Sie sind auf Seite 1von 12

Original Article

Proc IMechE Part I:


J Systems and Control Engineering
2014, Vol. 228(4) 245–256
Flow versus pressure control of pumps Ó IMechE 2013
Reprints and permissions:
in mobile hydraulic systems sagepub.co.uk/journalsPermissions.nav
DOI: 10.1177/0959651813512820
pii.sagepub.com

Mikael Axin, Björn Eriksson and Petter Krus

Abstract
This work studies an innovative working hydraulic system design for mobile applications, referred to as flow control.
The fundamental difference compared to load-sensing systems is that the pump is controlled based on the operator’s
command signals rather than feedback signals from the loads. This control approach enables higher energy efficiency
since the pressure difference between pump and load is given by the system resistance rather than a prescribed pump
pressure margin. Furthermore, load-sensing systems suffer from poor dynamic characteristics since the pump is oper-
ated in a closed-loop control mode. This might result in an oscillatory behaviour. Flow control systems have no stability
issues attached to the load pressure feedback since there is none. This allows the pump to be designed to meet the
response requirements without considering system stability. Pressure compensators are key components in flow control
systems. This study addresses the flow matching problem which occurs when using traditional compensators in combi-
nation with a flow-controlled pump. Flow sharing pressure compensators solve this problem since the pump flow will be
distributed between all active functions. Simulation results and measurements on a wheel loader application demonstrate
the energy-saving potentials and the dynamic improvements for the flow control system.

Keywords
Hydraulics, flow control, load-sensing, mobile systems, energy efficiency, dynamic characteristics, compensators

Date received: 29 August 2013; accepted: 15 October 2013

Introduction on the operator’s command signals when using an


electro-hydraulic pump controller. The pump displace-
Mobile hydraulic applications distinguish themselves ment setting is then controlled according to the sum of
from other hydraulic applications, such as industrial all requested load flows. This control approach enables
hydraulics, because the pressure and flow demand var- higher energy efficiency since the pressure difference
ies greatly over time and between different functions. between pump and load is given by the system resis-
Unlike other hydraulic applications, several functions tance rather than a prescribed pump pressure margin.
are often supplied by a single pump. This means that Furthermore, it also improves the dynamic characteris-
the total installed power on the actuator side is gener- tics since the pump is no longer operated in a closed-
ally considerably higher than the installed pump power. loop control mode.
This is possible because the actuators almost never In the literature, different researchers have used dif-
require their maximum power at the same time. The ferent names for systems where the pump displacement
need for only one system pump makes the hydraulic setting is controlled according to the sum of all
system compact and cost-effective. requested load flows. Initial considerations regarding
Other important properties of mobile hydraulic sys- this pump control strategy were patented by Stenlund1
tems are energy efficiency and controllability character-
istics. For these reasons, development has been pushed
towards load-sensing systems, which is state of the art in Division of Fluid and Mechatronic Systems, Department of Management
industry today. Load-sensing systems often use a hydro- and Engineering, Linköping University, Linköping, Sweden
mechanical pump controller. However, the development
of electro-hydraulic pump controllers opens up new pos- Corresponding author:
Mikael Axin, Division of Fluid and Mechatronic Systems, Department of
sibilities in terms of innovative pump control strategies. Management and Engineering, Linköping University, SE-581 83 Linköping,
Instead of using feedback signals from the loads, it is Sweden.
possible to control the pump displacement setting based Email: mikael.axin@liu.se

Downloaded from pii.sagepub.com at PENNSYLVANIA STATE UNIV on April 8, 2016


246 Proc IMechE Part I: J Systems and Control Engineering 228(4)

(a) (b)

Figure 1. Different system designs commonly used for the working hydraulics in mobile applications: (a) system with open-centre
valves and a fixed displacement pump and (b) system with pressure-compensated load-sensing valves and a pressure-controlled
variable displacement pump.

in the late 1980s under the name ‘Electrohydraulic Simulation and experimental results confirming the the-
guide system’. Similar ideas were published by Zähe2 in oretical expectations are also presented.
1993 under the name ‘Summenstromreglerung’, which
roughly means ‘aggregate flow control’. However, suit-
able electro-hydraulic components were not available Mobile working hydraulic systems
until several years later. In 2004, research intensified.3–5 Fluid power systems have been used successfully in
Jongebloed et al.3 used pressure sensors at all load mobile machines for several decades. Because of the
ports for the valve control, calling the system ‘load con- machines’ versatility, different hydraulic systems have
trol system (LCS)’. Djurovic6 studied a system design been developed for different applications. Important
with traditional pressure compensators, which requires properties of hydraulic systems are energy efficiency,
the pump flow to be matched against the sum of all dynamic characteristics, controllability and system
load flows, sometimes referred to as the ‘flow matching complexity. However, the order of importance of these
problem’.7 Consequently, he used the notation ‘electro- properties varies for different applications. This section
hydraulic flow matching (EFM)’, which is a proprie- gives an overview of the most commonly used working
tary Bosch Rexroth brand name.8 Fedde and Harms9 hydraulic systems of today. It also presents some inno-
studied a similar system design and used the notation vative system designs that have not yet been commer-
‘flow demand system’. They used a bleed-off valve to cialized but are attracting considerable attention both
deal with the flow matching and studied the pros and in industry and academia. Energy efficiency, dynamic
cons of overflow and underflow from the pump. characteristics, controllability and system complexity
Finzel10 continued Djurovic work and introduced flow are discussed and compared.
sharing compensators. Such compensators distribute Today, most hydraulic systems in mobile machines
the entire pump flow relative to the individual valve are operated with open-centre valves and fixed displa-
openings, thus eliminating the flow matching problem. cement pumps (see Figure 1(a)). Such systems can be
Axin11 studied the pros and cons of different types of considered to be relatively simple, robust and cost-
compensator design in combination with a flow- effective, but also often inefficient. These systems suffer
controlled pump, including the dynamic properties, from load interference, which means that the pressure
calling the system ‘flow control system’. In later publi- level at one load can heavily influence the velocity of
cations, Scherer et al.12 proposed a solution to deal another actuator. Furthermore, the flow rate is not
with a cylinder reaching its end stop and refer to the only dependent on spool position but also on load pres-
circuit as ‘flow-on-demand system’. sure, often referred to as load dependency. From a con-
This study gives an overview of the pros and cons of trollability point of view, this is often considered a
controlling the pump according to the sum of all drawback, but skilled operators can actually use this
requested load flows. Pressure compensators, energy information feedback from the system to their advan-
efficiency and dynamic characteristics are discussed tage. From a dynamic point of view, load dependency
and compared to conventional load-sensing systems. is a desired property. It gives the system a naturally

Downloaded from pii.sagepub.com at PENNSYLVANIA STATE UNIV on April 8, 2016


Axin et al. 247

high damping, which means that the system is less One hot research topic in the area of mobile hydrau-
prone to oscillations. To obtain damping from a valve, lics is systems in which the control valves are eliminated
the flow has to increase when the pressure drop across along with the metering losses. Multiple concepts have
the valve increases and vice versa. Damping is a pre- been developed, including pump-controlled actuators,
ferred property when handling large inertia loads, for hydraulic transformers and electro-hydraulic actuators
example, the swing function of a mobile crane. (EHAs).23 Such systems are not yet common commer-
Constant pressure systems improve the controllabil- cially in mobile applications but can be found in, for
ity compared to open-centre systems since it has no example, the aerospace industry.24
load interference issues. Other characteristics, such as Instead of using one pump to supply all actuators,
efficiency and dynamics, are similar to open-centre sys- every actuator has a dedicated pump in pump-
tems, and the complexity is slightly higher, mainly controlled actuator systems. To control the speed, the
because constant pressure systems often use a pressure- pump displacement setting is used as the final control
controlled variable displacement pump. It is, however, element. All losses are thereby ideally eliminated. In
possible to increase the energy efficiency of constant reality, the losses are heavily dependent on the effi-
pressure systems by, for example, using secondary ciency of the system pumps.23 These systems can princi-
control13 or introducing an intermediate pressure line.14 pally be differentiated in two different circuit layouts,
Load-sensing systems improve the energy efficiency either with the pump arranged in a closed circuit25,26 or
compared to open-centre and constant pressure systems in an open circuit.27
by continuously adapting their pressure just above the A hydraulic transformer converts an input flow at a
highest load. A pressure difference, usually around 20– certain pressure level to a different output flow at the
30 bar, between pump and load is necessary to over- expense of a change in pressure level, ideally maintain-
come losses in hoses and valves. This pressure margin is ing the hydraulic power. One way of realizing a trans-
often set substantially higher than necessary to ensure it former is to combine two hydraulic machines, where at
is high enough at all operational points. A load-sensing least one has a variable displacement. However, the
valve is often equipped with a pressure compensator efficiency is limited, mainly because at least one of the
which controls the pressure drop across the directional machines will operate under partial loading.28 In recent
valve (see Figure 1(b)). Different loads can thereby be years, an innovative transformer concept has been
operated almost without load interference and load developed by the Dutch company Innas BV.29 The con-
dependency, giving excellent controllability properties. ventional transformer with two hydraulic machines has
An early review of load-sensing systems was made by been replaced by one axial piston unit, thereby avoiding
Andersson.15 partial loading conditions. A mean efficiency of 93% in
One weakness of load-sensing systems using a broad region of operation has been reported.30
pressure-compensated valves is the hydraulic damping. The main component in EHA systems is a fixed dis-
The primary design endeavours to achieve low influ- placement bidirectional hydraulic pump. An electric
ence on the flow from the load pressure. This decreases motor is usually used to power the pump, enabling
the damping capability of the valve. When using pres- active control of the rotational speed and thereby the
sure compensators, only the outlet orifice in the direc- flow to the actuator. A conventional EHA requires a
tional valve will provide damping to the system.16,17 symmetrical actuator in order to ensure flow balance,
Furthermore, the pump in load-sensing systems is con- but solutions for handling asymmetrical cylinders have
trolled in a closed-loop control mode, where the highest been proposed.31 In EHA systems, the pump only oper-
load is the feedback signal. At certain points of opera- ates when control action is needed.
tion, this might result in an oscillatory behaviour. A When more than one load is actuated, often only the
complete investigation of load-sensing systems and heaviest load can be operated efficiently in single-pump
their dynamic properties, including pump controllers, systems. This issue is resolved in valveless systems.
can be found in Krus.18 The dynamics of pressure- When all loads have their own dedicated pump, the
compensated valves have been studied in, for example, pressure can always be matched against the present
Pettersson et al.19 and Wu et al.20 load. However, one has to bear in mind that valveless
A step forward from load-sensing systems using systems may require several valves to handle, for exam-
conventional spool valves is to decouple the inlet and ple, asymmetric cylinder actuation, and meet safety
the outlet orifices in the directional valve. Numerous requirements.23,27
configurations for individual metering systems have Furthermore, since all actuators have their own dedi-
been developed, both in academia and in industry.21 cated pump in the valveless concepts, each has to be
These concepts provide a higher degree of freedom as sized to handle maximum speed. A typical example of a
all four orifices are separated and can be controlled dimensioning motion is the lowering boom motion in a
individually. The main benefit of this increased free- wheel loader. The lowering flow can be several times
dom is that the flow paths can be changed during higher than the maximum pump flow in a similar valve-
operation. Four different operational cases can be controlled system. The difference is that all flows have
identified: normal, regenerative, energy neutral and to be handled by the pump in valveless system layouts.
recuperative.22 In single-pump systems, the pump can be downsized

Downloaded from pii.sagepub.com at PENNSYLVANIA STATE UNIV on April 8, 2016


248 Proc IMechE Part I: J Systems and Control Engineering 228(4)

since not every load is actuated at full speed simultane- sensors at all load ports for the valve control. To opti-
ously very often. For these reasons, the total installed mize energy efficiency, the valve at the highest load can
displacement tends to be high in valveless systems. be opened to its maximum while lighter loads are con-
When improving energy efficiency in fluid power sys- trolled by their valve openings.
tems, the trend is to use additional components and These controllability issues can also be resolved by
more sophisticated control algorithms.32,33 Meanwhile, using pressure compensators. There will, however, be
basic constraints such as space requirements, initial cost different demands on the compensator functionality
and control complexity are often overlooked. This work compared to load-sensing systems, but it also opens up
investigates how far it is possible to improve traditional new possibilities regarding the valve control.
load-sensing systems by changing the pump controller
from a closed-loop pressure control mode to an open Pressure compensators
control mode where the pump displacement setting is
controlled based on the sum of all requested load flows. Pressure compensators are commonly used in mobile
Only one electrically controlled pump and conventional applications to improve the controllability characteris-
spool valves are needed. Sensors are not required to tics. Basically, two different types of compensators can
achieve the desired functionality, and all components be realized: traditional and flow sharing. Both these
needed are available in the market.8 In this work, the types can be realized by placing the compensator either
system will be referred to as flow control. upstream or downstream of the directional valve (see
Figure 2).
Traditional compensators control the absolute flow
The flow control concept through the directional valve by reducing the pump
pressure relative to the load pressure of its own load.
In mobile hydraulic systems, the actuation of different This works fine as long as the pump pressure is actively
loads is controlled by joystick signals. These signals controlled, for instance, with a load pressure feedback.
pose either a flow or pressure demand from the opera- In case of the pump being saturated, the supply pres-
tor. In applications with high demands on controllabil- sure will drop, resulting in the heaviest load losing
ity, the signals from the operator often correspond to speed or even stopping.
flow demands. An example is load-sensing systems Flow sharing compensators act as relief valves
equipped with pressure compensators. Nevertheless, instead of reducing valves, which means that all func-
the pump in these kinds of systems is still often pressure tions will be given the same priority. The entire pump
controlled. flow will thus be distributed relative to the individual
In systems where the operator’s signals correspond valve openings also when the pump is saturated. A
to flow demands, it seems more natural to also control pressure-controlled pump which has been saturated
the pump by flow. This approach has some benefits cannot control the pressure and can therefore be seen
regarding energy efficiency, dynamic characteristics as a flow-controlled pump. Flow sharing compensators
and increased flexibility compared to load-sensing sys- are therefore appropriate to use together with a flow-
tems. It also presents some challenges, for example, the controlled pump.
compensator design.
The idea of flow control is to use the joystick signals
to control the pump flow and the valve openings simul- Pump and valve control approaches
taneously. The pump displacement setting is controlled In flow control systems, the operator’s joystick signals
according to the sum of all requested load flows. control the pump flow and the valve opening simulta-
When no function is activated, the pump is neously. For this to work properly, the system software
de-stroked, delivering no flow to the system, and all needs knowledge about every flow consumer. However,
directional valves are closed. Activating a joystick will solutions for attaching auxiliary functions have been
simultaneously open a valve and increase the displace- proposed.7,34 Different control approaches are possible
ment of the pump. Pressure is built up in the pump whether traditional or flow sharing compensators are
hose, and when the pump pressure becomes higher than used.
the load pressure, there will be a flow to the actuator. When using traditional pressure compensators (see
When stationary, the flow delivered by the pump will Figure 3(a)), the absolute flow through the valve is
go to the load. The pump pressure will therefore adapt determined by the valve opening. This means that the
itself to a level needed by the system, resulting in effi- pump flow has to be matched against the sum of all
ciency improvements compared to load-sensing systems. expected load flows. If this is not the case, the following
If more than one load is activated, all actuators will two situations may occur.
suffer from both load interference and load depen-
dency. This can be resolved by introducing sensors to The pump flow is too low. This is the same case as when
the system. Stenlund1 and Zähe2 used the velocities of the pump is saturated in load-sensing systems. The
the actuators as the main feedback signals for pump compensator spool at the highest load will open com-
and valve control. Jongebloed et al.3 used pressure pletely, resulting in a decrease in speed for that load.

Downloaded from pii.sagepub.com at PENNSYLVANIA STATE UNIV on April 8, 2016


Axin et al. 249

As qL As qL
pr
ps pr pL ps pL
Fs Fs

(a) (b)

pLmax
Fs
As qL As qL
ps
pr pL ps pr pL
Fs
pLmax
(c) (d)

Figure 2. Four different ways of realizing a pressure compensator. Traditional compensators control the absolute flow through the
directional valve, while flow sharing compensators distribute the entire pump flow relative to the valve openings: (a) traditional
compensator placed upstream of the directional valve, (b) traditional compensator placed downstream of the directional valve,
(c) flow sharing compensator placed upstream of the directional valve and (d) flow sharing compensator placed downstream of
the directional valve.

The pump flow is too high. Both compensator spools There are alternatives to address this flow matching
will close more and the pump pressure will increase problem without adding additional components or sen-
until the system relief valve opens. The throttle losses sors to the system. The key is to implicate the highest
will be huge and the system will emerge as a constant load pressure into the compensator and thus get the
pressure system. flow sharing behaviour described in the previous sec-
tion (see Figure 3(b)). The entire pump flow will then
The reason for this is that both the pump and the be distributed relative to all active functions and there
valves control the absolute flow, resulting in an overde- will be no flow matching issues. Instead of controlling
termined flow situation. A lot of research solving this the flow, the valves will serve as flow dividers. This has
flow matching problem has been presented. Djurovic been studied in, for example, Latour8 and Finzel and
and Helduser4 introduced a position sensor placed on Helduser.38
the directional valve. This gives precise knowledge of Using a flow-controlled pump in combination with
the flow expected by the valve. It is also possible to flow sharing pressure compensators opens up new pos-
equip the compensator with a position sensor.5 If no sibilities in terms of controlling the directional valves
compensator is close to be fully opened, the pump flow independently of the cylinder velocities.11 One control
is too high. In case of the pump flow being too low, the approach is to open the valve section at the load with
compensator at the highest load would be completely the highest flow demand to its maximum.39,40 Other
opened. A bleed-off valve to tank is proposed by sev- active functions must always be opened in proportion
eral authors.4,5,34 A small overflow is then acceptable, to its flow request. This control approach will minimize
which could be used in closed-loop control if a position the pressure drop across the directional valves and thus
sensor is added. Fedde and Harms9 discuss the pros save energy.
and cons of overflow and underflow when using a Another control approach would be to use the valves
bleed-off valve. Grösbrink and colleagues35,36 propose to increase the system damping. There is an optimal
a system design where the pump is pressure controlled valve opening where the damping is maximized.41 For
for low pump flows and flow controlled for high flow example, when a function is oscillating, the valve open-
rates. It is also possible to shift from flow control to ing could be reduced temporarily in order to dampen
pressure control in case of an undesirable pressure the oscillations. When no oscillations are present, a
build-up.37 more energy-efficient control strategy can be used.

Downloaded from pii.sagepub.com at PENNSYLVANIA STATE UNIV on April 8, 2016


250 Proc IMechE Part I: J Systems and Control Engineering 228(4)

(a) (b)
Figure 3. Two different flow control system designs. The operator joystick signals control the pump displacement setting and the
valve openings simultaneously: (a) simplified schematic of a flow control system using traditional compensators. The system can also
be realized with traditional compensators placed downstream of the directional valves. (b) Simplified schematic of a flow control
system using flow sharing compensators. The system can also be realized with flow sharing compensators placed downstream of the
directional valves.

Energy efficiency This is the case at partial loading conditions. The smal-
lest possible loss occurs when the compensator is fully
The energy efficiency of flow control systems is similar
opened. In that case, the required pressure drop
to that of load-sensing systems. The pump pressure is
increases with the square of the flow rate.
adjusted according to the highest load, and high losses
Losses across the directional valve. Typically, the com-
might occur when loads with different pressure
pensator ensures that the pressure drop across the
demands are operated simultaneously. However, directional valve is constant. However, the smallest
instead of a prescribed pressure margin, as in load- possible pressure drop occurs if the valve is fully open.
sensing systems, the pressure drop between pump and The pressure drop will then follow the flow equation,
load is given by the resistance in the hoses and in the similar to the compensator pressure drop.
valves. Furthermore, it is also possible to lower the
pressure drop across the directional valve by opening In Figure 4(a), these three different losses are shown.
the valve at the load with the highest flow demand to If the pressure margin is set perfectly, there will be no
its maximum. unnecessary losses at maximum flow rate in load-
In load-sensing systems, the pump pressure margin sensing systems. However, at lower flow rates, unneces-
is set to overcome the losses in the pump hose, the com- sary losses will occur. In flow control systems, these
pensator and the directional valve. These losses are sys- losses will be eliminated since the pump pressure is set
tem dependent and will change with internal and by the resistance in the hose and the valve.
external conditions such as temperature, oil properties It is possible to further reduce the losses in flow con-
and hose length. The pressure margin is set according trol systems. This is done by opening the valve section
to the worst case to ensure it is high enough at all oper- with the highest flow demand to its maximum, in which
ating points. case the pressure drop across the directional valve is
The pressure drop between pump and load can be minimized and additional energy savings are possible
divided into the following three different losses: (see Figure 4(b)).
A flow control system without pressure compensa-
Losses between pump and valve. There will be a pressure tors would increase the efficiency even further. In that
drop between the pump and the valve. The magnitude case, the valve section at the highest load might be
will depend on the internal and external properties opened completely. However, its functionality requires
mentioned above, but most importantly the flow rate. closed-loop control and is therefore sensor dependent.3
A simplified model is that the losses increase with the As can be seen in Figure 4, the two system layouts
square of the flow rate. have the same efficiency at maximum flow rate if the
Losses across compensator. There will be a pressure pump pressure margin is set perfectly in the load-
drop across the compensator. High losses occur if the sensing system. Flow control systems have higher effi-
supply pressure is much higher than the load pressure. ciency for smaller flow rates. However, it is important

Downloaded from pii.sagepub.com at PENNSYLVANIA STATE UNIV on April 8, 2016


Axin et al. 251

directionalvalvelosses fullyopeneddirectionalvalve

Pumppressuremargin[-]
Pumppressuremargin[-]

compensa
compensa
sses ents
rylo provem
c essa yim
unne ienc
effic

torlosses
torlosses
es es
loss loss
hose hose

Flow[-] Flow[-]
(a) (b)

Figure 4. Classification of the losses between pump and load. Three different losses occur: hose, compensator and directional valve
losses. At lower flow rates, unnecessary losses occur in load-sensing systems. No unnecessary losses occur in flow control systems.
(a) The pump pressure margin is fixed in load-sensing systems and unnecessary losses therefore occur at lower flow rates. (b) The
pump pressure margin is given by the system resistances in flow control systems. Efficiency improvements are therefore possible.

without increasing the total installed displacement.


fully opened This is achieved by connecting the two pumps when
directional valve high flow rates are required by one load. Connecting
several pumps at high flow rates is a common solution
for more simple systems, for example, in excavators.
Power [-]

Dynamic characteristics
power savings The only difference between load sensing and flow con-
trol is the absence of the feedback to the pump control-
ler in flow control systems. Nevertheless, there are
fundamental dynamic differences between the two sys-
Flow [-]
tem layouts.
The dynamic behaviour of load-sensing systems can
Figure 5. Power savings in flow control systems compared to be described by equations (1)–(4).44 By reducing the
load-sensing systems. More power can be saved if the block diagram shown in Figure 6(a), the open-loop
directional valve is completely opened. No power is saved at transfer function from desired pump pressure margin
maximum flow rate if the pressure margin is set perfectly in DPpref to actual pressure difference DPp = Pp  PL can
load-sensing systems. be derived according to equation (5)
Qp 1
Gp = = ð1Þ
to consider the power losses rather than the pressure DPpref  DPp Lp s
losses. For low flow rates, the power loss will be small Pp 1
even for high pressure drops. Figure 5 shows the power Hs = = ð2Þ
Qp  QL Cp s
saving opportunities for flow control systems. The larg-
QL
est power savings occur in the medium flow rate area. Gv = = Kc ð3Þ
If the directional valve is opened completely, even more Pp  PL
power can be saved. PL mL s + Bp
ZL = = ð4Þ
Flow control systems have no unnecessary losses for QL CL mL s2 + CL Bp s + A2c
the highest load. All losses that occur are necessary and Hs
limited by, for example, the diameter of the hoses and Gp Go = Gp ð5Þ
1 + Gv (ZL + Hs )
the maximum opening areas in the valve. However,
flow control systems still have high losses under partial By closing the control loop, the pump controller,
loading conditions. To increase efficiency even further, Gp , is a part of the loop gain, Gp Go , as shown in Figure
individual metering valves or additional hydraulic 6(b). To achieve a stable system, the loop gain must be
machines are required. kept lower than unity when the phase crosses 2180°.
A flow control system with two hydraulic pumps On the other hand, it would be feasible to increase the
has been studied by Finzel et al.42,43 The aim is to gain of the pump and its controller to achieve a system
reduce the losses under partial loading conditions that meets the response requirements. To achieve a

Downloaded from pii.sagepub.com at PENNSYLVANIA STATE UNIV on April 8, 2016


252 Proc IMechE Part I: J Systems and Control Engineering 228(4)

ΔPp,ref +
Qp + Pp + ΔPp QL
Gp Hs Gv
− − −
PL ΔPp,ref +
ΔPp
ZL Gp Go

1
Gv

(a) (b)

Figure 6. Linear model of a load-sensing system: (a) block diagram of a load-sensing system derived from equations (1)–(4) and
(b) rearranged block diagram with the loop gain GpGo.

0
log10 (G p Go ) [-]

−1

−2 1.4

−3
mL increasing 1.2
−4
100 101 102 103 Pump pressure margin [-] 1

0.8

−90
0.6
Phase [ ]

° −180 mL increasing 0.4

0.2
mL = 30000 kg
−270
mL = 6000 kg
0
100 101 102 103 0 0.2 0.4 0.6 0.8 1
Frequency [rad/ s] Time [-]
(a) (b)

Figure 7. Dynamic characteristics of load-sensing systems. The parameter values are shown in Table 1. At specific points of
operation, load-sensing systems may become unstable. Flow control systems have no such stability issues due to the absence of the
feedback to the pump controller: (a) bode plot of the open-loop gain in Figure 6(b), Gp Go and (b) step response of the closed-loop
gain in Figure 6(b), Gp Go .

Table 1. Parameter values used in Figure 7. feedback to the pump controller (see Figure 8). This
results in a fundamental dynamic difference between
Parameter Value Unit load-sensing systems and flow control systems. Since
Ac 0.005 m2 there is no closed loop for the pump controller, the sta-
Bp 10,000 Ns/m bility issues described above are eliminated. The pump
CL 4 3 10212 m3/Pa and its controller can thereby be designed to meet the
Cp 5 3 10212 m3/Pa response requirements without considering system sta-
Kc 1 3 1029 m5/Ns bility. This has been verified by experiments in Latour8
Lp 5 3 108 Pas2/m3
mL [6000; 12,000; 30,000] kg and Finzel and Helduser.38

system, with the desired response, the gain of the pump


Simulation results
controller is increased, but at the same time, the system A non-linear simulation model has been built in
is approaching its stability limit. One should bear in Hopsan45,46 to illustrate some of the differences
mind that stability at one operational point will not between load sensing and flow control. The model con-
guarantee stability at another (see Figure 7). sists of a pump, a directional valve and a cylinder load.
The dynamic behaviour of flow control systems can A step is made in the valve opening area and also in
be described by almost the same set of equations (equa- the external force according to Figure 9. The load-
tions (1)–(4)). The only difference is the absence of the sensing system model is more oscillative in both cases.

Downloaded from pii.sagepub.com at PENNSYLVANIA STATE UNIV on April 8, 2016


Axin et al. 253

Q pre f Qp + Pp + ΔPp QL
Gp Hs Gv
− −
PL Q pre f ΔPp
ZL Gp Go

(a) (b)

Figure 8. Linear model of a flow control system: (a) block diagram of a flow control system derived from equations (1)–(4) and
(b) rearranged block diagram with no feedback present.

0.95 0.26
0.9
0.24
Valve opening area, external force [-]

0.85
0.8
0.22

Velocity [m/s]
0.75
0.7 0.2
0.65
0.18
0.6
0.55
0.16
0.5 External force Load sensing
Valve opening area Flow control
0.45
0 2 4 6 8 10 0 2 4 6 8 10
Time [s] Time [s]
(a) (b)
150 0.62

145 0.6
0.58
140
Pump displacement setting [-]

0.56
135
Pressure [bar]

0.54
130 0.52

125 0.5
0.48
120
0.46
115 Load sensing 0.44 Load sensing
Flow control Flow control
110 0.42
0 2 4 6 8 10 0 2 4 6 8 10
Time [s] Time [s]
(c) (d)

Figure 9. Simulation results of a load-sensing system model and a flow control system model. The load-sensing system model is
more oscillative due to its closed-loop pressure control: (a) a step is made in the valve opening area after 3 s and in the external
force after 6 s, (b) cylinder velocities as a function of time, (c) cylinder pressures as a function of time and (d) pump displacement
settings as a function of time.

It can also be noted that the pump displacement setting a wheel loader application with an operational weight
for the load-sensing system is oscillating when a step is of 6900 kg. The machine was equipped with a pump
made in the external force, although the velocity should that can be operated in both pressure and flow control
remain constant. modes and a valve prepared for use with both tradi-
tional and flow sharing compensators, placed upstream
of the directional valve.
Experimental results
In Figure 10(c), the pump pressure margin for both
To verify the energy efficiency improvements in the the load-sensing and the flow control systems can be
flow control concept, measurements were performed on seen. The measurements agree with the theoretical

Downloaded from pii.sagepub.com at PENNSYLVANIA STATE UNIV on April 8, 2016


254 Proc IMechE Part I: J Systems and Control Engineering 228(4)

150 50
45
40
35
100

Pressure [bar]
30
Flow [l/min]

25
20
50
15
10
5
0 0
0 1 2 3 4 5 6 0 1 2 3 4 5 6
Time [s] Time [s]
(a) (b)
30

25 Load sensing

20
Pressure [bar]

15

10 ol
ntr
co
w
Flo
5

0
0 20 40 60 80 100
Flow [l/min]
(c)

Figure 10. Experimental results showing the potential of reducing the pump pressure margin in flow control systems compared to
load-sensing systems. (a) Measured flow for both systems. The flow is increased from 0 to maximum. (b) Measured pump pressure
margin for both systems while the flow is increased. (c) Measured pump pressure margin as a function of measured flow. Load-
sensing systems have a constant margin, while flow control systems have a margin given by the system resistances.

pressure margin as shown in Figure 4(b). The flow sent article. The fundamental difference between flow con-
by the pump is similar in both systems (see Figure trol and load sensing is that the load pressure feedback
10(a)). It can also be observed in Figure 10(b) that the hose to the pump controller can be removed. Instead of
pressure is more oscillative in the load-sensing system. controlling the pump in a closed-loop control mode, an
This is because the pump controller operates in a open control mode can be used with no feedback pres-
closed-loop control mode.18 ent. This makes the system design process simpler since
A short loading cycle47 has also been performed to the pump can be designed to meet the response require-
compare load sensing and flow control. Only the work- ments without considering system stability. As long as
ing hydraulics have been taken into consideration, nei- the pump is stable as an isolated component, it will not
ther the steering nor the transmission. For this cause any stability issues in the complete system. In
particular application, the energy consumption was load-sensing systems on the other hand, an apparently
reduced by 14% for the flow control system.40 This is stable pump can cause instability in the complete
the same order of magnitude as in experiments per- system.
formed in Mettälä et al.34 and Finzel and Helduser.38 Flow control systems are more energy efficient com-
pared to load-sensing systems. This is because the pres-
sure difference between pump and load is given by the
Conclusion
system resistance rather than a prescribed pump pres-
A system design where the pump displacement setting sure margin. The two system layouts have the same
is controlled based on the operator’s command signals efficiency when the pump is saturated. However, at all
rather than maintaining a certain pressure margin other operational points, flow control systems have
above the highest load pressure has been studied in this higher energy efficiency than load-sensing systems.

Downloaded from pii.sagepub.com at PENNSYLVANIA STATE UNIV on April 8, 2016


Axin et al. 255

There are also potential energy savings tied to the 11. Axin M.Fluid power systems for mobile applications –
absence of active control of the pump. with a focus on energy efficiency and dynamic charac-
It is possible to combine flow control with other teristics. Licentiate Thesis, Linköping University,
working hydraulic systems. For example, flow control Linköping, 2013.
could be used as a complement to pump-controlled 12. Scherer M, Geimer M and Weiss B. Contribution on con-
trol strategies of flow-on-demand hydraulic circuits. In:
actuators. Some high-power consumers could have one
Proceedings of the 13th Scandinavian international confer-
dedicated pump while other, low-power consumers
ence on fluid power (SICFP 2013), Linköping, 3–5 June
share one common pump. In that case, the total 2013.
installed displacement could be kept at a reasonable 13. Palmgren G.On secondary controlled hydraulic systems.
level while all pumps could be displacement controlled. Licentiate Thesis, Linköping University, Linköping,
Another possibility might be to use an electric motor in 1988.
combination with a fixed displacement pump, like in 14. Dengler P, Geimer M, Baum H, et al. Efficiency improve-
EHA systems, but share it with several loads. ment of a constant pressure system using an intermediate
pressure line. In: Proceedings of the 8th international fluid
power conference (IFK), Dresden, 26–28 March 2012,
Declaration of conflicting interests vol. 1, pp.567–578.
The authors declare that there is no conflict of interest. 15. Andersson BR.A survey of load-sensing systems. BFPR J
1980; 13: 103–115.
16. Axin M, Palmberg J-O and Krus P. Optimized damping
Funding in cylinder drives using the meter-out orifice – design and
This research was funded by Parker Hannifin Corp. experimental verification. In: Proceedings of the 8th inter-
national fluid power conference (IFK), Dresden, 26–28
March 2012, vol. 1, pp.579–591.
References 17. Axin M and Krus P. Design rules for high damping in
1. Stenlund S.Electrohydraulic guide system. Patent EP mobile hydraulic systems. In: Proceedings of the 13th
0417087, USA, 1988. Scandinavian international conference on fluid power
2. Zähe B.Energiesparende Schaltungen hydraulischer (SICFP 2013), Linköping, 3–5 June 2013.
Antriebe mit veränderlichem Versorgungsdruck und ihre 18. Krus P.On load sensing fluid power systems – with special
Regelung. PhD Thesis, Rheinisch-Westfaaalische Tech- reference to dynamic properties and control aspects. PhD
nische Hochschule Aachen, Aachen, 1993. Thesis, Linköping University, Linköping, 1988.
3. Jongebloed H, van Büren D, Völkel U, et al. Energy- 19. Pettersson H, Krus P, Jansson A, et al. The design of
saving valve system for mobile applications – load-control- pressure compensators for load sensing hydraulic sys-
system (LCS). In: Proceedings of the 4th international fluid tems. In: Proceedings of the UKACC international confer-
power conference (IFK), Dresden, 25–26 March 2004, ence on control ’96, Southampton, 2–5 September 1996,
pp.117–128. vol. 2, pp. 1456–1461.
4. Djurovic M and Helduser S. New control strategies for 20. Wu D, Burton R, Schoenau G, et al. Analysis of a
electrohydraulic load-sensing. In: Fluid power and motion pressure-compensated flow control valve. J Dyn Syst: T
control (FPMC), Bath, 6–9 September 2004, pp.201–210. ASME 2007; 129: 203–211.
5. Djurovic M, Helduser S and Keuper G.Neue lösungen 21. Eriksson B and Palmberg J-O.Individual metering fluid
zum elektrohydraulischen load-sensing. In: Proceedings power systems: challenges and opportunities. Proc
of the 4th international fluid power conference (IFK), IMechE, Part I: J Systems and Control Engineering 2011;
Dresden, 25–26 March 2004, vol. 2, pp.59–70. 225: 196–211.
6. Djurovic M.Energiesparende Antriebssysteme für die 22. Eriksson B.Mobile fluid power systems design – with a
Arbeitshydraulik mobiler Arbeitsmaschinen ‘Elektrohy- focus on energy efficiency. PhD Thesis, Linköping Uni-
draulisches Flow Matching’. PhD Thesis, Institut für versity, Linköping, 2010.
Fluidtechnik der Technischen Universität Dresden, Dres- 23. Williamson C and Ivantysynova M. The effect of pump
den, 2007. efficiency on displacement-controlled actuator systems.
7. Eriksson B and Palmberg J-O. How to handle auxiliary In: Proceedings of the 10th Scandinavian international con-
functions in energy efficient, single pump, flow sharing ference on fluid power (SICFP ’07), Tampere, 21–23 May
mobile systems. In: Proceedings of the 7th international 2007.
fluid power conference (IFK), Aachen, 22–24 March 24. Raymond ET and Chenoweth CC.Aircraft flight control
2010. Aachen: Apprimus Wissenschaftsverlag. actuation system design. Warrendale, PA: Society of
8. Latour C.Electrohydraulic flow matching (EFM) – the Automotive Engineers, 1993.
next generation of load sensing controls. In: Mobile con- 25. Rahmfeld R and Ivantysynova M.Displacement con-
ference, Ulm, 19–20 October 2006. trolled linear actuator with differential cylinder – a way
9. Fedde T and Harms H-H. An adaptive hydraulic system to save primary energy in mobile machines. In: Proceed-
for mobile applications. In: Proceedings of the 5th inter- ings of the fifth international conference on fluid power
national fluid power conference (IFK), Aachen, 20–22 transmission and control (ICFP), Hangzhou, China,
March 2006, vol. 3, pp.95–106. 2001, vol. 1, pp.316–322.
10. Finzel R.Elektrohydraulische Steuerungssysteme für 26. Rahmfeld R, Ivantysynova M and Weber J.Displacement
mobile Arbeitsmaschinen. PhD Thesis, Institut für Fluid- controlled wheel loader – a simple and clever solution. In:
technik der Technischen Universität Dresden, Dresden, Proceedings of the 4th international fluid power conference
2010. (IFK), Dresden, 25–26 March 2004, vol. 2, pp.183–196.

Downloaded from pii.sagepub.com at PENNSYLVANIA STATE UNIV on April 8, 2016


256 Proc IMechE Part I: J Systems and Control Engineering 228(4)

27. Heybroek K.Saving energy in construction machinery power (SICFP ’11), Tampere, 18–20 May 2011, vol. 2,
using displacement control hydraulics – concept realization pp.223–238.
and validation. Licentiate Thesis, Linköping University, 42. Finzel R, Helduser S and Jang D-S. Electro-hydraulic
Linköping, 2008. control systems for mobile machinery with low energy
28. Werndin R and Palmberg J-O. Hydraulic transformers – consumption. In: Proceedings of the seventh international
comparison of different designs. In: Proceedings of the conference on fluid power transmission and control
eighth Scandinavian international conference of fluid power (ICFP), Hangzhou, China, 7–10 April 2009, pp.214–219.
(SICFP ’03), Tampere, 7–9 May 2003. 43. Finzel R, Helduser S and Jang D-S. Electro-hydraulic
29. Achten PAJ, Fu Z and Vael GEM. Transforming future dual-circuit system to improve the energy efficiency of
hydraulics: a new design of a hydraulic transformer. In: mobile machines. In: Proceedings of the 7th international
Proceedings of the 5th Scandinavian international confer- fluid power conference (IFK), Aachen, 22–24 March
ence on fluid power (SICFP ’97), Linköping, 28–30 May 2010.
1997. 44. Merritt HE.Hydraulic control systems. New York: John
30. Achten P, Vael G, van den Brink T, et al. Efficiency mea- Wiley & Sons Inc., 1967.
surements of the hybrid motor/pump. In: Proceedings of 45. Axin M, Braun R, Dell’Amico A, et al. Next generation
the 12th Scandinavian international conference on fluid simulation software using transmission line elements. In:
power (SICFP ’11), Tampere, 18–20 May 2011, vol. 3, Fluid power and motion control (FPMC), Bath, 15–17
pp.41–49. September 2010, pp.265–276.
31. Gomm R and Vanderlaan D.Velocity control of unba- 46. Eriksson B, Nordin P and Krus P. Hopsan NG, a C++
lanced hydraulic actuator subjected to over-center load con- implementation using the TLM simulation technique. In:
ditions. Patent EP 2318720, USA, 2009. Proceedings of the 51st conference on simulation and mod-
32. Weber J and Burget W.Mobile systems – markets, indus- elling (SIMS), Oulu, 14–15 October 2010.
trial needs and technological trends. In: Proceedings of 47. Filla R.Quantifying operability of working machines. PhD
the 8th international fluid power conference (IFK), Dres- Thesis, Linköping University, Linköping, 2011.
den, 26–28 March 2012, vol. 2, pp.23–54.
33. Eriksson B.Control strategy for energy efficient fluid
power actuators – utilizing individual metering. Licentiate
Appendix 1
Thesis, Linköping University, Linköping, 2007. Notation
34. Mettälä K, Djurovic M, Keuper G, et al. Intelligent oil
flow management with EFM: the potentials of electrohy- The quantities used in this article are listed in the fol-
draulic flow matching in tractor hydraulics. In: Proceedings lowing. Capital letters are used for linearized and
of the 10th Scandinavian international conference on fluid Laplace transformed variables.
power (SICFP ’07), Tampere, 21–23 May 2007, vol. 3, Ac cylinder area (m2)
pp.25–34. As directional valve opening area (m2)
35. Grösbrink B and Harms H-H. Control concept for an Bp viscous friction coefficient (Ns/m)
advanced load-sensing system. In: Proceedings of the 7th CL capacitance of the load cylinder (m3/Pa)
international conference on fluid power transmission and Cp capacitance of the pump hose (m3/Pa)
control, Hangzhou, China, 7–10 April 2009. Fs compensator spring stiffness (N)
36. Grösbrink B, von Baumgarten T and Harms H-H. Alter-
Go open-loop transfer function
nating pump control for a load-sensing system. In: Pro-
ceedings of the 7th international fluid power conference
Gp pump transfer function
(IFK), Aachen, 22–24 March 2010. Aachen: Apprimus Gv valve transfer function
Wissenschaftsverlag.. Hs pump hose transfer function
37. Xu B, Liu W, Cheng M, et al. A new electrohydraulic Kc flow–pressure coefficient for the valve
load sensing control system for hydraulic excavators. In: (m3/Pas)
Proceedings of the 8th international fluid power conference Lp pump inductance (Pas2/m3)
(IFK), Dresden, 26–28 March 2012, vol. 1, pp.553–565. mL load mass (kg)
38. Finzel R and Helduser S. Energy-efficient electro- pL load pressure (Pa)
hydraulic control systems for mobile machinery/flow pLmax maximum load pressure (Pa)
matching. In: Proceedings of the 6th international fluid PL load pressure (Pa)
power conference, Dresden, 31 March–2 April 2008, vol.
Pp pump pressure (Pa)
1, pp.89–102.
39. Finzel R and Helduser S. New electro-hydraulic control
pr reduced pressure (Pa)
systems for mobile machinery. In: Fluid power and ps supply pressure (Pa)
motion control (FPMC), Bath, 10–12 September 2008, qL load flow (m3/s)
pp.309–321. QL load flow (m3/s)
40. Axin M, Eriksson B and Palmberg J-O.Energy efficient Qp pump flow (m3/s)
load adapting system without load sensing – design and s Laplace variable (s21)
evaluation. In: Proceedings of the 11th Scandinavian inter- ZL load transfer function
national conference on fluid power (SICFP ’09), Linköp-
ing, 2–4 June 2009. DPp pump pressure margin (Pa)
41. Axin M, Eriksson B, Palmberg J-O, et al. Dynamic anal- DPpref pump pressure margin demand (Pa)
ysis of single pump, flow controlled mobile systems. In:
The 12th Scandinavian international conference on fluid

Downloaded from pii.sagepub.com at PENNSYLVANIA STATE UNIV on April 8, 2016

Das könnte Ihnen auch gefallen