Requirements
of NFPA 820:
The Standard for Fire Protection in WW
Treatment and Collection Facilities
• www.nfpa.org
– Available for sale
– Free viewer
• Purpose:
– Provide fire & explosion protection
for life, property, continuation of
operations, and environmental
protection
– Reduce or eliminate the effects of fire
or explosion
• Applies to:
– New construction
– Additions or modifications to existing
facilities
• Owner to perform risk assessment
• Retroactive?
– Does not normally apply to facilities
constructed before effective date of standard
(1995)
– AHJ (Authority Having Jurisdiction)
CAN apply standard retroactively if
unacceptable degree of risk determined
– Retroactive requirements can be modified if
AHJ considers requirements impractical and
“reasonable degree of safety” provided
• Guidance/Requirements Document
– 1990 – Recommended Practice
– 1995 – Became a Standard
– 2016 – Current Edition
• Next edition open for public input
– Chap. 1– Administration
– Chap. 2 – Referenced Standards
– Chap. 3 – Definitions
– Chap. 4 – Collection Systems
– Chap. 5 – WW - Liquid Stream Treatment
– Chap. 6 – WW - Solids Treatment
– Chap. 7 – Fire/Explosion Prevention/Protection
– Chap. 8 – Materials of Construction
– Chap. 9 – Ventilation
– Chap. 10 – Administrative Controls
2016 ISA WWAC Symposium
Aug 2-4, 2016 – Orlando, Florida, USA 10
NFPA 820 Contents - Annexes
• Class
– Class I – Flammable Gases/Vapors
– Class II – Combustible Dusts
– Class III – Ignitable Fibers
• Division*
– Division 1 – Gas/vapor always present or
can exist under normal conditions
– Division 2 – Gas/vapor present under
abnormal conditions only (leak, accident)
• Group
– Group A – Acetylene
– Group B – Hydrogen, . . .
– Group C – Ethylene, . . .
– Group D – Methane, Gasoline, . . .
– Group E – Metal Dusts
– Group F – Coal Dust, . . .
– Group G* – Grain, Wood, Fibers, . . .
• CLASSIFIED
– HEADWORKS (BAR SCREENS)
– GRIT REMOVAL
– (PRE-AERATION)
– PRIMARY SETTLING
– ODOR CONTROL
Primary Settling Tank
• UNCLASSIFIED
– AERATION TANKS/TRICKLING FILTERS
– SECONDARY & FINAL SETTLING TANKS
– (FILTRATION)
– DISINFECTION
– PLANT EFFLUENT
Trickling Filter
• CLASSIFIED
– SLUDGE HANDLING
– SLUDGE THICKENING
– SLUDGE CAKE STORAGE (< 6 a.c.*)
– SLUDGE CAKE CONVEYANCE (< 6 a.c.)
– (DIGESTERS)
– SKIMMINGS (SCUM)
– ODOR CONTROL SYSTEMS
*a.c. – air changes
2016 ISA WWAC Symposium
Aug 2-4, 2016 – Orlando, Florida, USA 21
NFPA 820
Solids Treatment
• UNCLASSIFIED
– SLUDGE DEWATERING (CENTRIFUGE)
– SLUDGE CAKE STORAGE (> 6 a.c.)
– SLUDGE CAKE CONVEYANCE (> 6 a.c.)
– SLUDGE CAKE INCINERATION
– SKIMMINGS INCINERATION
Centrifuge
• Recommendations
– Produce a set of classified area drawings
for your WW plants and collection facilities
– Plans & elevations
– Shading and cross hatching
– Don’t use color as a differentiator of areas
– Can be used for current and future projects
– Can see where classified areas may overlap
– Preferred over notes on drawings
• Recommendation
– Produce a set of classified area drawings for
your WW plants and collection facilities
– Site plans
– Elevations
– Shading and cross hatching
– Can be used for current and future projects
OR
2016 ISA WWAC Symposium
Aug 2-4, 2016 – Orlando, Florida, USA 26
NEC Area Classifications
• Lessons learned
– Don’t assume area classifications are correct
– Check for rated area extending beyond tank or
structure
– Check that ventilation supply air is from an
unclassified area
– Don’t assume ventilation rates are sufficient
– Don’t assume ratings of electrical equip. are
correct (enclosures, exhaust fans, HVAC)
Location