1. Overview DS6-K5BMCComputer interlocking,It is a new system jointly
developed by our institute and Japan Jingsan Company.systemThe
interlocking machine and the input and output circuit adopt the Jingsan
company'sK5BMCType products. This product is all related to safetyAll
information processing and transmission components are taken in
accordance with the "fail-safe" principle.2Heavy structure design.
Interlocking processing unit takes doubleCPUShared clock, synchronous
comparison of data bus signals occursWhen the error is made, the
output is reversed safely and has "fail-safe" performance.
Interlocking2Heavy systemRedundancy, data exchange through high-
speed channels, guaranteed2Heavy-duty synchronous operation for
continuous cuttingchange. The input and output circuit adopts an
electronic terminal produced by Jingsan Company, and the circuit
is2Heavy work in parallel, withThere is "fail-safe" performance. Both
input and output are static. Eliminated the "static-dynamic"
transformationThe circuit simplifies the design of the relay interface
circuit. DS6-K5BMCThe communication between the microcomputers in
the system is all connected by fiber optic cable.Improve system anti-
jammingCapability and lightning protection ensure high stability of the
system. DS6-K5BMCSystem interlocking software in our hospitalDS6The
system is based on the system interlocking software,The core program
and data structure of the interlocking software tested by the Ministry of
Railways computer interlocking inspection station are retained.Ensure
that the interlocking function of the new system meets the
requirements of the computer interlocking technical conditions of the
station in China. Control display and supervisionThe application software
of the measuring machine is undertaken by our
hospital.WINDOWS2000The operating platform has been redeveloped
so thatThe operation interface has been improved and the function has
been further improved. DS6-K5BMCThe system has developed the
application software of our institute and the high production of the
Japanese Jingsan company.The combination of reliability and high
security of dedicated computer equipment makes the system safe,
reliable andApplicability has reached a new level.

3
2. Hardware system composition K5BMCThe computer interlock system is
controlled by the console,Electric maintenance station,Interlocking
machine,Input and output interface(in K5BMCIn the system, the input
and output circuits are called "electronic terminals"., represented by the
character "ET")Microcomputer detectionAnd the power supply consists
of six parts. As shown1Shown. The console consists of the operation and
indicating equipment for the operation of the two-machine and the
station attendant. eachTwo serial communication interface boards
connected by optical cables are installed in one control displayINIOCard
for the same interlockMachine2Heavy communication. The control and
display machines are alternate with each other. Controlled display
between the two machines through the control boxConversion. The
operating device can be selected from a button control panel, a mouse
or a digitizer. Display device optional graphicsA display or unit
representation disk. The electrical maintenance station equipment
includes: a monitor, a keyboard, a display, and a printer. Two inside the
monitorCable communication serial communication interface
boardINIOCard for use with interlocking machines2Heavy
communication, from interlocking doubleThe machine obtains the
interlock system maintenance information. The monitoring machine
obtains the mode from the microcomputer detecting the front-end
machine through the serial communication interface.Proximity detection
information. Electrical maintenance personnel can query or print out via
keyboard, monitor, printerVarious types of monitoring information.
Interlocking machine2Reorganize and run in parallel in master-slave
mode. Established through the parallel interface between the two
systemsHigh-speed channel exchange information, realized2Heavy
synchronization and switching. Each pair of interlocking machines uses a
pair of optical cablesAfter the optical splitter is connected with the
control display, each of the interlocks can communicate with the two
control displays.Each pair of interlocking machines is connected to two
optical communication interfaces of the monitoring machine by a pair of
optical cables, each of which is interlocked.The maintenance information
is sent to the monitoring machine separately. Each interlock
has5Communication interfaces connecting electronic
terminals,WeighETReturn line1 to 5. Each communication interface can
be connected to an electronic terminal rack. K5BMCThe system switch

4
quantity input and output interface adopts the electronic terminal
machine produced by Jingsan Company.(referred toET).Electronic
terminal circuit has2Heavy,2The input circuit of the heavy system
obtains the input letter from the same set of contacts of the
relayNumber, issued separately to the interlock2Heavy. Interlocking2The
output of the heavy system is sent to the electronic terminal
separately2Heavy. ElectricitySubterminal2The heavy output is
connected in parallel with the load.(see picture12: K5BMCInput and
output signal connection diagram) K5BMCPower supply by a setupsAnd
two-way DC24VRegulated power supply.upsInput by signalThe power
supply screen provides a separate communication220VPower supply.
Two way DC24VOne of the power sources is called logic24V.(with
symbolL24Express)Interlocking machineAnd inside the electronic
terminalDC-DCConversion circuit generation5VVoltage for the logic
circuit to work. Another DC24VInterface24V,(with symbolI24Express),
for the output circuit of the electronic terminal to drive the relay and the
inputInto the circuit to collect the representation information.

5
6
2.1 interlocking machine K5BMCInterlocking double machine (1Department
and2Department) installed in one800×330mmInside the rack. Two
seriesThe composition is exactly the same. Each lineF486-
4InterlockingCPUBoard, FSIO1Electronic terminal and host computer
interfaceboard,FSIO2The electronic terminal communication expansion
interface board is composed of three circuit boards.Each rack has two
free slotsSlots that can be plugged into interface boards that
communicate with other systems when needed (eg withCTCSystem
communicationOPUBoard, etc.Not used in this system). Passing the
bottom plate between the platesVMEBus interconnection.
Interlocking1Power and interlock2The power supply is two input DC24V,
output DC5VDC/DCpower supply. Interlocking1Department and
interlock2System logic5Vpower supply. Interlocking frame (front)

the back of the interlocking rack, there are two photoelectric conversion
boards in each system: EXT F107PwithF107 (P).EXT107PBoard
isFSIO2The photoelectric conversion board is used for the cable
connection between the interlocking machine and the electronic
terminal. F107(P) board isFSIO1Board photoelectric conversion
board,Optical cable connection between the interlocking machine and
the electronic terminalConnection and cable connection between the
interlocking machine and the display

7
2.1.1 F486-4board. F486-4Is the master of the interlocking
machineCPUboard.There is a piece in each of the two systems.F486-
4board,Installed in the jointThe first slot on the left side of each
frame of the lock frame (front). Function of F486-4: complete
interlocking logic operation; communication between two systems
and switching control;Significant inspection; system fault detection
and alarm, stop operation when abnormal, output reverse safety. The
hypervisor is stored inROMin. Interlocking program and station data
are stored inRAMin. Interlocking machineAfter each power outage,
you need to store the interlock program and station data.ICCard
insertionICCard slot, fromICcardRe-read the interlock program and
data before the system can be put into operation.

The functions of the F486-4 board panel indicators and switches are
described below. D7=Off: The system is running normally; D7=Bright:
The system is down; inWhen D7 is off, D0~D6Status definition:
D0=Bright: This board is1Department, D0=Off: This board is2system;
D1=Bright: This board is the main system, D1=Off: This board is the
slave system; D2=Bright: The two systems are out of sync, D2=Off:
two systems are synchronized; D3=Bright: Execute control function,
D3=Off: Control function stops; D4=Bright: APLStart execution,
D4=Off: APLStop execution; APL: Application Logic D5=Reservation
D6=Bright: The data connection is successful, D6=Off: The data
connection fails. inD7 In the case of lighting, D0~D6Indicates an error
code. See the table1. WT=Flash: Watchdog status; B0=extue: VMEBus
error, B0=light: no error; FLH, FLL = flash: bus clock status;
BER=Bright: ExternalRAMAccess bus error; MI, DC, WR, IM, VM, II, VI:
indicates the working status of the hardware, See the table2. SW1,
SW2: Operation mode setting switch, two switches must be set Set to
the same state. SW1, SW2=1: normal mode, SW1, SW2=F: debugging
mode; SW1, SW2Other states are not allowed to be set. SW3: Total
input switch, must be set to0. MON: 9Needle DType socket,
debugging interface RES: system reset switch

8
9
FSIOThe board is a communication interface board between the
interlocking machine and the display display machine, the monitoring
machine and the electronic terminal. installationIn the third slot of
the interlock, each blockFSIOThe board has only three loops
connected to the electronic terminal, such as insufficientYou can
insert another piece in the fourth slotFSIOBoard, but the address
setting in the board is different from the first board (XiangSee board
configuration diagram). BoardROMThere is a communication
program for curing. 2.1.3 Description of the optical interface board
on the back of the interlocking rack: F107PBoard isFSIOversusETInter-
communication and photoelectric signal change between the
monitoring machine and the display machineChange the interface.
F107POn the board3OneETThe cable interface of the return line and
two connections to the monitor and the displayCable interface.

10
2.2 Electronic terminal K5BMCThe information input and control output
interface circuit is called an electronic terminal (Electronic Terminal, referred
to asET). ETThe circuit is installed inET Inside the rack. One ET Inside the rack
12Slots.Two slots on the left side of the front of the rack are used to mount
twoET-LINE board. The remaining 10 Slots for installation PIO board. On the ET
LINE boardETCommunication interface with the interlocking machine
andDC24V-DC5Vpower supply. ETFor twoHeavy side-by-side structure. in
aETTwo must be installed in the rackET LINEModule. One with interlocking
machine1Connected. Another interlocking machine2Connected. The
communication between the ET and the interlock is optically connected.
inETInside the rackPIOThe boards must be installed adjacently in pairs from the
third slot on the front left side of the rack. inEach pairPIOIn the position on the
left is1systemPIOBoard, on the right is2systemPIOboard. OneETframeCan be
installed up to5CorrectPIOboard. 2.2.1 PIO Module address setting Actual
installation on the rackPIOThe number of boards is determined by the system
configuration needs. PIOBoards must be pairedinstallation. Each pairPIO The
board forms a parallel input/output interface for external connection32Road
output and32Road lossIn. PIOThe modules are universal.EachPIOCan be
inserted in any slot of the rack.System pairPIOIdentification(addressing)
throughETThe address setting for each slot on the bottom plate of the rac
11
There are two address switches that must be set to the same
address. Five pairs in each rackPIOThe address is set to01H, 02H, 03H,
04H, 05H (expanding the rack when using the extended connection
method)PIOAddress should be backwardsDelay. Software pairPIOThe
addressing is done with a two-digit hex code. The number set by the
above switch is the low addressBit code. The address high code
isETThe signature of the module type, generated by the software.
forPIO Module generationCode is6.So eachETInside the rackPIOThe
address is in order61H~65H(Extend the connection backwards).
PIOAddress setting switch atETOn the bottom of the inside of the
rack. EachPIOThe slot has a four-position groundAddress switch. The
device has been set up according to the system configuration when it
leaves the factory. The user does not need to change the switch
settings. Figure in" ”Indicates the position of the switch.

First1Correct PIOSlot 2 CorrectPIOSlot5CorrectPIOSlot address61H


address6H address 5FH

2.2.2 ETPIO2Panel indicator description LINEwithPIOPanel indicators:


NORMAL, SYSTEM: On = Run; Off = Stop; RXD: flash = receive; off = no
receive; TXD: flash = send; off = no send; DC5V ON: 5VPower switch
up = power on, down = power off;

12
13
14
2.2.3 ET PIO Online Socket Description (ETBACack of the chassis) LINE: J1:
Power socket. A3:1Department and 2The cable outlet of the system. The rest
of the socket is not used. PIO 1~5: J1: Input signal socket. J2: Output signal
socket. J3: 24VPower socket. J4, J5Use a short cable connection to not lead out

2.2.4 Input signal connection diagram of electronic terminal PIOInput


signal power from the interface of the microcomputer power
cabinet24V (IB24) "+" lead, through miningCollecting the contacts of
the relay to the interface frameCS-TX19-36T/ZType
plug/socket,Connected via signal cablePIOofJ1, enterPIOInput circuit
inside the moduleJ4, J5Back to interface24VPower supply "-"

15
2.2.5 Electronic terminal output signal connection diagram Electronic
terminalPIOOutput drive signal voltage is24V, the output signal
polarity is "+". Electronic terminal output drive signal
fromPIOModuleJ2Lead out, connected to the interface frame via a
signal cableCS-TX19-36T/ZType plug/socket,Connected to the
controlled relay by the inter-frame wiring.Electrical coilThe negative
pole returns to the interface through the common return line

2.2.6 Connection between the interlocking machine and the electronic


terminal K5BMCBoth the system interlocking machine and the electronic
terminal adopt a double system design. Each line of the interlock must receive
the input information of the dual system of the electronic terminal, after the
"or" processing,The input for the interlock operation. The output of the
interlocking double system is output in parallel through the double system of
the electronic terminal. The physical connection between the interlocking
machine and the electronic terminal is passedET NETCable implementation.
Interlocking machineFSIOThe module is a communication interface between
the interlocking machine and the electronic terminal and the monitoring and
display display machine,FSIOmoldOn the block3OneET NET aisle.
byF107PPhotoelectric conversion board leads3For fiber optic cable,
connectable3OneETRack, pass againEXTF107Can connect two moreETframe.
Figure4For interlocking machine.

16
Schematic diagram of optical cable connection between electronic terminal

Figure4Schematic diagram of optical cable connection

2.3 console K5BMCSystem consoleDS6The traditional structure of the


series. The operation display device is located in the operation
room.Operate the device according to user requirements to select a
button pad, digitizer or mouse. Indicates the optional unit of the
deviceIndicates a disc or display. Control displayPCBus industrial
computer. In addition to the interface board that connects the
operation display device, the chassis is
installed.installation2PieceSerial communication interface card with
photoelectric conversionINIO, withCommunicate with the
interlocking machine. The control display machine uses two machines
to spare each other. The console operation and presentation device
only set one set, through the control displayThe machine conversion
box is connected to the working display machine. Control display
dual-machine switching can be switched by automatic or manual
operation, console operation and presentationSwitch to the standby
machine. The dual system of the dual-machine and the interlocking
machine of the display display machine forms a redundant
relationship of the cross-connection through the optical splitter.The
connection between the display and the interlocking machine is as
shown in the figure.5Shown. Controlled display two units installed in
17
each unitINIOCommunication card: INIO1, INIO2. Used for
associationLock machine1Department and2Department of
communication. Each line of the interlock has two interfaces to
communicate with the display. In order to achieveEach line of the
interlock can communicate with either of the control units
simultaneously or with any of them. In the interlocking machineAn
optical branch unit (Optical Branch Unit) is added to the
communication line between the display and the display machine..
The function of the optical splitter is to split the input signal on one
side into two outputs. At the same time, the other side will lose two
ways.The incoming signals are combined into one output.
inK5BMCFour optical splitters are used in the system (Model: SPHC).
For interlocking dual system and monitoring machineAnd control the
cable connection of the dual machine.

18
Each optical splitter consists of two boards. a power boardSPHC-PW,
a signal transmission boardSPHC-TT. Optical splitter by interface24V
(I24V) power supply. Power board generation5VVoltage supply signal
transmission boardjobs.

Optical splitter cable connection diagram

19
Figure6: Optical splitter port location map

2.4 Electrical Maintenance Desk The electrical maintenance station is


composed of a monitor, a display, a keyboard, a printer, and the like.
Monitoring machine adoptionPCbusIndustrial computer. Install two
serial communication interface cards with photoelectric conversion in
the chassisINIO. Used in the same interlocking machine2Heavy
communication. The connection between the monitor and the
interlock is shown in the figure.6. Monitor receiving from
interlock2Heavy equipment action status information and monitoring
alarm information. The monitoring machine communicates with the
host computer of the microcomputer detecting device through the
serial communication interface, and the switch quantity monitoring
information isSend to the computer detection device.

3. Software system composition K5BMCThe software system consists


of interlocking software, control software and monitoring software.

3.1 interlocking machine software The interlock software runs


onK5BMCOn the interlocking machine.Basic program(system
manager)And interlockingThe composition of the program. The basic
program of the interlocking machine includes the following functional
modules:
1) Initialization module: hardware initialization after power-on of the
system, loading of interlocking operation parameter files, etc.jobs.

20
2) System cycle management module: completes the management of
system operation cycle management, cycle timeout and idle timeAnd
so on.
3) Dual-system management module: completes the check of the
master and slave status and the switchover control when the main
system fails.
4) Output program module: start the electronic terminal network and
the human-machine interface network driver to complete the
connectionLock the external device output data.
5) Input program module: Complete data input from the electronic
terminal and console device.
6) Inter-system transfer program module: complete double inter-
system data exchange. The interlocking operation program
completes the station signal interlock control function. Interlocking
arithmetic program and system basic program through a"Interlocking
calculation area"Specific memory area.

21
Line data exchange. The input program module of the basic program
of the system will be from the electronic terminal,Control display and
monitor to obtain input informationThe input data area of the
interlocking calculation area is placed in the agreed data format. The
interlock program takes input data from the area for interlocking
operations.Interlocking program will operateResult generationofThe
electronic terminal outputs commands, the console display
information and the monitoring information are put into the
interlocking play in the agreed data format.The output data area of
the area. The output program module of the basic program of the
system sends the output data from the output data area to the
corresponding externalDepartment equipment.

3.2 Control Display Software The control display software is the


human-machine interface software for the train duty personnel to
handle the driving operation.The main functions are:Communicate
with the interlocking machine, receive real-time change information,
operation prompts and alarm information of the station from the
interlocking machine;The lock machine sends button command
information; completes the console's station graphic display,
operation prompts and alarm information.Text and voice output;
mouse operation and button information processing.

3.3 Monitor software Monitor software is atWINDOWSDeveloped on


the operating platform, the power maintenance personnel conduct
equipment supervisionThe main functions of the human-machine
interface program for visual and fault diagnosis are: communication
with the interlocking machine, receiving and receiving the
interlocking machineSend the station real-time information
andK5BMCSystem working status information and system self-

22
diagnosis information. Monitoring procedureRecord all the
information in the real-time database. Maintenance personnel can
operate the query through the on-screen menu.Display or print out
various types of information.

4. device installation K5BMCComputer interlocking devices are


installed in: interlocking main cabinets, electronic terminal cabinets,
monitoring cabinets,On the computer power cabinet. Another
microcomputer monitoring workbench is provided. The dimensions
of the cabinet are shown below. Cabinet height1800mm. Depending
on the size of the station, the number of electronic terminal racks
used in the system varies. In the interlocking
cabinetInstallable2Electronic terminal racks. Up to install in the
electronic terminal cabinet3Electronic terminal racks. One stationThe
number of electronic terminal racks used exceeds5Time,
need2Electronic terminal cabinets.

23
Figure8: K5BMC equipment installation diagram

24
5. Power supply K5BMCThe computer system requires the signal
power screen to provide a single-phase AC through the isolation
transformer.220Vpower supply.From the power screen220VPower
deliveryK5BMCPower cabinet,throughupsBackward computerThe
device is powered. Control display, monitor and console
displayupsOutput220Vpower supply. K5BMCInterlocking machine
andETUsing two DC24VPower supply. The first road is called
logic24VElectricitySource (L24). This power supplyK5BMCInternalDC-
DCTransform, generating the logic needed to
work5VElectricitysource. The second way is called the
interface.24VPower supply (I24). For output interface drive relay and
input interface acquisitionRelay status.

Figure9: K5BMCPower system diagram

25
On the combination frame, all computer controlled
relays24VComputer systemofI24VPower supply. On the combination
frame, the power of the relay that is not controlled by the computer
still uses the signal power.Source screen power supply. Computer
output circuit24V+.After the relay coil,Loop into a public return
line,BackI24V-. The indirect point of the relay contact group collected
by the computer is connected toI24V+.Before collecting the contact
groupThe contact or the back contact returns to the computer input
circuit (see electronic terminal output, input circuit connection
diagram). forK5BMCTwo way of equipment24Vpower
supply,Installed in the power cabinet of the computer system.Every
way24VPower is made up of threeAC-DCSwitching power supply
module. Two of the modules work online for each other.Can be
switched automatically. The other module is a cold backup.(see
picture10: K5BMCPower cabinet installation diagram)

26
27
6. Operation and maintenance
6.1 Power-on sequence of system cold start The system starts from the cold
(unpowered) state, you should first confirm that all devices are connected
correctly, the connector is connectedConnect securely and then proceed.
Powering up the equipment should be in the order of the first peripheral and
the rear interlock.
1. ConnectUPS220VPower supply, confirmationupsOutput220VThe voltage is
correct.
2. Power on the console device. Console equipment includes: display display,
display, control conversion box.
3. Turn on the power of the monitor (including the monitor).
4. Turn on the power of the microcomputer power cabinet. Confirm two
ways24VThe power output is normal.(See the power supply for power cabinet
operation)Instruction manual)
5. Connect interlock1Department and interlock2The power switch of the
system. In the interlocking machineF486ModuleICCard slot
interpolationEnterICcard.
If there are twoICThe card can be inserted into the two-line interlocking
machine at the same time. If there is only oneICcard,A series of interlocking
machines can be inserted first, and after they enter the running state, they are
taken out.ICThe card is inserted into another interlockmachine. Interlocking
machine fromICCard reading program and data approximation30About
seconds. First power up and plug inICcardThe interlocking machine will enter
the "main system" state and the other machine will enter the "slave" state
(state judgment)Broken, see3.1FestivalF486Description).
6. Connect eachETEach on the rackET-LINEwithET-PIO2The power switch of the
module. Confirm each moduleEnter normal working status:"Normal"The
"System" indicator is on;The “Txd” indicator flashes. At this point, K5BMCThe
system is powered up from the cold state and is completed. When the system
is powered off, in principle, the power of each device should be cut off in the
reverse order described above.
6.2 Maintenance Precautions

28
1. The interlocking machine needs to start from the cold machineICThe
program and data read into the card can enter normal operation.
becausethisICThe card should be inserted in peacetimeICInside the card slot. In
this way, the system can automatically input after the power failure is
restored.run. Note: ICThe card is damaged by electrostatic shock and should be
kept in a safe place.
2. A fiber optic cable connection is used between the various devices in the
system. Optical cables are relatively fragile, and the following should be noted:
(1) Do not touch the optical port of the cable connector with your hand.When
the cable connector is not in use,Always wear a dust cap.
(2) The bending radius of the cable must be5More than centimeters,
otherwise it will cause the cable to break.
(3) The cable cannot be squeezed or pulled by strong impact, vibration and
gravity.
(4) Disassemble the fiber optic cable connection. Hold the outer casing of the
fiber optic cable connector and pull it out. Do not pull on the optical cable.
(5) Connect the cable connector to pay attention to the plug and the so

29
3. Three boards of the interlocking machine(F486,FSIO1FSIO2),Two
photoelectric conversion boards(F107P,EXTF107) and electronic
terminalET LINEwithET-PIO2The module must be inserted into the
rackFixed slot. The wrong position system cannot be operated and
may cause equipment failure.
4. All boards and modules in the system are forbidden to be plugged
and unplugged.Violation of this rule willCauses equipment damage.
5. ET-LINEWhen the power switch on the module is pulled, you must
hold the switch handle by hand and pull it out gently.Then move it
again. Do not force directly.
6. Daily maintenance work points.

1 Inspection inspection.
The inspection contents include: Whether the power supply voltage
and current value of each channel are normal. The ambient
temperature and humidity of the equipment room are within the
specified range: 0 °C ~ 40 °C, 20% ~ 80%; Whether there is local
overheating, abnormal noise or abnormal smell; Check if the
indication status of each device indicator is abnormal. It is confirmed
that the interlocking two-line system is the main system, and that
one is the slave system. And with the previous record pairCompare,
confirm whether there is any change in the master or slave. If there is
a change, look for the cause of the change. Make a detailed
inspection record on the duty record book. Because the system
interlocking machine and electronic terminal have adopted
redundant design. The single system has failed.The system can still
perform normal functions. Therefore, you must carefully identify the
status of the indicators on each module to confirm thatNothing is

30
running normally. It is also possible to check the fault alarm
information record through the monitoring machine to confirm the
operation of the equipment.Happening. 2 Troubleshooting. If the
device fails, first recognize the fault phenomenon, the scope of the
fault, and distinguish the module itself.Circuit failure and
communication failure between modules. After determining the
point of failure, replace it with spare parts. To replace the spare
parts, you must first cut off the power of the replaced module, and
then remove the faulty module from the rack.Insert a new module
and power up to restore. The redundant design of the system allows
the single-system module to be powered off and
replaced.Uninterrupted system operation.

7. Relay interface circuit

7.1 Overview K5BMCThe combination of computer interlocking and


outdoor signal equipment uses a relay circuit. Mainly have
signalsLighting circuit, switch control circuit, track circuit, 64DSemi-
automatic occlusion or automatic occlusion circuit, and
othersCombine the circuit. The relay that the signal circuit keeps
hasLXJ, DXJ, YXJ, TXJ, ZXJ, FXJ, DJ, 2DJWaitThe relay that the control
circuit retains hasDCJ, FCJ, 1DQJ, 2DQJ, DBJ, FBJ; track circuit
retentionGJ. Among the above relays, XJ, DCJ, and FCJ are driven by
control commands output from the microcomputer. in64DSemi-
automatic blocking circuit, reservedJSBJ, FSBJ, BSAJ, FUAJ, SGAJ; in
the double lineTwo-way change in the running direction circuit,
reservedFAJ, JFAJ, FFAJ, FSJ, CFJOutput control by
microcomputersystem. Others retain the original circuit unchanged.
One set of switches in each set of the system allows the relay to be
operatedYCJ(Double-action 岔 is treated as a set of switchesSet
oneYCJ). useYCJa set of front contacts connected to the switch start
circuitKZIn the loop. YCJUsuallyIn the state of falling. When the
switch is switched, if the switch section is unlocked, the
microcomputer will operate at the output switch.Simultaneous
outputYCJSuck up the order. After the switch is turned into place, the
microcomputer stops outputting, YCJfall. TurnoutFor some reason,
when the specified conversion time cannot be converted into place,

31
the microcomputer cancels the output of the fixed or reverse
command.CancelYCJ's output command, YCJ falls. K5BMCThe output
of the computer is static output.All computer-driven relays are
takenUse DC safety relays. Required for relay operation24VThe
power supply is given by the microcomputer system, no signalPower
screenKZ24V. Microcomputer output port is sent out24V+, the
negative end of the relay coil is connected to the common return
line, backTo the negative pole of the power supply. Relays that are
not controlled by the microcomputer still use the signal power
screenKZ24V. K5BMCThe input to the system is static.The acquisition
voltage is24V. The power is supplied by the microcomputer
system.The computer sends out the power cable through the input
acquisition cable.24V positive voltage, connected to the middle of the
collected contact groupcontact. The input port of the computer
returned by the front contact point or the rear contact point is
returned to the inside of the computer interface circuit.Go back to
the negative pole of the power supply. Microcomputer acquisition
signal circuitXJwithDJ, the circuit of the circuitDBJwithFBJ, YCJ, track
circuitGJStatus information. Microcomputer from64DCircuit
acquisitionJSBJ, FSBJ, KTJ, XZJ, SGAJ, BSAJ, FUAJwith64DtableStatus of
the light circuit; automatic blocking station, microcomputer
acquisition1LQJ, 2LQJ, 1JGJ, 2JGJstatus;Double line double direction
change running direction circuit
acquisitionFAJ,JFAJ,FFAJ,FSJ,CFJ,FJ,DJ,JQJ;

Other discrete conditions that require computer acquisition are


determined by the specific site. In order to complete the relevant
representation function on the console, it is necessary to collect the
frequency shift fault, the filament broken wire, and the track
stop.Status information such as electricity, fuse alarm, and main
power supply. The emergency disk is an emergency operation
method provided when the microcomputer system is seriously faulty
and cannot be used continuously.(For example: the power cabinet is
faulty, the power cannot be supplied normally; the communication
network is faulty, the information cannot be transmitted; the

32
consoleFailure, unable to arrange the route or display the station
graphic). The emergency disk is an optional device. On the emergency
diskDouble single button, guide the total lock button, guide signal
button, track setting, reverse position indicator light, guide totalThe
lock and pilot signals indicate lights. A single operation can be
realized on the emergency disk, confirming the position of the switch,
and guidingThe guide is always locked and the pilot signal is opened.
7.2 indicates the information collection interface The system takes
input information from the contacts of the relay. Each collected relay
only occupies one setpoint.The acquisition voltage
isKZ24V.KZ24VConnect to the indirect point of the collected contact
group.From the perspective of fail-safe,Different relays collect
different contact conditions. Provisions for closing conditions with
relay contacts (for calculationsThe input interface of the machine has
a current input), indicating that the signal is in a safe side state, that
is, the input circuit has a current throughAfter verifying that the
device is in a safe state, the logical value of the input information is
"1". Disconnect condition with relay contacts(There is no current
input to the input interface of the computer), indicating that the
signal is in the dangerous side state, input informationLogic value is
"0". For example: for signal relaysXJ, take the contact input, and then
close the contact to prove the signal relayThe device falls and the
signal is turned off. XJThe rear contact is disconnected and the signal
is open. For the interface to open,The barrier or interface is
disconnected and the signal is open. For track relayGJ, take the front
contact input, and prove the track segment empty with the front
contact closure condition.idle. The front contact is disconnected or
the interface open circuit fault and the interface disconnection are all
occupied by the track segment. The collection principle of other
relays is the same as above. The specific instructions are as follows:
For a relay that normally falls, such asXJ, YCJ, JSBJWait, take the
contact input.

33
34
7.3 Wiring of the output input interface An "interface frame"
between the computer and the relay combination frameAs a
computer and relay circuitThe interface between the two. Set on the
interface frameCS-TX19-5.08-36Ztype36Line socket. Each
socket32Root signal line.The wiring on one side of the relay circuit is
soldered to the socket.The cable on the side of the computer is
connected with a plug. In the station with the emergency disk, in
order to prevent the output on the computer when using the
emergency disk. AssumeA "machine control relay" JKJ. Set the
"machine control - emergency" switch on the emergency disk. Switch
in machine controlState, JKJSuck up, useJKJThe upper contact is
connected to the computer output interface24V+ power supply, The
output is valid. In the "emergency" state, JKJDrop, cut off the
computer output interface24V+ power supply,The computer output
is invalid.Station without emergency disk, no

Figure12: Input and output interface power connection diagram

35
inETThe back of the rack, each pairET-PIOThere are two rectangular
sockets. among themJ1For connection inputsignal.J1Socket has60
Core, with one of them32Core32Road input signal. On the interface
shelf, rightShould eachET-PIOof32Road input,Set oneCS-TX19-
36ZType socket.use36Core
signalcable.ElectricitycableofOneendusePressureConnectsquareform
ulaevenConnectversusJ1CorrectshouldofInserthead.Electricitycableof
anotherOneendweldConnectCS-TX19-36TType plug. inET-PIOThe
backJ2Socket andJ1Same model for introduction32Road output
signal. Connected electricityThe cable and the plugs on both ends are
in the same form as the input cable. There are four core wires in the
output cable for connecting output signals.The negative common end
of the number

ET-PIO input socket J1, output socketJ2Online socket with cabinet,


and input and output socket on the interface frameThe
correspondence between the terminals is as follows: In the following
table, the interface socket is usedCS-TX19-36ZType socket.

36
37
8. Ground wire and lightning protection DS6-K5BMCThe computer
system requires a protective ground wire. Grounding and grounding
resistance of this ground wireThe value shall be in accordance with
the "Technical Conditions for Computer Interlocking" issued by the
Ministry of Railways.. That is: the grounding body and other
equipment grounding grounding body spacing is not less
than20Meter; This ground wire shall not be used in conjunction with
the grounding wire of equipment such as electric power and
communication; Grounding resistance is not greater than4Ω.
K5BMCThe system is designed according to the Japanese company
Jingsan.Take the floating way to prevent lightning.Interlocking host
and electronic terminalThe installation of the circuit takes multiple
insulation measures. Working for computer logic circuits5VThe power
supply is floating to the ground.Input and output interface circuit
works24VThe power supply forms a closed loop and floats to ground.
In indoor environmentUnder the condition that the above isolation
requirements are met, no lightning protectio