Circuit protection www.schneider-electric.com/sg Circuit protection www.schneider-electric.

com/sg

Circuit breaker panorama Circuit breaker panorama

Selection guide Selection guide


Circuit breakers Instantaneous circuit breakers (ICB)
Type iC60N iC60H Type iC60L

Standard IEC/EN 60947-2, 60898-1 IEC/EN 60947-2, 60898-1 Standard IEC/EN 60947-2, 60898-1
Quality label Country approval pictogram Country approval pictogram Quality label Country approval pictogram
Number of poles 1P, 1P+N 2, 3, 4P 1P, 1P+N 2, 3, 4P Number of poles 1P 2, 3, 4P
Add-on residual current devices (Vigi) p p Add-on residual current devices (Vigi) p
Auxiliaries for remote tripping and indication p p Auxiliaries for remote tripping and indication p
Electrical characteristics Electrical characteristics
Curves B, C, D B, C, D Curves B, C, K, Z
Ratings (A) In 0.5 to 63 0.5 to 63 Ratings (A) In 0.5 to 63
Maximum operational voltage (V) Ue AC (50/60 Hz) 240/415, 440 240/415, 440 Maximum operational voltage (V) Ue max AC (50/60 Hz) 240/415, 440
max DC 250 250 DC 250
Minimum operational voltage (V) Ue AC (50/60 Hz) 12 12 Minimum operational voltage (V) Ue min AC (50/60 Hz) 12
min DC 12 12 DC 12
Insulation voltage (V AC) Ui 500 500 Insulation voltage (V AC) Ui 500
Rated impulse withstand voltage (kV) Uimp 6 6 Rated impulse withstand voltage (kV) Uimp 6
Limitation class 40 A (EN 60898) 3 3 Limitation class 40 A (EN 60898) –
Breaking capacity Breaking capacity
IEC/EN 60898 (A) Icn 240/415 V - 6000 6000 10000 10000 IEC/EN 60898 (A) Icn 240/415 V - 15000 15000
230/400 V 230/400 V
AC-Breaking capacity Ue (50/60 Hz) 1P, 1P+N 2, 3, 4P 1P, 1P+N 2, 3, 4P AC-Breaking capacity Ue (50/60 Hz) 1P 2, 3, 4P
Ratings (A) In 0.5 to 4 A 6 to 63 A 0.5 to 4 A 6 to 63 A 0.5 to 4 A 6 to 63 A 0.5 to 4 A 6 to 63 A Ratings (A) In 0.5 to 4 A 6 to 25 A 32/40 A 50/63 A 0.5 to 4 A 6 to 25 A 32/40 A 50/63 A
IEC 60947-2 (kA) Icu 12...60 V 50 36 – – 70 42 – – IEC 60947-2 (kA) Icu 12...60 V 100 70 70 70 – – – –
12...133 V – – 50 36 – – 70 42 12...133 V – – – – 100 70 70 70
100...133 V 50 20 – – 70 30 – – 100...133 V 100 50 36 30 – – – –
220...240 V 50 10 50 20 70 15 70 30 220...240 V 100 25 20 15 100 50 36 30
380...415 V – – 50 10 – – 70 15 380...415 V – – – – 100 25 20 15
440 V – – 25 6 – – 50 10 440 V – – – – 70 20 15 10
Ics 100 % 75 % 100 % 75 % 100 % 50 % 100 % 50 % Ics 100 % 50 % 50 % 50 % 50 % 50 % 50 % 50 %
of Icu of Icu of Icu of Icu of Icu of Icu of Icu of Icu of Icu of Icu(1) of Icu of Icu of Icu of Icu (1) of Icu of Icu
DC-Breaking capacity Ue DC DC-Breaking capacity Ue DC
IEC 60947-2 (kA) Icu 12...60 V (1P) 15 20 IEC 60947-2 (kA) Icu 12...60 V (1P) 25
y 72 V (1P) 10 15 y 72 V (1P) 20
y 125 V (2P) 10 15 y 125 V (2P) 20
y 180 V (3P) 10 15 y 180 V (3P) 20
y 250 V (4P) 10 15 y 250 V (4P) 20
Ics 100 % of Icu 100 % of Icu Ics 100 % of Icu
Other characteristics Other characteristics
Suitable for industrial isolation according to IEC/EN 60947-2 p p Suitable for industrial isolation according to IEC/EN 60947-2 p
Reference temperature IEC/EN 60947-2 50°C 50°C Reference temperature IEC/EN 60947-2 50°C
Fault tripping indication Visi-trip window Visi-trip window Fault tripping indication Visi-trip window
Positive contact indication p p Positive contact indication p
Fast closing p p Fast closing p
Degree of protection IP Device only IP20 IP20 Degree of protection IP Device only IP20
Device in modular IP40 IP40 Device in modular IP40
enclosure Insulation class II Insulation class II enclosure Insulation class II
For more detail, see module CA901002 CA901003 For more detail, see module CA901004
Accessories CA907000 and CA907001 CA907000 and CA907001 Accessories CA907000 and CA907001
Auxiliaries CA907000 and CA907002 CA907000 and CA907002 Auxiliaries CA907000 and CA907002
Add-on residual current devices (Vigi) CA902005 CA902005 Add-on residual current devices (Vigi) CA902005
(1) 100 % of Icu for ratings 6 to 25 A under Ue 100 to 133 V AC Ph/Ph and Ue 12 to 60 V AC Ph/N. (1) 100 % of Icu for ratings 6 to 25 A under Ue 100 to 133 V AC Ph/Ph and Ue 12 to 60 V AC Ph/N.

4 Version 2.0 - May 2017 Version 2.0 - May 2017 5