Sie sind auf Seite 1von 2

PERFORMA FOR HARYANA FIRE SERVICE

1. Name & address of the Building SCHOOL BUILDING SITUATED AT KHASRA


NO. 75/12/1, 13/1, 18/1, 19, 20, AT M.C. ROAD
GANAUR, DISTT. SONIPAT BELONGING TO
SH. KRISHAN GOPAL TYAGI S/O SH. NAIN
SINGH AND ANIL KUMAR & SUNIL KUMAR
S/O SH. KRISHAN GOPAL TYAGI
2. Type of occupancy EDUCATIONAL BUILDING (CATEGORY B)
3. No. of Block/ Tower 1 NO. BLOCK
4. Height of building 13.86 M
5. Permissible Height 30 M
6. Number of Floor G+3
7. Covered Area at ground Floor GROUND FLOOR = 3410 SQ.M
8. Typical Floor area/ area at each FIRST FLOOR = 2384.452 SQM
Floor SECOND FLOOR = 1560.744 SQM
THIRD FLOOR = 1435.934
9. No. of Basements NO BASEMENT
10. Basement floor if any NILL
11. Total Plot Area 7992.54 SQM
Check list according to HFS Act 2009/HBC-2017/NBC-2016
S.NO Minimum standards on fire HBC-2017/NBC-2016 PROVISIONS PROPOSED
prevention and fire safety requirement
(clause/code/BIS)
1. Access to fire
appliances (4.6/NBC-3)
 Road Width Required 18.4451 M WIDE ROAD
6 M WIDE GATE
 Gate Width Required
 Width of internal road NOT PROPOSED
Remarks, if any Not Required
2. Size (Width) Number, type &
arrangement of exits
Travel distance (4.4.2.2/NBC-4) 30 m 30 M

6M
Dead end travel 6m
Distance (4.4.2.2. (C))
6 Nos.
Number of staircase Required
(4.4.2.1/NBC-4)
 Upper Floor
 Basements 1500 MM WIDE – 2 Nos.
Width of staircases Required 2000 MM WIDE – 2 Nos.
(4.4.2.4.3.2/NBC-4) 2500 MM WIDE – 2 Nos.
 Upper Floor
 Basements YES PROPOSED

Provisions of staircase Required


(4.4.2.4.3/NBC-4) NOT PROPOSED
Fire fighting shaft/ fire tower Not Required YES EACH STAIRCASE
(2.24 & E2/NBC-4) CONTINUE TO TERRACE
No. of construction staircases to Required
terrace (4.4.2.4.3.2-H4/NBC-4) NOT PROPOSED

Ramp, if any (width) As specified 6 NOS EXIT


(4.4.2.4.3.5/NBC-4)

Protection of exits Minimum 2 Nos. exit YES PROPOSED IN


(4.4.2.5/NBC-4) Required ELECTRICAL SHAFT

 Fire check door Required NOT PROPOSED


(4.4.2.4.3.2-H2/NBC-4)
3005 MM WIDE
 Pressurization Not Required
(4.4.2.5 (b) & E2/NBC-4)
1200 MM WIDE
Width of corridor As Specified
(4.4.1 & 4.4.2.4.2/NBC-4)

Door size (4.4.2.4.1/NBC-4) 1.0 m wide


Remarks, if any

3. Compartmentation (4.5/NBC-4) Required if the


 No. of fire basement area more
compartmentations at than 3000 sq.m
basement level
 Type of compartmentation
a) By fire resisting wall of Yes/No
2hrs rating
b) By fire curtain of 02 hrs Yes/No
rating
c) By water curtain Yes/No
 Fire check door
Remarks, if any Not Required
4. Smoke management system