Exercise 1:
Change the setting group in dependence on the current
Setting group B becomes active if all line currents drop below 5% of the rated
nominal current.
Otherwise, setting group A is active.
© Siemens AG 2008
Exercise 1:
Change the setting group in dependence on the current
© Siemens AG 2008
Exercise 1:
Change the setting group in dependence on the current
© Siemens AG 2008
Exercise 1:
Change the setting group in dependence on the current
Step 3: Allocation
Bit 1
Open the Configuration Matrix (“Masking I/O”). 0 1
Bit 0
0 A C
© Siemens AG 2008
Exercise 1:
Change the setting group in dependence on the current
Step 4: Allocation
© Siemens AG 2008
Exercise 1:
Change the setting group in dependence on the current
X1 X2
AND: Y = X1 * X2 (+)
Y
X1 X2 Y
0 0 0
X1 1 0 0
Y 0 1 0
& 1 1 1
X2
© Siemens AG 2008
Exercise 1:
Change the setting group in dependence on the current
© Siemens AG 2008
Exercise 2:
Change the setting group in dependence on the time
After pressing the F1 key setting group B is active during the first 10 seconds.
Then, setting group A gets active again.
© Siemens AG 2008
Follow the CFC standard procedure!
© Siemens AG 2008
Follow the CFC standard procedure!
© Siemens AG 2008
Follow the CFC standard procedure!
Open the folder named “CFC”, insert a new CFC chart, give it a “good” name and open it.
© Siemens AG 2008
Follow the CFC standard procedure!
Q=(S+T2) * T1 * R
R => Timer Reset
S => Timer Start QT1= T1 * R
QT2= T2 * R
QT1 T1 T1
QT2 T2 T2
Delay Prolongation
T1 and T2 timer function Q is delayed by T1 Q corresponds to S prolonged by T2
© Siemens AG 2008
Exercise 2:
Change the setting group in dependence on the time
Insert a TIMER
block via
Drag & Drop.
© Siemens AG 2008
Exercise 2:
Change the setting group in dependence on the time
© Siemens AG 2008
Exercise 2:
Change the setting group in dependence on the time
© Siemens AG 2008
Exercise 2:
Change the setting group in dependence on the time
Connect the output “QT1“ (HIGH applies for as long as the T1 timer is running)
to the information “>Set Group Bit 0“
© Siemens AG 2008
Follow the CFC standard procedure!
© Siemens AG 2008
Follow the CFC standard procedure!
Changes must, however, be made if several function blocks are placed – and
some of them are maybe in the wrong order…
© Siemens AG 2008
Exercise 2:
Change the setting group in dependence on the time
© Siemens AG 2008
Follow the CFC standard procedure!
© Siemens AG 2008
Follow the CFC standard procedure!
© Siemens AG 2008
Follow the CFC standard procedure!
X1
OR: Y = X1 + X2 (+)
X2 Y X1 X2 y
0 0 0
1 0 1
X1 0 1 1
Y 1 1 1
X2 1
© Siemens AG 2008
Exercise 3:
Change the setting group dep. on the time and the current
Solution - Allocation
Connect the two charts via an additional internal single-point indication:
Chart “I < 5“: Priority class “MW_BEARB“ Chart “10s after start“: Priority class „PLC1_BEARB“
Matrix
Destination
CFC
Source
CFC
Solution - CFC
1 Chart “I < 5“ (priority class “MW_BEARB“):
© Siemens AG 2008
Exercise 4:
Time control 1 (2) – Simple switching sequence
© Siemens AG 2008
Exercise 4:
Time control 1 (2) – Simple switching sequence
© Siemens AG 2008
Exercise 5:
Time control 2 (2) - Flashing
© Siemens AG 2008
Exercise 5:
Time control 2 (2) - Flashing
Solution
© Siemens AG 2008