Sie sind auf Seite 1von 6

Feature Report

Pressure-Relief Unexpected high-


pressure situations can

System Design be relieved with a proper


relief-system design

Siddhartha Mukherjee failure. It is also required in systems should be limited to about 50% of the
Lurgi India Company Ltd. where a continuous flow of vapor or set pressure.
liquid is suddenly stopped by a down- Pilot operated: In such valves, the

P
ressure relief systems are vital stream blockage. main pressure-relief valve opens
in the chemical process indus- While a full description of the vari- through a pilot valve. Pilot operated
tries (CPI) for handling a wide ous causes of overpressurization is be- valves are used in the following cir-
variety of situations. They are yond the scope of this article, details cumstances: 1) The pressure-relief-
used to prevent pressurization above are provided by API [1]. The following valve set pressure is lower than 110%
a system’s design pressure; for vent- is a partial list: of the operating pressure and 2) when
ing during an unusual or emergency • Blocked outlet high back pressures are applicable.
situation; and for normal depressur- • Failure of control valve The opening of the valve is indepen-
ization during a shutdown, as exam- • Cooling water failure dent of back pressure.
ples. In some cases, such as when non- • Power failure
combustible gases including steam, • Instrument air failure Rupture disks
air and nitrogen are used, venting into • Heat-exchanger-tube failure A rupture disk is a pressure reliev-
the atmosphere may be an option. In • External fire ing device that is used for the same
other cases, such as those typically en- purpose as a relief valve, but a disk is
countered in the hydrocarbon sector, Safety relief valves a non-reclosing device — or in other
elaborate systems for the disposal of There are several types of safety re- words, once it is open it will not close.
vented gases may be required. lief valves available on the market, This means that whatever is in the
This article describes some of the including the following. system will continue to vent until
causes of overpressurization, the Conventional: Conventional pres- stopped by some form of intervention.
types of valves and rupture disks sure-relief valves are susceptible to The following are the applications of
that are available and some of the back pressure. Such valves are not rupture disks [3]:
components needed for a pressure recommended when the total back For quick action: Rupture disks
relief system. Example calculations pressure exceeds 10% of the set pres- are very fast acting. Therefore, they
are given, as well as a list of instal- sure. For systems operating at pres- are used in cases where relief valves
lation considerations. sures close to atmospheric or at low may not be fast enough to prevent a
pressures, the limit of 10% is rarely catastrophic failure. Some engineers
Causes of overpressurization achieved. Therefore, these valves find prefer to use rupture disks to prevent
An overpressurization may result application mainly in high-pressure heat-exchanger-tube ruptures because
from a single cause or a combination systems, or in systems that relieve to they are concerned that pressure relief
of events. Typically, not all causes the atmosphere (for example, steam valves would be too slow to prevent
will occur simultaneously. In case of and air). pressure build-up scenarios.
an external fire in vessels that pre- Balanced bellows: Balanced pres- To prevent plugging of relief
dominantly handle vapors, such as sure-relief valves are used when con- valves: In certain processes, the pro-
knockout drums, there may be a rapid ventional pressure-relief valves can- cess fluid contains solid particles that
temperature rise in the metal accom- not be used because of the reasons may cause blockage within a relief
panied with a rise in pressure due mentioned above. Such valves are valve, rendering it useless. In such
to expansion. In case of external fire not susceptible to back pressures as cases, a rupture disk is normally used
in vessels that contain liquids, there high as 50% of set pressure. The valve upstream of the relief valve. Purified
will be a rise in pressure as the liq- opening is independent of the back terephthallic acid plants (PTA) is a
uid vaporizes. Pressure may also pressure. At higher back pressures, typical application example.
rise abruptly due to thermal expan- these valves will still relieve at the set Handling highly viscous liquids:
sion when a blocked-in pipeline or point, but with a reduction in capac- In systems handling highly viscous
other equipment containing a liquid ity. Therefore, it is recommended that liquids, such as polymers, depressur-
is heated. Relieving pressure under if balanced pressure-relief valves are ization through a relief valve may be
these situations is essential to prevent to perform as rated, the back pressure too slow for a given situation. A rup-
40 Chemical Engineering www.che.com November 2008
Unit 01 Unit 02 Unit 03

01-PSV-01
01-PSV-02
01-PSV-03
01-PSV-04
01-PSV-05

02-PSV-01
02-PSV-02
02-PSV-03
02-PSV-04
02-PSV-05

03-PSV-01
03-PSV-02
03-PSV-03
03-PSV-04
03-PSV-05
Flare stack

Unit flare Unit flare Unit flare


K.O. drum K.O. drum K.O. drum

Battery limit Battery limit Battery limit


(unit 01) (unit 02) (unit 03)

Main flare header


Main flare
K.O. drum
Definition of Terms
Set pressure: The inlet gauge pressure at which the pressure relief valve is set to open
under service condition
Overpressure: The pressure increase over the set pressure of the relieving device ex-
pressed as a percentage FIGURE 1. A network of flare head-
Relieving pressure: The sum of the valve set pressure and the overpressure ers may be used in a complex process
Superimposed back pressure: The static pressure that exists at the outlet of a pressure
relief device at the time the device is required to operate. It is the result of the pressure in
the discharge system coming from other sources and may be constant or variable
(Figure 1) with a recommended mini-
Built-up back pressure: The increase in pressure in the discharge header that develops mum slope of 1:500. All unit flare
as a result of flow after the pressure relief device opens headers are continuously purged from
Back pressure: The pressure that develops at the outlet of a pressure relief device after the upstream end towards the respec-
the pressure relief device opens. It is the sum of the superimposed and the built-up back tive K.O. drums to avoid ingress of
pressures air into the system. Fuel gas, or inert
Abbreviations gases, such as nitrogen are typically
P1 Pressure at pipe inlet, kg/cm2a Mw Gas molecular weight, kg/kmol used as purge gas.
Unit-flare knockout drum: In cases
P2 Pressure at pipe outlet, kg/cm2a f Moody’s friction factor
where the discharge from a unit is ex-
W Gas flowrate, kg/h k Ratio of specific heats, Cp/Cv
pected to contain appreciable quanti-
Z Gas compressibility factor a Absolute pressure, as in kg/cm2a ties of liquids, especially corrosive,
T Gas temperature, K g Gauge pressure, as in kg/cm2g fouling and congealing liquids, a unit-
flare K.O. drum of a suitable size is
ture disk is the preferred choice. drocarbons are in use, the tail pipes mandatory. Another reason for requir-
Loss prevention: In systems han- are connected to a common flare ing such a drum may be that it is not
dling low-molecular-weight hydrocar- header, which is ultimately routed to feasible to have all headers continu-
bons, there is always a chance that a flare stack where the hydrocarbons ously slope toward the main-flare K.O.
some material will pass through the are burned. In many cases, the fluid drum. In this case, the unit flare head-
pressure relief valve into the flare relieved is toxic or flammable. In such ers are sloped toward the unit-flare
system — leading to material loss. In cases, it is mandatory to discharge K.O. drums. The vapors from these
such cases, a rupture disk is normally the gases through a closed disposal drums are then routed to the main
used upstream of the relief valve. system such as the flare. The flare flare header [2].
For economic reasons: Many pro- system converts the flammable va- Unit-flare K.O. drums are sized
cess industries use exotic materials, pors to less objectionable compounds to separate particles in the range
such as titanium and Hastelloy C. by combustion. of 300–600 microns, and hold liquid
In these cases, rather than having discharge for 5–10 min from a single
a pressure relief valve made of Has- Components of closed systems source. The liquid collected in these
telloy C, it may be cheaper to have a Pressure-relief valve-outlet pip- drums should preferably be drained
rupture disk made of Hastelloy C fol- ing: The flare system starts with out- by gravity to the blowdown drum. If
lowed by a stainless-steel pressure- let pipes from the various pressure re- a congealing type of liquid is likely to
relief valve. lief valves of a unit. These valves are be discharged, the drums should be
piped together to a common unit-flare heat traced or provided with steam
Pressure relief systems header, which is routed to the unit- coils [2].
Open and closed systems flare knockout (K.O.) drum. Main flare header: The main flare
In cases where non-hazardous fluids Unit flare header: Discharge pipes header receives discharge through in-
are used, such as steam, water and air, from the pressure relief valves in in- dividual unit-flare headers, or through
a typical pressure-relief system con- dividual units are connected to the unit-flare K.O. drums. The flare header
sists of several pressure relief valves respective unit-flare headers. These should not have pockets and should be
that discharge through short tail pipes headers are either connected directly free draining toward the nearest K.O.
to the atmosphere. These systems are to the main flare header, or are routed drum, typically with a slope of 1:500.
termed open disposal systems. to the flare K.O. drums, which in turn Although flare headers are nor-
When hazardous fluids, such as hy- are connected to the main flare header mally sized based on pressure drop,
Chemical Engineering www.che.com November 2008 41
Feature Report

Table 1. Relief Load Summary


Relief load, kg/h

PSV-06

PSV-05

PSV-04

PSV-03

PSV-02

PSV-01
To main flare
Relief Valve Cooling External K.O. drum
Tag No. water failure fire 

12,960 kg/h

14,076 kg/h
10,536 kg/h

12,870 kg/h
PSV-01 12,870 13,453
PSV-02   6,750
PSV-03 10,536 9,872
PSV-04 14,076 8,970 D 28,012 kg/h C 69,356 kg/h B 95,648 kg/h A
Unit flare
PSV-05   5,783
header
15,052 kg/h

16,732 kg/h

13,422 kg/h
PSV-06 12,960 11,423

Main flare
header
PSV-07 15,052 6,432
PSV-08   5,764
PSV-09 16,732 8,976
PSV-07

PSV-08

PSV-09

PSV-10

PSV-11

PSV-12
PSV-10   7,432
PSV-11 13,422 5,133
PSV-12   9,984
FIGURE 2. This sketch of a typical flare system is used as the basis for the sample
Total load 95,648  
calculations explained in the given example

velocity cannot be ignored. A Mach drums protect against flame flash- than the overpressure, it will tend to
number in the range of 0.2–0.5 is back from the flare tip. The seal drum close the valve. Therefore, proper siz-
recommended. The third criterion should have a diameter of at least two ing of discharge pipes is very impor-
that should be checked is the change times the flare pipe diameter [1]. tant in such systems.
in density of flare gases along the Flare stack: Flare stacks are usually Discharge piping and manifolds
length of the flare header. In many elevated structures designed to burn are sized for the contingency that
cases where flare discharges are at flammable vapors. produces the largest relief load. Pipe
high temperatures, the flare gases sizing is carried out by working back-
cool down due to the length of the Relief system piping ward from the battery limit of the
flare header. This leads to an increase Inlet piping: The inlet piping from unit flare header up to the outlet of
in density and, correspondingly, a de- the protected equipment to the pres- individual, pressure safety valves.
crease in flowrates. Therefore, while sure relief valve should be sized to The superimposed back pressure of
estimating pressure drops in such prevent excessive pressure loss that the flare header at the battery limit
flare lines, it is a good idea to divide can cause chattering with consequent is defined. Thereafter, based on the
the header into sections and estimate reduction in flow and damage to seat- relief loads, pressure drop calcula-
pressure drops separately. ing surfaces. The recommended prac- tions are carried out to arrive at the
Main-flare knockout drum: In ad- tice is to limit the total pressure drop back pressure of the individual, pres-
dition to the unit-flare K.O. drum, a in the inlet piping to 3% of the safety- sure relief valves. In the course of
main-flare K.O. drum close to the flare valve set pressure [1]. The piping is the calculations, two parameters are
stack should be provided. This takes designed to drain towards the pro- checked for compliance:
care of condensation in the header tected vessel. • The Mach number at each pipe sec-
that results from atmospheric cooling. Discharge piping: In case of over- tion should not exceed 0.5
Similar to the unit-flare K.O. drums, pressurization in a vessel, the rel- • The back pressure at each safety
these drums are also sized to separate evant pressure-relief valve will start valve should not exceed 30–50% of
out liquid droplets of 300–600 microns to open at the set pressure. At this the set pressure
in size, and for holdup of 20–30 min [1] moment, the downstream pressure at The isothermal flow equation based
of liquid release. Pumps are installed the valve is the superimposed back on the outlet Mach number is given by
with the K.O. drum to transport any pressure of the system. The valve API [1]. This method calculates pres-
collected liquid to a safe location. The keeps opening as the pressure builds sure buildup backward up to the out-
pumping capacity should allow the up. The resultant flow creates a built- let of relief valves, thus avoiding the
liquid holdup to be emptied in 15–20 up back pressure on the discharge need for trial and error methods:
min. When congealing liquids are in pipe. As long as the built-up back
use, the drums should be provided pressure is less than the overpres-
with steam coils [2]. sure after the valve opens, the valve
Seal drum: Seal drums are located will remain open and perform satis-
close to the flare stack or are sometimes factorily. If however, the built-up back  (1a)
integral with the flare stack. These pressure develops at a rate greater or,
42 Chemical Engineering www.che.com November 2008
Table 2. Flare Discharge Piping Calculations
Segment Set Line Line Flow- Pres- Den- Rough- Pipe No. of No. of No. of Pres- Pres- % of Mach
pres- size size rate sure sity ness length tees valves elbows sure sure set no.
sure P2 factor P1 P1 pres-
sure
kg/ m in. kg/h kg/ kg/m3 mm m kg/ kg/
cm2g cm2a cm2a cm2g
A to B 0.30 12 95,648 1.5000 4.2899 0.1 15 0 1 0 1.6234 0.5904 0.4004
B to PSV-01 5.0 0.10 4 12,870 1.6234 4.6428 0.1 30 0 1 3 2.7780 1.745 34.9 0.4480
B to PSV-11 5.0 0.15 6 13,422 1.6234 4.6428 0.1 30 0 1 3 1.8282 0.7952 15.9 0.2077

B to C 0.25 10 69,356 1.6234 4.6428 0.1 15 0 0 0 1.7528 0.7198 0.3863


C to PSV-03 5.0 0.15 6 10,536 1.7528 5.0129 0.1 30 0 1 3 1.8712 0.8382 16.8 0.1510
C to PSV-04 5.0 0.15 6 14,076 1.7528 5.0129 0.1 30 0 1 3 1.9616 0.9286 18.6 0.2017
C to PSV-09 5.0 0.15 6 16,732 1.7528 5.0129 0.1 30 0 1 3 2.0449 1.0119 20.2 0.2398

C to D 0.20 8 28,012 1.7528 5.0129 0.1 15 0 0 0 1.8111 0.7781 0.2258


D to PSV-06 5.0 0.15 6 12,960 1.8111 5.1796 0.1 30 0 1 3 1.9832 0.9502 19.0 0.1797
D to PSV-07 5.0 0.15 6 15,052 1.8111 5.1796 0.1 30 0 1 3 2.0417 1.0087 20.2 0.2088

B. Likewise, segment 2 is a section of 3.293 x 10–7 (95,648/(1.5 x 0.302)) x


the flare header between points B and (0.95 x 373/1.4 x 86)0.5 = 0.4003
 (1b) C. Let us assume a superimposed back
pressure at point A of 1.5 kg/cm2 a. Fanning’s friction factor (to be solved
The Mach number at the outlet of by iteration):
each pipe section is given as follows Piping between points A and B  1/√f = –4log[ε/(3.7D) + 1.256/(NRe√f)]
[1]: Data  = 0.0038
Flowrate: 95,648 kg/h (Table 1) Moody’s friction factor: 4 x 0.0038
Pressure at point A, P2: 1.5 kg/cm2a = 0.0152
Molecular weight of vapor, Mw: 86
Temperature of vapor: 100°C Equivalent length: 17.8 m
 (2) Straight length of pipe : 15 m fL/D: 0.0152 x 17.8/0.3
In the next section, a solved example Number of elbows: 0 Using Equation (1b), P1/P2 is calcu-
illustrates the procedure. Number of valves: 1 lated to be: 1.08226
Number of tees: 0 P1: 1.08226 x 1.5
Example Compressibility factor: 0.95 = 1.6234 kg/cm2a
An extractive distillation plant has Ratio of specific heats, Cp/Cv: 1.4 Hence, the pressure at point B is
twelve safety valves. There are two Viscosity: 0.000009 kg/m s 1.6234 kg/cm2a
major relief scenarios: cooling water
failure and external fire. Table 1 sum- Roughness factor, ε: Piping between point B and
marizes the relief rates under these 0.0001m (0.1 mm) PSV-01, 1st trial
two conditions. The governing case is Pipe diameter, D (assumed): Data
the cooling water failure because it 0.30 m (12 in.) Set pressure of PSV-01: 5.0 kg/cm2g
occurs plant wide. External fire oc- Flowrate: 12,870 kg/h (Table 1)
curs only at localized areas and the Calculations Pressure at point B, P2:
relief loads come from only a couple Density of vapor: PMw/ZRT 1.6234 kg/cm2a
of safety valves. Hence, we will con-  = 4.2899 kg/m3 Molecular weight of vapor Mw: 86
sider the cooling water failure case Volumetric flowrate: Temperature of vapor: 100°C
here. For simplicity, we will assume 95,648/(4.2899 x 3,600) = 6.193 m3/s Straight length of pipe: 30 m
that set pressures of all safety valves Velocity in pipe: 6.193 x 4/(π x (0.30)2) Number of elbows: 3
are 5.0 kg/cm2 g. = 87.61 m/s Number of valves: 1
The flare network is divided into Reynolds number, NRe: Number of tees: 0
segments as shown in Figure 2. Seg-  0.30 x 87.61 x 4.2899/0.000009 Compressibility factor: 0.95
ment 1 is a section of the flare header = 12,528,371 Ratio of specific heats, Cp/Cv: 1.4
between the battery limit A and point Outlet Mach Number, M2: Viscosity: 0.000009 kg/m s
Chemical Engineering www.che.com November 2008 43
Feature Report
Safety valve
Roughness factor, ε: Moody’s friction factor: 0.0196
 0.0001m (0.1 mm) Equivalent length: 43.31 m
Pipe diameter, D (assumed): P1/P2: 1.71121
0.08 m (3 in.) P1: 2.7780 kg/cm2a Column
outlet line
Hence, the back pressure at PSV-01 is
Calculations 2.7780 kg/cm2a, or 1.745 kg/cm2g. Safety
 (detailed steps not repeated) The ratio of the back pressure to valve
Density of vapor: 4.6428 kg/m3 the set pressure for PSV-01 is 34.90%, outlet line
Volumetric flowrate: 0.7700 m/s which is acceptable. The Mach num-
Velocity in pipe: 153.186 m/s ber is 0.4480, which is also within ac-
Reynolds number, NRe: 6,321,901 ceptable limits. Column
Outlet Mach number: 0.6998 A summary of parameters and cal-
Fanning’s friction factor: 0.0052 culation results is given in Table 2.
Moody’s friction factor: 0.0208
Equivalent length: 40.65 m Installation features
P1/P2: 2.67214 Correct installation of relief valves
P1: 4.3380 kg/cm2a and the associated relief system is
Hence, the back pressure at PSV-01 is very important for their proper opera-
4.3380 kg/cm2a, or 3.3050 kg/cm2g. tion during upsets to ensure the safety
The ratio of the back pressure to of personnel and the plant. Some use-
the set pressure for PSV-01 works out ful guidelines follow:
to 66.10% which is more than that • Pressure relief valves should be
recommend for balanced bellow-type connected to the vapor space of the FIGURE 3. In order to make relief
valves. In addition, the Mach number protected equipment valves self-draining to the flare header,
is 0.6998, which is greater than the • The inlet line should be self drain- it is recommended that they be in-
stalled at a high point in the system
recommended limit of 0.5. Therefore, ing back to the process vessel. This
we need to increase the line size in the is to prevent accumulation of liquid the “A” valve has been isolated, the
stretch between B and PSV-01. Let us that can corrode or block the sys- section between the isolation valve
now select a line size of 4 in. for the tem. Likewise, the outlet line from and the pressure relief valve is still
second trial. the pressure relief valve should be at the operating pressure of the col-
self-draining to the flare header. To umn. The bleeder is used to depres-
Piping between point B and meet this requirement, it is recom- surize this section before the valve
PSV-01, 2nd trial mended that relief valves are in- is removed from the line, otherwise
Data stalled at a high point in the sys- it could be an unsafe condition for
Set pressure of PSV-01: 5.0 kg/cm2g tem (Figure 3) maintenance personnel [4]
Flowrate: 12,870 kg/h • For reliable overpressure protection • Whenever two pressure relief
Pressure at point B, P2: it is best to install pressure relief valves are provided, it is mandatory
1.6234 kg/cm2a valves without any isolation valves. that a mechanical interlock system
Molecular weight of vapor, Mw: 86 However, pressure relief valves is installed between the respective
Temperature of vapor: 100°C sometimes do not reseat properly isolation valves to ensure that one
Straight length of pipe: 30 m and start to leak. Therefore, in many of the isolation valves is open at all
Number of elbows: 3 cases, two safety valves are installed times. This is to eliminate opera-
Number of valves: 1 to allow replacement of relief valves tor error, which might mistakenly
Number of tees: 0 that are leaking while the plant is create a situation where both the
Compressibility factor: 0.95 in operation. This also facilitates isolation valves are in the closed
Ratio of specific heats, Cp/Cv: 1.4 testing and servicing of relief valves position, leading to unavailability
Viscosity: 0.000009 kg/m s regularly without interrupting plant of either of the relief valves for any
Roughness factor, ε: operations particular equipment
0.0001m (0.1 mm) • Whenever two pressure relief valves • Pressure relief valves in steam,
Pipe diameter, D (assumed): are installed as mentioned above, water or air service are connected
0.10 m (4 in.) isolation valves are provided for each to the atmosphere through a short
Calculations relief valve (Figure 4). This is to fa- vertical pipe. To keep this pipe free
 (detailed steps not repeated) cilitate isolation of the “A” valve for from liquid accumulation, a small
Density of vapor: 4.6428 kg/m3 maintenance while taking valve “B” weep hole is drilled at the lowest
Volumetric flowrate: 0.7700 m/s online when required. In such cases, a point of this pipe
Velocity in pipe: 98.03 m/s ¾-in. bleeder valve with an isolation • Whenever a rupture disk is installed
Reynolds number, NRe: 5,057,041 valve is recommended in between the upstream of a pressure relief valve,
Outlet Mach Number: 0.4480 isolation valve and the pressure relief it is important to have a pressure
Fanning’s friction factor: 0.0049 valve. This is needed because when indicator in the section between the
44 Chemical Engineering www.che.com November 2008
Outlet piping
Pressure Isolation
relief valve valve

3/4"
Bleeder valve Isolation
valves Blind

Bypass
line

Inlet
piping

Protected vessel

FIGURE 4. When two pressure relief


valves are used, isolation and bleeder

THE REFERENCE
valves are needed to prevent an unsafe
condition
Relief valve

FOR
Pressure
two (Figure 5). The reason for this gage
is that in case of a pin-hole leak in
the disk, vapors from the protected Protected

HYDROGENATION
equipment would pass through to vessel Rupture disk
the section between the disk and
the safety valve. After some time,
the pressures upstream and down-
stream of the disk would be the same BIAZZI is specialized in hydro-
and the disk would never burst
• The unit and the main flare header genation and other gas-liquid
FIGURE 5. When a rupture disk is
should slope towards the main,
flare-header K.O. drum. This is to
installed upstream of a pressure relief reactions. Reactors and com-
valve, a pressure indicator is needed be-
ensure that condensed vapors, if tween the two plete plants from 10 litres to
any, do not back up and accumulate
immediately downstream of the Author 50 m3 and from 5 to 250 bar.
safety valves ■ Siddhartha Mukherjee is the
Edited by Dorothy Lozowski group leader – process, at Lurgi Full scale-up guarantee for
India Company Ltd. (A-30,

References
Mohan Cooperative Industrial
Estate, Mathura Road, New any plant size.
Delhi 110 044, India. Phone:
1. A Guide for Pressure-Relieving and Depres- +91–11–4259–5365; Fax:
surizing Systems, API Recommended Prac- +91–11–4259–5051; E-mail:
tice 521, American Petroleum Institute, 4th
ed., March 1997.
2. Process Design and Operating Philosophies
siddhartha.mukherjee@lurgi.
com). For the past eight years,
he has been involved in a lead
www.biazzi.com
role in the design, precom-
on Pressure Relief and Disposal Systems, missioning and commissioning of chemical and
Oil Industry Safety Directorate, OISD- petrochemical plants in India and elsewhere. He
Standard-106, Government of India, August has also been involved in inorganic and olech-
1999. emistry while at Lurgi. Prior to this, Mukher-
3. Leckner, Philip, Rupture Disks for Process jee worked as an environmental engineer with
Engineers Part-1, www.cheresources.com/ Development Consultants Ltd. (Kolkata), doing
asiseeit3.shtml various environmental assessment projects in-
4. Sizing, Selection and Installation of Pres- volving thermal power plants. Mukherjee earned
his B.Tech. and Ph.D. Ch.E. degrees from the
sure - Relieving Devices in Refineries, Part
Indian Institute of Technology, Kharagpur. He PROJECT S AND PL ANT S
II – Installation, API Recommended Practice
520, American Petroleum Institute, 4th ed., holds lifetime memberships in India’s Institute
of Engineers and the Indian Institute of Chemi-
FOR THE CHEMIC AL INDUS TRY
December 1994.
cal Engineers.
BIAZZI SA - CH-1816 Chailly/Montreux - Switzerland
Circle 33 on p. 66 or go to Phone: + 41 21 989 21 21 - Fax: + 41 21 989 21 20
adlinks.che.com/7378-33 E-mail: general@biazzi.com

Das könnte Ihnen auch gefallen