1. DELCOS 3100 electronics
M
DELCOS
3100
3
M 1 2
1 2 3
87°C 12.8 BAR 12.5 BAR
ON-LOAD
C MENU
Fig. 1
1.1.1 Keyboard
=> Switches the system on Clear text field: => 1st line: Indication of final tempera-
ture/final compression pres-
=> Switches the system off sure/line pressure
=> 2nd line: Status display (operating
mode)
=> Acknowledgement key
=> in the menu: Input mode interrupted MENU
=> Opens/closes the menu
(previous value is restored)
C => Input of an access code which pro-
tects various menu items
4
1. DELCOS 3100 electronics
1 2 3
87°C 12.8 BAR 12.5 BAR
ON-LOAD
b c d e f g h
Fig. 2
LED a => flashing: The system is in the stand- LED e => flashing: In timer control mode
by mode, i.e. the motor can Compressor OFF
start up automatically at any
on: In timer control mode
time.
Compressor ON
on: The drive motor is running
Messages:
LED b => The operator is within the menu
LED c => Automatic restart is switched ON LED f => Maintenance interval elapsed
LED g => Warning
LED d => flashing: Remote control, remote off LED h => Collective fault
on: Remote control, remote on
5
1. DELCOS 3100 electronics
1.1.3 Language selection 1.1.5 Clear text field - Line 2 status display
DELCOS 3100 is provided in 17 languages. You can The 2nd line of the clear text field shows the relevant
change from one language to the other by pressing status of the machine, which can be overwritten per-
keys [ ↵ ] and [ Θ ] simultaneously. The internationally manently in the case of faults or cyclically in the case
valid, national symbols show the current configuration. of warnings or maintenance.
Note
The status displays listed below have the following
The change-over of language is not possible within meaning:
the menu status (LED b => OFF).
In the English display variant you can select °C, bar
or °F,PSI. READY TO START
alternating with
Line pressure display The unit has been switched on in the "timer
control" operating mode - OPTION - (stand-
This indicates the actual mains pressure. by). The enable signal from the timer is not
yet available.
alternating with
6
1. DELCOS 3100 electronics
Motor starts up
OFF-LOAD
ON-LOAD
7
8
MENU
CUT-OUT POINT 13.0 bar/188 psi 12! EXT FAULT 11438 h Weekday Date Time
TOTAL RUNNING 12435 h 2! COMP TEMP 9877 h
CUT-IN POINT 12.5 bar/181 psi SA 29.05.2005 13:55:14
LOADED HOURS 10987 h 4 HIGH TEMP 9476 h
AUTOMATIC OPERATION [SA 05/29/2005 13:55:14]
AIR FILTER IN ------- h 18! EM-STOP 4867 h 1: _______00:00 00:00
REMOTE CONTROL ON
OIL FILTER IN 9999 h 6! MOTOR TEMP 4310 h 2: _______00:00 00:00
TIMER CONTROL OFF *
SEPARATOR IN 0h 5! MOTOR TEMP 4310 h 3: _______00:00 00:00
AUTO RESTART OFF
OIL CHANGE IN -385 h 2! SENSOR B2 88 h 4: _______00:00 00:00
POWER LOSS TIME 1.5 s
1. DELCOS 3100 electronics
p
2
CUT-OUT POINT: 13.0 bar/188 psi
p
[OPTIONAL INPUTS] [BASE LOAD SELECT] * 2
CUT-IN POINT: 12,5 bar/181 psi
[LIMIT VALUES]
DESIGN PRESS 13.0 bar/ 188 psi OPTION 1 DISCH TEMP AUTO CHANGE OVER ON
START PROTECT 0.8 bar/ 11 psi OPTION 2 EXT FAULT OPERATION Aus
HEAVY STARTUP 2.0 bar/ 29 psi OPTION 3 FREE CUT-OUT POINT 13.0 bar/188 psi
FINAL TEMP WARN110 °C / 230 °F CUT-IN POINT 12,5 bar/181 psi
FINAL TEMP MAX 120 °C / 248 °F BASE LOAD COMP 1
MIN START TEMP 1 °C / 34 °F 123h K2 K3 K4 k5 k1
RUN-ON TIME 360 s CHANGEOVER TIME 24h
SOFT STOP 30 s QUANT. SLAVES 4
STAR/DELTA TIME 8s QUANT. RESERVE 0
SOFTWARE: SD31V2.00 START DELAY 5s
LOAD NET IN 15min
VOLUME OF NET 20%
* (Option)
1. DELCOS 3100 electronics
Two minutes after the last key operation, the menu Shutdowns (faults) are identified with an "!", whereas
is quit automatically. for warnings the "!" is not displayed.
Note
For further information, see chapter 1.3.9., [FAULT
MEMORY].
9
1. DELCOS 3100 electronics
Two minutes after the last key operation, the menu is If the unit is to be switched on and off via the timer
quit automatically. control, you have to activate [TIMER CONTROL ON] in
the [CONTROL MENU] and put the unit into operation
1.2.5 Menu [OPTIONAL INPUTS] (switch on).
The menu heading [OPTIONAL INPUTS] is provided In order to set the timer or the pressure change-over,
in the form of optional software. You can have the indi- move to the menu item [TIMER] using the keys and
vidual additional monitoring features optionally installed. . Here, you can select/deactivate the individual param-
eters with the help of keys and .
Move to the [OPTIONAL INPUTS] menu using keys
and . Here, you can allocate three reserve in-
puts. You simply have to state, which monitoring func-
tion has been assigned to which input. Inputs, which Basic clock setting:
are identified as [FREE], are not activated/monitored.
Example: [SA 29.01.94 13:55:14] /
You can call up the individual parameters using keys
[SA 01/29/94 13:55:14]
and .
• Press key , the day of the week [SA] flashes
One allocation from the following list can be selected
• Re-set the day of the week using the keys and
for each input:
10
1. DELCOS 3100 electronics
The setting procedure of a timer clock can be inter- Timer Menu [BASE LOAD SELECT]
rupted at any time by pressing key . The previous block [OPERATION OFF]
setting will then be restored. p21.. p27
Not active The speed-controlled compressor
Example 1: operates within the pressure range set in
the menu [CONTROL]
With a working time from:
Active The speed-controlled compressor
Sunday 22:00 to Saturday 14:00 h, operates within the second pressure range
set in the menu [TIMER]
with a break - daily - from:
11
1. DELCOS 3100 electronics
During the pressure reduction the values for 1.2.8 Locking/unlocking of the code
[ CUT-OUT POINT ] and [ CUT-IN POINT ] In order to avoid unauthorized programming, the set-
tings can be protected by means of a code. The limit
are dispayed unchanged in the menu [CONTROL]. values, which are set in the factory, cannot be changed
The reduction times and the reduction pressure are by the operator.
adjusted in analogy to the timer setting.
When a timer block of pressure changeover is active, Locking
the symbol p2 flashes in the upper line before the indica-
If the code is to be locked, press key C . Then, the fol-
tion of the current line pressure.
lowing message appears:
Two minutes after the last key operation, the menu With a wrong code input, the following message will
is quit automatically. appear:
Danger.
During programming in the stand-by mode, the
machine can start up at any time. Unlocking
If the code (see chapter 1.2.8.) is unlocked, any The code can be unlocked again by:
value, except the [LIMIT VALUES] can be changed at
any time without the code inquiry. • pressing key C or
Move to the value to be changed using keys and • pressing key and by trying to change a protected
. Now press key in order to change to the input value.
mode. If the code has not yet been unlocked, the code
inquiry will appear. When the input mode is activated, The code inquiry will then appear:
the value will flash.
"CODE: LOCK" (for 1 second)
Note
In the input mode, keys and are inactive. "CODE INPUT: 0000" (value is flashing)
After having entered the new value with the keys Here, you have to enter CODE: [3031].
and , this new value must be acknowledged by
If the code input is correct, the following message ap-
pressing key . The display stops flashing, and a pears:
new menu item can be selected.
"CODE: UNLOCK" (for 1 second)
In the input mode, you can restore the original setting
and at the same time exit the input mode by pressing If the input was incorrect, the following message ap-
key . pears:
12
1. DELCOS 3100 electronics
the unit goes into the stand-by mode for the time be-
ing (ON-key flashes).
* OPTION
13
1. DELCOS 3100 electronics
The unit is set to automatic operation in the factory. Ignoring warnings can result in malfunction.
This means that the compressor supplies compressed
air and stops (stand-by) depending on the
1.3.6 Maintenance
consumption.
Maintenance messages are signalled by LED f, but will
If your compressed air mains has a low or even no not lead to a shutdown of the compressor and are also
consumption at all for a certain period of time, the unit not entered into the fault log.
automatically changes over to the idle running mode.
When a maintenance interval has elapsed, i.e. has
During the idle running phase, cooling (ventilator/ reached 0 h (hours), the clear text field displays the
cooling water) is switched off automatically dependent message [MAINTENANCE ELAPSED]. The elapsed
on the temperature. maintenance interval can be determined in the [MAIN-
TENANCE SCHED.] (see 1.2.1.).
When the running-on phase (idle running in the auto-
matic operating mode) is over, the motor is switched Ignoring maintenance intervals can result in malfunc-
off after the pre-selected running-on time and the com- tion (see chapter 1.5 Maintenance intervals).
pressor changes to the stand-by mode. The remaining
[RUN-ON TIME] is indicated in the clear text field.
14
1. DELCOS 3100 electronics
Example:
Explanation:
15
1. DELCOS 3100 electronics
1.4 Fault table DELCOS 3100 in the case 7. When retrofitting switch equipment, the power
control transformers must not be "tapped" under
of a fault or warning any circumstances, since this can result in
overloading.
1.4.1 Check list
Generally, loosened connections and plug-in connec- 8. Always use CompAir spare parts.
tors, defective power supplies or the non-observance of
installation instructions result in a variety of faults. The 9. Never connect additional switch or measuring
fault messages displayed can therefore often be traced equipment without CompAir's prior permission.
back to different causes.
10. Never relocate measuring transducers away from
For this reason, please always observe the following the unit.
check list:
11. In the case of queries, please have the following
1. The supply voltage to the unit must always be within information on hand so that we can provide quick
the permissible limits. and specific support:
2. If required, the control power transformer must be - Type of unit / serial no.
adjusted to suit local nominal voltages (see electric - Order no.
circuit diagram).
- Circuit diagram for drawing no. and Id no.
3. The switch cabinet temparature must not exceed - Information regarding the operating conditions of
55°C. the unit
- Information regarding the accessories retrofitted
4. Without a coupling relay, the line length of retrofitted by yourselves (remote controls, etc.)
remote controls (remote on/off, remote on-load/off- - Other subsequent modifications or attachments
load) must not exceed 20 m from the switch cabinet. to the unit
5. During commissioning and when carrying out - The exact description of the fault
maintenance work, check that all terminal screws are
tightened and all connectors fit properly.
6. The power supply cabling must have a sufficient 1.4.2 Table of faults/warnings
cross-section. Therefore, the installation On the following pages you will find the fault table
requirements, the line length and the expected DELCOS 3100 with possible causes and remedies
conductor temperatures must be taken into account
when selecting the cable(s).
16
1. DELCOS 3100 electronics
17
1. DELCOS 3100 electronics
18
1. DELCOS 3100 electronics
[[WARNING Input 1] One of the reserve inputs 1..3 was Check.appropriate input allocation (3)
[[WARNING Input 2] triggered, but is programmed as [Free].
[[WARNING Input 3]
[Malfunction: Power supply 20V controller transformer supply failed Check controller transformer and fuses
20V]
[COMPAIR] [SETUP- Hardware fault in DELCOS DELCOS electronics has to be replaced;
CODE 1: ___?] stopgap measure: Enter setup codes,
check all settings and, if required, re-set
(2)(3)(4)(5)
A fault/warning cannot be The fault/warning is still present Search for cause and rectify
acknowledged
No display No voltage to the machine Fix power supply, check fuses
– DELCOS control voltage (10 VAC) not Check fuses, if required, replace
applied
Pressure and temperature – DELCOS control voltage (20 VAC) not Check fuses, if required, replace
display failed, Display (----) applied
Unit does not restart – Function „Automatic restart“ not – Switch on (4)
automatically after power activated
failure
– Power failure lasted too long (4) –
Unit is permanently running Operating mode [CONTINUOUS Select [AUTOMATIC OPERATION]
in the idle mode without OPERATION] selected (4)
changing automatically over
to the stand-by mode
Very short pressure requirements during –
the running-on phase
No compressed air supply – External on-load/off-load control - Off- –
within the set switching peak reduction phase (5) activated
points (4) (OPTION)
19
1. DELCOS 3100 electronics
Moreover, a shutdown can be activated/deactivated To activate the input "remote control ON/OFF" (termi-
for maintenance intervals, if a maintenance interval nals X3.25/X3.26) you have to select [REMOTE CON-
has counted down to -100 hours. If one of the intervals TROL ON] in the [CONTROL MENU]].
has reached this shutdown threshold, the shutdown is * During [REMOTE CONTROL ON] LED d is on and
triggered off by the collective fault LED h, which acts in key [ I ] and key [O] of the compressor are locked.
addition to LED f. The message [FAULT MAINTE- * For starting the unit, the control requires a REMOTE
NANCE] is present in the fault memory as well as in ON edge at the Remote ON/OFF input.
the clear text field.
* The unit is operating as long as the remote ON/OFF
input is closed.
After having carried out the maintenance work, re-
* The unit stops when the remote ON/OFF input is
program the maintenance interval and then acknowl-
opened.
edge - for a restart - the [FAULT MAINTENANCE] by
* When the unit was switched on manually and the op-
pressing key [Θ].
erating mode is changed over to [REMOTE CON-
TROL ON] it remains in operation as long as the re-
mote ON/OFF input is closed.
* When the remote mode is switched off [REMOTE
CONTROL OFF], the unit remains switched ON or
OFF.
20
1. DELCOS 3100 electronics
1.6.3 Remote control (on-load/off-load) * In the normal operating mode, the on-load/off-load
control (1) of the compressor is exlusively controlled
Important via the internal electronic pressure switch (2) of the
Only potential-free contacts may be connected to unit. The switching points of the internal electronic
the terminal strip. External voltages result in the pressure switch (2) can be programmed in the [CON-
destruction of DELCOS 3100. TROL MENU] with the parameters [CUT-OUT
The distance between potential-free contacts and POINT] and [CUT-IN POINT].
the terminal strip must not exceed 20 metres. If re- * The external potential-free contact (3) is connected
quired, install coupling relays in the control cabi- in parallel to the internal pressure control (2).
net. * A safety circuit (4) interrupts the function of the exter-
nal potential-free contact (3), if you tried to operate
Danger. the unit at a pressure of 0.5bar/7psi above the nomi-
nal operating pressure. The display shows the mes-
In this operating mode, the compressor can start sage [WARNING: LINE PRESS] as long as the ex-
up automatically at any time! ternal potential-free contact (3) is deactivated. After
you have acknowledged the [WARNING: LINE
The control offers the possibility of switching the PRESS], the external potential-free contact (3) is
compressor externally to on-load and off-load again enabled.
operation via the connection of a potential-free contact.
4 2 p
1.6.4 Remote control (on-load mode ena-
ble)
X3.23
Important
3 Only potential-free contacts may be connected to
the terminal strip. External voltages result in the
X3.24 destruction of DELCOS 3100.
The distance between potential-free contacts and
1
the terminal strip must not exceed 20 metres. If re-
quired, install coupling relays in the control cabi-
net.
21
1. DELCOS 3100 electronics
Operating principle: You can combine this procedure with that described in
chapter 1.6.3.
Example:
2 p
4 2 p
X3.23
6
6
5
X3.24
1
3
Fig. 4
8
Legend:
Fig. 5
(1) On-load/off-load control of the compressor
(2) Internal electronic pressure switch; for the setting, Legend:
see [CONTROL MENU]
(5) Enable switch or external potential-free contact for (3) Load requirement by the higher-level control
remote load (7) Active signal of the higher-level control
(6) Terminals (8) Higher-level control
* During normal operation, the on-load/off-load control * In the example shown here, a higher-level control (8)
(1) of the compressor is controlled exclusively via the was connected to DELCOS 3100.
internal electronic pressure switch (2) of the unit. The * In the case of a failure of the control (8), contact (7)
switching points of the internal electronic pressure is used to switch DELCOS 3100 over to internal op-
switch (2) can be programmed in the [CONTROL eration (as illustrated above).
MENU] with the parameters [CUT-OUT POINT] and * When the higher-level control (8) is active and not
[CUT-IN POINT]. faulty, it withdraws the load enable from DELCOS
* Program one of the three programmable inputs for 3100 via contact (7) and then controls the compres-
the function [OPERATE_B1] in the menu sor autarkically via the own load requirement (3).
[OPTIONAL INPUTS]. Due to this, the selected input
with terminals (6) is now connected in series with the 1.6.5 Automatic restart after power failure
internal electronic pressure switch (2).
* Connect the external switch (5) to terminals (6). Danger.
In this operating mode, the compressor can start
Assignment of terminals (6) depending on the selected up automatically at any time !
input:
[OPTION 1] Terminals X3.15/X3.18 You can activate or deactivate [AUTO RESTART] in
[OPTION 2] Terminals X3.16/X3.19 the [CONTROL MENU] (see chapter 1.2.2).
[OPTION 3] Terminals X3.17/X3.20 After a power failure, which has not taken longer than
approx. 1.5 seconds, the compressor is automatically
Note restarted, provided that it was switched on before the
As a result of the series connection of the two pres- power failure occurred, i.e. it was in operation or in the
sure switches (2) + (5) the setting of the internal elec- stand-by mode.
tronic pressure switch (2) may have to be increased in Failures of a duration of more than 1.5 seconds trig-
the [CONTROL MENU]. ger off the message [POWER LOSS], and [AUTO RE-
START] does not take place.
With a clock timer OPTION installed, the menu item
[POWER LOSS TIME] (see chapter 1.2.2.) can be pro-
grammed to 2 to 999 seconds.
22
1. DELCOS 3100 electronics
23
2. Base load selection circuit DELCOS 3100
2.1 Overview
The base load selection circuit (BLS) can be adjusted under menu item [BASE LOAD SELECT]. The BLS is an independent
part of the normal compressor control of the master. It merely requires the following information from the master:
• Current line pressure
• Setting of the timer
It is therefore irrelevant, in which status the master machine is. The master can be switched off or even faulty. Only the
following events result in a failure of the BLS:
• Master without power supply
• Fault: pressure sensor
• Warning: MS-Bus: A06 (relay module for controlling the slaves failed)
The terms below are used in the following description:
BLS: Base load selection circuit
BLS series: Order of compressors referred to the given line pressure switching points.
Slave: Compressors K2 .. K5, which are switched to the on-load mode by a relay module.
Relay module A06: Printed circuit board in the control cabinet of the master machine, which is provided with potential-
free contacts for controlling the slaves and to which fault messages of the slaves can (optionally)
be connected.
Change-over time: Determination, how long the current base load machine is to be maintained before the BLS series
changes over. Compressors K2 to K5 receive on-load/off-load commands from the master control.
To this end, a relay module is provided in the master control (see electrical circuit diagram). The
relay contacts must be integrated into the control of the slaves so that a picked-up relay (contact
made) causes the connected compressor to change to the on-load mode. In order that the normal
on-load/off-load control of the machine has no influence on BLS operation, the switching points
must be changed accordingly on each slaves.
Remaining time: Indication, when the change-over of compressors will take place
24
2. Base load selection circuit DELCOS 3100
2.3 Interfacing the slaves with the BLS 2.5.1 Remote pressure change-over
2.3.1 Load requirement The BLS or the machine itself [OPERATION OFF] can
be forcedly changed over to the second pressure range
Compressors K2 to K5 receive on-load/off-load com- via input E07.5 (module A06) (see chapter [TIMER
mands from relay module A06 of the BLS. A picked-up CONTROL].)
relay means on-load operation.
While the pressure is being changed over, symbol p2
The relay contacts must be switched in the control of the flashes before the indication of the current line pressure.
slaves. In order that the normal on-load/off-load control
of the machine has no influence on BLS operation, its
setting must be changed accordingly.
2.5.2 Remote switching off in
[OPERATION ON]
2.3.2 Fault message
The BLS can be temporarily switched off via input E07.4
The fault messages of the slaves (K2..K5) can (option- (module A06).
ally) be wired to existing terminals of the master relay
module. A closed electric circuit means "no fault". This deactivation is not identical to manual switching off
of the BLS. Only the load requirements to all machines
are withdrawn. In contrast to manual switching off, the
message "BLS active" is maintained.
When the BLS is not switched on [OPERATION OFF] or 2.5.3 Remote switching on in
failed [OPERATION—], the master machine (K1) is
[OPERATION TIMER]
controlled on the basis of the line pressure switching
points set in the menu [CONTROL].
The BLS that was switched off via the timer can be force-
As soon as the BLS is switched on [ON/TIMER], the activated via input E07.4 (module A06).
master machine is coupled by the software to the BLS.
On-load and off-load commands will then be provided
exclusively by the BLS.
25
2. Base load selection circuit DELCOS 3100
The individual menu items and their function are described in the following.
This Base Load Selection circuit offers all possibilities The settings of the BLS are battery-backed against
of operating the compressed air system in the most loss. Battery-protection is only important for the de-
effective way. energised phase of the machine.
It allows smallest pressure bands with highest Long before the battery is no longer able to protect the
precision, lowest pressure level, etc. At the same time, data, a warning appears on the display: BATTERY. In this
the unnecessary activation of compressors, caused, for case, the clock module (RTC) of the electronics must
example, by irrelevant line pressure breakdowns over a soon be replaced.
very short period of time, is prevented.
When the battery is completely exhausted, that data will
On the other hand, certain conditions may be present, be lost after a power failure. In order to ensure the
which are not optimal, but cannot be avoided (e.g. in- compressed air supply also in this case, the BLS will
stalled compressor with long start-up time). Moreover, change over to its default values. The unit-specific data
the compressed air receiver may be too small or line can be adjusted temporarily (only until the next power
losses (leakage) too great. A lot of other reasons could failure).
be listed here.
26
2. Base load selection circuit DELCOS 3100
Here, the BLS is switched on or off. When the BLS failed The currently planned base load compressor is
as a result of the events described before, [OPERATION displayed or can be set here.
––] appears on the display until the fault is rectified. In this If a fault is detected on the base load compressor,
case, it is possible to switch from [OPERATION —] back another compressor will provide the base load
to [OPERATION OFF]. When the BLS is switched off, no (temporarily). The actual base load series can be
load requirements are sent to the slaves. seen from the status display described in the
following. When the fault is rectified, the planned
The compressors connected to the BLS can be control- machine re-assumes the base load.
led in dependence on the [TIMER]. The BLS receives the Changes to this setting have no effect on the
timer information from the menu [TIMER CONTROL] of remaining changeover time of the BLS series.
the master, which must be programmed accordingly.
The timer setting is/can be used by the BLS (menu:
[BASE LOAD SELECT]) and/or the machine itself (menu:
[CONTROL]).
27
2. Base load selection circuit DELCOS 3100
The status display provides information about the current BLS order, the time remaining until the next change-over and
the status of the machines (on-load/off-load/fault). The reserve machines are shown as well.
The time remaining until change-over can be changed within the range of 1h...change-over time in the input mode
(exceptions: [CHANGE-OVER TIME 300s] or [CHANGE-OVER TIME—h] set). The change-over time is counted down as
long as the base load unit is in the on-load mode.
The indication of the BLS series starts on the left with the base load machine , followed by the current medium/peak load
machines and the reserve compressors. The following is shown:
The same display structure is valid for reserve machines, however, with the letters "R/r“ (instead of "K/k“).
To get a quick overview of the BLS status during normal operation of the machines, you can show and hide this status
diplay with the help of key . Since this is possible outside the menu, the change-over time cannot be changed here.
The status display is maintened for max. 60 s in the display or is overwritten by any faults/warnings that occur.
Here, you can enter the setpoint time for the BLS series. Here, you can set, how many slave machines apart
The change-over time is counted down when the base from the master are to be included in the actual BLS
load unit is running in the on-load mode. It stops when circuit, i.e. exchange the base load in dependence upon
no compressor is requested. the operating hours. This does not apply to reserve
machines.
The change-over time can be set within the range of
300s, 1h .. 999h, —h. 2.6.9 Setting [QUANT. OF RESERVE]
300s: Test mode If the number of BLS slaves is less than 4, reserve
1h .. 999h: Normal change-over time machines can be defined. The reserve machines are not
—h: No change-over; the BLS series is main- included in the operating hours-related BLS circuit. They
tained permanently are always at the last position in the series and are cut
in only when required. Typical reserve machines are, for
In the test mode (300s) or if no change-over is requested example, outdated compressors, which are operable,
(—h), the remaining time until change-over cannot be but should be cut in in emergency cases only.
changed in the status display.
28
2. Base load selection circuit DELCOS 3100
When the pressure falls below CUT-IN POINT, the first Solution:
unit is cut in without delay.
The master compressor is activated by its timer at 5:45
o'clock for switching on the BLS. The BLS mode is set to
"timer" and "load net" to 15 min. After 15 minutes at the
2.6.11 Setting [LOAD NET IN] latest will a line pressure of 8.0 be reached and the
number of compressors cut in for this is kept to a
minimum.
[LOAD NET IN xymin] is used to start only the number
of compressors, which are required to charge the line in
the specified time. In this way, automatic cutting in of the
entire station is prevented.
Caution:
The correct setting of the parameter [VOLUME OF NET] is decisive for the satisfactory operation of the Base Load
Selection circuit!
Value set too small (slow): In the case of strong changes in demand, the BLS cannot recognize that it must cut in
or out compressors (progressively) as a precautionary measure within the range of CUT-IN-POINT and CUT-OUT-
POINT.
Value set too high (sensitive): The BLS cuts the compressors (progressively) too early in or out within the range
of CUT-IN-POINT and CUT-OUT-POINT.
29
2. Base load selection circuit DELCOS 3100
K1 K2 R3 R4 K1 K2 K3 K4 K5
¯ ¯
K2 K1 R3 R4 K2 K3 K4 K5 K1
¯
K3 K4 K5 K1 K2
¯
K4 K5 K1 K2 K3
¯
K5 K1 K2 K3 K4
When the changeover takes place, not only the line pressure switching points, but also the previously current load
enables are passed on.
When the BLS series is switched over, the new BSL series is newly set with the available machines.
Example: Circuit with 4 compressors, 1 reserve compressor, [BASE LOAD COMP 3], [CHANGEOVER TIME
250h], K4 faulty
Changeover: 250h K1 K2 k3 r5 k! {K4 is now the planned base load compressor, but faulty}
30
2. Base load selection circuit DELCOS 3100
Should the BLS fail, can the slave change over to its own
pressure switch.
31
CompAir UK Ltd. High Wycombe
Hughenden Avenue