Beruflich Dokumente
Kultur Dokumente
DOHA
OASIS CONSTRUCTION DOCUMENTS APRIL 2014
DOHA OASIS
QATAR
ACOUSTIC REPORT
Revision 0
1. Goal
2. Pertinent Standards and Regulations
3. The Airborne Noise Isolation
4. The Structure Borne Noise Isolation
5. The Background Noise Level
6. The Reverberation Time calculation
7. The maximum outdoor airborne sound level
8. The tolerance of the measurement
1- Reverberation Time
2- Calculation
3- Treatment
4- Reference drawings:
i. Acoustic Baffles distribution
ii. Data sheet: Baffle PC-B
1- General Specifications
2- Proposed Treatment for each generators room
3- Sound attenuators specification
4- Reference drawings:
a. Generations room layout
b. Data Sheet Sound absorbers Type ACS 20/75
c. Data Sheet Sound absorbers Type ACS 20/100
d. Data Sheet Sound absorbers Type ACS 20/150
e. Data Sheet Sound absorbers Type ACS 20/200
1- Vibration Isolation
2- Acoustic Enclosure
3- Reference drawings.
a. Data Sheet Acoustic Panels Pw-183
b. Data Sheet Sound absorbers Type ACS 20/100
c. Data Sheet Sound absorbers Type ACS 20/200
“Few People have ever experienced real comfort: Thermal, Visual or Acoustic. But once
they do, they tend to want more of it”
This document is directed to act as a tender performances report on the acoustical aspect
of this project to create an aesthetically pleasing environment suitable for social areas
without overwhelming the guests with excessive noises.
The acoustic works of this project shall be managed by using the following standards and
Regulations:
“ASTM E 336-05” :Test Method for Measurement of Air Borne sound insulation in
Buildings.
“ASTM E 1007-04”: Test Method for field Measurement of Tapping machine impact
sound transmission through floor ceiling.
These standards are to be used as appropriate in conjunction with the defined performance
objective to ensure that the project achieves the required levels of acoustic amenity.
The air borne noise generated in a multi-dwelling residential unit can be grouped in
four categories:
iii. Noise associated with plumbing addresses, water flow through pipes, water
hammer and plumbing fixtures.
iv. Noise due to room’s appliances generated by dishwashers, garbage chutes and
disposals, clothes washers and dryers.
The values representing the performances of isolation between two different spaces
are the FSTC values as defined by ASTM Standards E 336-05.
This item represents the sound transmission loss between two occupied
spaces.(vertical and Horizontal). The FSTC should not be confused with the sound
transmission class STC which represents the capacity of the acoustical isolation of an
element.
Technical floor vertically above public spaces in Mall second floor > 70
floor
first
floor
fifth
floor 11th
apartment Different apartment > 60
Tower 8th
floor
* STC > 35
In the below table are listed the responses that can be expected based on specific
FSTC isolation levels:
The Impact Insulation Class noted I.I.C. represents the acoustical laboratory test,
tested according to ASTM Standards E 1007-04: Standard test method for
measurement of tapping machine impact sound transmission through floor, ceiling
assembles and associates support structure.
The values representing the performances of the impact noise level of a slab is the
Field Impact Insulation Class noted FIIC
The I.I.C. values should not be confused with the FIIC representing the field
measurements performed in accordance with the ASTM E989-06 (site
measurement).
I.The FIIC of the slab of all the residential spaces should be FIIC > 50.
II.The FIIC of the slab of all the retails spaces and public spaces should be FIIC > 45.
III. A particular attenuation will be considered to protect the following areas where the
impact insulation class shall be: FIIC ≥ 65 (underlayer is required).
IV. A particular attenuation will be considered to protect the following areas where the
impact insulation class shall be: FIIC > 70 (a Floating floor is required)
b. Mall technical floor above cinemas and public spaces in mall second floor.
d. swimming pool and Gym in residential first floor above retails spaces and public
spaces in mall second floor
NOTE 2:
In the below table, we have listed the responses that can be expected based on
specific FIIC isolation levels:
FIIC between 40 and 45 Footsteps noise is easily audible and mildly objectionable
FIIC between 45 and 50 Footsteps noise is slightly audible and not objectionable
The acoustical design goal for the HVAC systems is the achievement of a level of
background noise that is unobtrusive in quality ( in terms of frequency) and low
enough in level (in terms of amplitude) that it does not interfere with the function of
the space being served.
The values of the background level will be represented by the Noise Criteria
curves, noted “NC”.All the mechanical equipment, including plumbing, ventilation,
elevators and air conditioning, should be designed and installed to meet with the
noise criteria levels:
Bedroom NC 30*
Cinema NC 30
Control room NC 35
Training room NC 35
Café NC 40
restaurant NC 40
NC 40
Shops/retails
NC 30
conference room/business center
NC 35
Breakfast area
Lobby/reception NC 40
Office NC 35
Kitchen NC 40-45
Parking NC 65
With all the following collective equipment, the generated noise should not
exceed 35 dB(A) inside all the spaces excluding the bedrooms where it
should not exceed 30 dB(A):
- Lifts
- Electrical transformers
- Generators
- AHUs
- Transformer room
- Etc…
In an enclosed space, when a sound source stops emitting energy, it takes some
time for the sound to become inaudible. This prolongation of the sound in the room
caused by continued multiple reflections is called “REVERBERATION TIME”.
The reverberation time is the necessary time for a sound pressure level produced
by a source to decrease 60 dB after the generation of this source. The
reverberation time used as a reference for the calculation is fixed 0.5s if it is not
mentioned.
The reverberation time plays a crucial role in the quality of music and the ability to
understand speech in a given space. When room surfaces are highly reflective,
sound continues to reflect or reverberate.
A high reverberation time will cause a build-up of the noise level in a space. The
effects of reverberation time on a given space are crucial to musical conditions and
understanding speech. It is difficult to choose an optimum reverberation time in a
multi-function space, as different uses require different reverberation times.
A reverberation time that is optimum for a music program could be disastrous to the
intelligibility of the spoken word. Conversely, a reverberation time that is excellent for
speech can cause music to sound dry and flat.
Offices / conference
At least 80% of the ceiling are should be acoustic type with
rooms /business center /
NRC 0.85
conference lounge
NOTE 3:
The reverberation time values are to be considered when these volumes are
empty. For achieving theses values; the following material must be taken into
consideration:
The choice of the absorbent material shall be coordinated with the ID.
It should be less or equal 50dB (A) from the façade of the closest building for the
inlet and outlet ventilation
For the cooling towers on the roof of the technical building, it should 50dB (A) at
the closest occupied space. Otherwise, acoustic enclosure ,acoustic louvers
and/or acoustic screens are required.
The tolerance of the measurement during the commissioning is fixed to 3dB (A). This
tolerance could not be used in the calculation. It is applied for the site measurements
only.
In an enclosed space, when a sound source stops emitting energy, it takes some
time for the sound to become inaudible. This prolongation of the sound in the room
caused by continued multiple reflections is called “REVERBERATION TIME”.
The reverberation time is the necessary time for a sound pressure level produced
by a source to decrease 60 dB after the generation of this source. The
reverberation time used as a reference for the calculation is fixed 0.5s if it is not
mentioned.
The reverberation time plays a crucial role in the quality of music and the ability to
understand speech in a given space. When room surfaces are highly reflective,
sound continues to reflect or reverberate.
A high reverberation time will cause a build-up of the noise level in a space. The
effects of reverberation time on a given space are crucial to musical conditions and
understanding speech. It is difficult to choose an optimum reverberation time in a
multi-function space, as different uses require different reverberation times.
A reverberation time that is optimum for a music program could be disastrous to the
intelligibility of the spoken word. Conversely, a reverberation time that is excellent for
speech can cause music to sound dry and flat.
2) CALCULATION
The reverberation time expected in large enclosures having irregular shapes such as
the Theme Park having a total volume of around 306 000 m3 and the height of 17
meters is around 3.5 s (with 20% tolerance)
3) TREATMENT
For achieving the recommended value of reverberation time , one of the following
solutions could be done:
Solution 1:
The ceiling total surfaces (~14950 m2) should be an acoustic ceiling having an absorption
coefficient of αw 0.5.
Acoustic performances report / Rev.0
Solution 2:refer to enclosed sketch
4) Ref.drawings:
600
10
0
20
0 00
10 10
0
20
0
10
0
CHAPTER III : GENERATORS ROOM –Acoustic Design
- The generators should be laid on isolated concrete pads with 200mm concrete
thickness. The natural frequency of the vibration isolators should be fo < 8Hz
under the static load. These isolators could be CDM-CR or equivalent.
- The surface, onto which the isolators are to be installed, should be horizontal and
clean.
- A special attention should be given to avoid any eventual bridging between the
isolated and non-isolated pads.
- The access door to the generator room shall be acoustical door. The acoustical
performance should not be less than STC = 45dB or 2 doors of STC 40
- No exhaust pipes and ducts inside the generators room should be fixed to the
ceiling. They must be suspended from an isolated metallic structure. The
ventilation and the silencers must be taken into consideration for the selection of
the generators. If the static pressure of the generator fan is not enough, booster
fans shall be used.
- Outside the generators room, the exhaust pipes should be suspended with
vibration isolator hangers Type CDM- PHS or equivalent.
- The inlet and outlet sound attenuators should be calculated to achieve the noise
criteria stated in the acoustic performance report
The following treatment or similar is highly recommended for the generators room
located in basement and ground floor in order to achieve an acceptable noise level at
the nearest occupied area.
The contractor should be responsible of the final selection of the sound attenuators
based on the final selected generators.
1x(5490x24400x2
-The room will be
00)
Axis Z-57 provided with
ACS 20/150 ACS 20/150 1x(5490x3050x20
1 x 1000 KW removable acoustic
35 Pa @ 101*m3/s 20 Pa @ 101*m3/s 0)
1 x 1500 KW panel (STC 45 dB)
(9200x2500x3000) (8400x3400x3500) 1x(6100x3050x20
1 x 2000 KW for generator
0) (60x60x60)mm
replacement
f0=8 Hz
-The room will be
provided with
ACS 20/75 ACS 20/100 (5490x2440x200)
removable acoustic
Ground Floor 27Pa @ 27m3/s 30Pa @ 27m3/s (60x60x60)mm
panel (STC 45 dB)
(4000x3500x2000) (2400x3900x2000) f0=8 Hz
for generator
replacement
- The attenuator casing shall be constructed from not less than 2 mm thick mild
steel, galvanized after manufactured or epoxy painted.
- The splitters frame shall be manufactured from galvanized sheet steel not less
than 1.25mm thick, with aerodynamically shaped leading and trailing edges. Each
splitter shall be secured to the casing by sealed rivets or PK screws. The acoustic
fill shall be an inert, non-combustible, non-hygroscopic and vermin proof mineral
wool having the density of not less than 30Kg/m³ and shall be sealed and
protected from particle migration by an impervious membrane.
- The casing shall be reinforced with a steel structure to avoid any eventual bending
of the steel plates.
- Depending on the silencer type, the splitter and the air gap width shall be as
follow:
4) Ref.drawings:
Pressure Drop in Pa
Face Velocity V ( m/s ) * 1.36 1.9 2.2 2.7 3 3.3 3.5 3.8 4.1 4.4
Pressure Drop ǻP ( Pa ) 15 25 35 50 60 75 85 100 110 125
Insertion loss in dB
Octave Band Center Frequency
Length - L(mm)
63 125 250 500 1K 2K 4K 8K
600 7 11 19 31 45 36 29 20
900 9 14 26 49 50 50 37 29
1200 10 18 33 50 50 50 47 36
1500 12 21 40 50 50 50 50 45
1800 13 24 47 50 50 50 50 50
2100 15 26 50 50 50 50 50 50
2400 17 31 50 50 50 50 50 50
2700 19 34 50 50 50 50 50 50
A c o u s y s t e m
Silence is our business
Tel.: +961.1.683530/1 Fax.: +961.1.683529 e-mail.: acousyst@inco.com.lb
DUCT SILENCER - TYPE ACS-F-P- 20/100
Pressure Drop in Pa
Face Velocity V ( m/s ) * 2.1 2.7 3.2 3.8 4.2 4.7 5 5.4 5.7 6
Pressure Drop ǻP ( Pa ) 15 25 35 50 60 75 85 100 110 125
3
* V (m/s) = Air flow (m /s)
2
W x H (m )
Insertion loss in dB
Octave Band Center Frequency
Length - L(mm)
63 125 250 500 1K 2K 4K 8K
600 6 9 14 22 36 28 21 15
900 8 11 19 31 48 37 26 21
1200 9 14 25 41 50 48 34 27
1500 11 17 30 50 50 50 42 33
1800 12 20 34 50 50 50 49 39
2100 14 23 39 50 50 50 50 45
2400 15 26 44 50 50 50 50 50
A c o u s y s t e m
Silence is our business
Tel.: +961.1.683530/1 Fax.: +961.1.683529 e-mail.: acousyst@inco.com.lb
DUCT SILENCER - TYPE ACS-F-P- 20/150
Pressure Drop in Pa
Face Velocity V ( m/s ) * 3 3.9 4.3 5.1 6 6.4 6.9 7.7 8.1 9
Pressure Drop ǻP ( Pa ) 15 25 35 50 60 75 85 100 110 125
Insertion loss in dB
Octave Band Center Frequency
Length - L(mm)
63 125 250 500 1K 2K 4K 8K
600 5 7 11 17 24 20 13 11
900 6 9 14 24 33 25 18 15
1200 7 11 18 31 42 33 23 19
1500 8 12 22 39 50 40 28 23
1800 9 14 25 45 50 47 34 27
2100 10 16 29 50 50 50 39 31
2400 11 19 32 50 50 50 44 35
2700 12 21 34 50 50 50 49 39
DUCT SILENCER - TYPE ACS-F-P- 20/200
Pressure Drop in Pa
Face Velocity V ( m/s ) * 4 5 6 7 8 8.5 9.5 10 11 11.5
Pressure Drop ǻP ( Pa ) 15 25 35 50 60 75 85 100 110 125
Insertion loss in dB
Octave Band Center Frequency
Length - L(mm)
63 125 250 500 1K 2K 4K 8K
600 5 6 9 13 18 14 10 9
900 6 7 12 20 25 20 14 12
1200 6 9 14 25 33 25 18 15
1500 7 10 18 30 40 31 22 18
1800 8 11 20 35 48 37 26 21
2100 8 13 24 40 50 42 30 24
2400 9 15 26 45 50 48 34 27
2700 9 17 28 50 50 50 38 30
3000 10 19 30 50 50 50 42 33
CHAPTER IV : COOLING TOWER YARD -Acoustic Design
Cooling Towers
For The factory assembled cooling towers, it shall be laid on spring isolators.
For The field erected cooling towers, each installed elements should be balanced
and isolated according to the manufacture recommendation.
2) ACOUSTIC ENCLOSURE:
To reach the required noise level at the surrounding buildings, The Cooling Towers yard
should receive a full acoustic enclosure.
This acoustic enclosure shall be consisting of acoustic panels with the related support steel
structures and include both inlet and outlet sound attenuators, for the ventilation
requirements as follow:
The selection of the cooling tower should take into consideration the additional
pressure drop through the inlet and outlet sound attenuators.
∆P inlet S.A ≥ 25 Pa
∆P outlet S.A ≥25 Pa
In addition, a clearance area should be provided around the cooling towers according to the
manufacturer's recommendations and for maintenance purpose.
3) Ref.drawings:
TECHNICAL SPECIFICATIONS
PW-183 PANELS
CONSTITUTION:
The panel sound absorber and sound Isolator, type Pw-183, 183 mm thick,consists of:
Pressure Drop in Pa
Face Velocity V ( m/s ) * 2.1 2.7 3.2 3.8 4.2 4.7 5 5.4 5.7 6
Pressure Drop ∆P ( Pa ) 15 25 35 50 60 75 85 100 110 125
Insertion loss in dB
Octave Band Center Frequency
Length - L(mm)
63 125 250 500 1K 2K 4K 8K
600 6 9 14 22 36 28 21 15
900 8 11 19 31 48 37 26 21
1200 9 14 25 41 50 48 34 27
1500 11 17 30 50 50 50 42 33
1800 12 20 34 50 50 50 49 39
2100 14 23 39 50 50 50 50 45
2400 15 26 44 50 50 50 50 50
A c o u s y s t e m
Silence is our business
Tel.: +961.1.683530/1 Fax.: +961.1.683529 e-mail.: acousyst@inco.com.lb
DUCT SILENCER - TYPE ACS-F-P- 20/200
Pressure Drop in Pa
Face Velocity V ( m/s ) * 4 5 6 7 8 8.5 9.5 10 11 11.5
Pressure Drop ∆P ( Pa ) 15 25 35 50 60 75 85 100 110 125
Insertion loss in dB
Octave Band Center Frequency
Length - L(mm)
63 125 250 500 1K 2K 4K 8K
600 5 6 9 13 18 14 10 9
900 6 7 12 20 25 20 14 12
1200 6 9 14 25 33 25 18 15
1500 7 10 18 30 40 31 22 18
1800 8 11 20 35 48 37 26 21
2100 8 13 24 40 50 42 30 24
2400 9 15 26 45 50 48 34 27
2700 9 17 28 50 50 50 38 30
3000 10 19 30 50 50 50 42 33