START
PRE-PURGE
WATER SUPPLY INITIALSATION PROCESS
FUEL SUPPLY INITIALSATION PROCESS
STEAM GENERATION PROCESS
POST-PURGE
STOP
1) 2)
START POST-PURGE
PRE-PURGE Stem pressure high (A2)
If damper flap is in closed position Boiler OFF indication
Start damper motor & in clockwise
Till flap reaches open position Start air blower for 5-Sec.&then
It should automatically become
Start air blower for 5-Sec.& then OFF
It should automatically OFF
If flap is open position start
Damper motor & move it in Anti
Clockwise direction till flap reaches
Closed position
STOP
3) Water supply initialization process
Pre-Purge & Extra Low Level/ Low Level
Start FWP-1 Yes [R1 () Water high level F.W.P-1 (X) Go to
Even F.S.I.P.
after 5 sec No [R1 (X)] Give Alaram (S7)
Start FWP-2 Yes [R2 () Water high level F.W.P-1 (X) Go to
Even F.S.I.P
after 5 sec No [R2 (X)] Give Alaram (S7)
If S7 & S8 both are ON then Lock out condition [Q1, Q5 & Q6 (X)]