Saved Configuration – ETM505-     .

DOC Model Number – ETM505-000     

505 Series Electronic Temperature Monitor


Configuration Form

CUSTOMER INFORMATION SECTION

Company Name:       Date:      

Contact Person:       E-mail:      

Billing Address:      

Telephone #:       Fax #:      

Requested Delivery Date:     

Shipping Address:      

Quantity:      

End User:       Site:      

IMPORTANT NOTE - ALL SENSORS SOLD SEPERATELY

DEVICE CONFIGURATION SECTION


Form 0-887 Rev. G 3/10/08 Page 1 of 6 Qualitrol Company LLC
Winding
A

Channel
NOTE:
Top oil
A temperature
(channel 2) is
Included used to derive the
winding

1 Temperature
temperature
Included

What More Do You Need to Measure?


NOTE:
N- No LTC If B is
selected, we
recommend

Channel
choice B for

Top Oil
Channel LTC Temperatu
channel 4
for
N- Nothing differential
temperature
calculation

3
2 Temperature
4-20mA Input Settings (If Applicable) Powered Unpowered (12V)
What Type of Enclosure Would You like?
Unpowered (24V)

A- Panel Mount

N- No Heater

Mounting
Heater Settings (If Applicable) Set point:      
Would You Like Additional Communications?
Hysteresis:      
NOTE: DNP or
Modbus is
software

Communications
N- Nothing selectable - only
one can function
at a time

Form 0-887 Rev. G 3/10/08


Additional
2nd Top Oil Page 2 of 6 Qualitrol Company LLC
ADDITIONAL ACCESORIES SECTION

RS232 Cable (Will appear as separate line item) Yes


RS232 to USB Converter (Will appear as separate line item) Yes

Yes
Hard Copy of Instruction Manual (Comes with electronic version standard)
Quantity      

EXTENDED WARRANTY (Will appear as separate line item)


1 Year Extension of the standard warranty beyond a period of 18 months from the
date of sale by seller to buyer, or a period of one year from the date of resale by 1YR
buyer to buyer’s customer, whichever is first to expire at a cost of 2% of purchase Extension
price. (SERVICE-1YR-505)
2 Year Extension of the standard warranty beyond a period of 18 months from the
date of sale by seller to buyer, or a period of one year from the date of resale by 2YR
buyer to buyer’s customer, whichever is first to expire at a cost of 4% of purchase Extension
price. (SERVICE-2YR-505)

3 Year Extension of the standard warranty beyond a period of 18 months from the
date of sale by seller to buyer, or a period of one year from the date of resale by 3YR
buyer to buyer’s customer, whichever is first to expire at a cost of 6% of purchase Extension
price. (SERVICE-3YR-505)

4 Year Extension of the standard warranty beyond a period of 18 months from the
date of sale by seller to buyer, or a period of one year from the date of resale by 4YR
buyer to buyer’s customer, whichever is first to expire at a cost of 8% of purchase Extension
price. (SERVICE-4YR-505)

SOFTWARE CONFIGURATION SECTION (OPTIONAL)


Form 0-887 Rev. G 3/10/08 Page 3 of 6 Qualitrol Company LLC
Values specified in this section can be configured with software included with the 505 Series Monitor. If no values are
specified, the monitor will be delivered using default Settings. If you want the factory to configure your 505, then the
following sheets need to be completed.

DEFAULTS
Fault
NFS or FS* Set points
(Y/N)
Relay1 (Fan1) non-failsafe N 60°C, 15°C hysteresis, Oil 65°C, 15 °C hysteresis, Winding inactive, LTC, differential
Relay2 (Fan2) fail safe N 70°C, 15°C hysteresis, Oil 75°C, 15°C hysteresis, Winding Inactive, LTC, differential
Relay3 (Alarm) fail safe Y 90°C, 5°C hysteresis, Oil 100°C, 5°C hysteresis, Winding 10°C, 15°C hysteresis, LTC Diff, 5 minute Delay
120°C, 2°C hysteresis, LTC, 0 minute Delay,
Relay4 (Trip) non-failsafe N 110°C, 2°C hysteresis, Oil 120°C, 2°C hysteresis, Winding
inactive Differential

Max Temperature Memory Displayed - Default is OFF, when turned on maximums will be included in scrolling display values
Remote Output - 4 - 20mA
Auto / Manual Relays - Default is automatic – relays 1 & 2 are controlled by set points – manual turns on relay 1 & 2
Fan exerciser - ON, 7 days interval; 1 minute on-time
Fan Bank switching - ON

*FAILSAFE / NON-FAILSAFE when the relay is in a non-failsafe condition (NFS), the normally closed and common contacts (NC-C) shorted together
when the power is off to the unit and when the set points have not been exceeded. The relay will change states when the set points have been exceeded.
When a relay is in a failsafe condition (FS) the normally closed and common contacts will be shorted together when there is no power to the unit. Upon
powering the unit, and if the set points have not been exceeded, the relay will change states causing the normally open and common contacts (NO-C) to be
shorted. The relay will change to normally closed and common contacts shorted together if the set points are exceeded or if the unit loses power. Any trip
contacts for a transformer should be configured non-failsafe. (See Table below)

RELAY NO POWER UNIT POWERED UNIT POWERED LOSS OF


CONDITION TO UNIT < SETPOINT >= SETPOINT POWER
NON-FAILSAFE NC - C NC - C NO – C NC - C
FAILSAFE NC - C NO - C NC – C NC - C

Alarm 1
Enabled
Fail Safe
Form 0-887 Rev. G 3/10/08 Page 4 of 6 Qualitrol Company LLC
Operate on Sensor Error
Oil Winding Channel 4 LTC Temp Differential
Set Point                              
Hysteresis                              
Time Delay            
Alarm 2
Enabled
Fail Safe
Operate on Sensor Error
Oil Winding Channel 4 LTC Temp Differential
Set Point                              
Hysteresis                              
Time Delay            
Alarm 3
Enabled
Fail Safe
Operate on Sensor Error
Oil Winding Channel 4 LTC Temp Differential
Set Point                            
Hysteresis                              
Time Delay            
Alarm 4
Enabled
Fail Safe
Operate on Sensor Error
Oil Winding Channel 4 LTC Temp Differential
Set Point                              
Hysteresis                              
Time Delay            

SCADA (Analog) Output Settings


Output Range 0-1mA 4-20mA
Channel 1 Oil Temperature (Fixed)

Form 0-887 Rev. G 3/10/08 Page 5 of 6 Qualitrol Company LLC


Channel 2 Winding Temperature (Fixed)
Channel 3 LTC Differential

Form 0-887 Rev. G 3/10/08 Page 6 of 6 Qualitrol Company LLC