User Manual
V1.000
Content
1. General ............................................................................................................................................ 3
1.1 Supported Relays........................................................................................................................... 3
2. Software and Hardware Requirements........................................................................................... 3
3. Hardware ......................................................................................................................................... 4
Hardware configuration for winding 1 earth-fault protection ............................................................ 4
Hardware configuration winding 2 earth-fault protection ................................................................. 5
4. Functional Range ............................................................................................................................ 6
5. XRIO Converter ............................................................................................................................... 7
5.1 Specialties of the Additional Information Block ................................................................................ 7
Transformer Data .......................................................................................................................... 7
Configuration Details ..................................................................................................................... 7
6. Specific protection tests ................................................................................................................. 7
6.1 Differential protection ..................................................................................................................... 7
Diff Configuration test .................................................................................................................... 7
Diff Operating Characteristic test ................................................................................................... 7
6.2 Thermal overload protection ........................................................................................................... 7
6.3 Low impedance restricted earth-fault .............................................................................................. 8
External fault ................................................................................................................................. 8
Pick-up.......................................................................................................................................... 8
Trip time........................................................................................................................................ 8
Harmonic blocking......................................................................................................................... 8
6.4 High impedance restricted earth-fault ............................................................................................. 8
Pick-up and drop-off ...................................................................................................................... 8
Trip time........................................................................................................................................ 8
1. General
This user manual describes details of testing ABB RET615 relays with the OMICRON
Protection Test Template. General information on the usage of OMICRON Protection Testing Library
items can be found in the OMICRON PTL user manual.
Furthermore you need a valid license for the following test modules:
Control Center
Quick CMC
Ramping
Advanced Differential
State Sequencer
Overcurrent
3. Hardware
There are multiple possibilities of wiring a RET615 relay to a CMC test set. The advised connections are
shown in Figure 1. These connections are the default settings in the Hardware Configuration of the PTT
and have to be used to get the correct test results, even if the relay is connected in another way to the
real CTs.
4. Functional Range
Supported functions:
Stabilized and instantaneous differential protection for 2-winding transformers TR2PTDF
Numerically stabilized low-impedance restricted earth-fault protection LREFPNDF
High-impedance-based restricted earth-fault protection HREFPDIF
Three-phase non-directional overcurrent PHxPTOC
Three-phase thermal overload protection for power transformers, two time constants T2PTTR
Non-directional earth-fault, low stage EFxPTOC
Negative-sequence overcurrent protection NSPTOC
Although the functions listed above are not supported by the Protection Test Template, the
Relay Parameter Section of the XRIO Converter includes all protection parameters of the relay.
5. XRIO Converter
The Test Object already contains the ABB RET615 XRIO Converter, which includes settings parameters
of the modelled protection relay. The settings parameters are built as an image of the ABB PCM600 V2.6
software.
The Standard Filter for XRIO Files can be used for importing settings into the
Relay Parameter Section.
Transformer Data
The information on the nominal power of the protected object should be entered under the "Nominal
Power". This parameter is used to display the transformer model in the test report correctly.
Configuration Details
The Configuration Details block contains specific information of the tested relay. The Generic Timer
block contains the parameter "Pulse time" for adjustment of the duration of the TRIP output signal.
Before each test shot the thermal memory of the relay has to be reset in order to set up a defined test
case. In this case the relay uses the “Initial temperature” parameter to initiate the temperature calculation.
As the converter uses the “Env temperature Set” parameter to initiate the calculation of the temperature
rise, the “Initial temperature” in the relay has to be set to the same value as the “Env temperature Set” to
perform the test (in ° C). Otherwise the relay would have a different start point for the temperature
calculation than the converter and the test fails.
External fault
An external fault is simulated using the State Sequencer test module. The angle between the residual
current (calculated 3I0) and the neutral current (measured IN) is set in external fault range and the relay
should not trip.
Pick-up
The pickup of the low impedance restricted earth-fault stage is tested with the Ramping test module. The
fault current (neutral current IN) is ramped until the relay picks up.
Trip time
The trip time is tested by simulating an internal fault. The State Sequencer test module is used for the trip
time test.
Harmonic blocking
The harmonic blocking is tested by simulating an internal fault with high content of the second harmonic.
The Ramping test module is used to decrease the second harmonic content to a value at which the relay
trips.
This value is then compared to the first harmonic content and assessed.
Trip time
The trip time is tested by simulating an internal fault with the Overcurrent test module. Test points are
preset in this test, but they can be adjusted by the user if necessary.