PCSPH1718B aprv

Warning Ask a qualified installer or contractor to install this product. Do not try to install the product by yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer. AIR CONDITIONING SYSTEM
COOLING ONLY [60Hz]

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as an acidic or alkaline gas, are produced.
2. When installing outdoor units in coastal areas, be sure to contact your local distributor and avoid direct exposure of the units to
sea breezes.

Specifications, designs and other content appearing in this brochure are current as of April 2018 but subject to change without notice.

c All rights reserved 04/18 SS


NEW New Inverters Launched!

Standard panel Standard panel


with Sensing

5.0–7.1 kW class 7.1–10.0 kW class 12.5–14.0 kW class


Designer panel Standard panel Standard panel Auto grille
with Sensing panel

Energy Saving Compact


Comparison of cooling seasonal power New outdoor units save even
consumption based on average CSPF more space
1. Blows horizontally values

2. Strikes the wall Circulation airflow cools the entire


50%
reduction!
92kg

64kg
100

power consumption
room to deliver comfort that never

Cooling seasonal
feels cold.
3. Reaches every 1,345
mm
990
corner of the room 50 mm

320mm
Previous non-inverter series New inverter RZF-C series 900mm 320mm 940mm
(average) (average)
(cassette type) (cassette type) R48NUY1 (In case of 14.0kW class) RZF140CYM

From R-410A to R-32,


Another step towards lower global warming potential.
If you want a new HFC refrigerant 100-year global warming potential (GWP) of different refrigerants
with zero ozone depletion
potential, which also has a lower
global warming potential than
R-410A, use R-32. approx. 1/3
*1

Achieving new levels of energy 10,900


14,800
efficiency while responding to 4,750
environmental needs, Daikin has 1,810 2,090
redesigned the SkyAir series 1 675

right from the basic design to use CO 2 R-32 R-22 R-410A R-11 R-12 R-23
R-32.
(HFC) (HCFC) (HFC) (CFC) (CFC) (HFC)

Standard panel Designer panel *1. Source: Values for 100-year global warming potential (GWP) from IPCC Fourth Assessment Report. Comparative 100-year GWP: HFC410A, 2,090; HFC32, 675.
- Fresh White - - Fresh White -

1 2
NEW Circulation Airflow Evenly Distributes Cool Air *1 *1. Applicable when wired remote controller BRC1E63 is used.
New Round Flow
Cassette movie at
Daikin official
YouTube site.

Airflow until now had areas that were either too cool or not cool enough. Comfort to the Entire Room with Even Temperatures and No Cold Air Pockets at Floor Level
30.0
4-way cassette (Swing) 29.0
Comparison Conditions
28.0 Room size:
Problem 1 27.0 Width 7.5m x depth 7.5m
26.0 x height 2.6m
Hot outdoor air entering through 25.0 Indoor unit capacity: 71 class
windows and walls causes these 24.0 Outdoor air temperature: 35°C
areas to become hot. 4-Way Flow 23.0
22.0 Airflow rate and air direction:
high / swing
21.0
20.0
Problem Problem 2
Hot Areas at floor level are
Cool air accumulating directly outdoor cold while areas
underneath causes cold air air around walls are hot.
pockets at floor level.

Problem 3 1 Circulation Airflow (2-way horizontal + 4-way swing)


Approx. 5% energy
※2

Airflow blowing directly on people savings by reducing


causes discomfort for people in 3 uneven temperatures
the room.
※2.Calculated under the following comparison
conditions: When the average temperature at a
Problem 4 height of 0.6m above the floor reaches set

4 2
temperature. (26°C)
Quick descent of cool air causes
insufficient cooling for corners of Full comfort is
the room. provided with no
cold feet.

Three Technologies That Achieved Circulation Airflow


Circulation airflow cools the entire room to deliver comfort that never feels cold.
1 Use of new wide flaps(Straight) 2 Optimizing airflow angle(Horizontally)
During 2-way With new, larger flaps, a straighter trajectory for airflow The airflow angle was made more horizontal.
horizontal flow was achieved.
Hot Conventional flap
outdoor air Conventional flap New wide flap

Airflow effectively avoids


blowing air directly on people.

Cool air moves down along New wide flap


Comfort without cold air Cools by airflow blocking out New wide flap construction
the walls and to every corner pockets at floor level. hot air near windows and walls.
of the room. inhibits ceiling dirt and grime.
By tapering both flap ends, the
airflow that causes dirty ceilings is
directed downward.
Velocity
10%
3 Increased velocity in ※
increase!

2-way flow(Strongly) All-round Two-way


Velocity increased by making 2-way flow. flow flow
Powerful airflow was realized.
※.Other 2 outlets are controlled by changing the flap ※

Configurations of Circulation Airflow


direction (angle) to suppress airflow volume.

Things to remember when using circulation airflow


[Table 1]
Operation Performs repeatedly Main points for use Installation conditions Distance to wall from indoor unit

(at start) Airflow Effectiveness may differ according to room conditions, room size,
Round flow Indoor unit
capacity FCF50-71 FCF100-140

direction and distance to walls.


When the set Maximum
1.5-5m 1.5-7m
changes temperature is reached, Airflow operation differs when using the designer panel. (Operation repeatedly distance

Wall surface
switches from 3-way horizontal flow to 4-way downward flow [swing] to Distance Minimum distance between
normal operation 2-way horizontal flow to 4-way downward flow [swing].) to wall indoor units [Table 2] [Table 2]
Minimum distance between indoor units
[Table 1]
(all-round flow) begins. Circulation airflow functions during connection with wired remote controller. 1.8m or more above floor surface Indoor unit
(BRC1E63). However, use is not possible for the following conditions: capacity FCF50-71 FCF100-140
- When a sealing material of air discharge outlet and branch ducts are used; Floor surface
Note: Minimum
- When individual airflow setting is selected; distance 5m or more 7m or more
Cools areas around Cools entire room Cools areas around Cools entire room Results may vary depending on
walls using using 4-way walls using using 4-way equipment conditions, room size, - When using group control other than round flow.
2-way horizontal flow swing flow 2-way horizontal flow swing flow and distance from indoor unit to walls.

3 4
NEW Individual Airflow Direction Control *1 *1. Applicable when wired remote controller BRC1E63 is used.
NEW Daikin Sensing Technology *1,2
*1. Applicable when wired remote controller BRC1E63 is used.
New Round Flow
Cassette movie at
Daikin official
YouTube site.
*2. Applicable when sensing panel (BYCQ125EEF/EEK) is installed.

Comfortable air conditioning for all room layouts and conditions Dual Sensors*2
Dual sensors and individual airflow direction control automatically provide
Airflow direction can be individually
adjusted for each air discharge outlet to
Easy setting is possible with a wired remote controller. optimal control of airflow.
deliver optimal air distribution.
NEW
BRC1E63
Infrared presence sensor
Position 0 There are
identification The sensor detects the presence of people in each of the
(Fixed airflow to marks near
the air outlets.
4 areas.
highest position)
Remote controller Ceiling height 2.7m 3.5m 4.0m
screen
Detection range approx. approx. approx.
(diameter)*3 8.5m 11.5m 13.5m
*3. The infrared presence sensor detects 80cm above the floor.
Detecting the
presence of people
No individual Individual airflow settings in each of the 4 areas Infrared floor sensor
setting ・No individual setting (Auto airflow)
(Auto airflow) ・Position 0 (Highest point) The sensor detects the floor temperature and
・Position 1 C automatically adjusts operation of the indoor unit to
・Position 2 B D reduce the temperature difference between the ceiling
・Position 3 and the floor.
Swing Position 4 ・Position 4 (Lowest point) A
(Up/down) (Fixed airflow to the ・Swing Ceiling height 2.7m 3.5m 4.0m
lowest position) Detecting the
Individual settings are possible as stated above. average temperature Detection range approx. approx. approx.
of the floor (diameter)*4 11m 14m 16m
When individual airflow is selected, airflow direction can be adjusted to room layout. *4. The infrared floor sensor detects at the floor surface.

For shops and restaurant

Swing
Swing is
selected for
Auto Airflow Function*5 *5.Airflow direction should be set to “Auto”.

areas near
the windows. No individual (Auto)
Direct Airflow (default: OFF) Cooling Dry
Auto is set for people

The seats here


sitting farthest from
the entrance.
When human presence is not detected When human presence is detected
Sitting here is hot are comfortable
because of the hot air though…
from outside.

Position 0
For offices The airflow is at the
highest setting (Position 0)
for people who
Swing dislike air blowing
Discussions near Swing is set for directly on them.
a hot window meetings near
quickly heat up.
the windows.
Optimal air direction by “Auto”

Optimal air direction by “Auto” Swing (narrow)


It’s quite pleasant
It is very cold here, when cold air isn’t
isn’t it?… Discussions also blowing on us.
go smoothly. With “Auto” airflow direction mode, flaps are controlled When presence is detected, air direction is set
to deliver optimal airflow when the room is unoccupied. to “Swing (narrow)” to deliver cool air to users.

5 6
Daikin provides your on-demand inv erters with a variety of indoor units
INDEX
New Round Flow Cassette
Circulation Airflow P.3-4
Individual Airflow Direction Control P.5
Sensing Technology P.6

Installation Image P.7-8

Lineup P.9-10

Daikin SkyAir Series


Ceiling mounted cassette type Ceiling mounted cassette type Ceiling suspended type
(Standard panel with Sensing) (Standard panel with Sensing) Energy Saving P.11
Compact & Lightweight P.12
Quick Cooling P.13
Benefits of Inverters P.14
Durability P.15
Convenient Functions P.16
Reuse of Existing Piping P.17
Design Flexibility P.18
Smart Airflow Control P.19
Special Situations P.19

Indoor Unit P.20

Ceiling Mounted Cassette type P.21-28


<Round Flow>
Duct Connection Middle Static P.29-30
Ceiling mounted cassette type Ceiling mounted cassette type Wall mounted type Pressure type
(Designer panel) (Standard panel) Ceiling Suspended type P.31-32

Wall Mounted type P.33-34


Floor standing type P.35-36

Outdoor Unit P.37-38

Remote Controller P.39-41

Functions P.43-46

Specifications P.47-50

Options P.51-53

Dimensions P.55-66
Duct connection Duct connection Floor standing type
middle static pressure type middle static pressure type Installation Service Space for Outdoor Unit P.67

7 8
Product Lineup
Cooling only

Series 50 60 71 100 125 140


CEILING MOUNTED
CASSETTE TYPE
Round Flow
Page
21
Indoor unit FCF50CVM FCF60CVM FCF71CVM FCF100CVM FCF125CVM FCF140CVM
Outdoor unit RZF50CVM RZF60CVM RZF71CVM RZF71CYM RZF100CVM RZF100CYM RZF125CVM RZF125CYM RZF140CVM RZF140CYM

DUCT CONNECTION
MIDDLE STATIC
PRESSURE TYPE
Page
29
Indoor unit FBA50BVMA FBA60BVMA FBA71BVMA FBA100BVMA FBA125BVMA FBA140BVMA
Outdoor unit RZF50CVM RZF60CVM RZF71CVM RZF71CYM RZF100CVM RZF100CYM RZF125CVM RZF125CYM RZF140CVM RZF140CYM

CEILING SUSPENDED TYPE

Page
31
Indoor unit FHA50BVMA FHA60BVMA FHA71BVMA FHA100BVMA FHA125BVMA FHA140BVMA
Outdoor unit RZF50CVM RZF60CVM RZF71CVM RZF71CYM RZF100CVM RZF100CYM RZF125CVM RZF125CYM RZF140CVM RZF140CYM

WALL MOUNTED TYPE

Page
33
Indoor unit FAA71BVMA FAA100BVMA
Outdoor unit RZF71CVM RZF71CYM RZF100CVM RZF100CYM

NEW NEW NEW NEW NEW NEW


FLOOR STANDING TYPE

Page
35
Indoor unit FVA50AMVM FVA60AMVM FVA71AMVM FVA100AMVM FVA125AMVM FVA140AMVM
Outdoor unit RZF50CVM RZF60CVM RZF71CVM RZF71CYM RZF100CVM RZF100CYM RZF125CVM RZF125CYM RZF140CVM RZF140CYM

OUTDOOR UNIT

Page
37
Outdoor unit RZF50CVM RZF60CVM RZF71CVM RZF71CYM RZF100CVM RZF100CYM RZF125CVM RZF125CYM RZF140CVM RZF140CYM

Power supply
1 phase, 3 phase, 1 phase, 3 phase, 1 phase, 3 phase, 1 phase, 3 phase,
220-230V, 60Hz 380V, 60Hz 220-230V, 60Hz 380V, 60Hz 220-230V, 60Hz 380V, 60Hz 220-230V, 60Hz 380V, 60Hz

9 10
New Inverters launched Compact & Lightweight
New outdoor units save even more space

Cooling only 109kg More compact,


much higher CSPF!
64kg

Energy Saving
1,345
23% reduction
in volume
Throughout the cooling season, 0.39m3 0.30m3
mm
990
Daikin’s new inverter models reduce energy consumption mm

40% reduction
Compared with previous non-inverter series, the new RZF-C series uses about 50% less power consumption
for quick and effective cooling that reduces electricity bills.
in weight
Comparison of cooling seasonal power consumption
320mm
109kg 64kg
based on average CSPF values 900mm 320mm 940mm

100
50%
reduction!
R140LUYAL (In case of 14.0kW class) RZF140CYM
power consumption
Cooling seasonal

Comparison with the previous mainstream non-inverter series


Outdoor units are much more compact and lighter weight.
50 They enable easy installation in places with limited space.

Note: Value 100 represents the amount of electricity used by a R71LUVAL R100LUVAL R125LUYAL R140LUYAL
non-inverter model during a similar annual cooling period.
75kg 92kg 98kg 109kg
Previous non-inverter series New inverter RZF-C series
(average) (average)
(cassette type) (cassette type)
Previous
1,170 1,170 1,345
non-inverter 770 mm mm mm

CSPF values by capacity for cassette models R-LU series mm

New inverter RZF-C series R32 <cassette type>


CSPF Previous non-inverter series R22 <cassette type>
7 900mm
Value *CSPF (cooling seasonal performance factor) is a new 900mm 900mm 900mm
international energy-efficiency criterion calculated by
6 6.60 6.31 methods stipulated in ISO 16358-1.
6.17
5 5.50 5.15 5.00
4
7.1 kW 10.0 kW 12.5 kW 14.0 kW
3
2.81 2.76 2.95 RZF71CVM RZF100CVM/CYM RZF125CVM/CYM RZF140CVM/CYM
2 2.64
41kg 48kg
1 64kg

0 New inverter
695 990
RZF-C 595 mm mm
Inverter RZF50CVM RZF60CVM RZF71CVM RZF100CVM RZF125CYM RZF140CYM mm
series
Non Inverter R71LUVAL R100LUVAL R125LUYAL R140LUYAL 845mm 930mm
940mm

What is CSPF? Reduced by 34kg 61kg 34kg 45kg


CSPF is the value for the annual total cooling load divided by the annual total power consumption at outdoor
air conditions specified by ISO standard. Unit weight is greatly reduced.
11 12
Quick Cooling Benefits of Inverters
Faster cooling and dehumidification Quick cooling start function
New inverter control technology brings quick comfort. Quickly and easily make space comfortable before
Why is inverter technology economical?
the arrival of office workers or shop customers.
As well as quick cooling at maximum capacity, new
Inverter system consumes less

unit price + cost of electricity


inverter control rapidly removes indoor humidity.
More than simple temperature reduction, this twin electricity, and soon recovers the Non inverter Inverter
reduction provides greater comfort (within a maximum
difference in initial cost.

Total cost =
New Inverter (RZF-C series) of 30 minutes).
Usual Inverter (RZR-L series) This results in lower total cost.
Inverters save more
Non inverter energy over time
Capacity
Time
Recovery point
INV Max

Non Max Inverter air conditioner can adjust its Rated condition

Better performance
cooling capacity according to the
than non-inverter models! cooling load. This results in less
Reaches maximum capacity faster
than usual inverter models.
power consumption. Non inverter cooling capacity

Capacity
Load
In response to fluctuating cooling load, Non inverter On/Off operation
air conditioners repeatedly perform ON (full-power)/ Lower efficiency Inverter cooling capacity
Time OFF (zero-power) operation. Inverter air conditioners,
Start
however, operate at optimal cooling capacity according
BRC1E63 wired remote controller to the cooling load. Since inverter air conditioners Cooling load Partial load area
Indoor is used for ‘Quick cooling start’. provide required minimum cooling capacity with
Reaches the
temp. minimum electrical power, total power consumption 0
set temperature faster. 35
can be reduced during cooling period.
Outdoor ambient temperature (°C)

Start Inverters operate without repeated ON/OFF operation.


Inverter Highway driving Non inverter City driving
Stop, go, stop ...

Setting
temp.
Start Time

Indoor Removes Continuous driving without stopping and starting is Constantly stopping and starting consumes energy
humidity humidity faster. more fuel efficient. and is less fuel efficient.

Start
Why is inverter technology more comfortable?
Non inverter Inverter
When temperature does not
fluctuate much, the set
temperature is maintained.
Start Time Inverter control responds to load changes
and causes minor temperature adjustments. Room
temperature Too hot
Non-inverter control frequently turns ON and
OFF in response to load fluctuations or load Large
temperature
mismatch and causes large temperature fluctuation
swings.
Set
temperature
Non inverter
Comfortable
Small
temperature
fluctuation
Inverter
Non inverter
Too cold Too cold

Time

13 14
Durability Convenient Functions
Overvoltage PCB Microchannel heat exchanger Navigation remote controller BRC1E63 includes various
(Outdoor unit option) See page 54
Microchannel technology utilises superior heat transfer convenient functions
benefits of aluminium to create a more efficient air Automatic return to temperature preset by owner. Owner can preset upper and lower temperatures.
Unstable power supply is a common problem in many conditioner.
regions. It can cause overvoltage which can significantly With a new resistance corrosion aluminium alloy, the Setpoint auto reset Setpoint range set
damage electronic devices. Daikin microchannel heat exchanger becomes highly - Even if the set temperature is - Saves energy by limiting the min.
To prevent voltage fluctuations, it is usually necessary to durable. changed, the new set and max. set temperature.
attach a stabiliser when installing an air conditioner. A salt spray test has been conducted to demonstrate the temperature returns to the - Avoids excessive heating or
The RZF-C series is equipped with a highly-durable corrosion-resistant capability of our products in previous preset value after a cooling.
electronic circuit. preset duration of time. - This function is convenient if the
corrosive environments for a certain period of time.
- Period selectable from 30, 60, remote controller is installed
This circuit eliminates the need for a stabiliser and offer
Test of durability 90, or 120 minutes. where anyone can change the
additional protection for devices in the outdoor unit, settings.
such as its fan motor and compressor. - Testing organization MTEC Thailand
- Testing standard ASTM B117
- Result
Restaurant example
Automatic protection against Before testing After testing
low voltage Restaurant opened Full tables at lunchtime After 30 minutes*

27 °C 24 °C
In AM and PM peak electricity consumption periods, Returns to
supply may fluctuate. Built-in low-voltage protection will
automatically cut operations. When normal voltage is 27 °C
restored, operation will resume as before. Normal Under automatically
observation telescope
No evidence of corrosion was observed

Outdoor unit installation is After undergoing an intensive test, the Daikin microchannel
Then is lowered to 24ºC Automatically returns to
heat exchanger is able to maintain its shape without Temperature is set to 27ºC
possible even with limited space corrosion, which strongly confirms its durability in a highly for crowded room preset temperature (27ºC)
corrosive environment. *Preset-return time can be set at 30, 60, 90, or 120 min

Coated printed circuit boards Demand control function


(outdoor unit) By setting limits that restrict power consumption, you can cut electricity bills. * RZF100-140CVM, 71-140CYM

* Field setting with remote controller


100 Coated circuit boards - Power consumption is given first priority, and limits maximum power
m or prevent problems
* Required for KRP58M51 (Option)
mo m or m me consumption of unit. Limitation
re 0 r

consumption
100
m 10 mo or
caused by humidity Maximum power consumption can be set at 40, 60, 70, 80, or 100%.
mo m or mm and airborne dust.

Power
re 0 r e
50 mo It also protects
against salt contained
in sea breezes.
8:00 12:00 16:00 20:00 Time
Both sides of the PCB
in outdoor units are
coated. Night quiet operation mode
Consideration is given for people living nearby.
Outdoor unit operating sound can be reduced. *Field setting with remote controller
Self-diagnosis functions enable Peak outdoor temperature

prompt maintenance response

Capacity (%)
The operating 100
An error message appears on the LCD of the remote noise bothers
controller and an LED lights up on the unit. 8 hours
me at night! 50 10 hours
When the BRC1E63 is installed, the error code appears

Load (%)
showing contact information and model name. Contact
0
your Daikin dealer and provide the error code and 48
model name.

Sound (dB(A))
Rated

Operating
Quiet mode
44 Quiet mode

8:00 12:00 16:00 20:00 0:00 4:00 8:00

Note: Daikin data for RZF71C


Operating sound about 4 dB quieter

15 16
Reuse of Existing Piping Design Flexibility
Benefit 1 Possible to forced OFF and ON/OFF operation using external command
*Field setting with remote controller
Simplified installation reduces replacement time and cost
Round flow cassette type Duct connection middle static pressure type

When considering air conditioner replacement, do the following


Lighting

things concern you? Interlock

The length of time the business will be closed


Effect on sales during replacement work Interlock
High costs and long work period due to scaffolding needed for pipe replacement

These problems are solved by Daikin!

Where feasible, we reduce work costs and time by reusing existing pipes*. External Equipment Interlock (FCF-C series only)
Power conservation is possible though interlock* of external equipment, *Optional adaptor for wiring: KRP1C11A is necessary.
such as lighting, with the infrared presence sensor.
*Strict conditions apply, please check the table on page 37 for acceptable pipe sizing (if pipes are to be reused).
Human presence is detected by the built-in infrared Sensor The presence detection signal of the infrared presence sensor
presence sensor in the sensing panel, and the interlock can turn only external equipment ON/OFF without interlocking
mode with air conditioner operation/stop (ON/OFF).
Benefit 2 presence detection signal can be output and interlocked
with external equipment such as ventilation and lighting
You can increase cooling capacity and achieve higher energy efficiency equipment.
Upgrade to an air conditioner with the latest technology for greater comfort and energy efficiency.
External equipment also
Presence Sensor Sensor automatically turns ON/OFF.
detection Undetected Detected
signal Contact OFF Contact ON Further energy savings
R22 R32 Lighting Ventilation and power conservation
Non inverter inverter equipment equipment
8.1 kW 14.0 kW Infrared presence Note:
class class sensor information Adaptor for wiring: When the presence detection signal is output to external equipment using the adapter
KRP1C11A (Option) for wiring, other functions, such as interlock with the duct booster fan and the output
of other signals, become disabled.
φ9.5 φ15.9 φ9.5 φ15.9
Pipes used
as they are!
Indoor units comply with D -Net standards
As a result, the greater capacity units
FHYC71KVE FCF140CVM ensure better performance to cope
R71LUVAL RZF140CVM
with the increasing amount of heat Previous indoor unit New indoor unit
CSPF: 2.64 CSPF: 5.00 generated by office equipment and
occupants.

Adaptor not
Technology required
Optional
Advanced technology, including the use of corrosion resistant electronic expansion valves, acid neutralisers and improved FHQ-BV interface adaptor
compressor reliability, enables the re-use of existing piping* without the need of pipe flushing for a simplified replacement process. is required FHA-B

Stronger refrigerating Highly corrosion resistant Highly reliable


machine oil electronic expansion valve compressor VRV
VRV

An acid neutraliser agent is added to disable Compressor durability is improved


acids (chlorine ions), which cause corrosion. by installing a filter or accumulator
to collect solid foreign substances.

Acid neutraliser
Filter or
accumulator
Acid (chlorine ion)
Compressor

Refrigerant pipe

*Strict conditions apply, please check the table on page 37 for acceptable pipe sizing (if pipes are to be reused). Easy connection to DIII-NET and long piping length makes this solution suitable for projects including and SkyAir.
17 18
Smart Airflow Control Detail of Each Product Specification
Indoor units can provide 5-step and 3-step fine control of air volume
5-step: FCF and FHA series
3-step: FBA, FAA, and FVA series

CEILING MOUNTED
Comfort ensured by ‘Auto’ CASSETTE TYPE FCF-C Series Page 21
airflow rate that matches Round Flow
load level
Convenient energy-efficiency for stores
with peak and quiet periods.

DUCT CONNECTION
Level 1 (Low) Level 2 Level 3 (Medium) Level 4 Level 5 (High) Auto
MIDDLE STATIC FBA-B Series Page 29
PRESSURE TYPE

CEILING SUSPENDED TYPE FHA-B Series Page 31

Also convenient for high ceilings and spaces with long blow distances
*Field setting with remote controller
Cassette type <Round Flow>: Ceiling suspended type:
maximum 4.2 m* maximum 4.3 m

WALL MOUNTED TYPE FAA-B Series Page 33

4.2 4.3
m m

See page 25 See page 32 FLOOR STANDING TYPE FVA-A Series Page 35

*Maximum 4.2 m for FCF100, 125, 140


Maximum 3.5 m for FCF50, 60, 71

More Economy or Comfort in Special Situations OUTDOOR UNIT RZF-C Series Page 37

High sensible cooling enables High dehumidification cooling


even greater power savings provides even greater comfort
In locations such as In restaurants and other
simple server rooms, spaces where many people
dehumidification is not gather, ‘High
required and greater dehumidification cooling’
power savings are mode reduces humidity and
possible with 'High creates greater comfort.
REMOTE CONTROLLER Page 39
sensible cooling' mode.

*Available with RZF100-140CVM,


*Available with RZF-C series. 71-140CYM models.
Field setting with remote controller. Field setting on outdoor unit.

19 20
CEILING MOUNTED CASSETTE TYPE Round Flow See P. 3-6 for new
functions of Round
New Round Flow
Cassette movie at
Flow Cassette. Daikin official

Cassette air conditioner with 360°


YouTube site.

Circulation Airflow

uniform airflow sets the standard


Cools the entire room to deliver comfort that never feels cold.

Cooling operation repeatedly performs the following at start.


2-way horizontal flow
NEW
4-way swing flow
FCF50/60/71/100/125/140CVM
2-way horizontal flow (direction changes)

4-way swing flow

Individual Airflow Direction Control 360° Airflow


Airflow direction can be individually adjusted for each air With uniform temperature distribution
discharge outlet to deliver optimal air distribution that
conforms to conditions for airflow direction (small and large
loads)
Option Selectable from position 0 to 4, swing, and no individual setting.
Accessory required for indoor unit. Airflow
distribution
Navigation Remote Controller creates uniform
(Wired Remote Controller) Example comfort throughout
NEW Position 0 No individual
the space.
BRC1E63 (Fixed airflow to
highest position)
setting
(Auto airflow)
Room remains
Note: Remote controller cable is not
included and must be obtained comfortable even
locally. when set temperature
Position 4 is raised 1℃.
Swing
(Up/down)
(Fixed airflow to the Greater comfort
lowest position)

Wireless LCD remote controller


A signal receiver must be added to the indoor unit.

NEW
Cooling only BRC7M635F
Selectable Airflow Pattern
(Fresh white)
BRC7M635K
(Black)
Because air flows out from corner outlets, comfort spreads more widely.
Signal receiver unit
(Installed type)
Typical flow patterns There are a total of 18 flow patterns.
Wireless remote controller is supplied in a
set with a signal receiver.
L-shaped Opposite
All-round flow 3-way flow
2-way flow 2-way flow

Panel variations

(E.g., installed in (E.g., installed (E.g., installed in (E.g., installed in


Standard panel with Standard panel middle of ceiling) near a wall) a corner) a long room)
Sensing (Fresh white) 4-way flow also possible.
(Fresh white)
Note:
- Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow,
Required * an air discharge outlet sealing material (option) must be used to close each unused outlet.
Designer panel distance to Minimum distance
wall surface - Operation sound increases when using 2-way or 3-way flow.
of 500mm
(Fresh white) for closing - Designer panel cannot operate 2-way and 3-way flow.
* 200mm for corner
air discharge * closing
outlet Wall surface
Standard panel with Standard panel
Sensing (Black)
(Black) Auto grille panel
(Fresh white)
21 22
CEILING MOUNTED CASSETTE TYPE Round Flow New Round Flow
Cassette movie at

Daikin Sensing Technology*1,2


Daikin official
*1. Applicable when sensing panel (BYCQ125EEF/EEK) is installed.
YouTube site.
*2. Applicable when wired remote controller BRC1E63 is used.

Dual Sensors*1
Comfort and Energy Saving Preventing Overcooling*6 *6.Airflow direction and airflow
rate should be set to “Auto”.

Dual sensors and individual airflow direction control automatically provide


optimal control of airflow. Floor temperature is detected and overcooling prevented. Cooling

Infrared presence sensor Without sensing function With sensing function

The sensor detects the presence of people in each of the


4 areas. 30°C near ceiling 30°C near ceiling
Ceiling height 2.7m 3.5m 4.0m
Room 2 Room temperature is
Detection range approx. approx. approx. temperature is calculated as 27°C in the area which
(diameter)*3 8.5m 11.5m 13.5m detected as is in the vicinity of the person.
30°C.
*3. The infrared presence sensor detects 80cm above the floor.

1 24°C near floor


20°C near floor
Detecting the
presence of people
Infrared floor sensor
in each of the 4 areas The floor temperature, Automatic control using
The sensor detects the floor temperature and Area around feet gets too cold because the air
conditioner continues until the temperature near the which is lower than the temperature near the
automatically adjusts operation of the indoor unit to
ceiling reaches the set temperature. near the ceiling, is person as the room
reduce the temperature difference between the ceiling
C and the floor.
detected. temperature.

B D
Ceiling height 2.7m 3.5m 4.0m Energy The temperature near the person is automatically calculated by detecting the temperature of the
A savings floor. Energy is saved because the area around the feet does not get too cold.
Detection range approx. approx. approx.
(diameter)*4 11m 14m 16m

Detecting the
*4. The infrared floor sensor detects at the floor surface.
Sensing Sensor Functions*7,8 *7. These functions are not available when using the group control system.
*8. User can set these functions with remote controller.
Standard range for infrared presence sensor *
average temperature
of the floor Sensing sensor low mode (default: OFF)
When there are no people in a room,
2.7m
ceiling the set temperature is shifted automatically. Operation is
height
- The system automatically saves energy by detecting reduced in places
whether or not the room is occupied. The set temperature is where there are
shifted automatically if the room is unoccupied. no people.
80cm
above floor 約8.5m
approx.8.5m • Cooling set temperature: 26°C • Shift temperature: 1.0°C
Example
*[Concerning infrared presence sensor] • Shift time: 30 min. • Limit cooling set temperature: 30°C

Set temperature (°C)


- People are detected by large movements such as the motion of people walking at a
certain distance away from sensor.
*9
- Human detection is not possible for blind areas of sensor.
28 28°C
[Concerning infrared floor sensor] *9
- The detected temperature may sometimes be affected by a heat source, window, or 27 27°C
device emitting heat in the detection range.
26 26°C
26℃ 26°C
26℃ If people do not return,
Occupied Automatically reverts the air conditioner will
when people return.
Auto Airflow Function*5 *5.Airflow direction should be set to “Auto”. Unoccupied
raise the set
temperature 1°C every
30 minutes and then
operate at 30°C.
Direct Airflow (default: OFF) Cooling Dry After 30 min After another 30 min
Time

When human presence is not detected When human presence is detected Shift temperature and time can be selected from 0.5 to 4°C in 0.5°C increments and 15, 30, 45, 60, 90 or 120 minutes respectively
with remote controller.

*9. On basic screen of remote controller, set temperature does not change.

Sensing sensor stop mode (default: OFF)


When there are no people in a room, the system stops automatically.*10, 11
- The system automatically saves energy by
detecting whether or not the room is occupied.
- Based on preset user conditions, the system Absent stop time can be selected from
1 to 24 hrs in 1 hr increments with
automatically stops operation if the room is
remote controller.
Optimal air direction Swing (narrow) unoccupied.
Optimal air direction by “Auto” by “Auto” *10.Please note that upon re-entering the room,
the air conditioner will not switch on automatically.
With “Auto” airflow direction mode, flaps are controlled When presence is detected, air direction is set *11.To protect the machine, the standby system may
to deliver optimal airflow when the room is unoccupied. to “Swing (narrow)” to deliver cool air to users. operate temporarily.

23 24
CEILING MOUNTED CASSETTE TYPE Round Flow

Comfort Quick and Easy Installation Washer fixing plate


Washer
m 95
950
m
0m
Unified square panels m Same for Lightweight Easy hanging
Panel size is the same for all models. all models All models can be installed without using a lifter. Washer fixing plates secure washers
It is easy to maintain a neat appearance when multiple units are in place and prevent washers from
installed in the same room. falling for easy installation.
Installable in tight ceiling spaces
Standard panel
Optimal comfort and convenience assured by 3 air discharge modes
261mm (50-71C)
Draft prevention setting Ceiling soiling prevention
256mm (50-71C)
298mm (100-140C) 303mm (100-140C) Easy removal of corner cover
Air direction Standard setting1 setting2 (field setting) It is possible to easily
(field setting)
remove without use
For shops with of screws or tools.
Desired situation For gentle drafts. When drafts are unwanted. light coloured ceilings that
must be kept spotless. Designer panel

256mm 261mm +42mm*1


Auto-swing 298mm 303mm
Note:
1
Air direction is set to the 42mm*1
standard position when the
5-level unit is shipped from the *1.Body height (ceiling required space) is 42 mm higher than standard panel.
air direction setting factory. The position can be
changed from the remote
controller.
The air direction is set automatically to the memorised 2 Auto grille panel
Closing of the corner
Auto air direction position of the previous air direction. discharge outlets is
control recommended. 256mm 261mm +55mm*2
298mm 303mm
55mm*2
Switchable fan speed: 5 steps and Auto Quiet operation dB(A)

Control of airflow rate has been improved from 3-step to 5-step. Indoor unit
Sound pressure level *2.Body height (ceiling required space) is 55 mm higher than standard panel.
Auto airflow rate is newly available. H HM M ML L *When the ceiling space is limited, an optional panel spacer is available.
50-71C 37.0 34.5 32.0 29.5 27.5 (see P.28)

100C 45.0 41.5 38.0 35.0 32.5

Suitable for high ceilings 125/140C 46.0 43.0 40.0 36.0 32.5
Easy height adjustment
Even in spaces with high ceilings, a comfortable airflow is carried down to the floor level.
Each corner of the unit has an Ease in temporary hanging
Criteria for ceiling height and number of air discharge outlets
Standard Setting Setting
(Ceiling height is reference value)
adjuster pocket that lets you
easily adjust the unit's
of decoration panel
Number of air discharge outlets used suspended height. In addition to the temporary
50-71C 100–140C hanging fixtures in 2 places
3.6 4.2 All round 4-way 3-way 2-way All round 4-way 3-way 2-way
Note: normally used, corner part
3.2 m flow flow flow flow flow flow flow flow If the wireless remote controller is installed,
mounting fixtures in 4 places
m m a signal receiver unit is housed in one of
Standard 2.7 m 3.1 m 3.0 m 3.5 m 3.2 m 3.4 m 3.6 m 4.2 m the adjuster pockets. are provided.
Ceiling
height
High ceiling 3.0 m 3.4 m 3.3 m 3.8 m 3.6 m 3.9 m 4.0 m 4.2 m Corner part mounting
High ceiling 3.5 m 4.0 m 3.5 m - 4.2 m 4.5 m 4.2 m - fixtures (in 4 places) Temporary hanging
fixtures (in 2 places)
Note:
When all round flow is selected, ceilings up to 4.2 m in height
can be accommodated. (100-140C)
The aforementioned is for standard panels. See the installation manual for designer panels.
Factory settings are for standard ceiling height and all-round flow. Temporary placement of control Drain pump
High ceiling settings (1) and (2) are set with the remote controller by field setting.
High-efficiency filters are not available for high ceiling applications. box lid Equipped as standard
accessory with
Because the control box lid can be temporarily hung 850 mm
Humidity sensor on the unit, there is no need to climb down the
850 mm lift.
Not only temperature but also humidity is stepladder to retrieve it.
detected, and adjustments are made for 175 mm
comfortable air conditioning.

Transparent drain socket


Cleanliness
Silver ion anti-bacterial drain pan Non-flocking flaps The detached lid can
Flaps can be detached without use of tools. be hung on a hook.
A built-in antibacterial Hanging height adjustment
treatment that uses silver Condensation does not easily
Because the configuration of the hanger bracket changed, the
ion in the drain pan prevents form and dirt does not cling to
the growth of slime, non-flocking flaps. Installed in any direction dimensions from the ceiling to the hanger bracket also change
during height adjustment for indoor unit.
bacteria, and mould that They are easy to clean. Since the orientation of the A Dimensions
Hanger
cause odours and clogging. suction grille can be bracket Standard panel 125-130mm
adjusted after installing,
(The lifespan of a silver ion
cartridge depends on the
Filter has anti-mould and the direction of the suction A
Designer panel
Auto grille panel
167-172mm
180-185mm

usage environment, but antibacterial treatment grille lines can be unified


Ceiling
Chamber option*+ standard panel 175-180mm

should be changed once Prevents mould and microorganisms growing out of the when multiple units are surface *High-efficiency filter, ultra long-life filter, and
fresh air intake
every two to three years.) dust and moisture that adheres to the filters. installed.
25 26
CEILING MOUNTED CASSETTE TYPE Round Flow

Easy Maintenance Options


Condition of the drain pan and Auto grille panel (option) Options required for specific operating environments
drain water Grille and air filter cleaning can be performed without need for
Ultra long-life filter unit Fresh air intake kit Note 1.2
Can be checked by removing the suction grille and a stepladder by lowering the grille.
drain plug. Even in dusty environments where the air conditioning Using this kit, a duct can be connected to take in outdoor
A dedicated remote controller for the auto grille panel (BRC16A2) is constantly operating, the ultra long-life filter only has air. There are two chamber types that have intake in two
Note: For inquiries concerning auto grille panel installations, please
contact your local dealer or Daikin representative. is included. to be cleaned once a year. places: with T-duct joint and without T-duct joint.
Operation is not possible using BRC1E63.
Filter chamber Outside
(Can be used with high-efficiency filter)
The drop length corresponds to
the ceiling height and can be set for
Drain outlet u s t open rille! 8 different levels.
J Ultra long-life filter
ion g
suct
(with rubber plug) Ceiling Height
Drop Length Dusty area: annual filter change
Standard (m) *For dust concentration of 0.3 mg/m3 (Requires separately sold Air purifier.)
1 year (Approx. 5,000 hr) 15 hr/day x 28 day/month x 12 month/year
The units can be installed in the following
2.4 1.2 different ways
Ordinary store or office: filter change every 4 years
2.7 1.6 *For dust concentration of 0.15 mg/m3
Chamber type (without T-duct joint) Note 3.4.5
3.0 2.0 4 years (Approx. 10,000 hr) 8 hr/day x 25 day/month x 12 month/years
x 4 years
24 mm diameter drain outlet 3.5 2.4 KDDP55B160

3.8 2.8 Flexible duct


The drain outlet allows
4.2 3.1
High-efficiency filter unit (obtained locally)
insertion of a finger or T-duct joint
dental mirror for inspection 4.5 3.5 Available in two types: 65% and 90% colorimetry. (obtained locally)
Suction
of the internal cleanliness 5.0* 3.9 Filter chamber chamber Intake duct
(obtained locally)
of the drain pan. Removal *Airflow range is up to 4.5m. (Can be used with ultra long-life filter)
Connection (duct length: 4 m max.)
of the suction panel Please refer to “criteria for ceiling height chamber
enables access. and number of air discharge outlets” on
page 25. High-efficiency filter Chamber type (with T-duct joint) Note 3.4.5

KDDP55B160K

Ultra long-life filter (option) Insulation kit for high humidity Flexible duct

See page 28 Please use if you think the temperature and humidity T-duct joint
inside the ceiling exceeds 30°C and RH 80%, Suction
Maintenance is not required in normal shops or respectively. chamber Intake duct
(obtained locally)
offices for up to four years. Connection (duct length: 4 m max.)
Top panel insulation(1) chamber
Top panel insulation(2) Direct installation type
Low gas pressure detection Top panel insulation(3)
Note 6

KDDP55X160A
Insulation for decoration panel
Side panel insulation
Suspension bracket insulation

Panel spacer Duct flange


(with insulation material)
Use when only minimal space is available between Intake duct
(obtained locally)
drop ceilings and ceiling slabs.
Note: Some ceiling constructions may
hinder installation. Contact your
Note: 1. Use of options will increase operating sound.
Daikin Dealer before installing your
unit. 2. Connecting ducts, fan, insect nets, fire dampers, air filters, and other
40mm parts should, as required, be obtained locally.
Panel spacer 3. When a local-obtained fan is used, an interlock with air conditioner is
necessary.Optional PCB (KRP1C11A) is required for interlocking.
4. When installing a fresh air intake kit (chamber type), two air outlet
Sealing material of air discharge outlet corners are closed.
5. It is recommended that the volume of outdoor air introduced through
Sealing material block air discharge openings not used the kit is limited to 10% of the maximum airflow rate of the indoor
in 2-way or 3-way blow. unit. Introducing higher quantities will increase the operating sound
and may also influence temperature sensing.
6. The volume of fresh air for direct installation type is approximately
1% of the indoor unit airflow.
Branch duct The chamber type is recommended when more fresh air is
necessary.
(direct-connection round duct)
A round duct can be attached without the need for a
chamber.
A flanged port for direct connection of a round duct is
provided. An existing branch duct chamber can also be
fitted (square slit hole).

27 28
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Design and Installation Flexibility

Thinner design allows greater Only 245 mm high


Installation is possible even in buildings
Adjustable E.S.P.
External static pressure can be controlled to within a

installation flexibility
with narrow ceiling spaces. range of 50 Pa to 150 Pa by using a DC fan motor.

245mm 50 Pa 150 Pa
NEW
One of the industry’s most compact
FBA50/60/71/100/125/140BVMA bodies in the mid-static pressure range.
Set to low static
pressure when ducts
Set to high static pressure for
advanced needs such as when
are short. using dampers and long ducts.
Indoor unit 50/60/71B 100/125/140B
Height (mm) 245 Comfort airflow is achieved in accordance with conditions
Width (mm) 1,000 1,400 such as duct length.
Depth (mm) 800

Higher lift is realized Airflow rate auto adjustment function


A built-in DC drain pump with standard accessory is utilised. Controls the airflow rate using a remote controller during
test run.
Middle & High static It is automatically adjusted to approximately ±10% of the
pressure type rated H tap airflow.
850mm (FBQ-D series)
Option
700mm
Accessory required for indoor unit. Interlock control
Navigation Remote Controller As an energy saving
(Wired Remote Controller) Bottom suction is available feature, the room air
NEW Wiring and servicing conditioning unit can be
can be done from the interlocked with the hotel
BRC1E63 unit joist
key card system.
Interlock
underside of the unit
Note: Remote controller cable is not (an option part Using a 3rd-party building
Air suction
included and must be obtained
required). management system, air
locally. ceiling
conditioning and lighting * Field setting with remote controller
can be interlocked.
Rear suction Bottom suction
Air suction flange Shield plate for side plate (option)
DIII-NET communication standard
Wireless LCD remote controller Connection to a centralised control system is available
A signal receiver must be added to the indoor unit.
without need for an optional adaptor.
Cooling only BRC4C66

Switch bottom plate with


Control box air suction flange.
Signal receiver unit cover Bottom Air suction

Easy Maintenance
(Separate type) plate Make the control box flange
face inward. Bottom plate

Wireless remote controller is supplied in a

Position of drain pan inspection opening


set with a signal receiver.

Modified for easier inspection work.


Control box cover
Control box faces outward. Control box faces inward.

Drain pan maintenance check window


Comfort This makes it possible to inspect for drain pan dirt and to
confirm drainage during installation without the use of
Switchable fan speed: 3 steps and Auto tools.
“Auto” is applicable when BRC1E63 is used.

Clean
Inspection
opening for
drain pan
Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening) Drain pan
When air conditioning two rooms
simultaneously, the air discharged into
Door-installed
ventilation grille
Wall-installed
ventilation grille Under-door cutout Silver ion anti-bacterial drain pan maintenance
check window

each room must be circulated back to A built-in antibacterial treatment that uses silver ion in the
the air conditioner. To achieve this, a drain pan prevents the growth of slime, bacteria, and mould
ventilation duct should be installed for
High Efficiency
Ventilates air through
Partitioning wall
the partitioning wall. that cause odours and clogging.
each room or one of the indicated
ventilation grilles should be installed
(See right)
Ventilation grille Ventilation grille Under-door cutout
(The lifespan of a silver ion
on the partitioning wall or under the cartridge depends on the
door between the rooms.
Note: The under-door cutout method should be used only when there is a small volume of airflow.
usage environment, but DC fan motor and DC drain pump
should be changed once These are utilised to improve energy efficiency.
every two to three years.)
29 30
CEILING SUSPENDED TYPE
Stylish Model Installation Flexibility for

Comfortable airflow travels Sophisticated design


Flap neatly closes when not in use.
Freedom of Design
Flexible

throughout the room White colour

Comfort
installation
The unit fits more
snugly into tight
spaces.
30 mm
or more
30 mm
or more

*Water used in the test-run can be drained from


the air discharge opening rather than from the
side as was formerly the case.
NEW
FHA50/60/71/100/125/140BVMA The technology of the DC fan motor, Drain pump kit (option)
wide sirocco fan, and large heat can be easily
exchanger combine for greater airflow incorporated 600
mm
and quiet operation Drain pipe connection can
be done inside the unit.
Auto swing (up and down) and louvers Refrigerant and drain pipe
outlets are at the same
Drain pump kit
(built inside
(left and right by hand) bring comfort opening. the unit)
to the room
DIII-NET communication standard
Louver manually adjusts for straight Connection to a centralised control system is available
or wide angle airflow without need for an optional adaptor.

Option All wiring and internal servicing can


Accessory required for indoor unit. be done from under the unit
Navigation Remote Controller
(Wired Remote Controller) Easier piping work for
NEW rear side by
BRC1E63
Suitable for high ceilings removable frame
Note: Remote controller cable is not

Easy Maintenance
included and must be obtained
locally.
4.3
3.5 m
m
Drain pump kit (option) includes a
Wireless LCD remote controller silver ion antibacterial agent
A signal receiver must be added to the indoor unit.
50-71BVMA 100-140BVMA That assists in preventing the growth of slime, bacteria,
and mould that cause odours and clogging.
NEW 50-71B 100B 125/140B
Cooling only BRC7M56 Standard 2.7m or less 3.8m or less 4.3m or less
High ceiling 2.7m-3.5m 3.8m-4.3m - Non-flocking flap
Note: Factory settings is “standard”. Condensation does not easily
“High ceiling” are set with remote controller by field setting. form and dirt does not cling to
non-flocking flap.
Signal receiver unit (Installed type) It is easy to clean. Non-flocking flap
Wireless remote controller is supplied in
a set with a signal receiver.
Switchable fan speed: 5 steps and Auto
Control of airflow rate has been improved from 3-step to 5-step.
Auto airflow rate is newly available. Easy-clean, flat surfaces
It is easy to wipe dirt off the flat side and lower surfaces
of the unit.

Quiet Operation
dB(A)
Sound pressure level
Oil Resistant Grille
Indoor unit
H HM M ML L
Oil-resistant plastic is used for the
50/60B 37.0 36.0 35.0 33.5 32.0
38.0 37.0 36.0 35.0 34.0
air suction grille.
71B
This satisfies durability in restaurants and other similar
100B 42.0 40.0 38.0 36.0 34.0 environments.
125B 44.0 42.5 41.0 39.0 37.0 Note: Intended for use in salons, dining rooms, and ordinary sales floors,
140B 46.0 44.0 42.0 40.0 38.0 this specification is not suitable for kitchens or other harsh environments.

31 32
WALL MOUNTED TYPE
Compact & Sophisticated Design Design and Installation Flexibility

Compact design and FAA100


9kg lighter FAQ100BV FAA100B
6-direction refrigerant
piping offers

easy installation
Height 360mm 340mm Left pipe

340
greater
Width 1,570mm 1,200mm
mm
installation
1,200mm Depth 200mm 240mm
flexibility Back-left pipe
370mm shorter Weight 26kg 17kg Bottom-left pipe
NEW Back-right pipe
Right pipe
FAA71/100BVMA Bottom-right pipe

Flaps neatly close when


not in use Maintenance possible from the
Fresh white colour front of the unit
All maintenance tasks can be carried out via front
access. During servicing, attachment and detachment
Comfort of parts is easier.

Auto swing (up and down) and wide-angle Drain pump kit is available as option
louvers (left and right by hand) Installs onto side of unit.

facilitate even room temperature Height of drain up

Refrigerant
piping
Wide-angle louvers (by hand) 1,000 mm
Soft material louver bends airflow over
a wider area
Option Indoor unit
Drain pump kit
Accessory required for indoor unit.
Drain pump kit can be installed on
Navigation Remote Controller either left and right side of the indoor
(Wired Remote Controller) An air discharge Auto-swing 5-level air direction setting
unit.
NEW modes ensure
BRC1E63 comfortable air
Note: Remote controller cable is not
distribution across Adjustable to 5
Interlock control
included and must be obtained
locally. the entire room different levels
As an energy saving feature, the room air
conditioning unit can be interlocked with the key card
system.

Wireless LCD remote controller


Comfort even on the far side of the room Using a 3rd-party building management system, air
conditioning and lighting can be interlocked.
A signal receiver must be added to the indoor unit. To carry air to the far side of long
rooms, extra-high airflow adds 10%
Cooling only BRC7EB519 more fan speed the "high" setting.
Lighting

Interlock
Air discharge strength is selected
from the remote controller by field
setting.
* Field setting with
Signal receiver unit (Installed type)
remote controller
Wireless remote controller is supplied in a
set with a signal receiver. Switchable fan speed: 3 steps and Auto
“Auto” is applicable when BRC1E63 is used.
DIII-NET communication
Programme "Dry" standard
Dehumidification is microprocessor controlled to prevent abrupt Connection to a centralised control system is
and uncomfortable changes in air temperature. available without need for an optional adaptor.

Easy Cleaning
Removable and Flat panel, easy to Non-flocking flaps
washable grille wipe dust off Condensation does not easily form
and dirt does not cling to non-flocking
flaps.
It is easy to clean.

33 34
FLOOR STANDING TYPE
Comfortable Airflow Control

New airflow control for Left and right directions (by remote controller) (Applicable when BRC1E63 is used.)

Auto swing direction is selectable from 3 patterns to suit the layout of the room.

more comfort Pattern 1 Swing wide across the front

New comfortable airflow control


Pattern 2 Swing across left side Pattern 3 Swing across right side

NEW

FVA50/60/71/100/125/140A

When installed in the center of a wall. When installed in the corner of a room.

Up and down directions (by hand)


Independent up-and-down airflow directions facilitate even room temperature and help save energy.

Freely select both Example applications


New unit
up and down Upper louver (1)
When cooling
airflow direction Upper interlocking louvers (4)
Turning louvers
with 8-louver Lower interlocking louvers (2)
and upward
(horizontal blade) Lower louver (1) and leaving
setting. and horizontal
BRC1E63 Each set of louvers to will reduce
can be can be independently uneven room
incorporated adjusted. (Manual adjustment) temperature.
into the
indoor unit.

Comfort Easy Maintenance


Switchable fan speed: 3 steps and Auto Long-life filter (standard) requires
“Auto” is applicable when BRC1E63 is used. no maintenance for about 1 year*
Option
High fan speed mode (applicable for FVA50-100)
The filter is washable and reused after 1 year.
* For dust concentration of 0.15 mg/m3
Accessory required for indoor unit.
To carry airflow to the far side of the room, airflow rate can -Two time settings (2500 hrs and 1250 hrs) are available to match the installation
environment. Maintenance time warning is displayed on the remote controller (filter
be increased 5% or 10% depending on the installation
Navigation Remote Controller sign).
(Wired Remote Controller)
condition or customer's request. (Field setting by remote -The periodical cleaning time for the filter can be shortened depending on the usage
environment.
controller.)

BRC1E63 Programme "Dry" Employs a safety lock function of


Note: Remote controller cable is not Dehumidification is microprocessor controlled to prevent suction grille
included and must be obtained
locally. abrupt and uncomfortable changes in air temperature. The grille will not open even upon impact.

High Efficiency Convenience


Wireless LCD remote controller
A signal receiver must be added to the indoor unit. DC fan motor improves efficiency Wireless remote controller
Cooling only BRC4C66 (separate type) is supplied
Easy Installation in a set with a signal receiver.
Signal receiver unit (BRC4C66)
(Separate type)
Lightweight indoor unit
Wireless remote controller is supplied in a
set with a signal receiver.
Enables smooth transport and installation of the indoor unit.
(kg)

Indoor unit 50/60/71A 100/125/140A


Weight 42 50
■ This product is equipped with a gas sensor.
The gas sensor reacts to nearby smoke, chemical agents, and paint as well as equipment containing flammable gas (including propane, butane, or
methane), and sprays using flammable gases (such as LPG), including insecticides and hair spray. When this occurs, a malfunction is displayed
and operation is not possible.
DIII-NET communication standard
■ A gas sensor that has once reacted must be replaced with a new gas sensor. Connection to a centralised control system is available
without option.
35 36
OUTDOOR UNIT
Technology for energy efficiency
Compact Outdoor Unit
The high efficiency compressor to
NEW
NEW
NEW achieve a high COP 3
RZF50CVM RZF125CVM
RZF71CYM
RZF60CVM
RZF71CVM
RZF100CVM
RZF125CYM
RZF140CVM
1 Compressor equiped with reluctance DC motor 2
RZF100CYM RZF140CYM Daikin DC Inverter models are equipped with the reluctance DC
motor for compressor.
The reluctance DC motor uses 2 different types of torque, neodymium 4
Easy Installation and Maintenance magnet*1 and reluctance torque*2. 1
This motor can save energy because it generates more power with a
4-direction piping offers greater layout Facilitates pump down (Refrigerant recovery function) smaller electric power than an AC or previous DC motor.
freedom (RZF125-140C) A pump-down switch is provided to make it easier to collect
The outer panel for the piping connection part of the front, refrigerant if the unit is to be moved or layout modified. Reluctance
right side and backside can be removed and is easier for *Pump-down function is available for pre-charged refrigerant amount.
Reluctance DC Motor
DC motor Swing compressor

Motor efficiency
post-installation piping work. *Although pumping-down operation allows most of the refrigerant to be High efficiency during partial load
recovered in a short period of time, some refrigerant will remain inside the
indoor unit and refrigerant piping. DC motor
operation.
Using a refrigerant recovery machine, recover remaining refrigerant from
Removable part of bottom the stop valve service port until the pressure falls to 0.09 MPa. (gauge
pressure:-0.011MPa) or less.
More than 20%
Energy savings is realised,
frame makes the piping AC motor eliminating the friction and the
work easier (RZF125-140C) Separation
Low gas pressure detection function leakage of refrigerant gas.
Swing bushing
available Effective gas monitoring reduces the labor required Refrigerant gas
for operation, maintenance, and repairs. Rotational speed
Small load Large load
Low capacity High capacity

Reuse of Existing Piping: Refrigerant Pipe Size Table


*1. A neodymium magnet is approximately 10
times stronger than a standard ferrite
Note: Data are based on studies conducted under magnet.
controlled conditions at a Daikin laboratory. *2. The torque created by the change in power
Existing pipe size (Liquid / Gas) 6.4 / 6.4 / 9.5 / 9.5 / 9.5 / 12.7 / 12.7 / Level Design pressure The allowable minimum piping length is 5 m. between the iron and magnet parts. Piston by incorporated
Outdoor Unit 12.7 15.9 12.7 15.9 19.1 15.9 19.1 difference (High pressure) blade and roller.
・Refer to the installation manual for details
Condition other than those mentioned in the left
RZF Max. table such as additional refrigerant charge
9.5 / 15.9 10m 10m 50m 50m ------- 25m ------- 4.15MPa
Refrigerant cooling
Max. piping length
50-71CVM 30m amount. 2 (RZF100-140CVM, RZF71-140CYM)
Chargeless pipng length 10m 10m 30m 30m ------- 15m ------- ・Clean the existing piping if its length
exceeds 30m. Daikin’s unique refrigerant cooling system exhibits
Existing pipe size (Liquid / Gas) 6.4 / 6.4 / 9.5 / 9.5 / 9.5 / 12.7 / 12.7 / Level Design pressure ・Clean the existing piping if existing piping
Outdoor Unit 12.7 15.9 12.7 15.9 19.1 15.9 19.1 difference (High pressure) length exceeds limit of chargeless piping
high cooling capacity even during high outdoor
Condition length to perform pump-down refrigerant temperatures.
RZF Max. recovery.
71CYM 9.5 / 15.9 Max. piping length 10m 10m 50m 50m 50m 25m 25m 4.15MPa
100-140C
30m Refrigerant cooling helps protect
Chargeless pipng length 10m 10m 30m 30m 30m 15m 15m the printed circuit board and
Standard pipe size Same condition with standard pipe Piping length and chargeless piping length are shortened maintains high cooling capacity
even during high outdoor
Piping length and chargeless piping length are much shortened Cooilng capacity is lowered (pay attention to piping length)
temperatures.
Reuse of existing piping is not allowed

Night Quiet Operation Mode 3 High efficiency by micro channel heat exchanger Reduced wind resistance
The flattening of the heat exchanger tubes
Peak outdoor temperature improves the flow of air and increases heat
The automatic night quiet mode will Sound pressure level1 exchange efficiency.
Capacity (%)

(dB(A))
initiate 8 hours after the peak Cooling
only
Rated2 Night Quiet
100
Conventional tube and fin coil Micro channel coil Conventional heat
exchanger
Micro channel
heat exchanger
temperature is reached in the daytime, Mode 8 hours
50 10 hours
The diameter of the The diameter of the

and normal operation will resume 10 48 44 refrigerant channel


Load (%)

RZF50-71C refrigerant channel


(holes where Flat, multi-hole (holes where refrigerant
0 refrigerant flows) is aluminium
hours after that 49 flows) is approx.1mm.
RZF100C 45 48 approx. 7mm heat exchanger
Sound (dB(A))

Rated
tubes
Operation

Quiet mode
Reducing noise will reduce capacity slightly. RZF125C 52 45 44 Quiet mode

Approx.
Note : 1Anechoic chamber conversion value, measured according to JIS parameters RZF140C 54 45 8:00 12:00 16:00 20:00 0:00 4:00 8:00 Approx.
1mm
7mm
and criteria. Note : Daikin date for RZF71C Utilizing flat, multi-hole heat exchanger tubes increases
Operating sound about 4 dB quieter
During operation these values are somewhat higher owing to ambient conditions. the heat exchange area and realizes energy savings.
2
Value when cooling. Value will differ when heating. Flow of refrigerant Flow of refrigerant

Fan
Demand Control Function 4

V-cut Propeller Fan (RZF50-100C)


* Field setting
By setting limits that restrict power * Required for KRP58M51 (Option) Through use of a V-cut propeller fan that imitates the
consumption, you can cut electricity bills Limitation efficiency of the swan, a migratory bird, airflow becomes
consumption

(RZF100-140CVM, 71-140CYM) smooth and loss is reduced.


Power

Maximum power use is maintained within a set level of system V-cut propeller fan Imitating the performance
capacity. This enables effective demand control while Φ440 for RZF50-71CVM of the swan
Φ550 for RZF100CVM,
maintaining comfort. Maximum power consumption can be set
RZF71-100CYM
at 40, 60, 70, 80, or 100%. 8:00 12:00 16:00 20:00 Time
37 38
REMOTE CONTROLLER Optional accessory

Easy-to-read LCD remote controller allows various system control configurations and can control multiple indoor units.
Remote controller options are shown on the page introducing each indoor unit model.

Navigation Remote Controller Wireless LCD remote controller


(Wired LCD Remote Controller) The wireless remote controller is supplied in a set with a signal receiver.
NEW
Signal receiver unit of installed type is contained inside decoration panel
or indoor unit.
NEW This simple, modern designed remote controller with fresh white Shape of signal receiver unit differs according to the indoor unit.
colour matches your interior design. Operation is much easier and Note: The signal receiver unit shown in the photograph is for mounting inside the decoration
panel of the ceiling mounted cassette type.
smoother, just follow the indications on the navigation remote
controller. NEW Backlight LCD of new wireless remote controller

BRC7M635F
Signal receiver unit
(For ceiling mounted cassette type)

Pressing the backlight button helps


BRC1E63 operating in dark rooms.

Energy saving
Wireless remote controller for each indoor unit type
Setpoint auto reset Setpoint range set Cooling only
- Even if the set temperature is changed, the new set temperature returns to the - Saves energy by limiting the BRC7M635F (Fresh white)
previous preset value after a preset duration of time. min. and max. set temperature. NEW CEILING MOUNTED CASSETTE TYPE
BRC7M635K (Black)
- Period selectable from 30, 60, 90, or 120 min. - Avoids excessive heating or DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE BRC4C66
Restaurant example cooling. NEW CEILING SUSPENDED TYPE BRC7M56
Restaurant opened Full tables at lunchtime After 30 minutes* - This function is convenient if WALL MOUNTED TYPE BRC7EB519
Temperature is set to 27ºC Then is lowered to 24ºC for Automatically returns to preset the remote controller is installed FLOOR STANDING TYPE BRC4C66
crowded room temperature (27ºC) where anyone can change the
Returns to
settings.
27°C 24°C 27 °C
automatically

Wired remote controller has built-in temperature-sensor


*Preset-return time can be set

OFF timer (programmed)


at 30, 60, 90, or 120 min
Enables temperature sensing closer to target area for improved comfort. (When using a remote control from another room,
- Sets and saves setting for an increment of time that automatically turns OFF air temperature-sensor of the indoor unit air inlet must be selected.)
conditioner after a preset period of time for each time operation starts.
- Period can be preset from 30 to 180 minutes in 10-minute increments. Facilitates maintenance and repair
All initial settings can be set from the remote controller. After interior construction is complete, ceiling mounted cassette type can
be remotely set without having to use a stepladder to access for manual setting.
Convenience Setting contents: High ceiling use, air direction, filter type, address for centralised control (group control address is set
automatically).
NEW 5-step airflow control Setback (default: OFF)
- The number of airflow steps depends on the type of - Maintains the room temperature in a specific range Remote controller is equipped with model name and failure display functions. This facilitates service in the unlikely event of a
indoor unit. during unoccupied periods by temporarily starting an malfunction.
5-step control applies to FCF and FHA series. air conditioner that had been turned OFF. (Model name display function applies to BRC1E63 only.)

Energy consumption monitoring *1,2,3,4 Weekly schedule


- 5 actions per day can be scheduled SkyAir shares common control with Heat Reclaim Ventilator and the other Daikin air-conditioning
- Past power consumption for the current and
previous days (2-hour intervals), week (1-day intervals), for each day of the week. units, thus simplifying interlocking operations.
and year (1-month intervals) can be checked. - The holiday function will disable Easily adaptable to large-scale, high-function, centralised remote control systems.
Note:
schedule timer for the days that have Installing and connecting control wiring between SkyAir and other Daikin air-conditioning equipment is easy.
*1
Availability of this function may vary according to model (limited to partial been set as holiday.
functionality)
*2
Time setting is necessary.  - 3 independent schedules can be set.
*3
This function cannot be used during group control.  (e.g. summer, winter, mid-season) LCD panel shows operating status in letters, numbers, and motion.
*4
This is a reference value for comparison and is not intended as a value for
investigation purposes in the calculation of electricity bills or contract for
electricity. Because it is a simple calculation of power consumption, there
NEW Auto display off Airflow / swing display Displays auto-swing operating status and setting position of air discharge angle.
are cases when the calculated value differs with the measurement results - While operation is stopping, LCD display can be turned OFF.
of a wattmeter. Preset temperature / operation mode display Displays preset room temperature and operating status (fan, dry, cool).
It will be displayed again if any button is pressed.
Operation start and stop time can be set for individual timers up to 72 hours. The LCD also shows
- Period can be preset from 10, 30, 60 minutes, and OFF. Programming time display
when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning.
Initial setting is 30 minutes. Self-diagnosis function Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs.

39 40
REMOTE CONTROLLER Optional accessory

Whatever your space, give it the comfort


System variation to control multiple indoor units
Control pattern Wired remote controller
LCD REMOTE CONTROLLER
Wireless remote controller it deserves
Control by 1 (Basic system)
remote controller
Non-polar, double-core Signal receiver unit installed
(max. wiring length 500 m) on indoor unit

Control by 1 wireless remote


For control from 2 controller and 1 wired remote
Control by 2 locations such as in controller (See note 2)
remote controllers room and control room, Signal receiver unit installed
Connects 2 wired remote
exits, etc. on indoor unit
controllers (See note 1)

For simultaneous
Group control control of up to 16
indoor units. Automatic address setting function Automatic address setting function
Signal receiver unit installed
on 1 indoor unit

Operation and monitoring


Control by is carried out using the (Command from outside) (Command from outside)
contact signal from the
external command operation control box in
the monitoring room. Optional wiring adaptor for Optional wiring adaptor for
electrical appendices is necessary electrical appendices is necessary

Central remote controller (option) Central remote controller (option)

Centralised control of
Centralised remote up to 64 indoor groups
control from remote location
up to 1 km away.

Interface adapter for SkyAir series (option) is Interface adapter for SkyAir series (option) is
required required

Heat Reclaim Heat Reclaim


Ventilator Ventilator
Link by remote
controller group control.
Can be operated simultaneously Can be operated simultaneously
or independently by remote controller by remote controller
(set by ventilation mode)
Central remote controller (option) Central remote controller (option)
Interlock control
with Heat Reclaim
Ventilator
Zone link control by Heat Reclaim Heat Reclaim
Ventilator Ventilator
centralised control.
Heat Reclaim Ventilator for indoor units within
a zone is operated by interlocking. Heat Reclaim Ventilator for indoor units within a
Can also be operated independently by zone is operated by interlocking.
remote controller.

Note: 1BRC1E62 can connect to BRC1E62 only. BRC1E63 can connect BRC1E63 only. 2
When a wireless remote controller is used, it is not possible to use 2 wireless remote controllers.
Combination of BRC1E63 (main) and BRC7M (sub) is available.

Easily adaptable to large-scale, high-function, centralised remote control system.


Central remote controller Unified on/off controller Schedule timer
DCS601C51 (Option)
DCS302CA61 (Option) DCS301BA61 (Option) DST301BA61 (Option)

Centralised control, with setting as Centralised control of on/off by Unified control of weekly schedule With its high functionality, the full
simple as it is with a standard group or all at once for up to 256 for up to 1,024 indoor units. colour “all-in-one” graphic controller
remote controller, of up to 64 groups indoor units. Schedule timer sets on/off time in 1 minute units facilitates management of SkyAir
(1,024 indoor units) is possible. to be executed twice a day for a week at a time. System in a variety of ways.

41 42
FUNCTIONS
CEILING MOUNTED CASSETTE TYPE Round Flow DUCT CONNECTION MIDDLE CEILING SUSPENDED TYPE WALL MOUNTED TYPE FLOOR STANDING TYPE
STATIC PRESSURE TYPE

Indoor unit FCF50-140CVM FBA50-140BVMA FHA50-140BVMA FAA71/100BVMA FVA50-140AMVM


Cooling only Outdoor unit RZF50-140CVM RZF50-140CVM RZF50-140CVM RZF71/100CVM RZF50-140CVM
RZF71-140CYM RZF71-140CYM RZF71-140CYM RZF71/100CYM RZF71-140CYM
Remote Wired BRC1E63 ------- BRC1E63 ------- BRC1E63 ------- BRC1E63 ------- BRC1E63 -------
controller Wireless ------- BRC7M635F (K) ------- BRC4C66 ------- BRC7M56 ------- BRC7EB519 ------- BRC4C66
1 Energy consumption monitoring *1 1
2 Sensing sensor stop mode *1 Sensing panel 2
3 Sensing sensor low mode *1, 2 Sensing panel 3
4 Auto display OFF *1 4
Energy
5 Setpoint auto reset *1 5
Saving
6 Setpoint range set *1 6
7 OFF timer (programmed) *1 7
8 Weekly schedule timer *1 8
9 ON/OFF timer 9

10 Circulation airflow *1 10
11 Setback *1 11
12 Quick start *1 12
13 Individual airflow control *1 13
14 Infrared presence sensor Sensing panel 14
15 Infrared floor sensor Sensing panel 15
16 Humidity sensor 16
17 Auto airflow function *1 Sensing panel 17
Comfort
18 Auto swing 18
19 Swing pattern selection 19
20 Switchable fan speed 5 step 5 step 20 3 step 3 step 5 step 5 step 3 step 3 step 3 step 3 step

21 Auto airflow rate 21


22 High fan speed mode 22 *8

23 Two selectable temperature-sensors *1 23


24 High ceiling application 3.5m / 4.2m 24 3.5m / 4.3m

25 Night quiet operation *3 25

26 Anti-bacterial air filter 26 *6

27 Mould-proof air filter 27


Cleanliness
28 Silver ion anti-bacterial drain pan 28
29 Mould-proof drain pan 29

30 Auto grille panel 30


31 Drain pump mechanism 31 *6 *6

32 Pre-charged for up to 30 m *3 32
33 Long-life filter 33 *6
Work &
34 Filter sign 34
Servicing
35 Low gas pressure detection *3 35
36 Emergency operation 36
37 Self-diagnosis function 37
38 Service contact display *1 38

39 Auto-restart 39
40 Control by 2 remote controllers *7 40 *7

41 Group control by 1 remote controller 41


42 External equipment interlock *4 Sensing panel 42
Control 43 External signal forced OFF and ON/OFF operation 43
44 External command control *5 44
45 Central remote control 45
46 Interlock control with Heat Reclaim Ventilator 46
47 DIII-NET communication standard 47

48 High-efficiency filter 48
49 Ultra long-life filter 49
Options
50 Fresh air intake kit 50
51 Overvoltage PCB *3 51
Note: *1: Applicable when BRC1E63 is used *2: Not applicable when group control *3: For outdoor units *6: Option is requied *7: It is not possible to use 2 wireless remote controllers. Combination of BRC1E63 (main) and BRC7M (sub) is available.
*4: Adaptor for Wiring (and installation box) is necessary *5: Wiring adaptor for electrical appendices (and installation box) is necessary *8: Applicable for FVA50-100
43 44
FUNCTIONS
Cleanliness
Abundance of functions that provide comfortable 26. Anti-bacterial air filter 28. Silver ion anti-bacterial drain pan
air-conditioning in stores and offices The air filter has an anti-bacterial treatment to help prevent the
growth of bacteria and mould on it.
A built-in antibacterial treatment that uses silver ion in the drain pan
prevents the growth of slime, bacteria, and mould that cause odours
Note: Some features are only available on selected models. See overview pages for full list of features applicable to each unit. and clogging.
27. Mould-proof air filter
29. Mould-proof drain pan
Energy Saving Sanitary filter has mould-resistant treatment.
Mould-proof drain pan prevents growth of mould in highly humid
conditions.
1. Energy consumption monitoring 6. Setpoint range set
Past power consumption is displayed for the current and previous Saves energy by limiting the minimum and maximum set temperatures.
days as well as in weekly and yearly intervals. Avoids excessive heating and cooling.
Work & Servicing
2. Sensing sensor stop mode 7. OFF timer (programmed)
When the room is unoccupied, the system stops automatically. Sets and saves setting for an increment of time that automatically 30. Auto grille panel 35. Low gas pressure detection
turns off air conditioner after a preset period of time for each time Grille and air filter cleaning can be performed without need for Insufficient gas charging is normally hard to detect. During test run
3. Sensing sensor low mode operation starts. a stepladder by lowering the grille. after installation and regular inspection, the refrigerant level is
When the room is unoccupied, the set temperature is shifted monitored by a microprocessor to maintain proper gas pressure.
automatically. 8. Weekly schedule timer 31. Drain pump mechanism Reliability is assured and maintenance and inspection can be carried
Up to five operation ON/OFF settings can be programmed per day for Steeper gradient realises more efficient out more quickly.
each day of the week. Not only can the time be set for the operation condensate drainage. High-lift is especially
4. Auto display OFF useful for long lengths of drain piping.
While operation is stopping, the LCD display can be turned off. 
ON setting, but also the temperature. 36. Emergency operation
It can be displayed again when any button is pressed.
9. ON/OFF timer 32. Pre-charged for up to 30 m Even if there is a malfunction elsewhere in the system, the fan or
compressor can still be operated. (depending on the malfunction)
If refrigerant piping length does not exceed 30 m, there is no
Operation starts when the preset time of the ON timer elapses and
5. Setpoint auto reset need for on-site gas charging.
Even if the set temperature is changed, the new set temperature
stops when the preset time of the OFF timer elapses.
37. Self-diagnosis function
returns to the previous preset value after a preset duration of time.
33. Long-life filter The operating parameters of indoor and outdoor units, and sensor
Maintenance is not required for one year*. data at critical locations throughout the system, are constantly
The filter is washable and can be reused. monitored using a microcomputer. To facilitate quick response in the
*For dust concentration of 0.15 mg/m3 event of a malfunction, a message appears on the LCD of the remote
controller and an LED on the unit illuminates.
Comfort 34. Filter sign
The filter sign warns you when it is time to clean the filter.
38. Service contact display
10. Circulation airflow 19. Swing pattern selection *When using a wired remote controller the sign is displayed in the LCD.
When using a wireless remote controller the filter sign lamp illuminates When installing the unit, registration of the service contact is available
At the start of operation, airflow changes repeatedly between You can freely set air discharge settings by remote controller. on the signal receiver unit. to the wired remote controller.
horizontal flow and downward flow (swing during cool operation), (1) Standard (2) Draft prevention (3) Ceiling soiling
and air is sent throughout the room to eliminate uneven setting setting prevention setting
temperatures.
Control
11. Setback
Maintains the room temperature in a specific range during 39. Auto-restart 43. External signal forced OFF and ON/OFF operation
unoccupied periods by temporarily starting an air conditioner that
had been turned OFF. 20. Switchable fan speed If there is a power outage while the equipment is operating,
operations will restart in the same mode as before the power
The air conditioner can be interlocked with the keycard system and
turned ON/OFF by locking and unlocking the room.
High setting provides maximum reach while low setting minimises drafts.
cut when electricity is restored. The air conditioner can be also be turned OFF by the interlock with
12. Quick start the ventilation and lighting OFF signal.
At operation start, capacity priority operation is possible. 21. Auto airflow rate 40. Control by 2 remote controllers *Field setting with remote controller.
Airflow rate is automatically controlled in accordance with the Using 2 remote controllers you can operate the equipment
13. Individual airflow control difference between room temperature and set temperature. locally or from a remote location. 44. External command control
Airflow direction can be individually adjusted for each air *When a wireless remote controller is used, it is not possible to use 2 Operation and monitoring is carried out using the contact signal from
wireless remote controllers.
discharge outlet to deliver optimal air distribution. 22. High fan speed mode Combination of BRC1E63 (main) and BRC7M (sub) is available.
the operation control box in the building monitoring room.
*Wiring adaptor for electrical appendices (and installation box) is necessary.
You can increase fan speed approximately 10% higher than the
14. Infrared presence sensor "high" setting. 41. Group control by 1 remote controller
The sensor detects the presence of people in each of the 4 areas. You can turn up to 16 indoor units ON/OFF with a single 45. Central remote control
remote controller. (When using connected indoor units, the Optional central remote controller enables centralised control of up to
23. Two selectable temperature-sensors settings must all be the same and on/off will be simultaneous.) 1024 indoor units (64 groups) from up to 1 km away.
15. Infrared floor sensor Temperature-sensors are included in
The sensor detects the floor temperature and automatically the indoor unit and optional wired 42. External equipment interlock 46. Interlock control with Heat Reclaim Ventilator
adjusts operation of the indoor unit to reduce the temperature remote controller. Temperature sensing Human presence is detected by the built-in infrared presence
closer to target area is possible to Enables interlocking control with external equipment such as Heat
difference between the ceiling and the floor. sensor in the sensing panel, and the presence detection
further increase the comfort level. Reclaim Ventilator.
signal can be output and interlocked with external equipment.
16. Humidity sensor Use the temperature-sensor in the indoor unit when Power conservation is possible though the interlock of
Not only temperature but also humidity is detected, and
controlling air conditioning from another room. external equipment, such as lighting, with the infrared 47. DIII-NET communication standard
Note: Wireless remote controllers have no temperature-sensor. presence sensor. Connection to a centralised control system is available
adjustments are made for comfortable air conditioning.
*Adaptor for Wiring (and installation box) is necessary. without need for an optional adaptor.

17. Auto airflow function 24. High ceiling application


Delivers air-conditioning comfort
When this function is set, airflow direction can be directed toward
or away from people when human presence is detected.
all the way down to the floor in
air-conditioning zones with high Options
ceilings.
18. Auto swing Note:When units are installed on high ceilings, depending on the model, 48. High-efficiency filter 50. Fresh air intake kit
Delivers comfortable air-conditioning to all areas, near to and far various restrictions concerning maximum height, air discharge direction,
Two types are available: 65% and 90% colorimetry. You can provide air-conditioning with fresh air from outside.
from the air-conditioner. and choice of options may apply.
Convenient for places where a ventilation fan cannot be installed.
The air flow direction can be fixed at your desired angle by the
25. Night quiet operation 49. Ultra long-life filter
remote controller.
Requires no maintenance for about 4 years* (10,000h) in
51. Overvoltage PCB
The Automatic night quiet mode will initiate 8 hours after the peak Optional circuit eliminates the need for a stabiliser and offer additional
temperature is reached in the daytime, and normal operation will stores and offices.
protection for devices in the outdoor unit, such as its fan motor and
resume 10 hours after that. *For dust concentration of 0.15 mg/m 3
compressor.

45 46
SPECIFICATIONS

CEILING MOUNTED CASSETTE TYPE < Round Flow > ( 1 Phase ) DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE ( 1 Phase )
50 60 71 100 125 140 50 60 71 100 125 140
Indoor unit FCF50CVM FCF60CVM FCF71CVM FCF100CVM FCF125CVM FCF140CVM Indoor unit FBA50BVMA FBA60BVMA FBA71BVMA FBA100BVMA FBA125BVMA FBA140BVMA
Model Model
Name Outdoor unit Name Outdoor unit
RZF50CVM RZF60CVM RZF71CVM RZF100CVM RZF125CVM RZF140CVM RZF50CVM RZF60CVM RZF71CVM RZF100CVM RZF125CVM RZF140CVM
Power supply Outdoor unit 1 Phase / 220-230V / 60Hz Power supply Indoor unit 1 Phase / 220-230V / 60Hz
Cooling Capacity 1,2 5.0 6.0 7.1 10.0 12.5 14.0 Outdoor unit 1 Phase / 220-230V / 60Hz
Rated (Min. - Max.) kW (3.2-5.6) (3.2-6.0) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
Cooling Capacity 1,2 5.0 6.0 7.1 10.0 12.5 14.0
Rated (Min. - Max.) kW (3.2-5.6) (3.2-6.0) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
17,100 20,500 24,200 34,100 42,700 47,800
Btu/h (10,900-19,100) (10,900-20,500) (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900) 17,100 20,500 24,200 34,100 42,700 47,800
Btu/h (10,900-19,100) (10,900-20,500) (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
Power consumption Cooling kW 1.14 1.53 1.93 2.97 4.18 5.47
COP W/W 4.39 3.92 3.68 3.37 2.99 2.56 Power consumption Cooling kW 1.35 1.64 2.15 3.01 4.44 5.69
CSPF Wh/Wh 6.60 6.31 6.17 5.50 5.15 5.00 COP W/W 3.70 3.66 3.30 3.32 2.82 2.46
Indoor unit Colour Unit ---------- CSPF Wh/Wh 5.51 5.30 5.19 4.88 4.70 4.47
Decoration panel Fresh white Indoor unit Colour ----------
Airflow rate 3
m /min 23.0 / 21.0 / 18.5 / 16.0 / 13.5 34.5 / 31.0 / 27.5 / 24.0 / 20.0 36.5 / 33.0 / 29.0 / 25.0 / 21.0 Fan Airflow rate (H/M/L) m3/min 18.0 / 15.0 / 12.5 23.0 / 19.5 / 16.0 32.0 / 27.0 / 22.5 36.0 / 30.5 / 25.0
(H / HM / M / ML / L) cfm 812 / 741 / 653 / 565 / 477 1,218 / 1,094 / 971 / 847 / 706 1,288 / 1,165 / 1,024 / 883 / 741 cfm 635 / 530 / 441 812 / 688 / 565 1,130 / 953 / 794 1,271 / 1,077 / 883
Sound pressure level 3 (H / HM / M / ML / L) dB(A) 37.0 / 34.5 / 32.0 / 29.5 / 27.5 45.0 / 41.5 / 38.0 / 35.0 / 32.5 46.0 / 43.0 / 40.0 / 36.0 / 32.5 External static pressure 3 Pa Rated 50 (50-150)
Dimensions Unit mm 256X840X840 298X840X840 Sound pressure level 4 (H/M/L) dB(A) 35.0 / 33.0 / 31.0 38.0 / 35.0 / 33.0 40.0 / 37.5 / 35.0
(HXWXD) Decoration panel mm 50X950X950 Air filter 5 ----------
Machine Unit kg 22 24 Dimensions (HXWXD) mm 245X1000X800 245X1400X800
weight Decoration panel kg 5.5 Machine weight kg 37 47
Certified Operation range °CWB 14 to 25 Certified Operation range °CWB 14 to 25
Outdoor Colour Ivory white Outdoor Colour Ivory white
unit Coil Type Micro channel unit Coil Type Micro channel
Compressor Type Hermetically sealed swing type Compressor Type Hermetically sealed swing type
Motor output kW 1.30 1.60 2.40 Motor output kW 1.30 16.0 2.40
Refrigerant charge (R32) kg 1.2(Charged for 30 m) 1.3(Charged for 30 m) 1.9(Charged for 30 m) Refrigerant charge (R32) kg 1.2(Charged for 30 m) 1.3(Charged for 30 m) 1.9(Charged for 30 m)
Sound Cooling dB(A) 48 49 52 54 Sound Cooling dB(A) 48 49 52 54
pressure level 3 Night quiet mode pressure level 4
dB(A) 44 45 Night quiet mode dB(A) 44 45
Dimensions (HXWXD) mm 595X845X300 695X930X350 990X940X320 Dimensions (HXWXD) mm 595X845X300 695X930X350 990X940X320
Machine weight kg 41 48 64 Machine weight kg 41 48 64
Certified Operation range °CDB 21 to 46 Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm 9.5 Piping Liquid (Flare) mm 9.5
connections Gas (Flare) mm 15.9 connections Gas (Flare) mm 15.9
Drain Indoor unit mm VP25 (I.D. 25XO.D. 32) Drain Indoor unit mm VP25 (I.D. 25XO.D. 32)
Outdoor unit mm 26.0 (Hole) 18.0 (Hole) 26.0 (Hole) Outdoor unit mm 26.0 (Hole) 18.0 (Hole) 26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70) Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30 Max. installation level difference m 30
Heat insulation Both liquid and gas piping Heat insulation Both liquid and gas piping

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE ( 3 Phase )


CEILING MOUNTED CASSETTE TYPE < Round Flow > ( 3 Phase ) 71 100 125 140
71 100 125 140 Indoor unit FBA71BVMA FBA100BVMA FBA125BVMA FBA140BVMA
Model
Indoor unit FCF71CVM FCF100CVM FCF125CVM FCF140CVM Name
Model Outdoor unit RZF71CYM RZF100CYM RZF125CYM RZF140CYM
Name Outdoor unit RZF71CYM RZF100CYM RZF125CYM RZF140CYM Power supply Indoor unit 1 Phase / 220-230V / 60Hz
Power supply Outdoor unit 3 Phase / 380V / 60Hz Outdoor unit 3 Phase / 380V / 60Hz
Cooling Capacity 1,2 7.1 10.0 12.5 14.0 Cooling Capacity 1,2 7.1 10.0 12.5 14.0
Rated (Min. - Max.) kW (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5) Rated (Min. - Max.) kW (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
24,200 34,100 42,700 47,800 24,200 34,100 42,700 47,800
Btu/h (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900) Btu/h (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
Power consumption Cooling kW 1.93 2.97 4.18 5.47 Power consumption Cooling kW 2.15 3.01 4.44 5.69
COP W/W 3.68 3.37 2.99 2.56 COP W/W 3.30 3.32 2.82 2.46
CSPF Wh/Wh 6.17 5.50 5.15 5.00 CSPF Wh/Wh 5.19 4.88 4.70 4.47
Indoor unit Colour Unit ---------- Indoor unit Colour ----------
Decoration panel Fresh white Fan Airflow rate (H/M/L) m3/min 23.0 / 19.5 / 16.0 32.0 / 27.0 / 22.5 36.0 / 30.5 / 25.0
Airflow rate m3/min 23.0 / 21.0 / 18.5 / 16.0 / 13.5 34.5 / 31.0 / 27.5 / 24.0 / 20.0 36.5 / 33.0 / 29.0 / 25.0 / 21.0 cfm 812 / 688 / 565 1,130 / 953 / 794 1,271 / 1,077 / 883
(H / HM / M / ML / L) cfm 812 / 741 / 653 / 565 / 477 1,218 / 1,094 / 971 / 847 / 706 1,288 / 1,165 / 1,024 / 883 / 741 External static pressure 3 Pa Rated 50 (50-150)
Sound pressure level 3 (H / HM / M / ML / L) dB(A) 37.0 / 34.5 / 32.0 / 29.5 / 27.5 45.0 / 41.5 / 38.0 / 35.0 / 32.5 46.0 / 43.0 / 40.0 / 36.0 / 32.5 Sound pressure level 4 (H/M/L) dB(A) 38.0 / 35.0 / 33.0 40.0 / 37.5 / 35.0
Dimensions Unit mm 256X840X840 298X840X840 Air filter 5 ----------
(HXWXD) Decoration panel mm 50X950X950 Dimensions (HXWXD) mm 245X1000X800 245X1400X800
Machine Unit kg 22 24 Machine weight kg 37 47
weight Decoration panel kg 5.5 14 to 25
Certified Operation range °CWB
Certified Operation range °CWB 14 to 25 Outdoor Colour Ivory white
Outdoor Colour Ivory white unit Coil Type Micro channel
unit Coil Type Micro channel Compressor Type Hermetically sealed swing type
Compressor Type Hermetically sealed swing type Motor output kW 1.60 2.40
Motor output kW 1.60 2.40 Refrigerant charge (R32) kg 1.3(Charged for 30 m) 1.9(Charged for 30 m)
Refrigerant charge (R32) kg 1.3(Charged for 30 m) 1.9(Charged for 30 m) Sound Cooling dB(A) 48 49 52 54
pressure level 4
Sound Cooling dB(A) 48 49 52 54 Night quiet mode dB(A) 44 45
pressure level 3
Night quiet mode dB(A) 44 45 Dimensions (HXWXD) mm 695X930X350 990X940X320
Dimensions (HXWXD) mm 695X930X350 990X940X320 Machine weight kg 48 64
Machine weight kg 48 64 Certified Operation range °CDB 21 to 46
Certified Operation range °CDB 21 to 46 Piping Liquid (Flare) mm 9.5
Piping Liquid (Flare) mm 9.5 connections Gas (Flare) mm 15.9
connections Gas (Flare) mm 15.9 Drain Indoor unit mm VP25 (I.D. 25XO.D. 32)
Drain Indoor unit mm VP25 (I.D. 25XO.D. 32) Outdoor unit mm 18.0 (Hole) 26.0 (Hole)
Outdoor unit mm 18.0 (Hole) 26.0 (Hole) Max. interunit piping length m 50 (Equivalent length 70)
Max. interunit piping length m 50 (Equivalent length 70) Max. installation level difference m 30
Max. installation level difference m 30 Heat insulation Both liquid and gas piping
Heat insulation Both liquid and gas piping Note :
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
External static pressure is changeable in 11 stages by remote controller.
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
4
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.
5
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% or more.

47 48
SPECIFICATIONS
100

CEILING SUSPENDED TYPE ( 1 Phase ) WALL MOUNTED TYPE ( 1 Phase, 3 Phase )


50 60 71 100 125 140 71 71 100 100
Indoor unit FHA50BVMA FHA60BVMA FHA71BVMA FHA100BVMA FHA125BVMA FHA140BVMA Indoor unit FAA71BVMA FAA71BVMA FAA100BVMA FAA100BVMA
Model Model
Name Outdoor unit Name Outdoor unit
RZF50CVM RZF60CVM RZF71CVM RZF100CVM RZF125CVM RZF140CVM RZF71CVM RZF71CYM RZF100CVM RZF100CYM
Power supply Outdoor unit 1 Phase / 220-230V / 60Hz Power supply Outdoor unit 1 Phase / 220-230V / 60Hz 3 Phase, 380V / 60Hz 1 Phase / 220-230V / 60Hz 3 Phase, 380V / 60Hz
Cooling Capacity 1,2 5.0 6.0 7.1 10.0 12.5 14.0 Cooling Capacity 1,2 7.1 10.0
Rated (Min. - Max.) kW (3.2-5.5) (3.2-6.0) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5) Rated (Min. - Max.) kW (3.2-8.0) (5.0-11.2)
17,100 20,500 24,200 34,100 42,700 47,800 24,200 34,100
Btu/h (10,900-19,100) (10,900-20,500) (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900) Btu/h (10,900-27,300) (17,100-38,200)
Power consumption Cooling kW 1.20 1.53 2.30 3.24 4.29 5.40 Power consumption Cooling kW 2.12 3.60
COP W/W 4.17 3.92 3.09 3.09 2.91 2.59 COP W/W 3.35 2.78
CSPF Wh/Wh 6.30 6.11 5.91 5.17 5.09 4.78 CSPF Wh/Wh 5.25 4.05
Indoor unit Colour White Indoor unit Colour Fresh white
Airflow rate m3/min 15.0 / 13.5 / 12.0 / 11.0 / 10.0 20.5 / 18.8 / 17.0 / 15.5 / 14.0 28.0 / 26.0 / 24.0 / 22.0 / 20.0 31.0 / 29.0 / 27.0 / 25.0 / 23.0 34.0 / 31.5 / 29.0 / 26.5 / 24.0 Airflow rate (H/M/L) m3/min 18.0 / 16.0 / 14.0 26.0 / 23.0 / 19.0
(H / HM / M / ML / L) cfm 530 / 477 / 424 / 388 / 353 724 / 664 / 600 / 547 / 494 988 / 918 / 847 / 777 / 706 1,094 / 1,024 / 953 / 883 / 812 1,200 / 1,112 / 1,024 / 935 / 847 cfm 635 / 565 / 494 918 / 812 / 671
Sound pressure level 3 (H / HM / M / ML / L) dB(A) 37.0 / 36.0 / 35.0 / 33.5 / 32.0 38.0 / 37.0 / 36.0 / 35.0 / 34.0 42.0 / 40.0 / 38.0 / 36.0 / 34.0 44.0 / 42.5 / 41.0 / 39.0 / 37.0 46.0 / 44.0 / 42.0 / 40.0 / 38.0 Sound pressure level 3 (H/M/L) dB(A) 45 / 42 / 40 49 / 45 / 41
Dimensions (HXWXD) mm 235X960X690 235X1270X690 235X1590X690 Dimensions (HXWXD) mm 290X1050X238 340X1200X240
Machine weight kg 25 32 38 Machine weight kg 13 17
Certified Operation range °CWB 14 to 25 Certified Operation range °CWB 14 to 25
Outdoor Colour Ivory white Outdoor Colour Ivory white
unit Coil Type Micro channel unit Coil Type Micro channel
Compressor Type Hermetically sealed swing type Compressor Type Hermetically sealed swing type
Motor output kW 1.30 1.60 2.40 Motor output kW 1.30 1.60
Refrigerant charge (R32) kg 1.2(Charged for 30 m) 1.3(Charged for 30 m) 1.9(Charged for 30 m) Refrigerant charge (R32) kg 1.2 (Charged for 30 m) 1.3 (Charged for 30 m)
Sound Cooling dB(A) 48 49 52 54 Sound Cooling dB(A) 48 49
pressure level 3 pressure level 3
Night quiet mode dB(A) 44 45 Night quiet mode dB(A) 44 45
Dimensions (HXWXD) mm 595X845X300 695X930X350 990X940X320 Dimensions (HXWXD) mm 595X845X300 695X930X350
Machine weight kg 41 48 64 Machine weight kg 41 48
Certified Operation range °CDB 21 to 46 Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm 9.5 Piping Liquid (Flare) mm 9.5
connections Gas (Flare) mm 15.9 connections Gas (Flare) mm 15.9
Drain Indoor unit mm VP20 (I.D. 20XO.D. 26) Drain Indoor unit mm VP13 (I.D. 13XO.D. 18)
Outdoor unit mm 26.0 (Hole) 18.0 (Hole) 26.0 (Hole) Outdoor unit mm 26.0 (Hole) 18.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70) Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30 Max. installation level difference m 30
Heat insulation Both liquid and gas piping Heat insulation Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

CEILING SUSPENDED TYPE ( 3 Phase )


71 100 125 140
Indoor unit FHA71BVMA FHA100BVMA FHA125BVMA FHA140BVMA
Model
Name Outdoor unit RZF71CYM RZF100CYM RZF125CYM RZF140CYM
Power supply Outdoor unit 3 Phase / 380V / 60Hz
Cooling Capacity 1,2 7.1 10.0 12.5 14.0
Rated (Min. - Max.) kW (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)
24,200 34,100 42,700 47,800
Btu/h (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900)
Power consumption Cooling kW 2.30 3.24 4.29 5.40
COP W/W 3.09 3.09 2.91 2.59
CSPF Wh/Wh 5.91 5.17 5.09 4.78
Indoor unit Colour White
Airflow rate m3/min 20.5 / 18.8 / 17.0 / 15.5 / 14.0 28.0 / 26.0 / 24.0 / 22.0 / 20.0 31.0 / 29.0 / 27.0 / 25.0 / 23.0 34.0 / 31.5 / 29.0 / 26.5 / 24.0
(H / HM / M / ML / L) cfm 724 / 664 / 600 / 547 / 494 988 / 918 / 847 / 777 / 706 1,094 / 1,024 / 953 / 883 / 812 1,200 / 1,112 / 1,024 / 935 / 847
Sound pressure level 3 (H / HM / M / ML / L) dB(A) 38.0 / 37.0 / 36.0 / 35.0 / 34.0 42.0 / 40.0 / 38.0 / 36.0 / 34.0 44.0 / 42.5 / 41.0 / 39.0 / 37.0 46.0 / 44.0 / 42.0 / 40.0 / 38.0
Dimensions (HXWXD) mm 235X1270X690 235X1590X690
Machine weight kg 32 38
Certified Operation range °CWB 14 to 25
Outdoor Colour Ivory white
unit Coil Type Micro channel
Compressor Type Hermetically sealed swing type
Motor output kW 1.60 2.40
Refrigerant charge (R32) kg 1.3(Charged for 30 m) 1.9(Charged for 30 m)
Sound Cooling dB(A) 48 49 52 54
pressure level 3
Night quiet mode dB(A) 44 45
Dimensions (HXWXD) mm 695X930X350 990X940X320
Machine weight kg 48 64
Certified Operation range °CDB 21 to 46
Piping Liquid (Flare) mm 9.5
connections Gas (Flare) mm 15.9
Drain Indoor unit mm VP20 (I.D. 20XO.D. 26)
Outdoor unit mm 18.0 (Hole) 26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation level difference m 30
Heat insulation Both liquid and gas piping

Note :
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Capacities are net, including a deduction for cooling for indoor fan motor heat.
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

49 50
SPECIFICATIONS OPTION
100

Indoor unit
FLOOR STANDING TYPE ( 1 Phase ) CEILING MOUNTED CASSETTE TYPE < Round Flow >
50 60 71 100 125 140
Kit name
Indoor unit FVA50AMVM FVA60AMVM FVA71AMVM FVA100AMVM FVA125AMVM FVA140AMVM Name of option Remark
Model FCF50CVM FCF60CVM FCF71CVM FCF100CVM FCF125CVM FCF140CVM
Name Outdoor unit RZF50CVM RZF60CVM RZF71CVM RZF100CVM RZF125CVM RZF140CVM Standard panel with Fresh white BYCQ125EEF
Sensing Black BYCQ125EEK
Power supply Outdoor unit 1 Phase / 220-230V / 60Hz
Decoration Fresh white BYCQ125EAF
Cooling Capacity 1,2 5.0 6.0 7.1 10.0 12.5 14.0 1 Standard panel
Rated (Min. - Max.) kW (3.2-5.6) (3.2-6.0) (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5) panel Black BYCQ125EAK
Designer panel 1 Fresh white BYCQ125EAPF
17,100 20,500 24,200 34,100 42,700 47,800
Btu/h (10,900-19,100) (10,900-20,500) (10,900-27,300) (17,100-38,200) (19,500-47,800) (21,200-52,900) Auto grille panel 2,3 Fresh white BYCQ125EASF
Power consumption Cooling kW 1.23 1.79 2.51 3.48 4.48 5.71 Sealing material of air discharge outlet 4 For usage of 3-, 4-way flow KDBH551C160
2
COP W/W 4.07 3.35 2.83 2.87 2.79 2.45 For usage of 2-way flow KDBH552C160
CSPF Wh/Wh 6.03 4.86 4.46 4.19 4.67 4.18 3 Panel spacer KDBP55H160FA

Indoor unit Colour Fresh white Fresh air intake kit Chamber Without T-duct joint KDDP55B160 (Components: KDDP55C160-1, KDDP55B160-2) 8
4 type 5,6 With T-duct joint KDDP55B160K (Components: KDDP55C160-1, KDDP55B160K2) 8
Airflow rate m3/min 18 / 16 / 14 28 / 25 / 22 28 / 26 / 24 30 / 28 / 26
(H / M / L) cfm 635 / 565 / 494 988 / 883 / 777 988 / 918 / 847 1,059 / 988 / 918 Direct installation type 7 KDDP55X160A
Sound pressure level 3 (H / M / L) dB(A) 43 / 41 / 38 50 / 47 / 44 51 / 48 / 46 53 / 51 / 48 High-efficiency filter unit 9 (Colorimetric method 65%) KAFP556C80 KAFP556C160
5 (Including filter chamber)
Dimensions (HXWXD) mm 1,850X600X270 1,850X600X350 (Colorimetric method 90%) KAFP557C80 KAFP557C160
Machine weight kg 42 50 Replacement high-efficiency filter 9,10 (Colorimetric method 65%) KAFP552B80 KAFP552B160
6
Certified Operation range °CWB 14 to 25 (Colorimetric method 90%) KAFP553B80 KAFP553B160
Ivory white 7 Filter chamber KDDFP55C160
Outdoor Colour
unit Coil Type Micro channel 8 Replacement long-life filter KAFP551K160
9 Replacement long-life filter (Auto grille panel) KAFP551H160
Compressor Type Hermetically sealed swing type
Motor output kW 1.30 1.60 2.40 10 Ultra long-life filter unit (Including filter chamber) 9 KAFP55C160
Refrigerant charge (R32) kg 1.2(Charged for 30 m) 1.3(Charged for 30 m) 1.9(Charged for 30 m) 11 Replacement ultra long-life filter 9,10 KAFP55H160H
Sound Cooling dB(A) 48 49 52 54 12 Branch duct chamber 4 KDJP55C80 KDJP55C160
pressure level 3 13 Insulation kit for high humidity 9,11 KDTP55K80 KDTP55K160
Night quiet mode dB(A) 44 45
Dimensions (HXWXD) mm 595X845X300 695X930X350 990X940X320 14 Remote controller Wireless type Cooling only BRC7M635F (Fresh white) / BRC7M635K (Black)
Machine weight kg 41 48 64 15 Navigation remote controller Wired type 12 BRC1E63
Certified Operation range °CDB 21 to 46 16 Central remote controller 13 DCS302CA61
Piping Liquid (Flare) mm 9.5 17 Unified ON/OFF controller 13 DCS301BA61
connections Gas (Flare) mm 15.9 18 Schedule timer 13 DST301BA61
Drain Indoor unit mm VP20 (I.D. 20XO.D. 26) 19 intelligent Touch Controller 13 DCS601C51
Outdoor unit mm 26.0 (Hole) 18.0 (Hole) 26.0 (Hole) 20 Adaptor for wiring 14 KRP1C11A
Max. interunit piping length m 50 (Equivalent length 70) 21 Wiring adaptor for electrical appendices 14 KRP4AA53
Max. installation level difference m 30 22 Installation box for adaptor PCB KRP1H98A
Heat insulation Both liquid and gas piping 23 Remote sensor (for indoor temperature) KRCS01-5B
Note: 1When installing designer panel, body height (ceiling required dimension) is 42 mm higher than 7
The volume of fresh air for direct installation type is approximately 1% of the indoor unit airflow.
standard panel. Designer panel cannot operate 2 and 3 way flow. The chamber type is recommended when more fresh air is necessary.
2
A dedicated remote controller (BRC16A2) for the auto grille panel is included for lowering and 8
Please order using the names of both components instead of set name.
raising the suction grille. 9
This option cannot be installed to designer panel and auto grille panel.
3
When installing auto grille panel, body height (ceiling required dimension) is 55 mm higher than 10
Filter chamber is required.
standard panel. 11
Please use in case temperature/humidity inside ceiling may get over 30˚C, 80% RH.
4
Circulation airflow is not available with this option. 12
Wiring for wired remote controller should be obtained locally.
5
When installing a fresh air intake kit (chamber type), two air outlet corners are closed. 13
The indoor unit is equipped standardly with the interface adapter for SkyAir series. An option is unnecessary.
FLOOR STANDING TYPE ( 3 Phase ) It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of Installation box for adaptor PCB(KRP1H98A) is necessary.
6 14

the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the
operating sound and may also influence temperature sensing.
71 100 125 140
Indoor unit FVA71AMVM FVA100AMVM FVA125AMVM FVA140AMVM
Model
Name
Round flow type: List of optional parts required to achieve different flow patterns
Outdoor unit RZF71CYM RZF100CYM RZF125CYM RZF140CYM For each flow pattern – all round, 4-way, 3-way, 2-way, branch duct connection – the compatibility of each independently installed option
Power supply Outdoor unit 3 Phase / 380V / 60Hz (shown in the column on the left) to accessory options (listed across the top of each table) is shown in the cells where the relevant row and column intersect.
Cooling Capacity 1,2 7.1 10.0 12.5 14.0 A circle (o) indicates compatibility, and a cross (x) indicates incompatibility. Any options not shown below are not suitable for independent or accessory installation.
Rated (Min. - Max.) kW (3.2-8.0) (5.0-11.2) (5.7-14.0) (6.2-15.5)

Btu/h
24,200
(10,900-27,300)
34,100
(17,100-38,200)
42,700
(19,500-47,800)
47,800
(21,200-52,900) All round flow 4-way flow
Power consumption Cooling kW 2.51 3.48 4.48 5.71 Optional accessory parts Fresh air intake kit Fresh air intake kit Insulation kit High-efficiency Ultra long-life
Designer panel Auto grille panel Panel spacer1
Independently installable optional parts (Chamber type) 1 , 2 (Direct installation type) for high humidity filter unit2 filter unit2
COP W/W 2.83 2.87 2.79 2.45
CSPF Wh/Wh 4.46 4.19 4.67 4.18 Panel/grille related Designer panel x o o o x x x
Indoor unit Colour Fresh white
Auto grille panel x o o o x x x
Airflow rate m3/min 18 / 16 / 14 28 / 25 / 22 28 / 26 / 24 30 / 28 / 26
Panel spacer 1
o o o o x o o
(H / M / L) cfm 635 / 565 / 494 988 / 883 / 777 988 / 918 / 847 1,059 / 988 / 918
Auxillary function related Fresh air intake kit (Chamber type)1,2 o o o x x o o
Sound pressure level 3 (H / M / L) dB(A) 43 / 41 / 38 50 / 47 / 44 51 / 48 / 46 53 / 51 / 48
Fresh air intake kit (Direct installation type) o o o x o o o
Dimensions (HXWXD) mm 1,850X600X270 1,850X600X350
Insulation kit for high humidity x x x x o x x
Machine weight kg 42 50
Filter related High-efficiency filter unit2 x x o o o x x
Certified Operation range °CWB 14 to 25
Ultra long-life filter unit2 x x o o o x x
Outdoor
unit
Colour
Coil Type
Ivory white
Micro channel
3-way flow 2-way flow 5

Compressor Type Hermetically sealed swing type Optional accessory parts Fresh air intake kit Fresh air intake kit Insulation kit High-efficiency Ultra long-life
Designer panel Auto grille panel Panel spacer1,3
Independently installable optional parts (Chamber type)1,2 (Direct installation type) for high humidity filter unit2 filter unit2
Motor output kW 1.60 2.40
Refrigerant charge (R32) kg 1.3(Charged for 30 m) 1.9(Charged for 30 m) Panel/grille related Auto grille panel x o o x x x
Sound Cooling dB(A) 48 49 52 54
Panel spacer1,3 x x x
pressure level 3
Night quiet mode dB(A) 44 45 Auxillary function related Fresh air intake kit (Chamber type)1,2 x o x x x o
Dimensions (HXWXD) mm 695X930X350 990X940X320
Fresh air intake kit (Direct installation type) x o x o x o
Machine weight kg 48 64
Insulation kit for high humidity x x x x o x x
Certified Operation range °CDB 21 to 46 Filter related Ultra long-life filter unit2 x x o o x x
Piping Liquid (Flare) mm 9.5
connections Gas (Flare) mm 15.9 Branch duct connection
Drain Indoor unit mm VP20 (I.D. 20XO.D. 26) Optional accessory parts Fresh air intake kit Fresh air intake kit Insulation kit High-efficiency Ultra long-life
Designer panel Auto grille panel Panel spacer1
mm 18.0 (Hole) 26.0 (Hole) Independently installable optional parts (Chamber type)1,2 (Direct installation type) for high humidity filter unit2 filter unit2
Outdoor unit
Max. interunit piping length m 50 (Equivalent length 70) Branch duct chamber 1 1-way branch / unit 3-way flow o o o o o 4
x x o
Max. installation level difference m 30
(Round duct type) 2-way branch / unit 2-way flow x o x o o 4
x x o
Heat insulation Both liquid and gas piping 1-way branch / unit 2-way flow x o x o o 4
x x o
Note : 1. In some cases, depending on how the unit is embedded in the ceiling, use of branch ducts and fresh air intake kits may not be possible. Before starting installation work make sure to check whether or not
1
Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal). joint installation is possible. In particular, ensure that the lower fixing position caused by the addition of panel spacers is acceptable.
2
Capacities are net, including a deduction for cooling for indoor fan motor heat. When branch ducts are used, circulation airflow is not available.
3
The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection. 2. When two different types of optional chambers are used together, a fresh air intake kit must be installed in the upper position.
3. It is not possible to use panel spacers in a 2-way flow installation. (△)
4. It is not possible to install a branch duct on the same side to which a fresh air intake kit (direct mount) is installed.
5. When 3-way or 2-way flow is selected, circulation airflow is not available.

51 52
OPTIONS

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE WALL MOUNTED TYPE


Kit name Kit name
No. Name of option Remark No. Name of option Remark
FBA50BVMA FBA60BVMA FBA71BVMA FBA100BVMA FBA125BVMA FBA140BVMA FAA71BVMA FAA100BVMA
High-efficiency filter1 65% KAFP632B80 KAFP632B160 1 Drain-up kit K-KDU572EVE
1
90% KAFP633B80 KAFP633B160 2 Remote controller Wireless type Cooling only BRC7EB519
2 Filter chamber(for rear suction)1 KDDFP63B80 KDDFP63B160 3 Navigation Remote Controller Wired type 1 BRC1E63
3 Long-life filter1 KAFP631B80 KAFP631B160 4 Wiring adaptor for electrical appendices(2) KRP4AA51
Service panel White KTBJ25K80W KTBJ25K160W 5 Installation box for adaptor PCB 2 KRP4AA93
4 Fresh white KTBJ25K80F KTBJ25K160F 6 Central remote controller 3 DCS302CA61
Brown KTBJ25K80T KTBJ25K160T DCS301BA61
7 Unified ON/OFF controller 3
5 Air discharge adaptor KDAP25A71A KDAP25A140A
8 Schedule timer 3 DST301BA61
6 Shield plate for side plate KDBD63A160
9 intelligent Touch Controller 3 DCS601C51
7 Remote controller Wireless type Cooling only BRC4C66
10 Remote sensor (for Indoor temperature) KRCS01-4B / BRCS01A-4
8 Navigation Remote Controller Wired type2 BRC1E63
11 Electrical box with earth terminal (3 blocks) KJB311AA
9 Adaptor for wiring KRP1C64
12 Electrical box with earth terminal (2 blocks) KEK26-1A
10 Wiring adaptor for electrical appendices(2) KRP4AA51
13 Noise filter ( For electromagnetic interface use only) KJB212AA
11 Mounting plate for adaptor PCB.3,4,5 KRP4A98
Note:
12 Remote sensor (for Indoor temperature) KRCS01-4B / BRCS01A-4 1
Wiring for wired remote controller should be obtained locally.
2
13 Central remote controller6 DCS302CA61 3
Installation box is necessary for each adaptor marked .
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.
14 Unified ON/OFF controller6 DCS301BA61
15 Schedule timer6 DST301BA61
16 intelligent Touch Controller6 DCS601C51
Note: 1If installing high efficiency filter and long-life filter to the unit, filter chamber is required. 4
Up to 2 adaptors can be fixed for each mounting plate.
2
Wiring for wired remote controller should be obtained locally. 5
Only one mounting plate can be installed for each indoor unit.
3
Mounting plate is necessary for each adaptor marked . 6
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary. FLOOR STANDING TYPE
Kit name
No. Name of option Remark
FVA50AMVM FVA60AMVM FVA71AMVM FVA100AMVM FVA125AMVM FVA140AMVM
1 Replacement long life filter KAFJ95L160
2 Remote controller Wireless type Cooling only BRC4C66

CEILING SUSPENDED TYPE 3 Navigation Remote Controller Wired type 1 BRC1E63

Kit name 4 Central remote controller 2 DCS302CA61


No. Name of option Remark
FHA50BVMA FHA60BVMA FHA71BVMA FHA100BVMA FHA125BVMA FHA140BVMA 5 Unified ON/OFF controller 2 DCS301BA61
1 Replacement long-life filter Resin net KAFP501A56 KAFP501A80 KAFP501A160 6 Schedule timer 2 DST301BA61
2 Fresh air intake kit KDDQ50A140 7 intelligent Touch Controller 2 DCS601C51
3 Drain pump kit KDUP50Q160 8 Adaptor for wiring 3 KRP1BA57
4 L-type piping kit (for upward direction) KHFP5N160 9 Wiring adaptor for electrical appendices(2) 3 KRP4AA52
5 Remote controller Wireless type Cooling only BRC7M56 10 Installation box for adaptor PCB KRP4AA95
6 Navigation Remote Controller Wired type 1 BRC1E63 Note:
7 Central remote controller 2 DCS302CA61 1
Wiring for wired remote controller should be obtained locally.
2
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.
8 Unified ON/OFF controller 2 DCS301BA61 3
Installation box for adaptor PCB (KRP4AA95) is necessary.
9 Schedule timer 2 DST301BA61
10 intelligent Touch Controller 2 DCS601C51
11 Adaptor for wiring KRP1BA54
12 Wiring adaptor for electrical appendices 3 KRP4AA52
13 Installation box for adaptor PCB KRP1D93A

Outdoor unit
14 Adaptor box mounting plate KKSAP50A56 ----------
15 Remote sensor (for indoor temperature) KRCS01-4B / BRCS01A-4
16 Electrical box with earth terminal (3 blocks) KJB311AA Kit name
17 Electrical box with earth terminal (2 blocks) KJB212AA No. Name of option 1 Phase RZF50/60/71CVM RZF100CVM RZF125/140CVM
3 Phase ---------- RZF71/100CYM RZF125/140CYM
Note:
1
Wiring for wired remote controller should be obtained locally. 1 Central drain plug KKP014A4 KKP937A4 KKPJ5G280
2
The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary. ---------- KKTP5B112
3 2 Fixture for preventing overturning ----------
Installation box for adaptor PCB (KRP1D93A) is necessary.
3 Wire fixture for preventing overturning ---------- ---------- K-KYZP15C
4 Demand adaptor ---------- KRP58M51 KRP58M51+EKMKSA1
Overvoltage PCB 1 Phase BRV2BPSF BRV2BPSS BRV2BPL
5
3 Phase ---------- BRV2BPSS+BRV2BPSS

53 54
DIMENSIONS (Unit: mm)

CEILING MOUNTED CASSETTE TYPE / Standard panel with Sensing CEILING MOUNTED CASSETTE TYPE / Standard panel with Sensing

[FCF50-71CVM] [FCF100-140CVM]
20 20 20 20 20 20 20 20
4 - M4 6 6 4 - M4 4 - M4
B Connection position 4 - M4 6 6
950 Note) 3 Prepared hole Prepared hole of branch duct Prepared hole B
160 950 Note) 3 Prepared hole
8 860~910 (celing opening spec)(Note 4) 81 2x100=200 85 160 Connection position

D
300 124 (Round shape type) 8 860~910 (celing opening spec)(Note 4) 81 2x100=200 85

D
25 25 or less 710 (suspention position) 109 124 300 167 of branch duct
Pipe connection 25 25 or less 710 (suspention position) 93 67 160 (Round shape type)
95

136

36 136
Pipe connection

94

94
side 420 C/L 16 - M4 420 95 C/L

E
Connection position side 10 16 - M4

E
10 Prepared hole Connection position 29
of branch duct Prepared hole

36
36
of branch duct

36
6

160

160
6 (Square-shaped type)

860-910 (celing opening spec)(Note 4)


(Square-shaped type)

860-910 (celing opening spec)(Note 4)

93 67
20 - M4 20 - M4

95
780 (suspention position)

167
780 (suspention position)
Prepared hole

950
Prepared hole
950

Arrow view D Arrow view E

29
Arrow view D Arrow view E

110
95
124
11 122 11

124
7

160
80 2x100=200 80
7

80 2x100=200 80
15 15 20 20 157
350 Connection position Connection position

25
Drain connection 4 - M4 5 Drain connection 15 350

25
6 of branch duct 15 20 20 of branch duct

157
350
4 - M4

122
350
side Prepared hole C C/L side 5 C C/L (Square-shaped type)
Prepared hole Arrow view B (Square-shaped type) 4 - M4 6 4 - M4
Prepared hole Prepared hole Arrow view B

213
10 25

213
94
94

Connection position Arrow view A 9 10 25 Connection position


Arrow view A

136
9

136
of branch duct of branch duct ø10
ø10

36

90
(Kn 0
36
(Round shape type)
(Kno 0 (Round shape type)

90
F ock

36
36
F ck h ho
Fresh air kit (direct type) ole) le)
Fresh air kit (direct type) 90
Arrow view F Arrow view G Connection position 90 420 196
183 Connection position
420

G
Arrow view F Arrow view G

G
Arrow view C Arrow view C

Connection position Connection position


16 - M4 of branch duct Decoration panel Decoration panel
Adjustable (0~675)

of branch duct

Adjustable (0~675)
Prepared hole (Square-shaped type) BYCQ125EEF Sensing panel (Fresh white) 16 - M4 (Square-shaped type) BYCQ125EEF Sensing panel (Fresh white)
3 (Note 2) Prepared hole (Note 2) BYCQ125EEK
BYCQ125EEK Sensing panel (Black) Connection position 3 Sensing panel (Black)
55 840 55 Connection position 55 840 55 20 - M4 55 840 55
of branch duct 55 840 55 27 - M4
Prepared hole
850

of branch duct Prepared hole Note: 340 Note:


340 81 2x100=200 85 Option decolation panel has 2 types which external (Square-shaped type) 64 81 2x100=200 85 Option decolation panel has 2 types which external
(Square-shaped type) 80 2x100=200 80 Hanger

850
80 2x100=200 80 64 Hanger 160
color are different. 160 50 color are different.

167
124

95
124 50
110
124

167
It can be chosen one of above 2 types depend on It can be chosen one of above 2 types depend on
95

93
95
110
124
105

105

29
60
95
60

5 your specify. your specify.

160
298
256

288

29
175
160
246

150
175

160
10
165
160

150

160
125
10

67
165
125

42
1 Liquid pipe connection 1 Liquid pipe connection
42

(Required space)
2 Gas pipe connection C/L 35 or less
C/L 35 or less 20 256 2 Gas pipe connection

(Required space)
256

50
40
20

1500 or more
157

(Ceiling side-
hanger fixture height)
hanger fixture height)
(Note 4)

1500 or more
50

(Ceiling side-
40

122 (Note 4) 157


Humidifier drain pipe
122 3 Drain pipe connection Suspention bolt Connection position 350 Humidifier drain pipe
connection position 350 3 Drain pipe connection
350 connection position 350 4 - M8~M10 of branch duct 280
4 4 1 2
Power-source wiring and a unit wiring Connection position 35 or less 4 Power-source wiring and a unit wiring

130
Suspention bolt Connection position 280 4 1 2 Connection position 35 or less (Round shape type) 330 of branch duct A

130
330 of branch duct A (Note 4)
4 - M8~M10 of branch duct
(Round shape type) (Note 4) connection (Round shape type) connection
(Round shape type)
5 Connection wiring / 5 Connection wiring /
Remote control wiring connection Remote control wiring connection
6 Air outlet 6 Air outlet
7 Suction grille 7 Suction grille
8 Corner decoration cover 8 Corner decoration cover
9 Sensor 9 Sensor
10 Drain hose (accessory) 10 Drain hose (accessory)
11 Drain hose connection port 11 Drain hose connection port

Note: Note:
1.Sticking location for Manufacture's label 1.Sticking location for Manufacture's label
Manufacture's label for Indoor unit : Suction grille inner side's electric components box's lid surface. INSTALLATION SPACE Manufacture's label for Indoor unit : Suction grille inner side's electric components box's lid surface. INSTALLATION SPACE
a a
Manufacture's label for Decoration panel : Decoration panel's corner decoration cover inner surface. ORE
Manufacture's label for Decoration panel : Decoration panel's corner decoration cover inner surface.
RM MORE
mm O m OR
200 200m
2.In case of having option part built-in, please refer outside drawing of option part. 2.In case of having option part built-in, please refer outside drawing of option part.
Fresh air intake kit..........................................inspection hole Need a a
Fresh air intake kit..........................................inspection hole Need a a
Natural evaporate type humidifier...................inspection hole Need Natural evaporate type humidifier...................inspection hole Need
Air purifier unit................................................ inspection hole No Need 200
mm
Air purifier unit.................................................inspection hole No Need 200
mm
High efficiency filter unit..................................inspection hole No Need OR
MO High efficiency filter unit.............................inspection hole No Need OR
MO
RE a RE a
Branch duct chamber......................................inspection hole No Need Branch duct chamber......................................inspection hole No Need
(both angle duct • circle duct) (both angle duct • circle duct)
- The necessary space is 500 mm or more when the air-outlet is - The necessary space is 500 mm or more when the air-outlet is
3.In case of using wireless remote controller. this position will be a signal receiver. 3.In case of using wireless remote controller. this position will be a signal receiver.
blocked with the accessory. blocked with the accessory.
Refer to the drawing of wireless remote controller in detail. Refer to the drawing of wireless remote controller in detail.
Moreover when the corner areas are blocked (both right and Moreover when the corner areas are blocked (both right and
4.Though the installation is acceptable up to maximum of 910 mm square ceiling opening, keep the left of the blocked air outlet), the necessary space is 200 mm 4.Though the installation is acceptable up to maximum of 910 mm square ceiling opening, keep the left of the blocked air outlet), the necessary space is 200 mm
clearance of 35mm or less between the indoor unit and the ceiling opening so that the panel overlap or more. clearance of 35mm or less between the indoor unit and the ceiling opening so that the panel overlap or more.
allowance can be ensured. - When the air-outlet is close to the wall surface (both sides of allowance can be ensured. - When the air-outlet is close to the wall surface (both sides of
the air-outlet), the recommended space is 2000 mm or more. the air-outlet), the recommended space is 2000 mm or more.
5.When the temperature and humidity in the ceiling exceed 30ºC and 80% RH or the fresh air is 5.When the temperature and humidity in the ceiling exceed 30ºC and 80% RH or the fresh air is
inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness
10mm or more of glasswool or polyethylene form) is required. 10mm or more of glasswool or polyethylene form) is required.

6.Please do not place the thing been damp and troubled under an indoor unit. when the case where 6.Please do not place the thing been damp and troubled under an indoor unit. when the case where
humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall. humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.

7.If put vent hole, lighting, equipment near the air flow disturb equipment, ceiling surface may get dirty, 7.If put vent hole, lighting, equipment near the air flow disturb equipment, ceiling surface may get dirty,
therefore shall install following to diagram as below. therefore shall install following to diagram as below.

INDOOR UNIT INDOOR UNIT INDOOR UNIT INDOOR UNIT


( 1) ( 1)
VENTILATION FAN VENTILATION FAN
LIGHTING LIGHTING

1500 OR MORE 1500 OR MORE

FROM WALL 2000 OR MORE FROM WALL 2000 OR MORE


a THE DISTANCE BETWEEN UNIT ( b) a THE DISTANCE BETWEEN UNIT ( b)

8. For fixing position of human detection and temp sensor will be follow to diagram instruction (can not change position). 8. For fixing position of human detection and temp sensor will be follow to diagram instruction (can not change position).
Model FCF50-71CVM Model FCF100-140CVM
a 1500-5000 a 1500-7000
Valid Valid
Circulation b 5000 or more Circulation b 7000 or more
air flow a 1500 or more air flow a 1500 or more
Invalid Invalid
b 4000 or more b 4000 or more
( 1)Lighting is targeted for exposed type (inverse fuji-shape etc.), for embedded type (type that not expose to ceiling surface), there is no restriction. ( 1)Lighting is targeted for exposed type (inverse fuji-shape etc.), for embedded type (type that not expose to ceiling surface), there is no restriction.

55 56
DIMENSIONS (Unit: mm)

CEILING MOUNTED CASSETTE TYPE / Standard panel CEILING MOUNTED CASSETTE TYPE / Designer panel

[FCF50-71CVM] [FCF50-71CVM]
20 20 20 20
4 - M4 6 6 4 - M4 B
950 Note) 3 Prepared hole Prepared hole 160 Connection position
8 860~910 (celing opening spec)(Note 4) 124 81 2x100=200 85 20 20 20 20

D
300 of branch duct
25 25 or less 710 (suspention position) 109 124 (Round shape type) 950 Note) 3 4 - M4 6 6 4 - M4
Pipe connection 95 B

36 94
420 C/L

94
side 16 - M4 8 Prepared hole Prepared hole 202 81 2X100=200 85 Connection position
9

E
Connection position Prepared hole 860~910 (celing opening spec)(Note 4)

D
of branch duct 300 124 124 of branch duct
Pipe connection

36
25 25 or less 710 (suspention position) 109
6 (Round shape type)

160
(Square-shaped type) side 95 C/L

94

94
420

860-910 (celing opening spec)(Note 4)


20 - M4 9 16 - M4

E
6 Connection position Prepared hole

780 (suspention position)


950

Arrow view D Arrow view E Prepared hole of branch duct

36

202
36
110
95
124
10 122 (Square-shaped type)

124

860-910 (celing opening spec)(Note 4)


7

80 2x100=200 80

950
15 15 Connection position 20 - M4
Drain connection 20 20 350 Prepared hole
of branch duct

25
7

780 (suspention position)


4 - M4 5 6 Arrow view D Arrow view E

350
122
side 4 - M4 (Square-shaped type)

110
C/L

95
Prepared hole C

124
Prepared hole 15 15 20 20 10

124
80 2X100=200 80
Arrow view B 122 Connection position
Drain connection 4 - M4 5 6 4 - M4 350

213
10 25 of branch duct

25
side Prepared hole
Prepared hole

122
350
Connection position

94
94

Arrow view A C C/L (Square-shaped type)


of branch duct Arrow view B
ø10 10 25

36
(Round shape type)
(Kn 0

90
36

94
94

213
F Fresh air kit (direct type) ock
ho le) Arrow view A Connection position
Connection position of branch duct

36
90

36
Arrow view F Arrow view G 183 (Round shape type) O10

90
420
F (Kno 0

G
Fresh air kit (direct type) ck h
connection position ole)
Arrow view C Arrow view F Arrow view G 90
420 225

G
Arrow view C

Connection position
of branch duct
Adjustable (0~675)

(Square-shaped type) Decoration panel


16 - M4 (Note 2)
Prepared hole 3 BYCQ125EAF Standard panel (Fresh white)
55 840 55 Connection position 55 840 55 20 - M4 BYCQ125EAK Standard panel (Black) Connection position of branch duct

Adjustable (0~675)
340 of branch duct Prepared hole
81 2x100=200 85 Note: 16 - M4 (Square-shaped type)(Note 2)
(Square-shaped type) 64 Hanger
850

80 2x100=200 80 124 Prepared hole Connection position 3


Option decolation panel has 2 types which external
124

124 50
110

55 840 55 of branch duct 55 840 55 20 - M4


95

color are different.

124
105

110
Prepared hole

95
60

5 It can be chosen one of above 2 types depend on 340 (Square-shaped type) 81 2X100=200 85
80 2X100=200 80 64 Hanger Decoration panel

905
your specify.
256

124

124
110
124 50
246

BYCQ125EAPF
175

Designer panel
165
160

160

95

124
150

105
10

110
125

95
60
42

5
1 Liquid pipe connection
C/L 35 or less 256

(Required space)
20 2 Gas pipe connection

298
Hanger fixture height)

246
50

1500 or more
(Ceiling side-
40

(Note 4)

217
122

207
52
1 Liquid pipe connection

192
122

202

167

202
Humidifier drain pipe

42
Suspention bolt Connection position
4 - M8~M10 of branch duct
350 connection position 350 3 Drain pipe connection
280 4 1 2 Connection position 2 Gas pipe connection
(Round shape type) 35 or less 4 Power-source wiring and a unit wiring

130
330 of branch duct A 35 or less 256
C/L 3 Drain pipe connection

(Required space)
(Round shape type) (Note 4) 20

97
connection

45
122 (Note 4) 122
4

1500 or more
Humidifier drain pipe 35 or less Power-source wiring and a unit wiring

Hanger fixture
Suspention bolt Connection position 350 350
5 Connection wiring / 4 1 2

Ceiling side-
4 - M8~M10 of branch duct connection position (Note 4)
(Round shape type)
280
Connection position connection
Remote control wiring connection A

172
330

height)
of branch duct
6 Air outlet (Round shape type) 5 Connection wiring /
7 Remote control wiring connection
Suction grille
6 Air outlet
8 Corner decoration cover
7 Suction grille
9 Drain hose (accessory)
8 Corner decoration cover
10 Drain hose connection port
9 Drain hose(accessory)
10 Drain hose connection port

CEILING MOUNTED CASSETTE TYPE / Standard panel CEILING MOUNTED CASSETTE TYPE / Designer panel

[FCF100-140CVM] [FCF100-140CVM]
20 20 20 20
6 6 4 - M4
4 - M4 Prepared hole B
Note) 3 Prepared hole 20 20 20 20
950 160 Connection position
8 300 860~910 (celing opening spec)(Note 4) 167 81 2X100=200 85 4 - M4
D

of branch duct 950 Note) 3 4 - M4 6 6


25 25 or less 710 (suspention position) 93 67 160 Prepared hole B
136

136

Pipe connection (Round shape type) 8 Prepared hole


420 95 C/L 202 81 2X100=200 85 Connection position
side 16 - M4 860~910 (celing opening spec)(Note 4) 167

D
29 300
E

9 Connection position 160 of branch duct


Prepared hole Pipe connection 25 25 or less 710 (suspention position) 93 67

136

136
(Round shape type)
36

of branch duct
36

side 95 C/L
160

6 (Square-shaped type) 420 16 - M4


29

E
860-910 (celing opening spec)(Note 4)

6 9 Connection position
93 67

20 - M4 Prepared hole
95
167

36
of branch duct

202
36
950

Arrow view E Prepared hole


780 (suspention position)

Arrow view D
(Square-shaped type)
29

860-910 (celing opening spec)(Note 4)

93 67
950
10 20 - M4
80 2X100=200 80

7 15 15
160

20 20

95
167
157 Connection position 7 Prepared hole
5

780 (suspention position)


4 - M4 350 Arrow view D Arrow view E
Drain connection 4 - M4 6 of branch duct

29
25

350
157

side Prepared hole Prepared hole 10

160
15

80 2X100=200 80
C C/L (Square-shaped type) 15 20 20 157
Drain connection 5 Connection position
Arrow view B 4 - M4 4 - M4 350 of branch duct

25
10 side 6

350
25
136
136

Prepared hole

157
213

Prepared hole C C/L (Square-shaped type)


Connection position Arrow view B
Arrow view A of branch duct 10 25

136
136

213
36
36

(Round shape type) O10


90

F (Kno 0 Arrow view A Connection position


Fresh air kit (direct type) ck h of branch duct
ole)

36
connection position

36
90 (Round shape type)

90
Arrow view F Arrow view G O10
420 196 F Fresh air kit (direct type) (Kno 0
connection position ck h
ole)
G

Arrow view C Arrow view F Arrow view G 90


420 238

G
Arrow view C

Connection position
Adjustable (0~675)

16 - M4 of branch duct Decoration panel


Prepared hole (Square-shaped type)(Note 2) BYCQ125EAF Standard panel (Fresh white)
Connection position 3
55 840 55 55 840 55 27 - M4 BYCQ125EAK Standard panel (Black)
of branch duct Connection position

Adjustable (0~675)
340 Prepared hole 16 - M4
(Square-shaped type) 64 81 2X100=200 85 Note: of branch duct
80 2X100=200 80 Hanger Prepared hole
850

(Square-shaped type)(Note 2)
167

160 Option decolation panel has 2 types which external 3


95

160 50 55 55 Connection position


840 55 840 55 27 - M4
167

color are different. of branch duct


95
93

5
105

29

340 Prepared hole


60

It can be chosen one of above 2 types depend on (Square-shaped type) 64 81 2X100=200 85


80 2X100=200 80 Hanger
160

Decoration panel

167
your specify. 905 160

95
298

160 50

167
288

175

BYCQ125EAPF Designer panel

95
29
160

160

93
150
10

105

29
60
165
125

67
42

1 Liquid pipe connection

160
(Required space)

340
35 or less 2
20 C/L 256 Gas pipe connection
288
50

29
40

1
Hanger fixture

157
52

Liquid pipe connection


217

(Note 4)
202

202
1500 or more

157

192
Ceiling side-

67
42
3 Drain pipe connection

167
350

207
Humidifier drain pipe 350
Suspention bolt Connection position 280 connection position 35 or less 2 Gas pipe connection
4 Power-source wiring and a unit wiring
height)

4 - M8~M10 of branch duct 330 4 1 2 (Note 4)


Connection position 35 or less 3 Drain pipe connection
130

(Round shape type) A 20 C/L 157 256

(Required space)
of branch duct
97

connection
45

(Note 4) 157
(Round shape type) 4 Power-source wiring and a unit wiring

Hanger fixture
350 Humidifier drain pipe

1500 or more
Suspention bolt Connection position 350 35 or less

Ceiling side-
5 Connection wiring / 4 - M8~M10 of branch duct 280 4 1 2 connection position (Note 4)
330 connection
Remote control wiring connection (Round shape type) Connection position

height)
A
of branch duct
5 Connection wiring /

172
6 Air outlet (Round shape type)
Remote control wiring connection
7 Suction grille
6 Air outlet
8 Corner decoration cover
7 Suction grille
9 Drain hose(accessory)
8 Corner decoration cover
10 Drain hose connection port
9 Drain hose(accessory)
10 Drain hose connection port

57 58
DIMENSIONS (Unit: mm)

CEILING MOUNTED CASSETTE TYPE / Auto grille panel DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

[FCF50-71CVM] [FBA50-71BVMA]
Inspection hatch 2
30-φ4.7hole 134 630 10 450 or more CASE1) Control box
(All around) (Hanging bolt position) Inspection hatch 1
( Drain

300 or more
pan removal
and part exchange. )
(450x450)
Inspection hatch 3

200 or less
8
20 20 20 20 8 ※When can work enters (SAME AS THE INDOOR
UNIT SIZE +300 OR MORE)
6 6 4 - M4 the space under the unit,
950 Note) 3 4 - M4 B inspection hatch 2 is Control box
Prepared hole Prepared hole 215 81 2X100=200 85 Connection position
860~910 (celing opening spec)(Note 4) unnecessary.
300 124

D
124 of branch duct Control box
Pipe connection 25 25 or less 710 (suspention position) 109 9 Inspection hatch Fig.A
C/L (Round shape type) Ceiling

1300 or more
side

94

94
420 95 16 - M4

11x65=715
1038(Hanging bolt position)
10

E
Connection position CASE 2),3)

1000 or more
Prepared hole Control box
of branch duct

835
6

36

215
Inspection hatch1

36
(Square-shaped type) (450x450)

860~910 (celing opening spec)(Note 4)

or less
20 or more
20 - M4 Air Air inlet
950

200
Prepared hole outlet Control box
Arrow view E

780 (suspention position)


Arrow view D

13x65=845
800 or more 800 or more

110
95
124

1000
11 36-φ4.7hole Inspection hatch 2

500
15 15

124
80 2X100=200 80
20 20 122 View B-1 View B-2
Inspection hatch

500
Drain connection 4 - M4 5 Connection position B
6 4 - M4 350 (All around) (SAME AS THE INDOOR Unit base

25
side Prepared hole of branch duct Ceiling UNIT SIZE OR MORE)
Prepared hole

122
350
C C/L (Square-shaped type)
Arrow view B
10 25 Air outlet Air inlet

94
94

213
9 Connection position
Arrow view A Suspention

200 or less
36 Fig. A-1 Inspection hatch 2※
36

of branch duct 16-8x12 oblonghole (4pieces) bolt


O10 450 (450X450)
(Round shape type)

53
(Service space)
90

65
69
(Kno 0 (All around)

450 or more
F Fresh air kit (direct type) ck h
connection position ole)
Arrow view F Arrow view G 90 13

176
100
194
420 238
Notes:

G
Connection position Arrow view C 1
Locations of Manufacturer's Label:Surface of a control box
Adjustable (0~675)

16 - M4 of branch duct Drain pan 5x156=780 26 2


Make sure to mount the air filter inside the air passage on

138
Prepared hole 3 (Square-shaped type)(Note 2) maintenance space
Connection position 792
55 55 of branch duct 55 840 55 20 - M4 OPTIONAL WIRELESS REMOTE CONTROLLER the suction side. (Select Duct Collection Efficiency
840 Control Box
Prepared hole 43 Inspection hatch 1 815
340 (Square-shaped type) 81 2X100=200 85 BRC16A2
450 or more 800 or more maintenance space <Gravimetric Method>50% or more.)
80 2X100=200 80 64 Hanger View If the temperature and humidity in the ceiling is likely to
905

3
124
124

(Service space)
110

124 50
105

exceed 30℃ and RH80%, strengthen heat insulation by


95

(From the Air outlet)

124
110
60

95
STOP

5
12
AUTO GRILLE

applying the additional insulation materials such as glass


鎮詩 賻

UP

3x50=150
(643 or less)
DOWN覺

2 6 5 300 or less 499 wool or polyethylene that has thickness of 10mm or more.
311

1 3

2x50=100
246

133
BRC16A2

207 Adjustable
65

230

220
215

215
205

EMERGENCY
180

4
Do not put things that should not get wet under the indoor unit.
42

LIFTING/LOWERING

850 or less
LIFTING/LOWERING STAGE
Dews may drop when humidity reaches over 80%, a drain
C/L 35 or less 256 gets stuck or air filters are not clean.

(Required space)
20
105

(Note 4)
40

122

Hanger fixture
AUTO GRILLE
122 Space for Service Works

245
5

222
Air Air inlet

Ceiling side-

1500 or more

183
Suspention bolt Connection position 350 Humidifier drain pipe 35 or less

208
136

226
123
4 1 2 350 18.5 outlet (Note.2)
4 - M8~M10 of branch duct connection position (Note 4)
280 Provide service spaces for service work such as check and

height)
(Round shape type) Connection position

185
330 A AUTO GRILLE RECEIVER WIRELESS REMOTE CONTROLLER
6x150=900 maintenance of the control box and drain pump by one of the

60
of branch duct 91

38
4 7 952 following ways.

300 or more

(A case without
(Round shape type) 179 50

2500 or more
11

(Note.5)
Decoration panel 977

the ceiling)
300 1)Inspection hatch 1and 2(450x450) (Fig.A-1) and a space of
BYCQ125EASF Auto grille panel
Drain pan maintenance 800
18-8x12 oblong hole (From the Air inlet) 300mm or more under the unit. (Fig.A)
check hole (All around) Note:Inspection hatch 2 is not needed when there is a space for
1 Liquid pipe connection 6 Air outlet Ceiling Floor surface service work under the unit.
2 Gas pipe connection 7 Suction grille 2)Inspection hatch 1(450x450) on the control box side, and
Inspection hatch 2 under the unit. (View B-1)
3 Drain pipe connection 8 Corner decoration cover 1 Liquid pipe connection 6 Remote control wiring connection 11 Socket(For maintenance) 3)Inspection hatch 3 under the unit and control box. (View B-2)
4 Power-source wiring and a unit wiring 9 Auto grille receiver 2 Gas pipe connection 7 Power supply wiring connection 12 Drain hose(Accessory)
connection 10 Drain hose(accessory) Provide enough space for maintenance and mount the drain
3 Drain pipe connection 8 Air discharge flange 13 Drain hose connection(Accessory) pan and control box.
5 Connection wiring / 11 Drain hose connection port 4 Earth terminal(terminal in Control box) 9 Air suction flange Check the drawing of optional accessories when mounting
Remote control wiring connection 5 Control box(Inside) 10 Hanger optional accessories such as filter chamber and humidifier.

CEILING MOUNTED CASSETTE TYPE / Auto grille panel DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

[FCF100-140CVM] [FBA100-140BVMA]
44-φ4.7hole 134 630 10
(All around) (Hanging bolt position) 50-φ4.7hole
20 20 20 20
(All around) CASE1) Control box
8
950 Note) 3 4 - M4 6 6 4 - M4 8
Prepared hole B
9

300 or more
Prepared hole Inspection hatch 1
215 81 2X100=200 85 Connection position (450x450) Inspection hatch 3
860~910 (celing opening spec)(Note 4) 167
D

300

200 or less
of branch duct Inspection hatch 2
Pipe connection or less 710 (suspention position) 93 67 160 450 or more (SAME AS THE INDOOR
25 25
136

136

side 95 C/L (Round shape type) UNIT SIZE +300 OR MORE)


420 16 - M4
10 29
( Drain
and part exchange. )
pan removal Control box
E

Connection position
Prepared hole Inspection hatch

1438(Hanging bolt position)


6 of branch duct
36

215

Fig.A Ceiling
36

Control box
(Square-shaped type)

1700 or more
18x65=1170
※When can work enters
860~910 (celing opening spec)(Note 4)

93 67

7 20 - M4 the space under the unit,


950

CASE 2),3) Control box


95
167

20x65=1300

1400 or more
1235
Prepared hole inspection hatch 2 is Inspection hatch1

200 or less
Arrow view E
780 (suspention position)

Arrow view D
unnecessary.

1400
(450x450)
29

20 or more
11
160

15
80 2X100=200 80

15 20 20 157
Drain connection 5 Connection position Control box
4 - M4 4 - M4 350
25

side 6 of branch duct Air inlet 800 or more 800 or more


157
350

Prepared hole Prepared hole Air


C C/L
Arrow view B (Square-shaped type) Inspection hatch B Inspection hatch 2 View B-2

500
outlet View B-1
10 Ceiling (SAME AS THE INDOOR
25
136
136

213

UNIT SIZE OR MORE)


9
Arrow view A Connection position Air inlet

500
of branch duct Air outlet
36
36

Unit base
90

(Round shape type) O10


F (Kno 0
Fresh air kit (direct type) ck h
connection position 90 ole) 650 20-8x12 oblonghole bolt Inspection hatch 2※
Arrow view F Arrow view G Suspention
251 (All around) (4pieces) (450X450)

200 or less
420 Fig. A-1

(Service space)
G

450 or more

53
65
69
Arrow view C
Adjustable (0~675)

16 - M4 Connection position of branch duct

176
100
194
Prepared hole (Square-shaped type)(Note 2) Notes:
13
55 840 55 Connection position 3 27 - M4
1
Locations of Manufacturer's Label:Surface of a control box
of branch duct 55 840 55 Control Box 26
340 Prepared hole OPTIONAL WIRELESS REMOTE CONTROLLER maintenance space 7x156=1092
2
Make sure to mount the air filter inside the air passage on

138
(Square-shaped type) 81 2X100=200 85
80 2X100=200 80 64 Hanger
43 Drain pan the suction side. (Select Duct Collection Efficiency
160 1192
167
905

160 50 BRC16A2
95

maintenance space <Gravimetric Method>50% or more.)


167
95
93

1215
105

5
29

If the temperature and humidity in the ceiling is likely to


60

3
Inspection hatch 1
800 or more View
450 or more exceed 30℃ and RH80%, strengthen heat insulation by
160

STOP
AUTO GRILLE
鎮詩 賻
353

(Service space)
UP

(From the Air outlet)


288

applying the additional insulation materials such as glass


29

DOWN覺
65

230
215

215
205

67

12
42
180
220

3x50=150
133

wool or polyethylene that has thickness of 10mm or more.


BRC16A2

300 or less
EMERGENCY
(643 or less) 699

2x50=100
LIFTING/LOWERING

2
207 Adjustable

1 6 5 Do not put things that should not get wet under the indoor unit.
850 or less

4
35 or less 256
3
20 C/L Dews may drop when humidity reaches over 80%, a drain
(Required space)

LIFTING/LOWERING STAGE
105

157
40

(Note 4)
Hanger fixture

157
gets stuck or air filters are not clean.
Ceiling side-

350
1500 or more

Suspention bolt Connection position Humidifier drain pipe 350 35 or less AUTO GRILLE

4 - M8~M10 of branch duct 280 4 1 2 connection position (Note 4) 5


Space for Service Works

226
208
245
Air inlet

60

222
height)

330 18.5
183

(Round shape type) Connection position A Air (Note.2)


136

123
185

of branch duct outlet


AUTO GRILLE RECEIVER WIRELESS REMOTE CONTROLLER Provide service spaces for service work such as check and
(Round shape type)
91 26-8x12 oblong hole maintenance of the control box and drain pump by one of the
38

300 or more
4 7

(A case without
2500 or more
100 100 6x150=900 100 100 following ways.
50

(Note.5)
Decoration panel 11 179 (All around)

the ceiling)
300 1352
BYCQ125EASF Auto grille panel 1377
1)Inspection hatch 1and 2(450x450) (Fig.A-1) and a space of
Drain pan maintenance 800
check hole 300mm or more under the unit. (Fig.A)
(From the Air inlet)
6 Note:Inspection hatch 2 is not needed when there is a space for
1 Liquid pipe connection Air outlet
Ceiling Floor surface service work under the unit.
2 Gas pipe connection 7 Suction grille 2)Inspection hatch 1(450x450) on the control box side, and
3 Drain pipe connection 8 Corner decoration cover 1 Liquid pipe connection 6 Remote control wiring connection 11 Socket(For maintenance) Inspection hatch 2 under the unit. (View B-1)
4 Power-source wiring and a unit wiring 9 Auto grille receiver 2 Gas pipe connection 7 Power supply wiring connection 12 Drain hose(Accessory) 3)Inspection hatch 3 under the unit and control box. (View B-2)
connection 10 Drain hose(accessory) 3 8 13 Drain hose connection(Accessory)
Drain pipe connection Air discharge flange Provide enough space for maintenance and mount the drain
5 Connection wiring / 11 Drain hose connection port 4 Earth terminal(terminal in Control box) 9 Air suction flange pan and control box.
Remote control wiring connection Check the drawing of optional accessories when mounting
5 Control box(Inside) 10 Hanger optional accessories such as filter chamber and humidifier.

59 60
DIMENSIONS (Unit: mm)

CEILING SUSPENDED TYPE CEILING SUSPENDED TYPE

210
[FHA50/60BVMA] 156
Connection position of fresh air intake kit
[FHA100-140BVMA]
105 φ100(Knock out hole) 210
18 17 20 16 120
102 9 156 Connection position of fresh air intake kit
131 57 90
105

35
18 17 20 16 120 φ100(Knock out hole)
102 9

157 63
90

92
131 57

175

35
87
163
30

100

90
189

115
210

195

157 63
92
87
30

163
189
100

90
210

175

115
195
40
63

bolt pitch)
(Hanging
116 51 60 134 59
12

260

40
10 63

bolt pitch)
(Hanging
Position slit hole for taking out in pipe back 116 51 60 134 59

260
10 12
(View from the front)

(Required space)
Position slit hole for taking out in pipe back
8

(Required space)
(View from the front)
(Required space)

220 8
920 103 220

(Required space)
690 (Hanging bolt pitch) 19 15 103
1550 19 15

5
690 (Hanging bolt pitch)
Hanging bolt

5
Hanging bolt
5

4 11

175
4-M8~M10 1 5
4-M8~M10 1 4 5 11

175
5
197

91
131
197

91
131
235

Position : Hole of wall for taking out in pipe back

197

197
235
Position : Hole of wall for taking out in pipe back
From the floor side 2500 or more

(Required space)

(View from the front)


For height installation

300 or more

13 57 (View from the front)


57 6 14

From the floor side 2500 or more

(Required space)
57

For height installation


14

300 or more
13 6
30 or more 960 30 or more φ 45 57 30 or more 1590 30 or more
(Service space) (Service space) (Service (Service φ45
Obstacle space) space)
The Front The Front
Floor side Brand name plate 1 Air discharge grille 1 Air discharge grille
Obstacle Brand name plate
(Note.2) 2 Air suction grille 2 Air suction grille
Floor side (Note.2)
3 Air filter 3 Air filter
4 Gas pipe connection 4 Gas pipe connection
Drain piping connection VP20 5 Liquid pipe connection
6 5 Liquid pipe connection Drain piping connection VP20
(For left pipe) 6
6 Drain pipe connection (For left pipe) 6 Drain pipe connection
7 Earth terminal (inside the control box) (M4) 7 Earth terminal (inside the control box) (M4)
8 Hanger 8 Hanger
9 Rear pipe penetration cover 9 Rear pipe penetration cover
268

268

268
221
214

268
221
214
10 Top panel penetration cover 10 Top panel penetration cover
11 Right side pipe connection 11 Right side pipe connection
76 83 12 Left back drain pipe connection 76 83 12 Left back drain pipe connection
3 2 7 5 105 4 3 2 7 5 105 4
13 Left side drain pipe connection 13 Left side drain pipe connection
156 156
Notes: 14 Right side drain pipe connection 14 Right side drain pipe connection
1
Location of unit's Name Plate: Bottom of fan housing inside the suction grille. 15 Hole of wall for taking out in pipe back Notes: 15 Hole of wall for taking out in pipe back
2
In case of using wireless remote controller, this position will be a signal receiver. 16 Upward drain pipe connection 1
Location of unit's Name Plate: Bottom of fan housing inside the suction grille. 16 Upward drain pipe connection
Refer to the drawing of wireless remote controller in detail. 17 Upward gas pipe connection 2
In case of using wireless remote controller, this position will be a signal receiver. 17 Upward gas pipe connection
3
Please do not place the thing been damp and troubled under an indoor unit. 18 Upward liquid pipe connection Refer to the drawing of wireless remote controller in detail. 18 Upward liquid pipe connection
When the case where humidity is 80% or more, and the drain outlet are choked up 19 Power supply wiring and a unit wiring back connection 3 Please do not place the thing been damp and troubled under an indoor unit. 19 Power supply wiring and a unit wiring back connection
and the air filter are dirty, dew may fall. 20 Power supply wiring and a unit wiring upper connection When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall. 20 Power supply wiring and a unit wiring upper connection

CEILING SUSPENDED TYPE WALL MOUNTED TYPE

[FHA71BVMA] [FAA71BVMA]
210 Connection position of fresh air intake kit
156
105 φ100(Knock out hole)
18 17 20 16 120 Piping direction
102 9
131 57 90

(Required space)
35

157 63
92
175
87
30

163
189
100
210

50 or more
115
90

Approx.400
195

240
40

63 238
bolt pitch)
(Hanging

116 51 60 134 59
260

12
10 7
Position slit hole for taking out in pipe back
(Required space)

(View from the front)


8

(Required space)
(Required space)

220
103 Dimensions

30 or more
1230 19 15 for full open

290
690 (Hanging bolt pitch) front panel 8
5

Hanging bolt 4 5 11
175
5

4-M8~M10 1
91
131

3
197

197

Position : Hole of wall for taking out in pipe back 9 2 1 Piping direction Name plate Note)2 Piping direction 120 or less
235

(View from the front) 2500 or more


50 or more 1050 50 or more For installation
(Required space)
From the floor side 2500 or more

57
6
For height installation

300 or more

13 14 (Requred space) (Requred space) in high spaces


57 φ45
30 or more 1270 30 or more
(Service space) (Service space) 104 894 52
The Front 1 Air discharge grille

14.5
Obstacle Brand name plate φ80 hole
2 Air suction grille
Floor side (Note.2)
3 Air filter Piping and
4 Gas pipe connection Outside line
Wiring intake
Drain piping connection VP20 5 Liquid pipe connection φ80 hole
6 6 Drain pipe connection
(For left pipe)
7 Earth terminal (inside the control box) (M4)
8 Hanger

105
9 Rear pipe penetration cover
268

44
268

221
214

10 Top panel penetration cover


11 Right side pipe connection 6

44
Approx.345 98 1 Front panel
76 83 12 Left back drain pipe connection 60 5
3 2 7 5 105 4 2 Front grill
13 Left side drain pipe connection 4 Approx.390
156 14 Right side drain pipe connection Mounting location 3 Air outlet
Approx.475 4 Gas piping
Notes: 15 Hole of wall for taking out in pipe back
1 16 Upward drain pipe connection Notes: 5 Liquid piping
Location of unit's Name Plate: Bottom of fan housing inside the suction grille.
2 17 Upward gas pipe connection 1
Location of unit's of Name Plate:Right side surface of casing 6 Drain hose
In case of using wireless remote controller, this position will be a signal receiver.
Refer to the drawing of wireless remote controller in detail. 18 Upward liquid pipe connection 2
In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote contorller in detail. 7 Earth terminal
3 Please do not place the thing been damp and troubled under an indoor unit. 19 Power supply wiring and a unit wiring back connection 3
Please do not place the thing been damp and troubled under an indoor unit. when the case where humidity is 80% or more, 8 Right side piping connection hole
When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall. 20 Power supply wiring and a unit wiring upper connection and the drain outlet are choked up and the air filter are dirty, dew may fall. 9 Left side piping connection hole

61 62
DIMENSIONS (Unit: mm)

WALL MOUNTED TYPE FLOOR STANDING TYPE

[FAA100BVMA] [FVA100-140AMVM]
260
Suction grille 4 holes for anchor bolts 130 215
Ø14 126
stopper
Piping direction
7

79
(Required space)

229
202
Approx.440

50 or more
0.7

130
242
240 DETAIL A
Fixture for preventing
Both sides identical VIEW B
7 overturning
Accessory 330

30
600

18
68 350
Pull-out

(Required space)
direction of Required
340

installation
Dimensions for air filter

30 or more

314
space
full open ·50
front panel · o

·2-7· x ·15·mm
r mo

oblong holes
8 re
·50

Dimension of air filter


· o
r

·740· or more
3 mo
re
2500 or more 120 or less

when pulled out


9 1 50 or more Piping direction 1200 Name plate Note)2 Piping direction 50 or more
2 For installation
ore

677
(Requred space) (Requred space) in high spaces m
r
2 · o
00
79.5 1085 35.5 A ·15
14.5

1850
8
φ80 hole
Outside line 9 1 Air suction grille
Piping and ±46
2 Air filter
φ80 hole Wiring intake
3 Hole for piping
(70x90 mm oblong holes)
4 Hole for piping ( 80 slit hole)
44
6 5 Hole for piping ( 27 slit hole)

825
49

114
3 6 Piping hole (rear)
45

45
(80x130 oblong slit hole)

Position of fully opened


1 Front panel 6

616
1 6

541
65 6 2 Front grill 10 7 Piping hole (bottom)
Approx.400 89 130 (126x130 oblong slit hole)
3 Air outlet B

50
50
5 Approx.460 8 Liquid pipe

95
4 Gas pipe 5

suction grille
Mounting location Approx.465 9 Gas pipe

100
4 5 Liquid pipe

95
Notes: 4 10 Drain pipe connection
1 6 Drain hose 130 200 190

100
Location of unit's of Name Plate:Right side surface of casing

75
223 260 184 184
Earth terminal

34
2
In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote contorller in detail. 7 190 266
Notes:
253
3
Please do not place the thing been damp and troubled under an indoor unit. when the case where humidity is 80% or more, 8 Right side pipe connection hole 266 322 The unit nameplate is located on the switch
Left side pipe connection hole 598 box cover, inside the suction grille.
and the drain outlet are choked up and the air filter are dirty, dew may fall. 9

FLOOR STANDING TYPE OUTDOOR UNIT // RZF50/60/71CVM

[FVA50-71AMVM] Drain outlet


I.D.O 18 hose for connection
845 78
Suction grille 4 holes for anchor bolts
260 300
stopper Ø14 131 573.5
130 215
126
57

7
149
144

130

0.7

342
326
300
DETAIL A
Both sides identical VIEW B Fixture for preventing
overturning
4-hole for anchor bolts

20
Earth terminal

7
Accessory 330 (M8 or M10)
30

600 Name plate Wiring inlet in switch box


18

270
68 Required
Pull-out installation
direction of
314

space
air filter ·50
· o
·2-7· x ·15·mm

r mo
oblong holes

re
·50

595
Dimension of air filter

2 · o
r mo
·740· or more

re

60
when pulled out
677

more
r
· o
00

105
A ·15
1850

8 144 20
Service port

9 1 Air suction grille Liquid stop vale


±46

112
2 Air filter

163
3 Hole for piping
269

272
Service port Gas stop vale
(70x90 mm oblong holes)
44
4 Hole for piping ( 80 slit hole)
49 5 Hole for piping ( 27 slit hole)
825

6
3 6 Piping hole (rear) Drain outlet
(80x130 oblong slit hole) 21
6
Position of fully opened
616

1 6
541

7 Piping hole (bottom) 94


10 (126x130 oblong slit hole)
B 50 200
50

95
50

Drain outlet
5 8 Liquid pipe 299
suction grille

9 Gas pipe 419


100

95

10 Drain pipe connection 449


200 110 184 184
100

50 4
75

223 180
34

Notes: 479
110 253 186
The unit nameplate is located on the switch
186 242 509
598 box cover, inside the suction grille.
559

63 64
DIMENSIONS (Unit: mm)

OUTDOOR UNIT // RZF100CVM, RZF71/100CYM REMOTE CONTROLLER

Wireless type

• Remote controller dimensions • Remote controller dimensions


23.5 CEILING MOUNTED CASSETTE TYPE <Round Flow>
Transmitting part • Receiver installation procedure
Receiver

15 930 46 350
Refrigerant
Piping side

Decoration

157
189
panel

Handle
695

62 17.5 Drain piping


58.5 side
• Remote controller holder

installation procedure Sensor


Remote controller holder • Receiver detail
Installation procedure Wireless remote control <installation to wall surface>
〈Installation to wall surface〉
Liquid crystal
420 remote controller
Power supply wiring intake
(wireless)
Control wiring intake
Remote controller
145 610 175 holder
(Installation leg pitch) Remote control
(Installation leg pitch)
376

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE


50

FLOOR STANDING TYPE CEILING SUSPENDED TYPE WALL MOUNTED TYPE


Grounding terminal
• Receiver detail • Receiver installation procedure • Receiver installation procedure
Receiver Receiver
11

24

497 2-5x9 Slot

Drain outlet
Liquid stop valve

(Ceiling opening)
Service port

83.5
120

106
72
Gas stop valve
• Receiver
detail

0.5
OUTDOOR UNIT // RZF125/140CVM / CYM 70 18 35 49
(Ceiling opening)

Switch box • Receiver detail


(field Supplied parts)
Hole for anchor
bolt 4-M12 Service space for ceiling installation
30

Note :

(Srevice space)
More than 90
Do not install more than 3
receivers in the vicinity of
(345∼355)

one another.
With 4 or more units, there
350

is always the possibility of


320

malfunction
55
37

38
30

91
160 620 160 Wired type • Remote controller dimensions

30 940 3 BRC1E63
Remote controller dimensions Upper case Lower case
Installation method
A Exposed cord Conduit
Staple B Embedded cord C Embedded cord (use switch box)
Top left 19 19
Top center

42
outlet
4 Operation
outlet

7 lamp

120

84
2 (Green)

40
6
1

84

84
990

7 5

40
5 6 Code outlet hole
120 19 28
5 Note)2 28
55

23 48.5 5×15 Oblong hole 48.5 46


5×7 Oblong hole Through hole 0~5
46 Left outlet Switch box for one switch Switch box for two Between remote
(ø8∼ø10)
control box )
( controller
19 Lower case portion Ex.)KJB111A switch
60

and
55
340
339

(optional accessory) Ex.)KJB211A


Lower case portion (optionalAccessory) Switch box
223
95
95

[field supplied part]


95

Specifications of cord
84

Note)
53

53

89 19
53

1. Remote controller cord and staple are not attached. They are field Type Vinyl cord with sheath or cable (insulated thickness: 1mm or more)
89

19 80 52 supplied parts.
7 6 142 Size 0.75~1.25 mm2
145 13 67 2.If the hole size is too large or the location is not proper, the hole
90 16 Total length 500 m
8 may come out from the remote controller.
16

1 Gas pipe connection


161
260

68

2 Liquid pipe connection


285
279

3 Service port
5 4 Earth terminal
36
61 5 Refrigerant piping intake
262 6 Power supply wiring intake
416 7 Transmission wiring intake
595
8 Drain pipe connection

65 66
Installation service space for outdoor unit (Unit: mm)

For RZF50-140CVM, RZF71-140CYM series


1.RZF50/60/71/100CVM, 71/100CYM 2.RZF125/140CVM / CYM series
MEMO
1 When there is an obstruction on the inlet side 2 When there is an obstruction on the outlet side

1) When the overhead space is open 1) When the overhead space is open
1 2
1. For single unit installation 1. For single
When there is an 1 2
unit installation
obstruction only
on the inlet side 0 mo
re
50 ore 0 or
or
m 50
re
mo 0 2. For multiple units installation (more than two units)
or 10 ore
50 m 10
or 0
mo or
When there are obstructions on 1 2 re 10
0
mo or
both sides re

1 2
25
0o
rm
ore
10 10 re
0o
rm 0o mo mo
re
ore rm or or
re ore 00 0
25 mo 10 10 100
0o r 0
rm 0o
0o
rm 10 ore
ore 10 ore or
m
2) When there is an obstruction in the overhead space
1. For single unit installation
2. For multiple units installation An obstruction
ss ss
(more than two units) 10 o r le
in the overhead
0o
r le
0
mo or 5 00 space 50

1000 or more
When there are re 10

1000 or more
0
mo or 1 2
re
obstructions on
both sides 10
00
or
mo
re

re
20 mo
0o
rm 0 or
ore 30 re re
mo mo
0 or or
50 0
50

2. For multiple units installation (more than two units)


ss
2) When there is an obstruction in the overhead space 0o
r le
ss
0o
r le
50 50
1 2

1000 or more
1. For single unit installation
1000 or more

10
0
mo or
re
When there is an obstruction on the inlet side
ss
r le
1000 or more

1 s 2 0o
r les 50 10
0o
or more

0
50 mo or
1000

re
25
An obstruction 0o
rm
in the overhead ore
An obstruction re
space ore in the overhead mo
o rm or
00 space 00
10 10
ore
rm 0
0o 10 ore
10 m
or
3 When there are obstructions on both
When there are obstructions on the inlet side and
both lateral sides
the inlet and outlet sides
An obstruction
in the overhead ss
(When the obstruction on the outlet side is higher than the
1000 or more

s
les r le
or 0o unit itself)
1000 or more

0 space 50
50
1 2
1) When the overhead space is open
(There is no limit to the height of the obstruction on the
outlet side.)
or 150 or 150
mo re mo
re mo re 0 1. For single unit 1 2
or 250 0o
r or 150 15 ore
mo
re
15 mo
re or
m
installation
H
L

2. For series installation (more than two units)


50 ore 0
10 ore
When there are obstructions on the inlet side and 0 e or
m
or
m
0
both lateral sides
0
5 o
m
r L H 50 ore
m
An obstruction or or
in the overhead
1 space 2 2. For series installation (more than two units)
1000 or more

s
s 10 les 10
les 0
mo or or 0
1000 or more

0o
r
re 50
0 1 2 mo or
50 re 10
0
mo or
re
10
0o
rm
L

1 1 ore
or 000 or 000
mo mo 25
re re 0o
or 250 rm
ore 0 0
mo ore 20 ore 30 ore
re rm m
0
20 ore 0o or or
m
or 250 m
2
or 00 30 00 00
mo or mo 10 ore 10 ore
re re or
m L H or
m

Note : As for other patterns of installation, please refer to Installation manual or Engineering Data Book.
67 68