Beruflich Dokumente
Kultur Dokumente
J4-1
January 1999 Motor Starters – NEMA Magnetic
General Description
Starter Selection Guide than one type starter will meet the application
requirements, reference to the table below will
In general, the application will determine the show which starter is best suited for the appli-
type of starter required. In cases where more cation.
General Application may exceed the mechanical limitations of the release, where power is applied to the motor
load or electrical limitations of the source, after a power failure, can be obtained by using
The following factors should be considered or both. a 2-wire pilot device (temperature, switch,
when applying reduced-voltage starters to a etc.). Low-voltage protection, where power is
squirrel cage motor-driven load. A reduced-voltage or reduced-inrush starter not applied to the motor after a power failure
will reduce both starting current and starting until restarted by an operator, can be ob-
1. The motor characteristics which will sat- torque. Care must be taken when meeting tained by using 3-wire control such as START
isfy the starting requirements of the load. power company limitations that the motor STOP push buttons.
will produce sufficient torque to accelerate
2. The source of power and the effect the the load to near rated speed. Closed transition Wye-Delta types require
motor starting current will have on the adequate ventilation to remove resistor heat.
line voltage. Part-winding starters are suited to low start-
ing torque loads such as fans, blowers and Cutler-Hammer also offers a line of solid-
3. The load characteristics and the effect the m-g sets. Autotransformer starters should be state reduced-voltage starters known as
motor starting torque will have on the used with “hard to start” loads such as recip- Easy-start.
driven parts during acceleration. rocating compressors, grinding mills, and
pumps. Wye-Delta starters are applicable to Solid-state starters are ideally suited for
The starter protection required to protect high inertia loads with long acceleration many loads including conveyor applications
the load, motor, starter, cables and power times which as centrifugal compressors since they provide controlled acceleration
source during overload, undervoltage and and centrifuges. from zero to full load.
fault conditions.
UL Listing – Combination E176513,
A typical NEMA B motor started with full volt- All starters, in addition to overload protection, Non-Combination E19224
age will develop as much as 150% full-load will provide either low-voltage release or
torque when started with a starting current of
around 600% full-load current. These values
low-voltage protection depending upon the J
pilot device used with the starter. Low-voltage
Starting Characteristics
CAT.71.01.T.E
Reduced Voltage Motor Control Cutler-Hammer
J4-2 Motor Starters – NEMA Magnetic January 1999
Part-Winding Type
Description Operation (Refer to schematic diagram) Opening the STOP button or other pilot
Part-Winding starting provides convenient, Closing the START button or other pilot de- device de-energizes contactors (1M), (2M)
economical one-step acceleration at reduced vice energizes the start contactor (1M) which and timer (TR), removing the motor from
current where the power company specifies a seals in through its interlock (1M) and ener- the line.
maximum or limits the increments of current gizes the timer (TR). The (1M) contacts con-
Contactor Sequence
drawn from the line. These starters can be nect the first half-winding of the motor across
used with nine-lead dual-voltage motors on the line. After a preset time interval, the timer Contactor Start Run
the lower voltage and with special part- (TRTC) contact closes energizing contactor 1M ● ●
winding motors designed for any voltage. (2M). The (2M) contact connect the second
When used with dual-voltage motors, it half-winding of the motor across-the-line.
2M ●
should be established that the torque pro-
duced by the first half-winding will accelerate Typical Schematic Diagram
the load sufficiently so as not to produce a
second undesirable inrush when the second Part Winding 1M OL Select Overload Heater Packs for 50%
T1 of Rated Full Load Motor Current
L1 L1 #1
half-winding is connected to the line. Most L2 L2
CKT BKR
or #2
T2
Motor
motors will produce a starting torque equal to L3 L3
SW & FU
#3
T3
between 1/2 to 2/3 of NEMA standard values 2M OL T7
with half of the winding energized and draw T8
about 2/3 of normal line current inrush. T9
TBX2
Stopped
1M
Design Features 7 8
G
Run
Contactors – (1M) (2M)
R
A three-pole contactor (1M) connects only the Start 1M
(1M) (2M)
Stop A1 A2 TB4 OL A OL
first half-winding of the motor for reduced TB1 TB1 TB2 TB3
95 96 95 96
inrush current on starting (see table below for On-Delay 1.5 – 15 Sec.
PS 1M TR
size). A three-pole contactor (2M) connects Auto 2 7
TB1 TB1 TB3 E
the second half-winding of the motor for Off 2M
running (see table below for size). Hand
T.C. = Timed Closing 8 TR 6 5 A1 A2
T.C.
Maximum NEMA Size
Hp
Starter Contactor
(1M) (2M) Reduced Voltage Enclosures (Refer to page J4-5 for dimensions)
230 Volts, 60 Hz Size Freedom ECN Box Number Freedom ECN Box Numer
15 1 PW 1 1 NEMA 1 3R, 4X, 12 NEMA 1 3R, 4X, 12
25 2 PW 2 2
50 3 PW 3 3 Class 45: Partwinding – Non-combination
75 4 PW 4 4
150 5 PW 5 5 2PW 3 7 7➁ 7
300 6 PW 6 6 3PW-4PW 9 9 9➁ 9
460-575 Volts, 60 Hz 5PW E E E➁ E
15 1 PW 1 1 Class 46: Partwinding – With Disconnect
40 2 PW 2 2 Class 47: Partwinding – With Thermal Magnetic Trip CB
75 3 PW 3 3
150 4 PW 4 4 2PW-4PW E E E E
J 350
600
5 PW
6 PW
5
6
5
6
Other Types
Part-winding Type ECN45 starters are also
available in combination (Type 46 and 47),
reversing and three point (primary resistor)
types.
CAT.71.01.T.E
Cutler-Hammer Reduced Voltage Motor Control
J4-3
January 1999 Motor Starters – NEMA Magnetic
Wye-Delta Type
Description Operation (Refer to schematic diagram) de-energizes the timer (TR) opening timer
Wye-Delta type starters are applied exten- Closing the START button or other pilot device (TRTC) thus energizing contactor (2S).
sively to industrial air conditioning installa- energizes contactor (1S) whose contacts con-
tions because they are particularly suited for nect the motor in a wye connection. Interlock An overload, opening the STOP button or
starting motors driving high inertia loads (1S) closes, energizing contactor (1M) and other pilot device de-energizes contactors
with resulting long acceleration times. They timer (TR). The (1M) contacts energize the (1M) and (2M), removing the motor from the
are not, however, limited to this application. motor windings in a wye. After a preset time line. (TRP) de-energizes and locks out the
When six- or twelve-lead delta-connected interval, timer (TRTC) contact closes energiz- control circuit if the duty cycle of the transi-
motors are started wye-connected, approxi- ing contactor (2S). Interlock (2S) opens, drop- tion resistors is exceeded.
mately 58% of line voltage is applied to each ping out contactor (1S). The motor is now
winding and the motor develops 33% of energized in series with the resistors. Interlock Wye-Delta Class ECN51 closed transition start-
full-voltage starting torque and draws 33% of (1S) closes, energizing contactor (2M), bypass- ers are also available in combination types
normal locked-rotor current from the line. ing the resistors and energizing the delta con- and Class ECN48 open transition non-combi-
When the motor is accelerated, it is recon- nected motor at full voltage. Interlock opens, nation and combination starters.
nected for normal data operation.
Typical Schematic Diagram
Design Features
Wye-Delta
Closed Transition 2M
Contactors – (1S) (1M) (2S) (2M) L1 L1 CKT BKR #1
T6
T4
A three-pole contactor (1S)➀ shorts the L2 L2 or #2
T5
L3 L3 SW & FU #3
motor leads T4-T5-T6 during starting to con- 1S 1S
nect motor in wye (see table below for size). 2S
1S
T2B
T3B
T1B
A three-pole contactor (1M) energizes motor Select Overload Heater Coils
Resistor
Resistor
Resistor
leads T1-T2-T3 for both wye and delta con- for 58% of Rated Full Load
Motor Current
nections (see table below for size). 1M OL T1
T1A T2 Motor
A three-pole contactor (2S) connects resis- T2A T3
T3A
tors in series with the motor windings during Stopped
1S 2M TBX2
the start-to-run transition period (see table 5 5 7 8
G
below for size).
Run
R
A three-pole contactor (2M) energizes the On-Delay 1.5 – 15 Sec. TR
Stop Start
motor leads T4-T5-T6 during running to con- TB1 TB1 TB2 TB3 2
E
7
nect the motor in delta (see table below for 2M 1S
1S 51 2S 52 A1 A2 TB4 1 TRP 4
size).
T.O. 95 96
1M
TRP
Max. NEMA Size 1 TR 3 53 2 7
Hp E
Starter Contactor PS T.C. 2S
Auto A1 A2
(1M) (2M) (1S) (2S) TB1 TB1 TB3
Off 1M T.O. = Timed Opening
1S 54 A1 A2
230 Volts, 60 Hz Hand T.C. = Timed Closing
1M
10 1 YD 1 1 1 1 1S 2M
8 TR 6 55 A1 A2
25 2 YD 2 2 2 1 56
50 3 YD 3 3 3 1 T.C.
75
150
300
4 YD
5 YD
6 YD
4
5
6
4
5
6
4
4
5
2
3
4
J
500 7 YD 7 7 6➀ 5 Reduced Voltage Enclosures (Refer to page J4-5 for dimensions)
800 8 YD 8 8 7➀ 6
Size Freedom ECN Box Number Freedom ECN Box Number
460-575 Volts, 60 Hz
15 1 YD 1 1 1 1 NEMA 1 3R, 4X, 12 NEMA 1 3R, 4X, 12
40 2 YD 2 2 2 1 Classes 48, 51: Wye Delta – Non-combination
75 3 YD 3 3 3 1 Classes 49, 52: Wye Delta – With Disconnect
150 4 YD 4 4 4 2 Classes 50, 53: Wye Delta – With Thermal Magnetic Trip CB
300 5 YD 5 5 4 3
700 6 YD 6 6 5 4 WYD-4YD E E E E
1000 7 YD 7 7 6➀ 5
1500 8 YD 8 8 7➀ 6
CAT.71.01.T.E
Reduced Voltage Motor Control Cutler-Hammer
J4-4 Motor Starters – NEMA Magnetic January 1999
Autotransformer Type
Description Operation (Refer to schematic diagram) contactor (R) which seals in through its inter-
Autotransformer type starters are the most Closing the START button or other pilot lock (R). The run contacts are now closed, and
widely used reduced-voltage starter because device energizes the start contactor (1S). The the motor is running at full voltage. Start con-
of their efficiency and flexibility. All power interlock (1S) closes, energizing the timing tactor (2S) and relay (TR) are de-energized
taken from the line, except transformer loss- relay (TR) and contactor (2S) which seal in when interlock (R) opens.
es, is transmitted to the motor to accelerate through the interlock (2S). With the (1S) and
the load. Taps on the transformer allow (2S) contactors closed, the motor is connect- An overload, opening the STOP push button
adjustment of the starting torque and inrush ed through the autotransformer for reduced- or other pilot device de-energizes the (R) con-
to meet the requirements of most applica- voltage start. After a preset time interval, the tactor removing the motor from the line.
tions. The following characteristics are (TRTO) contacts time open, de-energizing
produced by the three-voltage taps: contactor (1S) and connecting the autotrans- Other Types
former as a reactor in series with the motor. Autotransformer starters are also available in
Tap Starting Torque Line Inrush Interlock (1S) immediately energizes the run combination and reversing types.
% Locked % Locked
Torque Ampere
Typical Schematic Diagram
50%➀ 25% 28%➁
65% 42% 45%➁ R 3C
80% 64% 67%➁
100%
80%
65%
50%
0%
RVNR AUTOXFMR (3-coil) 2S 1S OL T1
5C 1C
Closed transition is standard on all sizes R 3E T2
Motor
L1 L1 #1
100%
CKT BKR
80%
65%
50%
assuring a smooth transition from reduced to T3
0%
2S 1S
L2 L2 or #2
5E 1E
full voltage. Since the motor is never discon- L3 L3
SW & FU
#3 R 3D
nected from the line there is no interruption
100%
80%
65%
50%
0%
2S 1S
of line current which can cause a second 5D 1D TBX2
inrush during transition.
1S R Stopped
7 8 9 10
Duty cycle of these starters is as follows: up G
T.C.
A three-pole contactor (Run) bypasses the au-
totranformer and connects the motor for full-
voltage across-the-line running (see table be-
low for size). Reduced Voltage Enclosures (Refer to page J4-5 for dimensions)
Size Freedom ECN Box Number Freedom ECN Box Number
J Maxi-
mum
Hp
NEMA Size
Starter Contactor
NEMA 1 3R, 4X, 12 NEMA 1 3R, 4X, 12
Class 42: Autotransformer – Non-combination
Run Starting Class 43: Autotransformer – With Disconnect
(1S) (2S) Class 44: Autotransformer – With HMCP
(Three (Three 2-4 E2 E2 E2 E2
Pole) Pole)
230 Volts, 60 Hz
15 2 2 2 2
30 3 3 3 3
50 4 4 4 4
100 5 5 5 5
200 6 6 6 6
300 7 7 6➂ 6
450 8 8 7➂ 7
460-575 Volts, 60 Hz
25 2 2 2 2
50 3 3 3 3
100 4 4 4 4
200 5 5 5 5
400 6 6 6 6
600 7 7 6➂ 6
900 8 8 7➂ 7
CAT.71.01.T.E
Cutler-Hammer Reduced Voltage Motor Control
J4-5
January 1999 Motor Starters – NEMA Magnetic
Dimensions
J
Boxes 7, 9
Boxes 3
CAT.71.01.T.E
Reduced Voltage Motor Control Cutler-Hammer
J4-6
Solid-State Motor Starters January 1999
General Description
Applications
Cutler-Hammer’s Easy Start solid-state
products can be applied in a wide array of
customer applications. Typical benefits of
solid-state include:
● Reduced starting torque stress on me-
chanical equipment allowing longer life of
belts, gears, pulleys, and motor shafts
commonly weakened during “across-the-
line” starting.
● Reduction of voltage drop during starting
on weak utility systems where the perfor-
mance of nearby equipment would be
negatively affected.
● Reduced inrush current during starting
which will allow better management of
utility peak demand charges.
● Energy savings where light load condi-
tions allow the phase-back of voltage dur-
ing “idle” periods.
● Smooth, stepless starting with an infinite
amount of torque and ramp time settings
allowing superior flexibility over typical
electromechanical starting methods.
Enclosure Type
Airborne particulate may be detrimental to
starter performance and reliability, so caution
must be exercised in choosing the enclosure
best suited to the environment. The NEMA
Cutler-Hammer offers a complete family of where few advanced protection features are rating of the enclosure defines its ability to
UL listed solid-state reduced voltage starters required. Available from 10-390 amperes. withstand the ingress of foreign particulate
from 1-750 hp at 460 volt. Ratings at 208/230 as described below:
and 575 volt 60 Hz and 380 volt 50 Hz are also Easy Start ES – Solid-State Starter
available. Units can be mounted in NEMA 1, Full featured starter with Class 20 electronic
J NEMA 12 and open panel construction.
Motor control center mounting is also
overload and advanced motor protection
package (phase loss, current unbalance,
NEMA 1
A general purpose, indoor-type enclosure.
possible utilizing the Easy Start EA allowing undervoltage, and overtemperature protec- NEMA 12
mounting of up to 600 hp in a 20-inch wide tion). Door mounted status and diagnostic A dust-tight and drip-tight enclosure for
Motor Control Center section. Starters in LEDs and an abundance of standard options. indoor industrial applications.
specialty enclosures such as NEMA 4 and 4X, Available from 6-950 amperes.
are also available using a unique and NEMA 4
electrically efficient method of power Easy Start EA – Solid-State Starter with A watertight and dust-tight enclosure for
semiconductor bypass. Advantage Contactor Bypass. either indoor or outdoor use.
This unique product utilizes the SCRs during
Available in 4 different product classes, these the start sequence only, and then a contactor NEMA 4X
starters provide soft-starting of ac induction is closed in parallel to handle continuous cur- Identical to NEMA 4, with the additional
motors. Motor voltage is adjustable by rent during run duty, significantly reducing requirement that the enclosure be corrosion-
means of back-to-back SCRs (silicon con- power losses. This extremely small efficient proof as well.
trolled rectifiers) providing a smooth, step- product is ideal for the space conscious user.
less start (and stop) of the motor driven load. Available from 11-760 amperes.
C514 – Solid-State Controller All Easy Start products include standard ad-
Typically retrofited between an existing elec- justments such as adjustable starting torque,
tromechanical starter and motor. No over- ramp time, and current limit settings. A pat-
load protection is included. Available from ented load sensing circuit that reduces ap-
10-100 amperes. plied voltage during “light load” conditions is
included on all EJ/ES units and can result in
Easy Start EJ – Solid-State Starter energy savings when duty cycles allow. The
Complete starter with Class 10 electronic EA product achieves lower losses by bypass-
overload protection. Ideal for applications ing the less efficient semiconductors.
CAT.71.01.T.E
Cutler-Hammer Reduced Voltage Motor Control J4-7
January 1999 Solid-State Motor Starters
General Description
CAT.71.01.T.E
Reduced Voltage Motor Control Cutler-Hammer
J4-8
Solid-State Motor Starters January 1999
3-Phase Supply
L1 L2 L3
J 52/52
92/80/96
40/50
30/30/75
460/575
200/230/460
C514ENOD
C514FNOC
9.75 (248)
9.05 (230)
12.00 (305)
14.50 (368)
6.09 (155)
7.87 (200)
8.01 (204)
6.42 (163)
11.00 (279)
7.42 (189)
1/4"
1/4"
14 (6.35)
27 (12.3)
96/99 75/100 460/575 C514FNOD 9.05 (230) 14.50 (368) 7.87 (200) 6.42 (163) 7.42 (189) 1/4" 27 (12.3)
NEMA 3R/12 Enclosed
11/9.6/11 3/3/7.5 200/230/460 C514BDOC 8.09 (206) 11.64 (296) 5.84 (148) 6.44 (164) 10.80 (274) 10 - 32 17 (7.7)
11/11 7.5/10 460/575 C514BDOD 8.09 (206) 11.64 (296) 5.84 (148) 6.44 (164) 10.80 (274) 10 - 32 17 (7.7)
17.5/22/21 5/7.5/15 200/230/460 C514CDOC 7.44 (189) 15.13 (384) 5.91 (150) 5.79 (147) 14.13 (359) 1/4" 21 (9.5)
21/22 15/20 460/575 C514CDOD 7.44 (189) 15.13 (384) 5.91 (150) 5.79 (147) 14.13 (359) 1/4" 21 (9.5)
32.2/42/40 10/15/30 200/230/460 C514DDOC 10.64 (270) 16.13 (410) 6.83 (174) 9.00 (229) 15.00 (381) 1/4" 27 (12.3)
40/41 30/40 460/575 C514DDOD 10.64 (270) 16.13 (410) 6.83 (174) 9.00 (229) 15.00 (381) 1/4" 27 (12.3)
48.3/54/52 15/20/40 200/230/460 C514EDOC 10.64 (270) 16.13 (410) 6.83 (174) 9.00 (229) 15.00 (381) 1/4" 27 (12.3)
52/52 40/50 460/575 C514EDOD 10.64 (270) 16.13 (410) 6.83 (174) 9.00 (229) 15.00 (381) 1/4" 27 (12.3)
92/80/96 30/30/75 200/230/460 C514FDOC 20.40 (518) 31.36 (797) 12.51 (318) 18.37 (467) 29.65 (753) 1/4" 125 (56.7)
96/99 75/100 460/575 C514FDOD 20.40 (518) 31.36 (797) 12.51 (318) 18.37 (467) 29.65 (753) 1/4" 125 (56.7)
CAT.71.01.T.E
Cutler-Hammer Reduced Voltage Motor Control J4-9
January 1999 Solid-State Motor Starters
Easy Start E J Soft Start Controller
Open Type
10- 26 5/7.5/15 208/230/460 EJ026 15 14 8 22
20- 52 10/15/30 208/230/460 EJ052 15 14 8 22
25- 68 20/25/50 208/230/460 EJ068 15 14 8 26
28- 75 20/30/60 208/230/460 EJ075 15 14 8 26
37-100 30/30/75 208/230/460 EJ100 15 14 8 Does not apply 26
47-130
70-190
40/50/100
60/75/150
208/230/460
208/230/460
EJ130
EJ190
27
39 (47.68)➀
14
26.75 (18.5)➀
8
14 (9.5)➀
40
100
J
100-270 75/100/200 208/230/460 EJ270 39 (47.68)➀ 26.75 (18.5)➀ 14 (9.5)➀ 100
142-390 125/150/300 208/230/460 EJ390 39 (47.68)➀ 26.75 (18.5)➀ 14 (9.5)➀ 110
NEMA 12 Enclosed
10- 26 5/7.5/15 208/230/460 EJ026 17.6 13.5 10.75 6 35
20- 52 10/15/30 208/230/460 EJ052 17.6 13.5 10.75 6 35
25- 68 20/25/50 208/230/460 EJ068 28.5 25.25 10.75 Does not 6 86
28- 75 20/30/60 208/230/460 EJ075 28.5 25.25 10.75 apply 6 86
37-100 30/30/75 208/230/460 EJ100 28.5 25.25 10.75 6 86
47-130 40/50/100 208/230/460 EJ130 33.8 24.5 13 6 107
NEMA 1 Enclosed
70-190 60/75/150 208/230/460 EJ190 46.38 18.5 9.5 12 100
Does not
100-270 75/100/200 208/230/460 EJ270 46.38 18.5 9.5 12 100
apply
142-390 125/150/300 208/230/460 EJ390 46.38 18.5 9.5 12 110
CAT.71.01.T.E
Reduced Voltage Motor Control Cutler-Hammer
J4-10
Solid-State Motor Starters January 1999
Description Line A
Line B
Motor
Line C
To SCR Gates
Control
Reset Logic
Control &
Stop Start Protection
Power
CAT.71.01.T.E
Cutler-Hammer Reduced Voltage Motor Control J4-11
January 1999 Solid-State Motor Starters
Easy Start ES Soft Start Controller
Line
DIP CT
Switch
Rectifier
Inverse Curr.
Current Instant Time Gates SCR’s
Feedback Trip Limit
Trip
Init. Step Time
Voltage
Phase
Rotation
Phase
Loss
Lockout Digital
Trigger
Current
Unbalance
Over Temp
Motor
Aux. Trip
Remote Contact
CAT.71.01.T.E
Reduced Voltage Motor Control Cutler-Hammer
J4-12
Solid-State Motor Starters January 1999
Easy Start EA
J ➃
➀ User supplied Remote Reset can be installed by ➂ Starter is reset by interrupting 120-volt supply at EA045 through EA135 require 150VA minimum
removing jumper between terminals 2 and 3. remote reset; or, by using the “RESET” pushbutton CPT. Models EA270 through EA760 require 300VA
➁ End-of-ramp Relay (K201) and Trip Relay (K200) on the main logic board, which is at low level minimum CPT.
are part of Logic Board; a remote fault device, voltage.
such as Shunt Trip, may be connected in series ➃ CPT and operator devices to be supplied by users
with the N.O., K200 contact at point 8. unless ordered with enclosed units. Models
CAT.71.01.T.E
Cutler-Hammer Reduced Voltage Motor Control J4-13
January 1999 Solid-State Motor Starters
Easy Start EA
FLA — 045, 090, 135, 270, 360, FLA — 045, 090, 135, 270, 360, 540, 760
540, 760
Voltage: D = 200-600V, 60 Hz
G = 200-600V, 50 Hz
Open Panel (50 Hz):
E A PN5
Type: Ø = Standard Design 40°C
Ratings
Catalog Amperes Horsepower Kilowatts
Number Base Maximum Minimum 208V 230V 460V 575V 380V 415V
Rating Continuous
EA045 45 52 12 15 15 30 40 22 22
EA090 90 104 23 30 30 60 75 45 45
EA135 135 155 34 50 50 100 125 55 75
EA270 270 311 69 100 100 200 250 110 110
EA360 360 414 92 125 125 250 350 160 160
EA540 540 621 137 200 200 450 500 250 300
EA760 760 874 193 250 300 600 750 400 450
CAT.71.01.T.E
Reduced Voltage Motor Control Cutler-Hammer
J4-14
Solid-State Motor Starters January 1999
Typical Specifications
Soft Start Controller Type C514 Solid-State Reduced Voltage Motor 14. Tripped functions shall be designed to be
Starter Type EJ cleared by removing power from the solid-
1. Controller shall be Cutler-Hammer type state logic board.
C514. 1. Motor starter shall be Cutler-Hammer
type EJ. 15. The starter shall have a light emitting
2. The solid-state low-voltage controller diode (LED) to indicate incorrect phase
shall consist of a power section mounted 2. The solid-state reduced voltage motor rotation.
on an electrically isolated heat sink, a controller shall consist of a power sec-
logic board located above the power sec- tion, a one-piece printed circuit logic 16. Two (2) ground lugs shall be furnished,
tion and shall be used in series with a board and field wiring interface terminals. one (1) for incoming and one (1) for out-
separately specified electromagnetic going ground connections.
starter with class 10 overload protection. 3. The power section shall be three-phase,
60 hertz, and rated for the hp, current and 17. Power terminations shall consist of pres-
3. The power section shall be three-phase, voltage as shown on the drawings. It shall sure type terminals for top or bottom
60 hertz, and rated for the hp, current and consist of three (3) sets of back-to-back entrance.
voltage as shown on the drawings. It shall phase-controlled power semiconductors.
consist of three (3) sets of back-to-back Maximum current limit shall be 500% for 18. Enclosure
phase controlled power semiconductors. standard units.
a. Unit shall be supplied as an [open
4. Power semiconductors shall be rated with 4. Resistor/capacitor snubber networks shall panel] [NEMA 1 enclosed] [NEMA 12
peak inverse voltage at least 2.5 times be used to prevent false firing of SCRs enclosed].
rated line-to-line voltage. Suitably rated due to dv/dt effects. b. A door-mounted device panel shall be
snubbers for voltage suppression shall be provided for [field] [factory] mounting
included. 5. Fan cooled units shall be supplied with of operator’s devices.
thermal sensors on the heat sink to trip
5. The one-piece logic board shall be the control protective logic for over- 19. Units enclosed in motor control centers
mounted for easy testing and adjustment temperature condition. shall be of the same manufacturer as that
with quick disconnect plugs. Logic cir- of the circuit breaker and motor control
cuitry shall include: 6. The one-piece logic board shall be center for coordination and design issues.
mounted for easy testing, service and
a. Voltage ramp-up time adjustment – 5 replacement. 20. The manufacturer of the solid-state
to 45 seconds starter shall employ a field-based factory
b. Initial voltage adjustable from 20% to 7. Three-phase current sensing via current service organization for the purpose of
80% of rated voltage to provide for transformers for closed loop control to start-up and repair of units. Third party
optimum starting torque insure motor stability shall be provided. service contractors are not acceptable.
c. The logic boards of all current ratings
for a given voltage shall be inter- 8. The logic board shall use quick discon- Solid-State Reduced-Voltage Motor
changeable nect plug-in connectors for current trans- Starter Type ES
d. Each unit to be capable of multiple former inputs, line-and-load voltage
voltage operation inputs, SCR gate firing output circuits, 1. Motor starter shall be Cutler-Hammer
e. Optional smooth stop time adjustment and status panel. type ES.
from 5 to 45 seconds with an interlock
to release starter seal-in lock upon 9. The logic circuitry shall include as a 2. The solid-state reduced voltage motor
completion of stop cycle. Unit shall minimum: controller shall consist of a power sec-
automatically reset upon removal of
J line power. a. Inverse time running overcurrent
tion, a one-piece printed circuit logic
board and a field wiring interface termi-
protection nal board.
6. The solid-state logic shall be phase b. Auxiliary trip circuitry
sequence insensitive. c. Gate firing circuit lockout protection 3. The power section shall be three-phase,
on trip 60 hertz, and rated for the hp, current and
7. A cover plate shall be mounted above the d. Fault relay lockout protection voltage as shown on the drawings. It shall
logic board to provide: e. 250% to 500% current limit adjustment consist of three (3) sets of back-to-back
f. Initial voltage adjustment phase controlled power semi-conductors.
a. An insulating safety barrier g. Acceleration time adjustment. Maximum current limit shall be 500% for
b. Warning labels standard units.
c. Adjustment and setup instructions for 10. The logic board soldering shall be treated
current limit, time, torque, and horse- with a conformal protective coating 4. Resistor/capacitor snubber networks shall
power (ampere) ratings system. be used to prevent false firing of SCRs
d. Identified holes shall be located above due to dv/dt effects.
adjustment pots so that screwdriver 11. The logic board shall include, as stan-
adjustments can be achieved without dard, current and motor slip sensing cir- 5. Fan-cooled units shall be supplied with
removing the cover. cuitry that continually monitor motor load thermal sensors on the heat sink to trip
and regulate motor voltage to minimize the control protective logic for over-
8. Ground lug shall be furnished mounted motor kWh energy consumption. temperature condition. Thermal sensors
on the isolated heat sink. shall be rated 90 degree C maximum.
12. The solid-state logic shall provide phase
9. Enclosures sequence protection. 6. The one-piece logic board shall be
mounted for easy testing, service and
a. Enclosures shall be NEMA 3/12. 13. External interface circuitry shall include replacement.
120-volt relay logic interface capability.
CAT.71.01.T.E
Cutler-Hammer Reduced Voltage Motor Control J4-15
January 1999 Solid-State Motor Starters
Typical Specifications
7. Three-phase current sensing via current f. 200% to 500% current limit adjustment. 21. Maximum continuous operation shall be
transformers for closed loop control to at 120% of base amp rating.
insure motor stability shall be provided. 16. Two (2) ground lugs shall be furnished,
one (1) for incoming and one (1) for out- Reduced Voltage Bypass Motor
8. The logic board shall use quick discon- going ground connections. Starter Type EA
nect plug-in connectors for current trans-
former inputs, line-and-load voltage 17. Power terminations shall consist of 1. Motor starter shall be Cutler-Hammer
inputs, SCR gate firing output circuits and pressure-type terminals for top or bottom type EA.
status panel. entrance.
2. The solid-state reduced voltage starter
9. The logic circuitry shall include as a 18. Enclosure shall be UL and CUL listed and consist of
minimum: an SCR based power section, logic board
a. Unit shall be supplied as an [open and paralleling bypass contactor.
a. Short-circuit electronic trip overcur- panel] [NEMA 1 enclosed] [NEMA 12
rent protection. Time not to exceed enclosed] 3. The SCR based power section shall con-
1/2 cycle
b. Enclosures shall not be less than 16- sist of six (6) back-to-back SCRs and shall
b. Inverse time running overcurrent gauge steel. Type 12 enclosures shall be rated for a minimum peak inverse volt-
protection be of welded construction with gas- age rating of 1500 volts PIV.
c. Auxiliary trip circuitry keted heat sink and doors
d. Gate firing circuit lockout protection c. Doors shall include plastic device 4. Units using triacs or SCR/diode combina-
on trip holders for mounting up to six (6) tions shall not be acceptable.
e. Fault relay lockout protection (eight (8) for above 200 hp motors)
f. 250% to 500% current limit adjustment operator devices 5. Resistor/capacitor snubber networks shall
g. Minimum and maximum voltage d. The following shall be included: be used to prevent false firing of SCRs
adjustments due to dv/dt effects.
h. Voltage stability adjustment. 1. The operating handle of the dis-
connect, when supplied, shall 6. The logic board shall be mounted for
10. The logic board soldering shall be treated always remain connected to the ease of testing, service and replacement.
with a conformal protective coating breaker or switch. The operating It shall have quick disconnect plug-in con-
system. handle shall not be mounted on nectors for current transformer inputs,
the door of the enclosure, but on line and load voltage inputs and SCR gate
11. The logic board shall include, as stan- the controller for safe “stand- firing output circuits.
dard, current and motor slip sensing cir- aside” operation. The position of
cuitry that continually monitor motor load the operating handle will indicate 7. The logic board shall be identical through
and regulate motor voltage to minimize ON or OFF position of switch or all ampere ratings and voltage classes
motor kWh energy consumption. circuit breaker and include provi- and shall be conformally coated to pro-
sion for padlocking in the OFF tect for environmental concerns.
12. The solid-state logic shall provide phase position.
sequence protection. 8. The paralleling bypass contactor shall
2. Interlock provisions shall prevent energize when the motor reaches full
13. External interface circuitry shall include unauthorized opening or closing of speed and close/open under one (1) times
120-volt relay logic interface capability. the starter door with the discon- motor current.
nect in the ON position.
14. Tripped functions shall be designed to be 9. The contactor shall be fully rated for
cleared by removing power from the 3. The structure, when floor-mounted,
solid-state logic board. shall be provided with adequate
lifting means and shall be capable
across-the-line starting duty should this
be desired. J
15. The starter shall have additional features of being rolled or lifted into instal- 10. The contactor shall utilize an energy bal-
as follows: lation position and bolted to the anced contact closure to limit contact
floor. bounce and an intelligent coil controller
a. Individual light emitting diodes (LEDs) to optimize coil voltage during varying
to indicate run, undervoltage, phase 4. A door-mounted status panel shall system conditions.
loss, phase current unbalance, over- provide individual light emitting
current trip, overtemperature, current diodes (LEDs) to indicate run, 11. The coil shall have a lifetime warranty.
limit, end of ramp, and incorrect phase undervoltage, phase loss, phase
rotation current unbalance, overcurrent 12. The overload protection shall be elec-
b. Single-phase protection with built-in trip, overtemperature, current tronic and be based on an inverse time-
short time delay limit, end of ramp, and incorrect current algorithm.
c. Undervoltage protection with built-in phase rotation.
short time delay 13. Overload protection shall be adjusted via
d. The power section shall have metal 19. Units enclosed in motor control centers logic board.
oxide varistor (MOV) type surge sup- shall be of the same manufacturer as that
pressors across the SCRs rated 10% of the circuit breaker and motor control 14. Class 10 or 20 overload characteristic
above the rated voltage. The power center for coordination and design issues. shall be selectable.
semiconductors shall be rated with
peak inverse voltage at least 2.5 times 20. The manufacturer of the solid-state 15. Units using bimetal overload relays are
SCR rated line-to-line voltage. Suitably starter shall employ a field-based factory not acceptable.
rated snubbers for voltage suppres- service organization for the purpose of
sion shall be included. start-up and repair of units. Third party 16. Overtemperature protection (on heat
e. 100% to 120% full load running cur- service contractors are not acceptable. sink) shall be standard.
rent trip adjustment
CAT.71.01.T.E
Reduced Voltage Motor Control Cutler-Hammer
J4-16
Solid-State Motor Starters January 1999
Typical Specifications
17. The solid-state logic shall be phase sensi- 21. The following logic board adjustments 24. Starters and breakers/HMCPs are to rated
tive, and shall inhibit starting on incorrect are required: per UL 508D for a withstand rating of 65
rotation. kAIC RMS.
a. Ramp Time; 1 to 45 seconds, on a
18. Improper phase rotation shall be indi- hexadecimal switch 25. Units enclosed in motor control centers
cated on the starter logic board. b. Initial Torque; 100 to 200% current, on shall be of the same manufacturer as that
a hexadecimal switch of the circuit breaker and motor control
19. Starters shall protect against a phase c. Current limit; 100 to 500% current, on center for coordination and design issues.
loss/unbalance condition shutting down if a hexadecimal switch
a 35% current differential between any d. FLA of motor; 4 to 1 range of starter, 26. The manufacturer of the solid-state
two phases is encountered. on a DIP switch. starter shall employ a field-based factory
service organization for the purpose of
20. A normally open (NO) contact shall 22. Optional smooth stopping shall provide a start-up and repair of units. Third party
annunciate fault conditions, with contact linear voltage deceleration should the service contractors are not acceptable.
ratings of 60 VA (resistive load) and 20 VA load require it. It is to be adjustable from
(inductive load). In addition, an LED dis- 1 to 75 seconds. 27. Maximum continuous operation shall be
play on the logic board shall indicate type at 115% of continuous ampere rating.
of fault (current trip, phase loss, phase 23. Enclosed units shall include a thermal
rotation). magnetic circuit breaker or HMCP for
short-circuit protection and quick discon-
nect means.
CAT.71.01.T.E