www.vtsgroup.com
01 VTS Group
1.1. VTS Group ...................................................................................................................................................................................................................................................................................................06
1.2. 3 pillars of success ..................................................................................................................................................................................................................................................................08
ATLANTA LC
SHORTEST *
ON THE MARKET
L E A D
TIME
Central Station Air-Handling Units
AHRI Standard 430
*
Logistics center
06
VTS Group
OUR MISSION
AHU#1
MOSCOW LC
WARSAW LC
SHANGHAI LC
DUBAI LC
BANGALORE LC
VVS021 - VVS650
07
VTS Group
3 PILLARS OF SUCCESS
Constantly highest quality of products. Best prices on the market.
Shortest lead time. These 3 pillars of marketing policy allows VTS
to be always one step head, wherever in the world.
ON THE MARKET
VTS has created a network of 6 efficiently L E A D
TIME
running production and logistic centers
(Atlanta, Dubai, Moscow, Shanghai,
Warsaw, Bangalore), enable to ensure the
6
shortest lead time on the market, wherever CENTERS
in the world.
L O G I S T I C
$ PRICE
COMPETITIVE
5
WARRANTY
YEARS
UP TO FOR EACH
U N I T
08
09
02
Support
for designers
Support for designers
Certified by
VVS021 - VVS650
»» any
web-browser
»» any device
DATA EXPORT TO
12
Support for designers
CCOL 4.0 utilises latest technologies and software platforms. The tool has been developed
in SaaS model (Software as a Service). It’s best advantage is, that service is accessible wherever
in the world. Any device equipped with web-browser and internet access is all you need to experience
the power of our CCOL 4.0.
DESIGN VERSATAILTY
Hd
H2
based on automatic air treatment functions.
placements with regard to minimum gaps between
them in order to secure their propper performance.
Hf
L_1
www.ccol4.com
13
Support for designers
Login to CCOL 4.0 AHU configuration and Selection export to .fra file
You can login using our web-site: parameters specyfing In order to generate .fra model, all
Intuitive unit configurator enables you need to do is to enter personal
to select a unit, perfectly fitting information (including e-mail address)
to your design assumptions. of a person to whom the model is to be
sent. The system will automatically sent
the link to the site from where model
can be downloaded. Entire process take
no longer than 15 minutes.
14
Support for designers
Digital model of the air handling unit with fully parametrized VTS enables also a library of static families for WING air curtains
connectors: and VOLCANO air heaters.
Air, The models includes:
Hydraulic, parametrized electric and hydraulic connectors,
Sanitary, both vertical and horizontal mounting options,
Electric, presentation of units effective air range,
and also a set of complete technical and dimensioning parametrized angle of heater’s to the horizontal plane.
information, including clearly marked maintenance and
service zone of the unit.
Models can be downloaded from: http://vtsgroup.com/vtsbim.html 15
Support for designers
LOD
(Level Of Development) standard.
In 2019, ClimaCAD OnLine 4.0 will
400
support customization of the model’s
Level of Development, at the moment
of their generating.
16
Support for designers
17
03
Units
- VENTUS VVS
VVS
DURABLE RELIABLE
AND TIGHT COMPONENTS
STRUCTURE
Airflow
from 1 100 m3/h
from 100 000 m /h
3
Up to 92%
of energy recovery
efficiency
14
sizes
SMART USER
CONTROLS SAFETY
Technical Specification
STRUCTURE
CORROSION RESISTANCE
Resistance of new
coating applied
to VENTUS
Number of hours
»» Rigid, durable structure of the casing. »» Improved longitudinal rigidity of the structure.
»» Low absorption of heat radiation and UV. »» Facilitated sections joining.
»» High resistance to weather conditions.
22
Technical Specification
ALUMINUM
POSTS
OF SPECIAL
CONSTRUCTION
IN EACH AHU
TYPE
23
Technical Specification
TIGHTNESS
»» The canopy is made of 0,5 mm steel sheet, double »» Highly aesthetic and ergonomic handles
side coated with 185 um of zinc (DX51D AZ185). securing perfect tightness of inspection panels.
»» Canopy is assembled of modules equipped
with self-latching grooves securing perfect tightness
of the joints. Modular structure of the canopy
ensures its easy and safe assembly.
24
Technical Specification
THERMAL LABIRYNTH
BREAK TIGHTNENING
ADDITIONAL ADDITIONAL
POST SEALING SEALING BLADE
»» Broken thermal bridge as standard – eliminates humidity condensation on units structural elements.
»» Blade along the inspection window ensures labyrinth tightening between panel and AHU body
– currently the most effective solution on the market, mainly applied to laboratory equipment.
»» Symmetrical groove in the vertical post’s mounting feet secures its 100% tightness with the AHU casing
structure.
25
Technical Specification
18 000
12 000
6 000
[m3/h]
Min airflow 806 806 806 1 180 1 180 1 180 1 958 1 958 1 958 2 878 2 878 2 878 3 805 3 805 3 805 4 863 4 863 4 863 5 815 5 815 5 815
Max airflow 2 730 2 184 2 163 3 900 3 120 3 090 5 200 4 160 4 120 7 150 5 720 5 665 9 750 7 800 7 725 13 000 10 400 10 300 15 600 12 480 12 360
Hfd 90 90 90 90 90 90 90
Hfu - - - - - - -
H 538 670 670 805 925 1 025 1 062
W 961 961 1 168 1 339 1 480 1 660 1 891
[mm]
26
Technical Specification
WB 1
WB
HC HC 1
LB
LB 1
Hi
HA HA 1
H2
H
Hi
K= L
11 LC
Hfd LC 1 WA WA1
L1
Wi
W
27
Technical Specification
90 000
60 000
[m3/h]
30 000
Min airflow 7 167 7 167 7 167 8 640 8 640 8 640 10 398 10 398 10 398 13 491 13 491 13 491 18 704 18 704 18 704 21 817 21 817 21 817 28 725 28 725 28 725
Max airflow 19 500 15 600 15 450 23 400 18 720 18 540 29 900 23 920 23 690 39 000 31 200 30 900 52 000 41 600 41 200 71 500 57 200 56 650 84 500 67 600 66 950
28
Technical Specification
Hfd
29
Technical Specification
18 000
12 000
[m3/h]
6 000
Min airflow 806 806 806 1 180 1 180 1 180 1 958 1 958 1 958 2 878 2 878 2 878 3 805 3 805 3 805 4 863 4 863 4 863 5 815 5 815 5 815
Max airflow 2 730 2 415 2 163 3 900 3 450 3 090 5 200 4 600 4 120 7 150 6 325 5 665 9 750 8 625 7 725 13 000 11 500 10 300 15 600 13 800 12 360
Hfd 90 90 90 90 90 90 90
Hfu 0 0 0 0 0 0 0
H 538 670 670 805 925 1 025 1 062
W 961 961 1 168 1 339 1 480 1 660 1 891
[mm]
30
Technical Specification
Hfd
31
Technical Specification
90 000
60 000
[m3/h]
30 000
Min airflow 7 167 7 167 7 167 8 640 8 640 8 640 10 398 10 398 10 398 13 491 13 491 13 491 18 704 18 704 18 704 21 817 21 817 21 817 28 725 28 725 28 725
Max airflow 19 500 16 350 15 450 23 400 19 620 18 540 29 900 25 070 23 690 39 000 32 700 30 900 52 000 43 600 41 200 71 500 59 950 56 650 84 500 70 850 66 950
32
Technical Specification
Hfd
33
Technical Specification
20 000
15 000
10 000
[m3/h]
5 000
Min airflow 806 806 806 806 1 180 1 180 1 167 1 167 1 958 1 958 1 958 1 958 2 878 2 878 2 878 2 878 3 805 3 805 3 805 3 805 4 863 4 863 4 863 4 863 5 815 5 815 5 815 5 815
Max airflow 2 163 2 730 3 570 3 780 3 090 3 900 5 100 5 400 4 120 5 200 6 800 7 200 5 665 7 150 9 350 9 900 7 725 9 750 12 750 13 500 10 300 13 000 17 000 18 000 12 360 15 600 20 400 21 600
Hfd 90 90 90 90 90 90 90
H 538 670 670 805 925 1 025 1 062
[mm]
FCV
34
Technical Specification
35
Technical Specification
120 000
90 000
60 000
[m3/h]
30 000
Min airflow 7 167 7 167 7 167 7 167 8 640 8 640 8 640 8 640 10 398 10 398 10 398 10 398 13 491 13 491 13 491 13 491 18 704 18 704 18 704 18 704 21 817 21 817 21 817 21 817 28 725 28 725 28 725 28 725
Max airflow 15 450 19 500 25 500 27 000 18 540 23 400 30 600 32 400 23 690 29 900 39 100 41 400 30 900 39 000 51 000 54 000 41 200 52 000 58 000 62 000 56 650 71 500 77 000 79 000 66 950 84 500 87 000 100 000
FCV
36
Technical Specification
37
Technical Specification
C
L 366 366 366 366 366 366 366
C
[mm]
Dimension Function version Remaining configuration functions – typical lengths of function arrangement
VVS150 VVS180 VVS230 VVS300 VVS400 VVS500 VVS650
C
L 366 366 366 366 366 366 366
C
[mm]
38
Components
COMPONENTS
DIRECT DRIVE PLUG FAN SET
> AC MOTORS »» Fan and motor mounted on common »» Available Energy classes: IE2, IE3
housing, separated from AHU casing »» Rated voltage: 3x230V AC,
by set of rubber vibration absorbing 3x400V AC.
mounts.
»» Number of poles: 2 or 4.
»» Motors of TEFC type
»» Motor winding insulation class: F
(Totally Enclosed, Fan-Cooled).
(fitted for VFD operations).
»» Motors fitted for IEC standard.
»» Bearings lifetime: L10= 20000h
»» Variable Frequency Drive (VFD) – / L50 = 100000h.
standard equipment of the fan-set.
»» Protection degree: IP55.
»» Maximum working ambient
temperature: 60°C.
> EC MOTORS »» Set of fan and motor mounted on »» Available Energy classes: IE4.
common rail, fixed to the AHU fan »» Rated voltage: EC motors of nominal
diaphragm. capacity exceeding 0,75kW -
»» EC motors are Permanent Magnet 3x400V AC.
motor, characterised by much higher »» Rated voltage: EC motors of nominal
efficiency vs traditional inductive AC capacity equal or less 0,75kW -
motors. 1x230V AC.
»» EC motors (Electronically »» Motor widing insulation class: F.
Commutated) – where mechanical
»» Protection degree: IP54.
commutator switching the windings
has been replaced with electronic »» Maximum working ambient
one. temperature: 55°C.
»» Change of revolutions is done by »» Lifespan:
means of changing the frequency - 70 000 hours at load not exceeding
rate of windings switching (rate or 70% of nominal capacity at ambient
magnetic field rotating). temperature not exceeding 35°C,
- 30 000 hours at 100% capacity
»» Highly inductive permanent magnets
load at ambient temperature not
have applied in EC motors used by
exceeding 55°C.
VTS, which enabled to achieve high
torque at relatively small dimensions,
together with reaching IE4 efficiency
class.
40
Components
CASING
PANEL FILTERS
BAG FILTERS
41
Components
42
Components
RUN-AROUND COIL
MIXIN SECTION
43
Components
WATER HEATER
Design and application Specification
»» Block of copper pipes integrated »» Max glycol concentration: 50%.
with another block of aluminum fins, »» Max medium temperature: 150°C.
creating expanded heat exchange
»» Max medium working pressure:
surface. Pipes are bonded to the
1,6MPa = 16bar (test: 21bar).
collectors, equipped with headers
(for connecting entire coil to the »» Heating capacity: parameter resulting
medium supply system). from individual performance
calculaation of selected unit (CCOL).
»» Heating of the air supplied to the
handled spaces. »» Medium side pressure drop –
parameter resulting from individual
»» Re-heating of the air as a part of air
performance calculation of selected
dehumidifying process.
unit (CCOL).
»» The coil can be applied if heating
medium is available (local boiler or
district heating system).
»» Coil headers are equipped with
medium damping valve and air vent.
»» Connecting the coil in parallel
medium flow vs air, will result in its
capacity reduction by over a dozen
percent.
ELECTRIC HEATER
44
Components
WATER COOLER
DX COOLING COIL
Design and application Specification
»» Block of copper pipes integrated »» Min. Refrigerant evaporation
with another block of aluminum fins, temperature: +3°C.
creating expanded heat exchange »» Max refrigerant working pressure:
surface. Pipes are bonded to the 2,2MPa=22bar (test: 29 bar).
collectors, equipped with headers
»» Cooling capacity - parameter
(for connecting entire coil to the
resulting from individual performance
cooling system circuit).
calculation of selected unit (CCOL).
»» DX cooler is also available as heater
execusion (so calleed Condenser).
»» Cooling and dehumidifying of
the air as a part of air complex
dehumidifying process in summer
season.
»» Coil usually applied for smallerd
cooling capacity systems vs
water coolers or for individual air
conditioning systems.
45
Components
EVAPORATIVE HUMIDIFIER
INTERNAL LIGHT
46
Components
AIR DAMPER
Design and application Specification
»» Blades made of aluminium with rubber »» Air leakage at closted damper:
gasket on the edges. 50 m3/h*m2 - at 100 Pascals of
»» Aluminum frame. pressure difference.
»» Blades drive realized by means of gears »» Workint temperature range:
made of composite material, installed -40 ÷ +70°C.
on frame internal side.
»» Damper is equipped with square pivot,
fitted for actuator (dampers of cross
section greater than 4 m2 have 2 linked
pivots).
FLEXIBLE CONNECTION
47
Controls
CONTROLS
All controls for VENTUS air handling units is available as optional equipment.
Range of controls is always fitted to configuration of the AHU selected in the CCOL4 tool. Controls is capable
to regulate all user parameters: air temperature, its humidity, maximum permissible CO2 concentration and the
flow rate. Also, controls support preventive and securing functions like protection of the water heater against
freezing or energy recovery system against icing, protection of motors against overloading, monitoring of air
filters actual status of contamination and many other. Applied algorithms can optimize performance of all air
treatment components in order to minimize consumption of all energy media supplied to the unit.
HMI Basic
»» Engaging and disengaging the AHU,
change of operational modes.
»» Change of temperature, airflow,
humidity, max CO2 level settings, etc.
»» Errors reporting.
»» Time schedule setting.
HMI Advanced
»» All users and service functions except
visualization
• AHU engaging and disengaging,
• Change of operational modes.
»» Change of temperature, airflow,
humidity, max CO2 level settings, etc.
»» Parameters setting and reporting.
»» Errors reporting.
»» Time schedule setting.
USER
BMS
»» User function like in HMI Advanced.
»» User’s customized visualization (BMS).
Remote visualization
»» All user function like in HMI Advanced:
• VTS visualization.
»» Clear interface of schedule
programming, presenting unit’s
operating time individually for each day
of the week.
»» Energy consumption analysing module.
»» Individual parameters monitoring of
each functional block.
»» Filing of all AHU’s parameters recorded
in few minutes intervals.
48
Controls
CO2 regulation
»» By means of mixing box – for units with air recirculation.
»» By means of airflow rate change – for all types of supply and exhaust units (function can be engages together
with mixing box control).
[Pa]
3050
2000
obr/min
1800
2815
Change of ductwork resistance
1600 – by adjusting damper
1400
2425
1200 Change of fan revolutions
1000
2035
800
600
400
200
1000 2000 3000 4000 5000 6000 7000 8000 9000 [m3/h]
QN
PROTECTION FUNCTIONS
»» Protection against rotary heat wheel icing, by means of wheel revolutions reduction.
»» Protection against hexagonal counterflow and cross-flow recuperator icing by means of by-pass damper
opening. Functions realized as optional:
• Optimizing of icing protection function by change of minimum return air temperature threshold downstream
the energy recovery unit vs return air parameters.
• Minimizing of recovery efficiency drop during defrosting
»» Anti-freezing protection of water heater
• Antifreeze thermostat installed downstream the heater
• Strap-on return water temperature sensor
»» Fans overload protection (functions realized by EC motors drives)
»» Fire alarm input – AHU immediate disengaging in case of lack of external start permission from overall fire
protection system.
49
Controls
PREVENTIVE FUNCTIONS
»» Constant filter contamination status control:
• Constant monitoring of filter pressure drop by means of static pressure transducers,
• Evaluation of filter contamination status for vs actual airflow rate.
»» Fans shutting-down delay – fan’s run out for systems with electric heater
»» Water heater pre-heating before fun’s start up.
»» Periodical heater pump engaging in summer – to prevent against limescale accumulation
»» Opening of water heater regulation valve before engaging the fans.
50
Controls
CONTROL ELEMENTS
CONTROL ELEMENTS
ANTI-FREEZE THERMOSTATE
52
Controls
CO2 TRANSDUCER
56
04
Units
- VENTUS Compact
VENTUS Compact
SUSPENDED UNITS
AIRFLOW LENGTH WIDTH HEIGTH
[m3/h] [mm] [mm] [mm]
up to 92%
of energy recovery
efficiency
60
VENTUS Compact
FLOOR-MOUNTED UNITS
Unit size
840 - 2310 900 - 3300 1200 - 4400 1650 - 6050 2250 - 8250 3000 - 11000 3600 - 13200 4500 - 16500
up to 86%
of energy recovery
efficiency
61
VENTUS Compact
SUSPENDED UNITS
CASING
»» Anticorrosive coating: Aluzinc, AZ 150.
»» Availability of spigots for round and rectangular duct.
CONTROLS
Multifunctional, factory installed controls
in the unit’s casing – configured
and ready to run.
62
VENTUS Compact
MINI-PLEAT FILTERS
Highly absorptive filters with wide active filtration cross-section.
»» Supply - EU 7 class,
»» Exhaust - EU 5 class.
up to 93%
motor efficiency
63
VENTUS Compact
FLOOR-MOUNTED UNITS
CASING
»» Anticorrosive coating: Aluzinc, AZ 150.
ENERGY RECOVERY
»» Highly efficiency Rotary Heat Wheel
with EC motor.
»» Thermal efficiency reaching 86%.
64
VENTUS Compact
MINI-PLEAT FILTERS
»» Highly absorptive compact filters
with expanded filtration are:
• Supply – class EU7.
• Return – class EU 5.
CONTROLS EC MOTORS
»» Multifunctional controls, factory installed »» Effective, silent and low vibrations fan
in the AHU casing – configured and ready equipped with IE4 class EC motor
to run.
65
Technical Specification
VVS 005s-030s
- SUSPENDED COMPACT UNITS
Nominal parameters Recommended airflow range
Unit size VVS005s VVS010s VVS015s VVS020s VVS030s
4 000
3 000
2 000
[m3/h]
1 000
0
Hex 005s Hex 010s Hex 015s Hex 020s Hex 030s
Counterflow
[mm]
Selected
Dimension Function Length of supply and exhaust compact units
configurations version
66
Technical Specification
W2
Duct fittings
C
L 370 370 370 370 370
(2R-6R)
C(de)
L 600 600 600 600 600
C (2R-6R)
[mm]
67
Technical Specification
VVS 021c-150c
- FLOOR MOUNTED COMPACT UNITS
Nominal parameters Recommended airflow range
Unit size VVS021c VVS030c VVS040c VVS055c VVS075c VVS100c VVS120c VVS150c
16 000
12 000
8 000
[m3/h]
4 000
Min airflow 806 1 167 1 958 2 878 3 805 4 863 5 815 5 815
Max airflow 2 310 3 300 4 400 6 050 8 250 11 000 13 200 16 500
Hfd 90 90 90 90 90 90 90 90
H 538 670 670 805 925 1025 1062 1163
W 967 967 1174 1345 1486 1666 1897 2091
[mm]
68
Technical Specification
Hi
H
Hfd
L
E 550 550 550 630 630 650 650 670
E
69
Components
COMPONENTS
DIRECT DRIVE PLUG FAN SET
> EC MOTORS »» Set of fan and motor mounted on »» Available Energy classes: IE4.
common rail, fixed to the AHU fan »» Rated voltage: EC motors of nominal
diaphragm. capacity exceeding 0,75kW -
»» EC motors are Permanent Magnet 3x400V AC.
motor, characterised by much higher »» Rated voltage: EC motors of nominal
efficiency vs traditional inductive AC capacity equal or less 0,75kW -
motors. 1x230V AC.
»» EC motors (Electronically »» Motor widing insulation class: F.
Commutated) – where mechanical
»» Protection degree: IP54.
commutator switching the windings
has been replaced with electronic »» Maximum working ambient
one. temperature: 55°C.
»» Change of revolutions is done by »» Lifespan:
means of changing the frequency - 70 000 hours at load not exceeding
rate of windings switching (rate or 70% of nominal capacity at ambient
magnetic field rotating). temperature not exceeding 35°C,
- 30 000 hours at 100% capacity
»» Highly inductive permanent magnets
load at ambient temperature not
have applied in EC motors used by
exceeding 55°C.
VTS, which enabled to achieve high
torque at relatively small dimensions,
together with reaching IE4 efficiency
class.
70
Components
71
Components
72
Components
MIXIN SECTION
WATER HEATER
Design and application Specification
»» Block of copper pipes integrated »» Max glycol concentration: 50%.
with another block of aluminum fins, »» Max medium temperature: 150°C.
creating expanded heat exchange
»» Max medium working pressure:
surface. Pipes are bonded to the
1,6MPa = 16bar (test: 21bar).
collectors, equipped with headers
(for connecting entire coil to the »» Heating capacity: parameter resulting
medium supply system). from individual performance
calculaation of selected unit (CCOL).
»» Heating of the air supplied to the
handled spaces. »» Medium side pressure drop –
parameter resulting from individual
»» Re-heating of the air as a part of air
performance calculation of selected
dehumidifying process.
unit (CCOL).
»» The coil can be applied if heating
medium is available (local boiler or
district heating system).
»» Coil headers are equipped with
medium damping valve and air vent.
»» Connecting the coil in parallel
medium flow vs air, will result in its
capacity reduction by over a dozen
percent.
ELECTRIC HEATER
73
Components
WATER COOLER
DX COOLING COIL
Design and application Specification
»» Block of copper pipes integrated »» Min. Refrigerant evaporation
with another block of aluminum fins, temperature: +3°C.
creating expanded heat exchange »» Max refrigerant working pressure:
surface. Pipes are bonded to the 2,2MPa=22bar (test: 29 bar).
collectors, equipped with headers
»» Cooling capacity - parameter
(for connecting entire coil to the
resulting from individual performance
cooling system circuit).
calculation of selected unit (CCOL).
»» DX cooler is also available as heater
execusion (so calleed Condenser).
»» Cooling and dehumidifying of
the air as a part of air complex
dehumidifying process in summer
season.
»» Coil usually applied for smallerd
cooling capacity systems vs
water coolers or for individual air
conditioning systems.
74
Components
AIR DAMPER
Design and application Specification
»» Blades made of aluminium with rubber »» Air leakage at closted damper:
gasket on the edges. 50m3/h*m2 - at 100 Pascals of
»» Aluminum frame. pressure difference.
»» Blades drive realized by means of gears »» Workint temperature range:
made of composite material, installed -40 ÷ +70°C.
on frame internal side.
»» Damper is equipped with square pivot,
fitted for actuator (dampers of cross
section greater than 4 m2 have 2 linked
pivots).
FLEXIBLE CONNECTION
75
Controls
CONTROLS
VENTUS COMPACT AIR HANDLING UNITS IN PLUG&PLAY STANDARD
Savings
Ventus Compact – range of floor-mounted units with rotary heat wheel and suspended
Comfort with hexagonal recuperator. Equipped with complete, factory mounted controls, pre-configured
in accordance to actual selection and ready to run just after connecting to mains.
Safety
Controls is capable to regulate all user parameters: air temperature, its humidity, maximum permissible CO2
concentration and the flow rate. Also, controls support preventive and securing functions like protection
of the water heater against freezing or energy recovery system against icing, protection of motors against
overloading, monitoring of air filters actual status of contamination and many other. Applied algorithms can
optimize performance of all air treatment components in order to minimize consumption of all energy media
supplied to the unit. The system includes control and power supply circuits:
HMI Basic
»» Engaging and disengaging the AHU,
change of operational modes.
»» Change of temperature, airflow,
humidity, max CO2 level settings, etc.
»» Errors reporting.
»» Time schedule setting.
HMI Advanced
»» All users and service functions except
visualization
• AHU engaging and disengaging,
• Change of operational modes.
»» Change of temperature, airflow,
humidity, max CO2 level settings, etc.
»» Parameters setting and reporting.
»» Errors reporting.
»» Time schedule setting.
USER
BMS
»» User function like in HMI Advanced.
»» User’s customized visualization (BMS).
Remote visualization
»» All user function like in HMI Advanced:
• VTS visualization.
»» Clear interface of schedule
programming, presenting unit’s
operating time individually for each day
of the week.
»» Energy consumption analysing module.
»» Individual parameters monitoring of
each functional block.
»» Filing of all AHU’s parameters recorded
76 in few minutes intervals.
Controls
CO2 regulation
»» By means of mixing box – for units with air recirculation.
»» By means of airflow rate change – for all types of supply and exhaust units
(function can be engages together with mixing box control).
[Pa]
3050
2000
obr/min
1800
2815 Change of ductwork resistance
– by adjusting damper
1600
1400
2425
1200 Change of fan revolutions
1000
2035
800
600
400
200
1000 2000 3000 4000 5000 6000 7000 8000 9000 [m3/h]
QN
PROTECTION FUNCTION
»» Protection against rotary heat wheel icing (VENTUS Compact floor mounted units), by means of wheel
revolutions reduction.
»» Protection against hexagonal counterflow recuperator icing (VENTUS Compact suspended units)
by means of by-pass damper opening:
• optimizing of icing protection function by change of minimum return air temperature threshold downstream
the energy recovery unit vs return air parameters,
• minimizing of recovery efficiency drop during defrosting.
»» Anti-freezing protection of water heater:
• antifreeze thermostat installed downstream the heater,
• strap-on return water temperature sensor
»» Fans overload protection (functions realized by EC motors drives)
»» Fire alarm input – AHU immediate disengaging in case of lack of external start permission from overall
fire protection system.
PREVENTIVE FUNCTIONS
»» Constant filter contamination status control:
• constant monitoring of filter pressure drop by means of static pressure transducers,
• evaluation of filter contamination status for vs actual airflow rate.
»» Fans shutting-down delay – fan’s run out for systems with electric heater.
»» Water heater pre-heating before fun’s start up.
»» Periodical heater pump engaging in summer – to prevent against limescale accumulation.
CONTROL CIRCUITS
»» All control circuits installed inside the base unit are fully wired and configured in accordance to its technical
selection.
»» Control of fans operation is done by means of digital communication based using ModBUS protocol.
Each of the fan is adequately programmed with individual address enabling its recognition by the control
system (fans should never be swapped).
»» Control elements handling external modules (antifreeze thermostat of the water heater, valves for heater
and cooler, supply air temperature sensor) should be connected to terminal block.
»» Clear and easy to ready description of terminal block facilitates correct connecting of control peripheral
components.
78
Controls
CONTROL ELEMENTS
CONTROL ELEMENTS
ANTI-FREEZE THERMOSTATE
80
Controls
81
Controls
82
Components
CODING
Range of product
Inspection side
VVS075-R-FPHV/VVS075-L-FVPD_CD
84
Components
F Air filter
V Fan
C Cooler
H Heater
M Mixing box
G Run-around coil
D Droplet eliminator
W Humidifier
S Sound attenuator
Auxiliary codes
(cw) water cooler
(dx) direct expansion cooler
(xR) coil number of rows
(hw) water heater
(el) electric heater
(sx) sound attenuator version
85
06
VOLCANO & WING
units
Volcano
RELIABLE
AND ENERGY SAVING
EC MOTORS
3 years warranty
for the unit
ErP
Ready
AHU N° 06.06.320 AHU N° 06.06.320
Range: VENTUS VS 10 - VS 650 Range: VENTUS VS 10 - VS 650
TECHNICAL SPECIFICATION
VOLCANO VOLCANO VOLCANO VOLCANO VOLCANO VOLCANO
Parameter Unit
VR MINI VR1 VR2 VR3 VR-D MINI VR-D
EC EC EC EC EC EC
VTS item code
1-4-0101-0455 1-4-0101-0442 1-4-0101-0443 1-4-0101-0444 1-4-0101-0498 1-4-0101-0450
Casing colors front: RAL 9016 Traffic White, rear + mounting brackets: RAL 7036 Platinum Grey, impeller: RAL 6038 Green
CONTROLS
Parameters
DIMENSIONS
530 mm 700 mm
530 mm
700 mm
VR MINI
395 mm
425 mm
AIR RANGES
MOUNTING
HEIGTH
VR MINI
ON-WALL 3-8 m
MOUNTING CEILING
HEIGTH MOUNTING VR 1
3-12 m SUSPENDED
VR MINI VR 2 MOUNTING
2-5 m 3-11 m
VR 1/2/3/VR-D VR3
2,5-8 m 3-12 m
VR-D
3-15 m
Horizo
nta
air ran l VR MINI
ge VR 1
14 m
23 m VR 2
22 m VR 3
VR-D
25 m
28 m
PIPES DIAMETERS
Number of heaters supplied VR Mini VR1 VR2 VR3
from common heating Max water flow Pipe Max water flow Pipe Max water flow Pipe Max water flow Pipe
water trunk line** rate [m3/h] diameter [”] rate [m3/h] diameter [”] rate [m3/h] diameter [”] rate [m3/h] diameter [”]
1 0,9 3/4 1,3 3/4 2,2 3/4 3,3 3/4
2 1,8 3/4 2,6 3/4 4,4 1 6,6 1 1/4
3 2,7 1 3,9 1 6,6 1 1/4 9,9 1 1/2
4 3,6 1 5,2 1 8,8 1 1/4 13,2 1 1/2
5 4,5 1 6,5 1 1/4 11 1 1/2 16,5 2
6 5,4 1 1/4 7,8 1 1/4 13,2 1 1/2 19,8 2
7 6,3 1 1/4 9,1 1 1/4 15,4 2 23,1 2 1/2
8 7,2 1 1/4 10,4 1 1/2 17,6 2 26,4 2 1/2
9 8,1 1 1/4 11,7 1 1/2 19,8 2 29,7 2 1/2
10 9,0 1 1/4 13 1 1/2 22 2 1/2 33 3
*
- Pipe diameters are specified for max water face velocity of 25 m/s
**
- Units supplied from common heating water trunk line 89
Wing
Air curtain
RELIABLE
AND ENERGY SAVING
EC MOTORS
3 years warranty
for the unit
ErP
Ready
AHU N° 06.06.320 AHU N° 06.06.320
Range: VENTUS VS 10 - VS 650 Range: VENTUS VS 10 - VS 650
TECHNICAL SPECIFICATION
WATER HEATER WATER HEATER NO HEATER
Parameter Unit WING WING WING WING WING WING WING WING WING
W100 W150 W200 E100 E150 E200 C100 C150 C200
EC EC EC EC EC EC EC EC EC
VTS item code 1-4-2801-0055 1-4-2801-0056 1-4-2801-0057 1-4-2801-0058 1-4-2801-0059 1-4-2801-0060 1-4-2801-0061 1-4-2801-0062 1-4-2801-0063
Maximum airflow*** m³/h 1850 3100 4400 1850 3150 4500 1950 3200 4600
~230/1/50
Supply voltage V/ph/Hz ~ 230/1/50 for 2kW ~400/3/50 ~230/1/50
~400/3/50
for 2/4/6kW
Capacity of heating
elements kW - 2 and 4 4 and 8 6 and 9 -
Motor capacity (EC) kW 0,15 0,18 0,26 0,15 0,18 0,26 0,15 0,18 0,26
Motor rated current (EC) A 1,1 1,3 1,9 1,1 1,3 1,9 1,1 1,3 1,9
Unit mass (empty coil) 21,5 29 37,5 22 30,5 39 19 25,5 32,5
– EC kg
Protection degree IP 20
CONTROLS
VTS item code 1-4-0101-0451 VTS item code 1-2-1204-2019 VTS item code 1-4-0101-0454
DIMENSIONS
200 W/E/C
210
2098*
150 W/E/C
210
1582* 465
100 W/E/C
210
1066*
AIR RANGES
5 - 7 m/s *
2,2 m/s *
SPEED 3
2,3 m/s*
7 - 9m/s*
SPEED 2
** - no heating version
2,3 m/s*
2,9
9,6 - 11 m/s*
2,3 m/s*
SPEED 3
2,3 m/s*
3,7 (4,0**)
* - air stream velocity
** - No heat
Air stream range [m] 2,3 2,9 3,7 (4,0**)
MOUNTING
min. 30 cm
max. 4 m
montaż poziomy
91
1m
NOTES
92
PSYCHROMETRIC CHART
Water vapour
pressure
air temperature
Due to continuous improvement of the products, VTS reserves right to implement modifications.
Some of technical data and descriptions may vary from the actual products specification.
Before placing the order, please, confirm all technical specification with VTS sales representative.
www.vtsgroup.com