𝐵𝑡𝑢
𝐶𝑙 = 𝑎𝑖𝑟 𝑙𝑎𝑡𝑒𝑛𝑡 ℎ𝑒𝑎𝑡 𝑓𝑎𝑐𝑡𝑜𝑟 = 4840
ℎ𝑟. 𝑐𝑓𝑚
Through interpolation we can get the outdoor and indoor humidity ratio from Table 13.
𝑊𝑜 = 0.0326814
𝑊𝑖 = 0.0172785
𝑄𝑙,𝑖𝑛𝑓 = 𝐶𝑙 𝑄𝑠 (𝑊𝑜 − 𝑊𝑖 )
𝐵𝑡𝑢
𝑄𝑙,𝑖𝑛𝑓 = (4840 ) (231.7𝑐𝑓𝑚)(0.0326814 − 0.0172785)
ℎ𝑟. 𝑐𝑓𝑚
𝐵𝑡𝑢
𝑄𝑙,𝑖𝑛𝑓 = 17273.24
ℎ𝑟
𝐵𝑡𝑢 𝐵𝑡𝑢
𝑄𝑖𝑛𝑓/𝑣𝑒𝑛 = 4817.043 + 17273.24
ℎ𝑟 ℎ𝑟
𝐵𝑡𝑢
𝑄𝑖𝑛𝑓/𝑣𝑒𝑛 = 22090.283 ℎ𝑟
41
The internal cooling load due to occupants consists of both sensible and latent
heat components. The full design capacity of the conference room is 18 persons. 10 are
assumed seated with very light work and the other 8 are moderately active in office work.
CLF for people is a function of the time people spending in the conditioned space,
and the time elapsed since first entering. CLF is equal to 1 if the space temperature is not
Refer to Table 17 for the values of sensible and latent heat given off by the
humans. The full design capacity of the first floor is 18 persons. 10 are assumed seated
with very light work and the other 2 are moderately active in office work. The average
Since the latent heat gain from the occupants is instantaneous the CLF for latent
Lighting adds sensible heat to the conditioned space. Since the heat transferred
Where
The lighting usage factor is the ratio of wattage in use, for conditions under which
the load estimate is being made, to total installed wattage. For commercial applications
such as stores, the use factor is generally 1.0 (ASHRAE Handbook-Fundamentals, 2009).
The special allowance factor takes into account the heat from ballasts. This factor
is typically 1.2 for fluorescent lights and 1.0 for incandescent lights due to the lack of
Space Fraction
Refer to Table 18 for space fraction for recessed fluorescent luminaire. The first
floor has two recessed fluorescent luminaire and has 40𝑊 wattage each.
𝐵𝑡𝑢
𝑄𝑙𝑖𝑔ℎ𝑡𝑖𝑛𝑔 = 3.41 ℎ𝑟 . (80𝑤𝑎𝑡𝑡𝑠)(1)(1.2)(0.69)
𝑤𝑎𝑡𝑡𝑠
𝐵𝑡𝑢
𝑄𝑙𝑖𝑔ℎ𝑡𝑖𝑛𝑔 = 225.8784
ℎ𝑟
44
Instantaneous sensible heat gain from equipment operated by electric motors such
𝑃
𝑄𝑒𝑚 = 2545. ( ) . (𝐹𝑈 ). (𝐹𝐿 )
𝐸𝑀
Where
𝐵𝑡𝑢/ℎ 0.1ℎ𝑝
𝑄𝑒𝑚 = 2545 .( ) . (1). (1)
ℎ𝑝 0.55
For appliances and equipment such as televisions, computers, printers etc., the
load is in the form of sensible heat transfer and is estimated based on the rated power
consumption.
𝐵𝑡𝑢
𝑄𝑎𝑝𝑝𝑙𝑖𝑎𝑛𝑐𝑒𝑠 = 628𝑤𝑎𝑡𝑡𝑠 × 3.41 ℎ𝑟
𝑤𝑎𝑡𝑡𝑠
𝐵𝑡𝑢
𝑄𝑎𝑝𝑝𝑙𝑖𝑎𝑛𝑐𝑒𝑠 = 2141.48
ℎ𝑟
The total building load consists of heat transferred through the envelope (walls,
roof, floor, windows, doors etc.) and heat generated by occupants, equipment, and lights.
The total heat load is needed to be cooled by the air-conditioner. It is needed to be able
to choose the proper size of an air-conditioner for the conference room of Barangay Hall
The selection of air-conditioner for the Conference Room at 2nd floor of Barangay
Hall varies from the required cooling load. The total heat load needs to convert to
horsepower in order to select appropriate size of air conditioner. The air conditioner is
𝐵𝑡𝑢 8 ℎ𝑜𝑢𝑟𝑠
𝑅𝑒𝑞𝑢𝑖𝑟𝑒𝑑 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐿𝑜𝑎𝑑 = 39464.55 ×
ℎ𝑟 24 ℎ𝑜𝑢𝑟𝑠
𝐵𝑡𝑢 1𝑇𝑅
𝑅𝑒𝑞𝑢𝑖𝑟𝑒𝑑 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐿𝑜𝑎𝑑 = 13154.85 ×
ℎ𝑟 12000 𝐵𝑡𝑢
ℎ𝑟
An 1.5 𝑇𝑅 Air conditioner can remove the heat per hour from the Conference Room
at 2ND Floor of the Barangay Hall of Brgy. Poblacion 2-B because the capacity of the air
We consider the room is not affected on sunlight at all directions because of the
partitions, see the figure below for the sun effect directions.
2
1𝑓𝑡 2
𝐴𝑤𝑒𝑠𝑡 𝑤𝑎𝑙𝑙 = 12548.598𝑖𝑛 × ( )
12𝑖𝑛
𝐴𝑛𝑜𝑟𝑡ℎ 𝑤𝑎𝑙𝑙 = (𝐿 × ℎ)
2
1𝑓𝑡 2
𝐴𝑛𝑜𝑟𝑡ℎ 𝑤𝑎𝑙𝑙 = 10457.16𝑖𝑛 × ( )
12𝑖𝑛
𝐴𝑤𝑖𝑛𝑑𝑜𝑤 = (𝑊𝑤 × ℎ𝑤 )
1𝑓𝑡 2
𝐴𝑤𝑖𝑛𝑑𝑜𝑤 = 1549.21𝑖𝑛2 × ( )
12𝑖𝑛
𝐴𝑤𝑖𝑛𝑑𝑜𝑤 = 10.76𝑓𝑡 2
𝐴𝑐𝑒𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 = (𝐿 × 𝑊)
1𝑓𝑡 2
𝐴𝑐𝑒𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 = 11619.072𝑖𝑛2 × ( )
12𝑖𝑛
𝐴𝑐𝑒𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 = 80.69𝑓𝑡 2
50
Where:
𝑊𝑤 = 𝑤𝑖𝑑𝑡ℎ 𝑜𝑓 𝑤𝑖𝑛𝑑𝑜𝑤
Windows 10.76
Ceiling/Roof 80.69
Table 28. List of Surface Area for Office of the Punong Barangay
𝑈 = 1/𝑅
1
𝑈=
1 𝑥1 𝑥2 1
+ + +
ℎ𝑖 𝑘1 𝑘2 ℎ𝑜
51
The materials, thickness, and surface conductance for the 1st floor walls are the
same with the office of the punong barangay at 2nd floor. So the 𝑈𝑤𝑎𝑙𝑙 of 1st floor is the
𝐵𝑡𝑢
𝑈𝑤𝑎𝑙𝑙 = 0.719
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
The materials, thickness and surface conductance for the conference room is the
same as the office of the Punong Barangay. So the 𝑈𝑐𝑒𝑖𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 of office of the Punong
1
𝑈𝑐𝑒𝑖𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 =
ℎ𝑟 − 𝑓𝑡 2 − ℉
3.48 𝐵𝑡𝑢
𝐵𝑡𝑢
𝑈𝑐𝑒𝑖𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 = 0.287
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
U-Factor (ℎ𝑟−𝑓𝑡 2 −𝐹)
Walls 0.719
Ceiling/Roof 0.287
This is a sensible heat transfer process. The heat transfer rate through opaque
𝑄𝑜𝑝𝑎𝑞𝑢𝑒 = 𝑈. 𝐴. 𝐶𝐿𝑇𝐷
Where
𝐴 = ℎ𝑒𝑎𝑡 𝑡𝑟𝑎𝑛𝑠𝑓𝑒𝑟 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑡ℎ𝑒 𝑠𝑢𝑟𝑓𝑎𝑐𝑒 𝑜𝑛 𝑡ℎ𝑒 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑡ℎ𝑒 𝑐𝑜𝑛𝑑𝑖𝑡𝑖𝑜𝑛𝑒𝑑 𝑠𝑝𝑎𝑐𝑒 (see Table 20)
𝐵𝑡𝑢
𝑄𝑤𝑒𝑠𝑡 𝑤𝑎𝑙𝑙 = (0.719 ) . (87.14𝑓𝑡 2 ). (22.9℉)
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
𝑄𝑤𝑒𝑠𝑡 𝑤𝑎𝑙𝑙 = 1434.77
ℎ𝑟
𝐵𝑡𝑢
𝑄𝑛𝑜𝑟𝑡ℎ 𝑤𝑎𝑙𝑙 = (0.719 ) . (72.62𝑓𝑡 2 ). (20.9℉)
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
𝑄𝑛𝑜𝑟𝑡ℎ 𝑤𝑎𝑙𝑙 = 1091.27
ℎ𝑟
𝐵𝑡𝑢
𝑄𝑐𝑒𝑖𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 = (0.287 ) . (80.69𝑓𝑡 2 ). (27.9℉)
ℎ𝑟 − 𝑓𝑡 2 − 𝐹
𝐵𝑡𝑢
𝑄𝑐𝑒𝑖𝑙𝑖𝑛𝑔/𝑟𝑜𝑜𝑓 = 646.11
ℎ𝑟
53
Heat transfer through transparent surface such as window, includes heat transfer
by conduction due to temperature difference across the window and heat transfer due to
Where
𝑆𝐶 = 𝑆ℎ𝑎𝑑𝑖𝑛𝑔 𝐶𝑜𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑡
See Table 11 for the value of Solar Heat Gain Factor (SHGF) at windows facing
towards west.
𝐵𝑡𝑢
SHGF for West Windows = 1048 𝑓𝑡 2 −𝑑𝑎𝑦
54
The materials, thickness and type of glass windows used in the conference room
are the same as the windows in the office of the Punong Barangay.
See Table 13 for the value of Cooling Load Factor (CLF) when the direction the
sunlit window is facing is west at 15 h solar time. So CLF for West Wall = 𝟎. 𝟕𝟐
Now we can get the heat gain through fenestration on the window
𝐵𝑡𝑢 1𝑑𝑎𝑦
𝑄𝑡𝑟𝑎𝑛𝑠 = 10.76𝑓𝑡 2 . (1048 × ) . (0.86). (0.72)
𝑓𝑡 2− 𝑑𝑎𝑦 24ℎ𝑟𝑠
𝐵𝑡𝑢
𝑄𝑡𝑟𝑎𝑛𝑠 = 290.93
ℎ𝑟
components.
𝑄𝑠,𝑖𝑛𝑓 = 𝐶𝑠 𝑄𝑠 (𝑇𝑜 − 𝑇𝑖 )
55
Where
𝐵𝑡𝑢
𝐶𝑠 = 𝑎𝑖𝑟 𝑠𝑒𝑛𝑠𝑖𝑏𝑙𝑒 ℎ𝑒𝑎𝑡 𝑓𝑎𝑐𝑡𝑜𝑟 = 1.1
ℎ𝑟. 𝑓𝑡 3 . ℉
𝑉
𝑄𝑆 = (𝐴𝐶𝐻). (𝑐𝑓𝑚)
3600
Where
Table 30. Air Change per Hour (Flow Tech Inc., 2019)
Figure 24. Length, Width and Height for Office of the Punong Barangay
𝑉 = 𝐿×𝑊×ℎ
1𝑓𝑡 3
3
𝑉 = 1234782.02𝑖𝑛 × ( )
12𝑖𝑛
𝑉 = 714.57𝑓𝑡 3
Substitute the values of ACH and volume to get the infiltration rate:
𝑉
𝑄𝑠 = (𝐴𝐶𝐻). 3600
714.57𝑓𝑡 3
𝑄𝑠 = (8 𝑎𝑖𝑟 𝑐ℎ𝑎𝑛𝑔𝑒𝑠 𝑝𝑒𝑟 ℎ𝑜𝑢𝑟).
3600
𝑓𝑡 3 60𝑠
𝑄𝑠 = 1.59 × = 95.276 𝑐𝑓𝑚
𝑠 1𝑚𝑖𝑛
𝑄𝑠,𝑖𝑛𝑓 = 𝐶𝑠 𝑄𝑠 (𝑇𝑜 − 𝑇𝑖 )
𝐵𝑡𝑢
𝑄𝑠,𝑖𝑛𝑓 = (1.1 ) (95.276𝑐𝑓𝑚)(91.4 − 72.5)℉
ℎ𝑟. 𝑐𝑓𝑚. ℉
𝐵𝑡𝑢
𝑄𝑠,𝑖𝑛𝑓 = 1980.79
ℎ𝑟
57
𝑄𝑙,𝑖𝑛𝑓 = 𝐶𝑙 𝑄𝑠 (𝑊𝑜 − 𝑊𝑖 )
Where
𝐵𝑡𝑢
𝐶𝑙 = 𝑎𝑖𝑟 𝑙𝑎𝑡𝑒𝑛𝑡 ℎ𝑒𝑎𝑡 𝑓𝑎𝑐𝑡𝑜𝑟 = 4840
ℎ𝑟. 𝑐𝑓𝑚
Through interpolation we can get the outdoor and indoor humidity ratio from Table 13.
𝑊𝑜 = 0.0326814
𝑊𝑖 = 0.0172785
𝑄𝑙,𝑖𝑛𝑓 = 𝐶𝑙 𝑄𝑠 (𝑊𝑜 − 𝑊𝑖 )
𝐵𝑡𝑢
𝑄𝑙,𝑖𝑛𝑓 = (4840 ) (95.276𝑐𝑓𝑚)(0.0326814 − 0.0172785)
ℎ𝑟. 𝑐𝑓𝑚
𝐵𝑡𝑢
𝑄𝑙,𝑖𝑛𝑓 = 7102.83
ℎ𝑟
𝐵𝑡𝑢 𝐵𝑡𝑢
𝑄𝑖𝑛𝑓/𝑣𝑒𝑛 = 1980.79 + 7102.83
ℎ𝑟 ℎ𝑟
𝐵𝑡𝑢
𝑄𝑖𝑛𝑓/𝑣𝑒𝑛 = 9083.62 ℎ𝑟
58
The internal cooling load due to occupants consists of both sensible and latent
heat components. The full design capacity of the office of the Punong Barangay is 8
persons. 4 are assumed seated with very light work and the other 4 are moderately active
in office work.
CLF for people is a function of the time people spending in the conditioned space,
and the time elapsed since first entering. CLF is equal to 1 if the space temperature is not
Refer to Table 17 for the values of sensible and latent heat given off by the
humans. The full design capacity of the first floor is 8 persons. 4 are assumed seated with
very light work and the other 4 are moderately active in office work. The average sensible
Since the latent heat gain from the occupants is instantaneous the CLF for latent
Lighting adds sensible heat to the conditioned space. Since the heat transferred
Where
60
The lighting usage factor is the ratio of wattage in use, for conditions under which
the load estimate is being made, to total installed wattage. For commercial applications
such as stores, the use factor is generally 1.0 (ASHRAE Handbook-Fundamentals, 2009).
The special allowance factor takes into account the heat from ballasts. This factor
is typically 1.2 for fluorescent lights and 1.0 for incandescent lights due to the lack of
Space Fraction
Refer to Table 18 for space fraction for recessed fluorescent luminaire. The office
of the Punong Barangay has one recessed fluorescent luminaire and has 20𝑊 wattage
each.
𝐵𝑡𝑢
𝑄𝑙𝑖𝑔ℎ𝑡𝑖𝑛𝑔 = 3.41 ℎ𝑟 . (40𝑤𝑎𝑡𝑡𝑠)(1)(1.2)(0.69)
𝑤𝑎𝑡𝑡𝑠
𝐵𝑡𝑢
𝑄𝑙𝑖𝑔ℎ𝑡𝑖𝑛𝑔 = 112.94
ℎ𝑟
61
Instantaneous sensible heat gain from equipment operated by electric motors such
𝑃
𝑄𝑒𝑚 = 2545. ( ) . (𝐹𝑈 ). (𝐹𝐿 )
𝐸𝑀
Where
𝐵𝑡𝑢/ℎ 0.05ℎ𝑝
𝑄𝑒𝑚 = 2545 .( ) . (1). (1)
ℎ𝑝 0.55
For appliances and equipment such as televisions, computers, printers etc., the
load is in the form of sensible heat transfer and is estimated based on the rated power
consumption.
1 LED Television 40
𝐵𝑡𝑢
𝑄𝑎𝑝𝑝𝑙𝑖𝑎𝑛𝑐𝑒𝑠 = 119𝑤𝑎𝑡𝑡𝑠 × 3.41 ℎ𝑟
𝑤𝑎𝑡𝑡𝑠
𝐵𝑡𝑢
𝑄𝑎𝑝𝑝𝑙𝑖𝑎𝑛𝑐𝑒𝑠 = 405.79
ℎ𝑟
The total building load consists of heat transferred through the envelope (walls,
roof, floor, windows, doors etc.) and heat generated by occupants, equipment, and lights.
The total heat load is needed to be cooled by the air-conditioner. It is needed to be able
to choose the proper size of an air-conditioner for the Office of the Punong Barangay at
Table 33. Total Heat Load for Office of the Punong Barangay
The selection of air-conditioner for the Office of the Punong Barangay at 2nd floor
of Barangay Hall varies from the required cooling load. The total heat load needs to
convert to horsepower in order to select appropriate size of air conditioner. The air
𝐵𝑡𝑢 8 ℎ𝑜𝑢𝑟𝑠
𝑅𝑒𝑞𝑢𝑖𝑟𝑒𝑑 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐿𝑜𝑎𝑑 = 16696.79 ×
ℎ𝑟 24 ℎ𝑜𝑢𝑟𝑠
𝐵𝑡𝑢 1𝑇𝑅
𝑅𝑒𝑞𝑢𝑖𝑟𝑒𝑑 𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐿𝑜𝑎𝑑 = 5565.6 ×
ℎ𝑟 12000 𝐵𝑡𝑢
ℎ𝑟
An 1 𝑇𝑅 Air conditioner can remove the heat per hour from the Office of the Punong
Barangay at 2ND Floor of the Barangay Hall of Brgy. Poblacion 2-B because the capacity
of the air conditioner must be greater than the required cooling load.
64
REFERENCES
[4] Flow Tech, Inc. (2019). Air Change per Hour Table. ABB-HVAC. Retrieved from
www.flowtechinc.com
[5] World Weather Online. (13 March 2019). Maximum Temperature, Maragondon,
Cavite (2009-2018), Max, Min, and Average Temperature (°C). Accessed from
https://www.worldweatheronline.com/maragondon-weather-averages/cavite/ph
65
APPENDICES
66
Appendix 1
Appendix 2
2009)
67
Appendix 3
Appendix 4
Appendix 5
Appendix 6
Appendix 6
Appendix 7
Appendix 8
Appendix 9
Appendix 10
Appendix 11